Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY 149

CODE COMMENTARY
10.10.4 — Elastic second-order analysis R10.10.4 — Elastic second-order analysis

Elastic second-order analysis shall consider section The stiffnesses EI used in an analysis for strength design
properties determined taking into account the influ- should represent the stiffnesses of the members immediately
ence of axial loads, the presence of cracked regions prior to failure. This is particularly true for a second-order
along the length of the member, and the effects of load analysis that should predict the lateral deflections at loads
duration. approaching ultimate. The EI values should not be based
totally on the moment-curvature relationship for the most
highly loaded section along the length of each member.
Instead, they should correspond to the moment-end rotation
relationship for a complete member.

Design computations for slender columns and frames


include both a strength reduction factor φ for the cross-
sectional strength and a stiffness reduction factor φK for the
member stiffnesses. The variability in the cross-sectional
strength is accounted for by φ in the interaction diagrams
while the variability of member stiffness is accounted for by 10
φK in the structural analysis.

10.10.4.1 — It shall be permitted to use the following R10.10.4.1 — The values of Ec , I, and A have been
properties for the members in the structure: chosen from the results of frame tests and analyses and
include an allowance for the variability of the computed
(a) Modulus of elasticity ...................... Ec from 8.5.1 deflections. The modulus of elasticity of the concrete, Ec , is
(b) Moments of inertia, I based on the specified concrete compressive strength while
Compression members: the sway deflections are a function of the average concrete
Columns.................................................... 0.70Ig strength, which is higher. The moments of inertia are taken
Walls—Uncracked..................................... 0.70Ig from Reference 10.36, which are multiplied by the stiffness
—Cracked ........................................ 0.35Ig reduction factor φK = 0.875. For example, the moment of
Flexural members: inertia for columns is 0.875(0.80Ig) = 0.70Ig. These two
Beams....................................................... 0.35Ig effects result in an overestimation of the second-order
Flat plates and flat slabs ........................... 0.25Ig deflections on the order of 20 to 25 percent, corresponding
(c) Area ........................................................... 1.0Ag to an implicit stiffness reduction of 0.80 to 0.85 on the
stability calculation.
Alternatively, the moments of inertia of compression
and flexural members, I, shall be permitted to be The moment of inertia of T-beams should be based on the
computed as follows: effective flange width defined in 8.12. It is generally suffi-
Compression members: ciently accurate to take Ig of a T-beam as two times the Ig
for the web, 2(bwh3/12).
A st Mu Pu
I =  0.80 + 25 --------  1 – ----------- – 0.5 ------ I g ≤ 0.875I g (10-8) If the factored moments and shears from an analysis based
 Ag   Pu h P o
on the moment of inertia of a wall, taken equal to 0.70Ig,
indicate that the wall will crack in flexure, based on the
where Pu and Mu shall be determined from the
modulus of rupture, the analysis should be repeated with I =
particular load combination under consideration, or
0.35Ig in those stories where cracking is predicted using
the combination of Pu and Mu resulting in the
factored loads.
smallest value of I. I need not be taken less than
0.35Ig .
The values of the moments of inertia were derived for
Flexural members: nonprestressed members. For prestressed members, the
moments of inertia may differ depending on the amount,
bw location, and type of the reinforcement and the degree of
I = ( 0.10 + 25ρ )  1.2 – 0.2 ------- I g ≤ 0.5I g (10-9) cracking prior to ultimate. The stiffness values for
 d prestressed concrete members should include an allowance
for the variability of the stiffnesses.

American Concrete Institute Copyrighted Material—www.concrete.org


150 STRUCTURAL CONCRETE BUILDING CODE (ACI 318M-11) AND COMMENTARY

CODE COMMENTARY
For continuous flexural members, I shall be permitted to Section 10.10 provides requirements for strength and
be taken as the average of values obtained from assumes frame analyses will be carried out using factored
Eq. (10-9) for the critical positive and negative moment loads. Analyses of deflections, vibrations, and building
sections. I need not be taken less than 0.25Ig . periods are needed at various service (unfactored) load
levels10.38,10.39 to determine the serviceability of the structure
The cross-sectional dimensions and reinforcement ratio and to estimate the wind forces in wind tunnel laboratories.
used in the above formulas shall be within 10 percent of The moments of inertia of the structural members in the
the dimensions and reinforcement ratio shown on the service load analyses should be representative of the degree
contract documents or the stiffness evaluation shall be of cracking at the various service load levels investigated.
repeated. Unless a more accurate estimate of the degree of cracking at
service load level is available, it is satisfactory to use
1.0/0.70 = 1.43 times the moments of inertia given here for
service load analyses.

Equations (10-8) and (10-9) provide more refined values of


EI considering axial load, eccentricity, reinforcement ratio,
and concrete compressive strength as presented in References
10 10.40 and 10.41. The stiffnesses provided in these references
are applicable for all levels of loading, including service and
ultimate, and consider a stiffness reduction factor φK
comparable to that included in 10.10.4.1(b). For use at load
levels other than ultimate, Pu and Mu should be replaced
with their appropriate values at the desired load level.

10.10.4.2 — When sustained lateral loads are R10.10.4.2 — The unusual case of sustained lateral loads
present, I for compression members shall be divided might exist, for example, if there were permanent lateral
by (1 + βds ). The term βds shall be taken as the ratio of loads resulting from unequal earth pressures on two sides of
maximum factored sustained shear within a story to a building.
the maximum factored shear in that story associated
with the same load combination, but shall not be taken
greater than 1.0.

10.10.5 — Moment magnification procedure R10.10.5 — Moment magnification procedure

Columns and stories in structures shall be designated This section describes an approximate design procedure that
as nonsway or sway columns or stories. The design of uses the moment magnifier concept to account for slenderness
columns in nonsway frames or stories shall be based effects. Moments computed using an ordinary first-order
on 10.10.6. The design of columns in sway frames or frame analysis are multiplied by a moment magnifier that is
stories shall be based on 10.10.7. a function of the factored axial load Pu and the critical buckling
load Pc for the column. Nonsway and sway frames are
10.10.5.1 — It shall be permitted to assume a column treated separately. A first-order frame analysis is an elastic
in a structure is nonsway if the increase in column end analysis that does not include the internal force effects
moments due to second-order effects does not exceed resulting from deflections.
5 percent of the first-order end moments.
The moment magnifier design method requires the designer
10.10.5.2 — It also shall be permitted to assume a to distinguish between nonsway frames, which are designed
story within a structure is nonsway if: according to 10.10.6, and sway frames, which are designed
according to 10.10.7. Frequently this can be done by inspection
ΣP u Δ o by comparing the total lateral stiffness of the columns in a
- ≤ 0.05
Q = ----------------- (10-10) story to that of the bracing elements. A compression
V us l c
member may be assumed nonsway by inspection if it is
located in a story in which the bracing elements (shear
where ΣPu and Vus are the total factored vertical load walls, shear trusses, or other types of lateral bracing) have
and the horizontal story shear, respectively, in the such substantial lateral stiffness to resist the lateral deflections
story being evaluated, and Δo is the first-order relative of the story that any resulting lateral deflection is not large
lateral deflection between the top and the bottom of enough to affect the column strength substantially. If not
that story due to Vus .
American Concrete Institute Copyrighted Material—www.concrete.org

You might also like