LEGEND FOR ELECTRICAL SCHEMATIC LEGEND FOR GENERAL LIGHTING GENERAL NOTES FOR LIGHTING

NOTE: 1. ALL LUMINAIRES IN ENCLOSED ROOMS SHALL BE CONTROLLED VIA A LOCAL SWITCH WHERE
QUICK ACTING FAULT MAKING EARTH SWITCH REFER TO THE ARCHITECTURAL / LANDSCAPE PACKAGES FOR THE FINAL SHOWN.
SELECTION OF LIGHT FITTINGS, NOTED FITTINGS IN THE ELECTRICAL 2. EMERGENCY LIGHTING SHALL BE POWERED UP FROM STAND ALONE BATTERY WITH 2hrs
PACKAGE IS ONLY FOR REFERENCE AND GUIDANCE TO CARRY OUT BACKUP TIME.
ON-LINE ISOLATION SWITCH (FAULT MAKE INSTALLATION AT THE SITE. 3. ALL CABLING IN CEILING SPACE TO BE TIED AND FIXED TO THE UNDERSIDE OF THE SLAB, NO
LOAD BREAK DISCONNECTOR) CABLING SHALL REST ON THE PLASTER BOARD CEILING, CEILING TILES OR SUPPORTED BY
OTHER SERVICES.
MOULDED CASE CIRCUIT BREAKER (MCCB) UNLESS STATED L1 CEILING/SOFFIT MOUNTED LED ROUND PANEL LIGHT
4. ALL CEILING MOUNTED DEVICES ARE TO BE PROVIDED WITH BACKING PLATES FOR
OTHERWISE (RATING AS NOTED) 10W, 650lm, 4000K, IP20
ADEQUATE SUPPORT.
xxxA xxxA DENOTES SETTING OF CIRCUIT BREAKER 5. PROVIDE CIRCUIT IDENTIFICATION ON ALL SWITCHES.
yyyA yyyA DENOTES FRAME SIZE OF CIRCUIT BREAKER
L2 CEILING/SOFFIT MOUNTED LED SQUARE PANEL LIGHT 6. ALL LIGHT SWITCHES SHALL HAVE MECHANISM HOLDING SCREWS.
45W, 4000lm, 2' x 2', 4000K, IP20 7. REFER TO ARCHITECTS DRAWINGS FOR THE EXACT LOCATION AND SET-OUT OF ALL LIGHT
FITTINGS.
RESIDUAL CURRENT CIRCUIT BREAKER LED BATTEN LIGHT 8. ALL ELECTRICAL AND ELV DUCT SHALL BE PROVIDED WITH WALL MOUNTED LED LIGHT WITH
L3 30W, 2700lm, 4000K, IP20 UNLESS SPECIFIED OTHERWISE SWICTH.
9. CABLE FOR OUTDOOR LIGHTING SHALL BE ARMORED CABLES AND SHALL BE BURIED AT 2' 4"
DEPTH. PROPER CABLE IDENTIFICATION TAPES AND PROTECTION TILES SHALL BE LAID ON
LED BATTEN LIGHT
SINGLE PHASE L4 2x30W, 5400lm, 4000K, IP20 UNLESS SPECIFIED OTHERWISE
THE CABLE.
10. NECESSARY LIGHTING TO BE PROVIDED BY THE LIFT CONTACTOR WITHIN THE LIFT SHAFT.
11. LIGHTING FIXTURES IN SERVICES ROOMS ETC SHALL BE INSTALLED IN FULL COORDINATION
TWO PHASE L5 WALL MOUNTED LED BULKHEAD LIGHT WITH CABLE TRAYS, CONDUITS ETC.
15W, 1080lm, 4000K, IP65 12. EXACT LOCATION OF EXTERNAL LIGHTING SHALL BE COORDINATED WITH LANDSCAPE
WORKS.
THREE PHASE 13. ALL THE TOILET EXHAUST FANS (SINGLE PHASE AND POWER LESS THAN 200W) TO BE
L6 SOFFIT MOUNTED LED ROUND PANEL LIGHT
POWERED FROM THE NEAREST LIGHTING CIRCUIT AND TO BE CONTROLLED VIA A
20W, 1800lm, 4000K, IP20
DEDICATED 10A LIGHT CONTROLLING SWITCH.
NEUTRAL L7 WALL MOUNTED LED BATTEN LIGHT
30W, 2700lm, 4000K (IP65)
GENERAL NOTES FOR POWER
EARTH
1. ALL CABLING IN CEILING SPACE TO BE RUN ON CATENARY WIRE FIXED TO UNDERSIDE OF
L8 MIRROR LIGHT SLAB WHERE CABLE TRAY/BASKET IS NOT SHOWN. NO CABLING SHALL REST ON CEILING
CT CURRENT TRANSFORMER 12W, 4000K, IP20 TILES, OR SUPPORTED BY OTHER SERVICES.
2. ALL POWER COVER PLATES TO BE EQUAL IN SIZE.

LINK
L9 CEILING/SOFFIT MOUNTED LED ROUND PANEL LIGHT
3. COORDINATE ON SITE THE INSTALLATION OF REED SWITCHES AND DOOR LATCHES ON
SECURITY/ENTRY DOORS.
20W, 1300lm, 4000K, IP20 4. ALL POWER AND DATA SOCKETS ARE MOUNTED AT 1' 6" FROM FFL TO THE BOTTOM OF THE
SOCKET UNLESS SPECIFIED OTHERWISE.
FUSE 5. OUTLETS ABOVE BENCHES ARE TO BE MOUNTED AT 6" FROM THE WORK SURFACE TO THE
BOTTOM OF THE OUTLET
SWITCH
6. CABLE TRAYS AND LADDERS WITHIN CEILING VOIDS TO BE CONNECTED TO RISER CABLE
R INDICATOR LIGHT (G1 - 1 GANG, G2 - 2 GANG, G3 - 3 GANG, G4 - 4 GANG, G5 - 5 GANG)
LADDERS TO ENSURE COMPLETE CONNECTION OF THE SYSTEMS.
7. CONTRACTOR SHALL ALLOW FOR ALL CONNECTIONS. ALL FIRE DOOR, ELECTRIC DOOR
ENERGY (kWh) METER STRIKES TO WORK INDEPENDENTLY WITH FAIL SAFE MECHANISM.
M 1200MM CEILING FAN 8. WHERE POWER OUTLETS ARE MOUNTED ON METAL PARTITIONING, THE PARTITIONING SHALL
COMPATIBLE WITH BMS
BE EARTHED AND A SHROUD SHALL BE PROVIDED TO COVER THE BACK OF THE OUTLET.
DIGITAL POWER ANALYZER FOR MEASURING 9. MAINTAIN MINIMUM 1' SEGREGATION BETWEEN LV AND ELV CABLES. PROVIDE FIXED
P/A V,A,kVA,kW,kVAr,P.F.
FAN REGULATOR
MECHANICAL BARRIERS WHERE THE MINIMUM CLEAR DISTANCE CANNOT BE ACHIEVED.
COMPATIBLE WITH BMS 10. ELECTRICAL AND COMMUNICATION CABLE TRAY IN ALL AREAS ARE TO BE RETICULATED
ABOVE THE CEILING
NCx CONTROL RELAY OR CONTACTOR COIL 11. SINGLE PHASE 230V POWER SOCKET OUTLETS SHALL BE, 13A SWITCHED SHUTTERED FLUSH
DOOR BELL BUTTON MOUNTING TYPE COMPLYING WITH BS 1363.
12. PROPER MECHANICAL PROTECTION SHALL BE PROVIDED FOR CABLES RETICULATE IN THE
SHT SHUNT TRIP UNIT
CAR PARKS.
DOOR BELL 13. All WALL MOUNTED PANEL BOARDS MOUNTING HEIGHT SHALL BE 5' TO THE PANEL BOARD
UNDER VOLTAGE TRIP UNIT TOP.
UVT 14. POWER TO THE TOILET EXHAUST FANS SHALL BE PROVIDED FROM THE LIGHTING CIRCUIT.
15. NECESSARY POWER PROVISIONS TO BE PROVIDED BY THE LIFT CONTRACTOR WITHIN THE
DISTRIBUTION BOARD BOUNDRY
ELR EARTH LEAKAGE RELAY LIFT SHAFT.
16. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL JUNCTION BOXES REQUIRED FOR
EQUIPMENT, WHETHER OR NOT SPECIFICALLY INDICATED ON THE PLANS.
EFR EARTH FAULT RELAY TENANCY LINE

PFR PHASE FAILURE RELAY ABBREVIATION (GENERAL)


APFCR AUTOMATIC POWER FACTOR CORRECTION RELAY SH SHOP
EARTH GENERAL NOTES FOR ELECTRICAL SYSTEM ATS AUTOMATIC TRANSFER SWITCH CA COMMON AREA
1. ALL ELECTRICAL WORKS CARRIED OUT IN THIS PROJECT SHALL COMPLY WITH THE LATEST LOCAL MDB MAIN DISTRIBUTION BOARD CO CORPORATE
SURGE ARRESTER AUTHORITY STANDARD ELECTRICAL INSTALLATION CODE OF PRACTICE AND BS 7671:2018,18TH
GDB GENERATOR DISTRIBUTION BOARD CN CINEMA
EDITION OF IEE WIRING REGULATIONS OR LATEST EDITION.
ATS (AUTOMATIC TRANSFER SWITCH) (SOCOMEC OR 2. EARTHING INSTALLATION SYSTEM SHALL COMPLY WITH THE LATEST 18TH EDITION IEE WIRING FDB FLOOR DISTRIBUTION BOARD SK SNACK
EQUIVALENT TYPE) REGULATION.
3. THE ELECTRICAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL RELEVANT DB DISTRIBUTION BOARD CS COFFEE SHOP
ARCHITECTURAL AND SPECIALIST DRAWINGS AND SPECIFICATIONS. MCCB MOULDED CASING CIRCUIT BREAKER KIT KITCHEN
4. ALL OUTLET SWITCHES FITTINGS EXPOSED TO EXTERNAL ENVIRONMENT SHALL BE WEATHER
TAP OFF BOX PROOF TYPE FITTING & ACCESSORIES SHALL COMPLY WITH IP RATING AS NECESSARY. MCB MINIATURE CIRCUIT BREAKER PA PLAY AREA
5. EXACT LOCATION OF ALL MECHANICAL EQUIPMENT AND ASSOCIATED DISCONNECTING SWITCHES FP FIRE PUMP FHU FRESH AIR HANDLING UNIT
AND OUTLETS SHALL BE COORDINATED WITH RELEVANT SERVICES DRAWINGS AND VERIFIED AT
PROVISION FOR TAP OFF BOX EAF EXHAUST AIR FAN ODU OUTDOOR UNIT
SITE.
6. ALL PANELS SHALL HAVE RELEVANT CIRCUIT DIRECTORIES REFLECTING THE CIRCUIT FAF FRESH AIR FAN LT LIFT
ARRANGEMENT AS IT IS ACTUALLY INSTALLED.
SUB DISTRIBUTION BOARD WBP WATER BOOSTER PUMP
7. THE POSITIONING OF ALL LIGHT FITTINGS, SWITCHED SOCKET OUTLETS,DISTRIBUTION BOARDS WTP / TP WATER TRANSFER PUMP
ETC. AS SHOWN IN THE DRAWINGS ARE APPROXIMATE ONLY. THE EXACT POSITION SHALL BE
SP SUBMERSIBLE PUMP FFL FINISHED FLOOR LEVEL
FLOOR DISTRIBUTION BOARD DETERMINED AT SITE & SHOULD TAKE THE CONSULTANTS APPROVAL. REFER TO THE
ARCHITECTURAL DRAWINGS FOR SETOUT OF LIGHT FITTINGS. CC CASH AND CARRY APT APARTMENT
8. THE OVERALL IMPEDANCE FOR THE EARTHING SYSTEM (ELECTRICAL) SHALL COMPLY WITH
WAPDA REQUIREMENTS. CCA CASH AND CARRY AIR HANDLING UNIT PH PRAY HALL
ELECTRICAL DISTRIBUTION BOARD
9. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING OF ALL CABLE ES / ESC ESCALATOR PR PUMP ROOM
PENETRATION THROUGH ANY FIRE COMPARTMENT WALLS IF SPECIFIED WITH APPROVED FIRE
MSSB MECHANICAL SERVICES SWITCH BOARD RATING MATERIAL/ SEALANT TO ENGINEERS APPROVAL. PFCR POWER FACTOR CORRECTION RELAY FCU FAN COIL UNIT
(CONTROL PANEL BY OTHER TRADES) 10. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING OF ALL CABLE PENETRATION BMS BUILDING MANAGEMENT SYSTEM FCC FIRE COMMAND CENTER
OPENINGS THROUGH ROOF, WALL WITH APPROVED WATERPROOF MATERIALS AFTER THE
APFCR AUTOMATIC POWER FACTOR CORRECTION RELAY INSTALLATION OF CABLES. ELR EARTH LEAKAGE RELAY AHU AIR HANDLING UNIT
11. ALL CABLES TO BE LAID IN HEAVY GRADE uPVC PIPES WHEN LAID UNDERGROUND. ALL UNDER
GCP GENERATOR CONTROL PANEL ISO ISOLATOR
GROUND WIRING SHALL BE OF CU/XLPE/SWA/PVC/CABLE OR CU/PVC/SWA/PVC CABLE.
CABLE TAP-OFF BOX 12. ALL PANEL BOARD CABLES SHOULD BE LABELED WITH WARNING SIGNS. NGR NEUTRAL GROUNDING RESISTOR CH CHILLER
13. IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE EARTH FAULT AND OVER CURRENT
TRIPPING DISCRIMINATION BETWEEN SWITCHBOARD WITH POWER SUPPLY INCOMING FEEDER TO PFR PHASE FAILURE RELAY ACB AIR CIRCUIT BREAKER
VOLTAGE TRANSFORMER
VT COMPLY WITH THE WAPDA REQUIREMENT. SDB SUB DISTRIBUTION BOARD MB MEP BUILDING
0 - 12.5 kV* 14. IN ALL CASES WHERE HOT DIPPED GALVANIZED FINISH IS SPECIFIED, THE MINIMUM COATING
THICKNESS SHALL BE 50 MICRONS. LSDB LIFE SAFETY DISTRIBUTION BOARD CW CONDENSER WATER PUMP
INDICATOR LIGHT
15. ALL PANEL BOARDS SHALL BE CONSTRUCTED IN SUCH A WAY THAT NO LIVE PARTS OR SHT SHUNT TRIP HW HEATING HOT WATER BOILER
TERMINALS ARE EXPOSED WHEN THE PANEL DOORS ARE OPENED.
16. CONTRACTOR SHALL MAINTAIN CORRECT BENDING RADIUS ACCORDINGLY TO THE SIZE OF THE TF TRANSFORMER CT COOLING TOWER
CABLES.
CTB CABLE TAP-OFF BOX HDHC HARD DRAWN HIGH CONDUCTIVITY
17. CONTRACTOR SHALL PROVIDE METHOD STATEMENTS & DETAILS OF SUPPORTING, FIXING & FINAL
TERMINATION ARRANGEMENT OF ALL CABLES, CONDUITS, CABLE TRUNKING SYSTEM & LUMINAIRE ADJ ADJUSTABLE CHW CHILLED WATER PUMP
LEGEND FOR GENERAL POWER SUSPENSION ARRANGEMENT, ETC PRIOR TO COMMENCE.
18. THE CONTROL WIRING OF THE APFCRs SHOULD BE IN SUCH A WAY THAT THE APFCRs SHOULD PF PRESSURIZATION FAN
SINGLE 13A SWITCHED SOCKET OUTLET NOT BE CONNECTED TO THE SYSTEM WHILE GENERATORS ARE IN OPERATION.
19. NEUTRAL CABLE FOR THE POWER FACTOR CORRECTION PANEL SHALL BE DRAWN FROM A
EX
SINGLE 13A SWITCHED SOCKET OUTLET FOR EXIT
NEARBY LOCATION. CONTRACTOR SHALL SIZE THE NEUTRAL CABLE AS PER MANUFACTURER'S ABBREVIATION FOR LIGHTING
RECOMMENDATIONS.
SIGN 20. MDB, GENERATOR SHOULD BE PROVIDED WITH ITS OWN EARTH PIT MAINTAIN THE RESISTANCE EX EXPLOSION PROOF
LESS THAN 5 Ohms.
SINGLE 13A SWITCHED SOCKET OUTLET
21. CIRCUIT BREAKERS SHALL PROVIDE FULL DISCRIMINATION. EM MAINTAINED TYPE EMERGENCY LIGHTING
(SOFFIT) - FOR HVAC EQUIPMENT
22. CIRCUIT BREAKERS SHALL PROVIDE FAULT LEVEL CASCADE PROTECTION TO ENABLE THE USE OF (MINIMUM 2 HOUR BATTERY BACKUP)
10kA MINIATURE CIRCUIT BREAKERS. WHERE PROTECTION CANNOT BE GUARANTEED BY THE
DOUBLE 13A SWITCHED SOCKET OUTLET MANUFACTURER THEN FAULT CURRENT LIMITER (FCL) FUSES SHALL BE PROVIDED AT THE
NECESSARY SWITCHGEAR.
23. SUB-MAINS CABLE IDENTIFICATION TAGS SHALL BE PROVIDED AT SOURCE, TERMINATION AND ON
ABBREVIATION FOR GENERAL POWER
SINGLE 15A SWITCHED SOCKET OUTLET EITHER SIDE OF ANY BARRIER. WP WATER PROOF (IP65 OR ABOVE)
24. MAIN SWITCHBOARDS SHALL INCORPORATE THERMO-SCAN FACILITIES TO ALLOW THE SAFE
THERMAL IMAGING OF ALL BUSBARS AND BUSBAR/CABLE FACILITIES SHALL INCLUDE ALL
BUSBARS WITHIN ACCESSIBLE COMPARTMENTS AND ALL LIVE COMPONENTS. CL ABOVE CEILING LEVEL
DOUBLE 15A SWITCHED SOCKET OUTLET
25. MAIN SWITCHBOARD SEGREGATION SHALL EXCLUDE 'I' AND 'H' FORMS. THDI AT IL MAX NOT TO
EXCEED 5% TOTAL HARMONIC CURRENT DISTORTION AND NOT GREATER THAN 5% FOR THE MDBs FL FLOOR MOUNTED
AND MSSBs. ENSURE MANUFACTURER NAMEPLATE IS PERMANENTLY FIXED TO BOARDS.
SHAVER SOCKET OUTLET
26. PROPER WATER PROOFING SHALL BE DONE TO THE PLACES WHERE CABLE TRENCH AND CABLE HL HIGH LEVEL (8' FROM FFL UNLESS SPECIFIED OTHERWISE)
TRAYS ARE CONNECTED TO THE BUILDING.
27. MINIMUM CONDUIT SIZE EMBEDDED IN A SLAB TO BE Ø1".
TWO POLE SWITCH WITH RED NEON INDICATOR 28. ALL CONCEALED RISING CONDUITS SHALL RUN IN THE WALLS OR COLUMNS AND SHALL NOT RUN EX EXIT SIGN
IN PLASTER.
29. IN ANY PARTICULAR AREA WHERE SUSPENDED CEILING IS AVAILABLE THE POINT WIRING SHALL
BE CARRIED OUT USING PVC CONDUITS WITH INJECTION MOULDED FITTINGS.
THREE PHASE ISOLATOR WITH METAL CLAD ENCLOSURE
30. ALL EXPOSED CONDUITS USED FOR POINT WIRING SHALL BE DONE USING GI CONDUITS ONLY. IF
THE POINT WIRING IN EXPOSED CONDUITS IN AREAS WHERE RISK OF MECHANICAL DAMAGE IS
LESS, SHALL BE DONE USING HIGH IMPACT RESISTANCE WATER TIGHT PVC CONDUITS &
THREE PHASE ISOLATOR WITH PVC ENCLOSURE RELEVANT ACCESSORIES TO MAINTAIN SPECIFIED IP RATINGS OF THE FINAL TERMINATIONS.
31. EARTH LEAKAGE PROTECTION FOR THE FIRE PUMP AND SUBMERSIBLE PUMP IN THE MAIN CABLE SUPPORT SYSTEM
BUILDING TO BE PROVIDED BY THE CONTRACTOR.

SINGLE PHASE PHASE ISOLATOR WITH PVC ENCLOSURE E-CT-10X2 CABLE SUPPORT DESCRIPTION:

MINIMUM CABLE SIZES FOR POINT WIRING 2 DENOTES THE HEIGHT IN INCHES / FEET
FLOOR BOX (TO BE DETAILED)
LIGHT POINTS - 10A/1P MCB 2x1Cx2.5mm² Cu/PVC/PVC 10 DENOTES THE WIDTH IN INCHES / FEET
+2.5mm² Cu/PVC EARTH CABLE
JB JUNCTION BOX CT DENOTES CABLE TRAY
2x1Cx4mm² Cu/PVC/PVC
13A/15A RADIAL CIRCUITS - 20A/1P MCB CL DENOTES CABLE LADDER
+4mm² Cu/PVC EARTH CABLE
FLOOR DISTRIBUTION BOARD E DENOTES FOR ELECTRICAL SUBMAINS
2Cx4mm² Cu/PVC/PVC
20A 2 POLE ISOLATOR - 20A/2P MCB
+4mm² Cu/PVC EARTH CABLE LP DENOTES FOR LIGHTING AND
DISTRIBUTION BOARD GENERAL POWER SUB-CIRCUITS
4Cx4mm² Cu/PVC/PVC
20A 4 POLE ISOLATOR - 20A/4P MCB FR DENOTES FIRE RATED
+4mm² Cu/PVC EARTH CABLE Architects:
MSSB MECHANICAL SERVICES SWITCH BOARD E/C COMPARTMENT CABLE TRAY
(CONTROL PANEL BY OTHER TRADES)
TWO COMPARTMENT STAINLESS STEEL PERIMETER SKIRTING DUCT.
ENERGY (kWh) METER MINIMUM 5" HIGH AND 2" DEEP. architecture l planning l interiors
RECOMMENDED MCB TYPE 84- PESHAWAR ROAD, RAWALPINDI CANTT.
Email: aradesign.net@gmail.com,
TYPE / PANEL BOARD NUMBERING SYSTEM Web:www.aradesign.net.pk
CABLE TRAY BREAK APPLICATION Contact. 051-5567685, Fax: 5584511.
CURVE CLASS
DB-G1-ME1
B GENERAL POWER CIRCUITS, LIGHTING, HEATING
CABLE TRAY C LIGHTING PANELS, CONTROL PANELS, FANS, COILS
ME MECHANICAL FCC FIRE COMMAND CENTER MEP. Consultant:
CA COMMON AREA PF PRESSURIZATION FAN
K SMALL MOTORS Headrogen (Pty) Ltd
HONESTY I TRUST I INTEGRITY
DISTRIBUTION BOARD BOUNDRY LEVEL NUMBER / AREA / UNIT Head Office
D LARGE MOTORS, CENTRALIZED UPS SYSTEMS Le e een St e o rne stra ia
Pakistan Office (Remote)
TENANCY LINE SDB SUB DISTRIBUTION BOARD Office irst oor r P a e ock arka s ama ad Pakistan
DB DISTRIBUTION BOARD Sri Lanka Office
CHARACTERISTICS OF INSTALLATION (LIGHTING) MSSB MECHANICAL SERVICES SWITCH BOARD Le e Station Road o om o Sri Lanka
CABLE IN CONDUIT / TRUNKING LIGHTING POWER RATED
LSDB LIFE SAFETY DISTRIBUTION BOARD
(KW) CURRENT (A) MAXIMUM CABLE LENGTH (m) ISO ISOLATOR Web: www.headrogen.com | Email: contact@headrogen.com
0.2 1 783 FDB FLOOR DISTRIBUTION BOARD
0.4 2 391 587
PROJECT:
0.7 3 261 391 652
1.3 6 130 196 326 522
2.2 10 78 117 196 313 489
3.5 16 49 73 122 196 306
4.4 20 39 59 98 157 245
5.5 25 31 47 78 125 196
7.0 32 37 61 98 153
8.7 40 49 78 122
10.9 50 63 96
J7 ICON
13.8 63 78 RAZIA SHARIF PLAZA, BLUE AREA, ISLAMABAD
CABLE CROSS SECTION (mm2) 4 6 10 16 25
REV DATE REVISION DETAIL
0 25.04.2022 SCHEMATIC DESIGN
RECOMMENDED RCD TYPE
TYPE APPLICATION
AC HEATING APPLICATIONS
A LIGHTING, GENERAL POWER
SCALE SIZE DATE
B UPS SYSTEMS, LIFTS, MOTORS, PUMPS SCHEMATIC DESIGN
F VSD DRIVES, SMALL MOTORS NTS A0 25.04.2022 ISSUED FOR INFORMATION
DRAWN APPROVED
HS
DESIGNED
HS TK
CHECKED
DA
TITLE

ELECTRICAL SYSTEM
LEGEND & GENERAL NOTES
DRAWING No. REV

G20022-HDG-ED-30001 0