J7 Icon - Electrical Schematic Drawings R0 (25.04.2022) - L&G
J7 Icon - Electrical Schematic Drawings R0 (25.04.2022) - L&G
NOTE: 1. ALL LUMINAIRES IN ENCLOSED ROOMS SHALL BE CONTROLLED VIA A LOCAL SWITCH WHERE
QUICK ACTING FAULT MAKING EARTH SWITCH REFER TO THE ARCHITECTURAL / LANDSCAPE PACKAGES FOR THE FINAL SHOWN.
SELECTION OF LIGHT FITTINGS, NOTED FITTINGS IN THE ELECTRICAL 2. EMERGENCY LIGHTING SHALL BE POWERED UP FROM STAND ALONE BATTERY WITH 2hrs
PACKAGE IS ONLY FOR REFERENCE AND GUIDANCE TO CARRY OUT BACKUP TIME.
ON-LINE ISOLATION SWITCH (FAULT MAKE INSTALLATION AT THE SITE. 3. ALL CABLING IN CEILING SPACE TO BE TIED AND FIXED TO THE UNDERSIDE OF THE SLAB, NO
LOAD BREAK DISCONNECTOR) CABLING SHALL REST ON THE PLASTER BOARD CEILING, CEILING TILES OR SUPPORTED BY
OTHER SERVICES.
MOULDED CASE CIRCUIT BREAKER (MCCB) UNLESS STATED L1 CEILING/SOFFIT MOUNTED LED ROUND PANEL LIGHT
4. ALL CEILING MOUNTED DEVICES ARE TO BE PROVIDED WITH BACKING PLATES FOR
OTHERWISE (RATING AS NOTED) 10W, 650lm, 4000K, IP20
ADEQUATE SUPPORT.
xxxA xxxA DENOTES SETTING OF CIRCUIT BREAKER 5. PROVIDE CIRCUIT IDENTIFICATION ON ALL SWITCHES.
yyyA yyyA DENOTES FRAME SIZE OF CIRCUIT BREAKER
L2 CEILING/SOFFIT MOUNTED LED SQUARE PANEL LIGHT 6. ALL LIGHT SWITCHES SHALL HAVE MECHANISM HOLDING SCREWS.
45W, 4000lm, 2' x 2', 4000K, IP20 7. REFER TO ARCHITECTS DRAWINGS FOR THE EXACT LOCATION AND SET-OUT OF ALL LIGHT
FITTINGS.
RESIDUAL CURRENT CIRCUIT BREAKER LED BATTEN LIGHT 8. ALL ELECTRICAL AND ELV DUCT SHALL BE PROVIDED WITH WALL MOUNTED LED LIGHT WITH
L3 30W, 2700lm, 4000K, IP20 UNLESS SPECIFIED OTHERWISE SWICTH.
9. CABLE FOR OUTDOOR LIGHTING SHALL BE ARMORED CABLES AND SHALL BE BURIED AT 2' 4"
DEPTH. PROPER CABLE IDENTIFICATION TAPES AND PROTECTION TILES SHALL BE LAID ON
LED BATTEN LIGHT
SINGLE PHASE L4 2x30W, 5400lm, 4000K, IP20 UNLESS SPECIFIED OTHERWISE
THE CABLE.
10. NECESSARY LIGHTING TO BE PROVIDED BY THE LIFT CONTACTOR WITHIN THE LIFT SHAFT.
11. LIGHTING FIXTURES IN SERVICES ROOMS ETC SHALL BE INSTALLED IN FULL COORDINATION
TWO PHASE L5 WALL MOUNTED LED BULKHEAD LIGHT WITH CABLE TRAYS, CONDUITS ETC.
15W, 1080lm, 4000K, IP65 12. EXACT LOCATION OF EXTERNAL LIGHTING SHALL BE COORDINATED WITH LANDSCAPE
WORKS.
THREE PHASE 13. ALL THE TOILET EXHAUST FANS (SINGLE PHASE AND POWER LESS THAN 200W) TO BE
L6 SOFFIT MOUNTED LED ROUND PANEL LIGHT
POWERED FROM THE NEAREST LIGHTING CIRCUIT AND TO BE CONTROLLED VIA A
20W, 1800lm, 4000K, IP20
DEDICATED 10A LIGHT CONTROLLING SWITCH.
NEUTRAL L7 WALL MOUNTED LED BATTEN LIGHT
30W, 2700lm, 4000K (IP65)
GENERAL NOTES FOR POWER
EARTH
1. ALL CABLING IN CEILING SPACE TO BE RUN ON CATENARY WIRE FIXED TO UNDERSIDE OF
L8 MIRROR LIGHT SLAB WHERE CABLE TRAY/BASKET IS NOT SHOWN. NO CABLING SHALL REST ON CEILING
CT CURRENT TRANSFORMER 12W, 4000K, IP20 TILES, OR SUPPORTED BY OTHER SERVICES.
2. ALL POWER COVER PLATES TO BE EQUAL IN SIZE.
LINK
L9 CEILING/SOFFIT MOUNTED LED ROUND PANEL LIGHT
3. COORDINATE ON SITE THE INSTALLATION OF REED SWITCHES AND DOOR LATCHES ON
SECURITY/ENTRY DOORS.
20W, 1300lm, 4000K, IP20 4. ALL POWER AND DATA SOCKETS ARE MOUNTED AT 1' 6" FROM FFL TO THE BOTTOM OF THE
SOCKET UNLESS SPECIFIED OTHERWISE.
FUSE 5. OUTLETS ABOVE BENCHES ARE TO BE MOUNTED AT 6" FROM THE WORK SURFACE TO THE
BOTTOM OF THE OUTLET
SWITCH
6. CABLE TRAYS AND LADDERS WITHIN CEILING VOIDS TO BE CONNECTED TO RISER CABLE
R INDICATOR LIGHT (G1 - 1 GANG, G2 - 2 GANG, G3 - 3 GANG, G4 - 4 GANG, G5 - 5 GANG)
LADDERS TO ENSURE COMPLETE CONNECTION OF THE SYSTEMS.
7. CONTRACTOR SHALL ALLOW FOR ALL CONNECTIONS. ALL FIRE DOOR, ELECTRIC DOOR
ENERGY (kWh) METER STRIKES TO WORK INDEPENDENTLY WITH FAIL SAFE MECHANISM.
M 1200MM CEILING FAN 8. WHERE POWER OUTLETS ARE MOUNTED ON METAL PARTITIONING, THE PARTITIONING SHALL
COMPATIBLE WITH BMS
BE EARTHED AND A SHROUD SHALL BE PROVIDED TO COVER THE BACK OF THE OUTLET.
DIGITAL POWER ANALYZER FOR MEASURING 9. MAINTAIN MINIMUM 1' SEGREGATION BETWEEN LV AND ELV CABLES. PROVIDE FIXED
P/A V,A,kVA,kW,kVAr,P.F.
FAN REGULATOR
MECHANICAL BARRIERS WHERE THE MINIMUM CLEAR DISTANCE CANNOT BE ACHIEVED.
COMPATIBLE WITH BMS 10. ELECTRICAL AND COMMUNICATION CABLE TRAY IN ALL AREAS ARE TO BE RETICULATED
ABOVE THE CEILING
NCx CONTROL RELAY OR CONTACTOR COIL 11. SINGLE PHASE 230V POWER SOCKET OUTLETS SHALL BE, 13A SWITCHED SHUTTERED FLUSH
DOOR BELL BUTTON MOUNTING TYPE COMPLYING WITH BS 1363.
12. PROPER MECHANICAL PROTECTION SHALL BE PROVIDED FOR CABLES RETICULATE IN THE
SHT SHUNT TRIP UNIT
CAR PARKS.
DOOR BELL 13. All WALL MOUNTED PANEL BOARDS MOUNTING HEIGHT SHALL BE 5' TO THE PANEL BOARD
UNDER VOLTAGE TRIP UNIT TOP.
UVT 14. POWER TO THE TOILET EXHAUST FANS SHALL BE PROVIDED FROM THE LIGHTING CIRCUIT.
15. NECESSARY POWER PROVISIONS TO BE PROVIDED BY THE LIFT CONTRACTOR WITHIN THE
DISTRIBUTION BOARD BOUNDRY
ELR EARTH LEAKAGE RELAY LIFT SHAFT.
16. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL JUNCTION BOXES REQUIRED FOR
EQUIPMENT, WHETHER OR NOT SPECIFICALLY INDICATED ON THE PLANS.
EFR EARTH FAULT RELAY TENANCY LINE
SINGLE PHASE PHASE ISOLATOR WITH PVC ENCLOSURE E-CT-10X2 CABLE SUPPORT DESCRIPTION:
MINIMUM CABLE SIZES FOR POINT WIRING 2 DENOTES THE HEIGHT IN INCHES / FEET
FLOOR BOX (TO BE DETAILED)
LIGHT POINTS - 10A/1P MCB 2x1Cx2.5mm² Cu/PVC/PVC 10 DENOTES THE WIDTH IN INCHES / FEET
+2.5mm² Cu/PVC EARTH CABLE
JB JUNCTION BOX CT DENOTES CABLE TRAY
2x1Cx4mm² Cu/PVC/PVC
13A/15A RADIAL CIRCUITS - 20A/1P MCB CL DENOTES CABLE LADDER
+4mm² Cu/PVC EARTH CABLE
FLOOR DISTRIBUTION BOARD E DENOTES FOR ELECTRICAL SUBMAINS
2Cx4mm² Cu/PVC/PVC
20A 2 POLE ISOLATOR - 20A/2P MCB
+4mm² Cu/PVC EARTH CABLE LP DENOTES FOR LIGHTING AND
DISTRIBUTION BOARD GENERAL POWER SUB-CIRCUITS
4Cx4mm² Cu/PVC/PVC
20A 4 POLE ISOLATOR - 20A/4P MCB FR DENOTES FIRE RATED
+4mm² Cu/PVC EARTH CABLE Architects:
MSSB MECHANICAL SERVICES SWITCH BOARD E/C COMPARTMENT CABLE TRAY
(CONTROL PANEL BY OTHER TRADES)
TWO COMPARTMENT STAINLESS STEEL PERIMETER SKIRTING DUCT.
ENERGY (kWh) METER MINIMUM 5" HIGH AND 2" DEEP. architecture l planning l interiors
RECOMMENDED MCB TYPE 84- PESHAWAR ROAD, RAWALPINDI CANTT.
Email: aradesign.net@gmail.com,
TYPE / PANEL BOARD NUMBERING SYSTEM Web:www.aradesign.net.pk
CABLE TRAY BREAK APPLICATION Contact. 051-5567685, Fax: 5584511.
CURVE CLASS
DB-G1-ME1
B GENERAL POWER CIRCUITS, LIGHTING, HEATING
CABLE TRAY C LIGHTING PANELS, CONTROL PANELS, FANS, COILS
ME MECHANICAL FCC FIRE COMMAND CENTER MEP. Consultant:
CA COMMON AREA PF PRESSURIZATION FAN
K SMALL MOTORS Headrogen (Pty) Ltd
HONESTY I TRUST I INTEGRITY
DISTRIBUTION BOARD BOUNDRY LEVEL NUMBER / AREA / UNIT Head Office
D LARGE MOTORS, CENTRALIZED UPS SYSTEMS Le e een St e o rne stra ia
Pakistan Office (Remote)
TENANCY LINE SDB SUB DISTRIBUTION BOARD Office irst oor r P a e ock arka s ama ad Pakistan
DB DISTRIBUTION BOARD Sri Lanka Office
CHARACTERISTICS OF INSTALLATION (LIGHTING) MSSB MECHANICAL SERVICES SWITCH BOARD Le e Station Road o om o Sri Lanka
CABLE IN CONDUIT / TRUNKING LIGHTING POWER RATED
LSDB LIFE SAFETY DISTRIBUTION BOARD
(KW) CURRENT (A) MAXIMUM CABLE LENGTH (m) ISO ISOLATOR Web: www.headrogen.com | Email: contact@headrogen.com
0.2 1 783 FDB FLOOR DISTRIBUTION BOARD
0.4 2 391 587
PROJECT:
0.7 3 261 391 652
1.3 6 130 196 326 522
2.2 10 78 117 196 313 489
3.5 16 49 73 122 196 306
4.4 20 39 59 98 157 245
5.5 25 31 47 78 125 196
7.0 32 37 61 98 153
8.7 40 49 78 122
10.9 50 63 96
J7 ICON
13.8 63 78 RAZIA SHARIF PLAZA, BLUE AREA, ISLAMABAD
CABLE CROSS SECTION (mm2) 4 6 10 16 25
REV DATE REVISION DETAIL
0 25.04.2022 SCHEMATIC DESIGN
RECOMMENDED RCD TYPE
TYPE APPLICATION
AC HEATING APPLICATIONS
A LIGHTING, GENERAL POWER
SCALE SIZE DATE
B UPS SYSTEMS, LIFTS, MOTORS, PUMPS SCHEMATIC DESIGN
F VSD DRIVES, SMALL MOTORS NTS A0 25.04.2022 ISSUED FOR INFORMATION
DRAWN APPROVED
HS
DESIGNED
HS TK
CHECKED
DA
TITLE
ELECTRICAL SYSTEM
LEGEND & GENERAL NOTES
DRAWING No. REV
G20022-HDG-ED-30001 0