Fast Response Contact Monitoring LE FRCMA I
Fast Response Contact Monitoring LE FRCMA I
Specification
Supply Voltage 25.3 ~ 39 VDC
Average Current 630μA (Typical)
Features Consumption 6.3mA (Alarm)
• Single input contact monitor SCI On Resistance 40m ohm Max. (Normal Condition)
• Fast, reliable contact monitoring utilizing the LIFECO DCP (Digital SCI Fault Detection
Communications Protocol) 12 volts (Typical)
Threshold
• Two different mounting configurations SCI Isolation Current
• 127 devices can be used per DCP loop (Short Circuit 10mA (Typical)
• Bi-colored indicating LED provides module status (Both Models) Condition)
• Yellow LED indicates a short circuit condition (FRCMA-I only) Maximum Quantity Per
• Can be programmed to monitor Normally Open (NO) or Normally 127
Loop
Closed (NC) contacts in Class B
Dimensions 4.2"W x 4.7"H x 1.4"D
• Operates on Class A or Class B SLC loop
Ambient Temperature 32°F (0°C) ~ 120°F (49°C)
• Accepts up to 14 AWG wire
Mounting 4" square electrical box
Relative Humidity 90% RH Non-condensing
Operation
The LIFECO LE-FRCMA/-I Fast Response Contact Monitoring Engineering Specification
Modules are designed to be used with pull stations, water flow
switches, and other applications requiring the monitoring of dry The contractor shall furnish and install where indicated on the
contact alarm initiating devices. The interrupt driven Digital Com- plans, addressable contact monitoring modules LIFECO
munications Protocol (DCP) combines maximum communication LE-DCP-FRCMA/-I. The modules shall be UL listed and compatible
reliability and fast response to emergency conditions. Two different with the Fire alarm control panel. The device address shall be
mounting configurations are provided to meet a wide range of electrically programmable and stored in EEPROM.
applications. The LE-FRCMA/-I contact monitoring module does
not require a separate 24 VDC power source. The LE-FRCMA/-I shall be supplied with a plastic face plate and
shall be suitable for mounting to a 4" square or doublegang electri-
Each addressable contact monitoring module is programmed with cal back box. The LE-FRCMA/-I shall provide a monitor LED that is
its own unique Signaling Line Circuit (SLC) loop address. The device visible through the face plate. LE-FRCMA-I shall provide a SCI LED
address is electricallyprogrammable and stored on onboard that is visible through the face plate.
EEPROM. Up to 127 devices can be placed on the LIFECO DCP
SLC loop.
Wiring Diagram
LE-DCP-FRCMA/-I
WIRING DIAGRAMS FOR CLASS A (STYLE D) WIRING NOTE: CLASS A can only monitor N/O contacts
E.O.L. DEVICE
PART NUMBER
0400-03180
Lichfield Fire & Safety Equipment Co.
LE-DCP-FRCMA-I
TB1 TB2
LIFECO
ANY NUMBER OF UL LISTED N/O CONTACT CLOSURE E.O.L. DEVICE
DEVICES MAY BE USED . DO NOT MIX FIRE ALARM PART NUMBER
INITIATING OR SUPERVISORY ON THE SAME MODULE 0400-03180
FIGURE 2B
In line with our policy of continuous product improvement LIFECO reserves the right to modify specifications without prior notice.