User Manual
Shenzhen Megmeet Electrical Co., Ltd. provides customers a full range of technical support.
Users can contact the nearest Megmeet office or customer service center, or directly
contact the company headquarters.
China
Postal code:518057
Web:www.megmeet.com
E-mail:sales@megmeet.com
Content
sources,this power supply device realizes two-way conversion of 48Vdc power supply. It can be
used in the scenario where the load is stretched far in the 5G power supply solution, when lithium
batteries and old batteries are used together, or when different 48V power systems are used in
parallel,the module is a plug-in module unit designed for rack and cabinet compatibility.
1.1 Appearance
–10℃~+75℃
Note:
output power of the module is linearly derated from 3000W to 1500W(For every 1℃
Operating
temperature increase, the power derates by 2.5%);
When the ambient temperature is-40℃~-10℃, the module can start normally
Storage Note:The maximum allowable rate of storage temperature is not more than 1℃
temperature
/min.
Transport
–40℃~+75℃
temperature
≤5000m (Starting from 3000m, the maximum working ambient temperature will
Altitude
be reduced by 1℃ for every increase of 200m)
Note
This module is A two-way module. According to the energy flow, the direction is specified as follows:
Side A refers to the golden finger side of the module, and side B refers to the panel side of the module.
Input working
37Vdc to 60Vdc,typical value 53.5Vdc
voltage range
Rated output
Typical value 53.5Vdc/57Vdc
voltage
Output voltage
42Vdc to 60Vdc
range
Rated output
Typical value 56.1A/52A
current
Maximum current 62.5A(The current limiting point is adjustable,value ranges from 0 to 62.5A. The
output default value is 62.5A)
3000W, when the value ranges from 48 to 60Vdc , it can be 3000W full load
Maximum output output;when the value ranges from 37 to 48Vdc,the power output is limited, and
power
the power of 37Vdc is not less than 2300w.
The load effect is less than or equal to ±0.5% of the DC output voltage setting in
Load effect
the required input/output range.
The source effect shall not exceed ±0.5% of the DC output voltage setting within
Source effect
the required input/output range.
Voltage regulation The voltage stabilization accuracy in the required input/output range shall not
accuracy exceed ±0.6% of the DC output voltage setting value
Telephone weighs
≤4mV
noise voltage
Peak machine
98±0.3%(Peak efficiency at each input and output load)
efficiency
Dynamic response recovery time shall not exceed 200μS, and the overshoot shall not exceed ±5%
recovery time
of the output setting value. Load current change rate: 1A/μs.)
Dynamic response
±5%
overshoot
Sleep power
≤4w
consumption
Temperature The temperature coefficient shall not exceed ±0.2‰ of the DC output voltage
coefficient setting value under the required working environment conditions.
Fault isolation
If a power module is faulty, other modules in the system will not work properly.
function
Module parallel Because the DC/DC module is a non-isolated topology, do not use the input and
function output of multiple modules concurrently.
Input working
40Vdc to 60Vdc,typical value 53.5Vdc
voltage range
Rated output
typical value 53.5Vdc/57Vdc
voltage
Output voltage
42Vdc to 60Vdc
range
Rated output
typical value 56.1A/52A
current
Maximum current 62.5A(The current limiting point is adjustable. The value ranges from 0 to 62.5A.
output The default value is 62.5A)
3000W,when the input is 48~60Vdc, it can output 3000W fully loaded;when the
Maximum output input ranges from 37 to 48Vdc, the power output is limited, and the power of
power
40Vdc is not less than 2400w。
The load effect is less than or equal to ±0.5% of the DC output voltage setting in
Load effect
the required input/output range.
Voltage regulation The voltage stabilization accuracy in the required input/output range shall not
accuracy exceed ±0.6% of the DC output voltage setting value
Peak-to-peak noise
≤200mV
voltage
Telephone weighs
≤2mV
noise voltage
Peak machine
98±0.3%(Peak efficiency at each input and output load)
efficiency
Dynamic response recovery time shall not exceed 200μS, and the overshoot shall not exceed ±5%
recovery time
of the output setting value. Load current change rate: 1A/μs.)
The temperature coefficient shall not exceed ±0.2‰ of the DC output voltage
Temperature
coefficient setting value under the required working environment conditions.
Fault isolation If a power module is faulty, other modules in the system will not work properly.
function
Because the DC/DC module is a non-isolated topology, do not use the input and
Module parallel
function output of multiple modules concurrently.
Item Specification
41.5mm(H)×106.4mm(W)×291mm(D)
Dimensions
Note: For slot design, please contact sales for 3D model of the module
Weight(Without
<2.5Kg
packaging)
Cooling mode Forced air cooling, built-in fan (with linear speed regulation function)
Output current(A)
Output current(A)
Output current(A)
48Vdc≤Input voltage≤60Vdc
Percentage of output power
Environment temperature(℃)
Output current(A)
Figure 1-1 Efficiency curve
IPT573000DCG1 User Manual
1.6 Other features
Item Index
Protective characteristics
The minimum protection voltage is 61V without locking, and the protection return
Input over voltage
difference is 2V~4V. During protection, visible light alarm should be issued and
protection
reported to CSU.
The minimum protection voltage is 61V, and report to CSU. Visible light alarm signal
Output over voltage
should be sent during protection, and the protection will be locked for 5 minutes, and
protection
then the module will restart.
The maximum protection voltage is 36V without locking, and the protection return
Input under voltage
difference is 2V~4V. During protection, visible light alarm should be issued and
protection
reported to CSU.
Output under The maximum protection voltage is 36V without locking, during protection, visible
voltage protection light alarm should be issued and reported to CSU.
Output over current 65~75A, automatic shutdown protection, and lock, need to manually power on to
protection restore the output. Visible light alarm signals should be sent during protection.
Environmental over If the ambient temperature exceeds the operating temperature range of 75 ℃, report
temperature the alarm to the CSU and send an over temperature alarm to the monitoring system.
protection The protection does not lock, and the return difference is 8 ℃ to 15 ℃.
Internal over
When the temperature of the internal devices of the module is too high, it should be
temperature
protected to prevent malignant faults such as fire, and the protection is not locked.
protection
When a short circuit fault occurs on the output side, the output is automatically shut
Short-circuit
down and reported to CSU. When the fault is rectified, the power supply returns to
protection
normal.
Fault isolation When a power supply module fails, it does not cause other modules in the system to
function malfunction.
Protection is not locked, the alarm information is reported to the CSU and a visible
Input power failure
light alarm is generated.
When the fan fails, the module turns off the output, and the alarm information is
Fan failure
reported to the CSU and a visible light alarm is issued.
CAN
communication The module outputs normally, and the alarm information is reported to CSU and a
failure visible light alarm is issued.
Authentication&
Production Conform to IEC62368
compliance
Reliability
Acoustic noise
The A-weighted sound power level Lwad of the whole machine is not higher than
Index
55dB(25°C±2°C)
The rear connection adopts the golden finger connection mode, and the output golden finger socket
specifications are shown in the following table.
The definition of each gold finger pin is shown in the figure below:
底面视图 顶面视图
Bottom View 10 9 Top View
8 7
6 5
4 3
2 1
1 2 3 4 5
There are three LED indicators on the front panel of the module, which can be used to indicate the running,
alarm, and fault information of the module. Indicators are defined as follows:
Fan failure
DANGER
It is forbidden to extend your hand into the module slot to prevent electric shock.
Non-professional maintenance personnel are not allowed to insert, remove or replace the DCDC module
with power on.
ATTENTION
Indoor scene DCDC module after packing and unpacking, suggest to electricity within seven days, if not
timely access to electricity, you need to place the DCDC module to indoor, dry, non-corrosive gas
environment.
Outdoor scene DCDC module after packing and unpacking, Suggestions on electricity in 24 hours, if not
timely access to electricity, you need to place the DCDC module to indoor, dry, non-corrosive gas
environment.
Module is installed, must through the fixed screw on the front panel, the module and slot fixed tightly.
Otherwise, the vibration during the operation of the product will cause the module to slip out of the
DANGER
Be careful when unloading, the surface of the DCDC module may be very hot when running.
ATTENTION
1、Removing a DCDC module from a running system will cause a system alarm. After the DCDC module is
replaced, the system monitoring module must be reset. For additional information on DCDC module
replacement, refer to the separate documentation for the relevant power system or monitoring module.
2、The lock frame mounting of the DCDC module is located on the right side of the DCDC module cross latch
module. The dowel pin and module handle are interlinked.
Steps
1. When replacing the module, loosen the screw on the handle of the module (turn several turns
counterclockwise to loosen the screw) and pivot handle 90 degrees to the open position.
2. Grab the handle and pull the module forcefully from the frame.
3. When replacing the module, loosen the screw on the module (turn several turns counterclockwise to
loosen the screw) and pivot handle 90 degrees to the open position.
4. Place the module in the mounting position of the rack with the handle in the open position and push the
module fully into the rack.
5. Push the handle into the front panel of the module to secure the module to the rack, then tighten the
screws on the handle.