SECTION 13341
INSTRUMENTATION AND CONTROL SYSTEMS
INSTRUMENTS — FLOW DEVICES
PART 1 GENERAL
Ld
12
13
14
15
16
17
1.8
SCOPE OF WORK
A. Referto Sections 13300.
B. This section covers the furnishing, installation, and services for the field-mounted
instruments as detailed on the Drawings and in the Loop Diagrams. All equipment to be
supplied for installation in the field shall have aluminum tags with the Device ISA TAG
No. attached prior to delivery.
C. Related Work
1. Refer to Section 13300.
2. Instrument List included at end of this section.
QUALITY ASSURANCE
A. Refer to Section 13300.
REFERENCE STANDARDS
A. Refer to Section 13300.
SYSTEM DESCRIPTION (NOT USED)
SUBMITTALS
A. Refer to Section 13300.
DELIVERY, STORAGE AND HANDLING (NOT USED)
PROJECT / SITE REQUIREMENTS (NOT USED)
GUARANTY
A. Inaddition to Refer to Section 13300,
B. Imaddition to the Manufacturer’s standard guaranty for individual components, the
Contractor shall retain the services of qualified factory-trained servicemen to correct all
defects due to faulty design, calibration, materials or workmanship of all instruments and
controls provided under this project, commencing with the successful completion of start-
up and extending throughout the Guaranty period stated in the General Requirements.
‘cM
Biological Sludge Thickening Facility Instrumentation and Control Systems Instruments — Flow Devices
June 2008, 19341 -11.9 SPARE PARTS
A. Refer to Section 13300 for spate part and test equipment requirements.
PART 2 PRODUCTS
2.1 GENERAL REQUIREMENTS
A. Refer to Section 13300 for general requirements of all instrumentation and control
equipment.
2.2. MAGNETIC FLOWMETERS
A. Flow Element:
1. Type:
a. Pulsed DC type.
2. Functional/Performance:
a
b.
a
3. Physical:
a.
b.
c
a.
f
Operating Temperature: Process liquid temperatures of minus 10 to 70 degrees C
and an ambient of minus 10 to 60 degrees C.
Radio Frequency Interference (RFI) protection: RFI protection shall be provided
as recommended by the manufacturer,
Pressure rating: Equal to piping system where meter is installed.
Additional: Meter shall be capable of running empty indefinitely without damage
to any component.
Metering Tube: 304 stainless stee! or equivalent.
Flanges: ANSI 150 Ib. or DIN PN 16 carbon steel, as required by the piping
system, unless otherwise indicated.
Liner: Polyurethane unless otherwise indicated on the Drawings or in the
Instrument Device Schedule.
Electrodes: 316 stainless steel, bullet nosed or elliptical self-cleaning type unless
otherwise noted.
Housing: Meters below grade shall be suitable for submergence for up to 48
hours to a depth of 30 ft (9m). Meters above grade shall be NEMA 4X ([P65).
‘Where hazardous areas are indicated on the Drawings, the equipment shall be
rated for that area.
Finish: All external surfaces shall have a chemical and corrosion resistant finish.
4. Accessories/Documentation Required:
b.
Factory calibration: All meters shall be factory calibrated. A copy of the report
shall be included in the O&M manual.
Grounding: Meter shall be grounded in accordance with the manufacturer's
recommendation. Provide ground ring, ground wires, gaskets, ete., as required.
All materials shall be suitable for the liquid being measured,
Signal cable for installation between the flowtube and the transmitter, Length
shall be as required by installation indicated on the Drawings.
Instrumentation and Control Systems instruments — Flow Devices Biological Sludge Thickening Facility
PAWASA\BIOTHICKENING DESIGNISPECS\FINAL BID SET SPECS - JUNE 2008\FINAL DIV 13113341 18C -
INSTRUMENTS - FLOW DEVICES.D0C.
19341 -2
June 20085.
Maanficturer:
ABB Instruments MagMaster.
Krohne OPTIFLUX 2000.
Rosemount Series 8700.
orequal
pore
B. Flow Converter/Transmitter.
1
2.
3.
4.
‘Type:
a. Micro processor based, intelligent transmitter compatible with flowtube provided.
b. Mounted remote from the flowtube.
Functional/Performance:
a. Accuracy (including flowtube): Plus/minus 0.5 percent of flowrate.
b. Operating Temperature: -10 to 50 degrees C.
¢. Output: Isolated 4-20 mA with HART protocol. Current output adjustable over
the full range of the instrument.
d. Diagnostics: Self diagnostics with on screen display of faults.
e. Display: Digital indicator displaying flow in engineering units indicated in the
Instrument Device Schedule.
£. Totalizer: A fully configurable totalizer integral to the transmitter. Totalized flow
shall be displayed.
g. Empty Tube Zero: ‘The transmitter shall include a feature that will lock the output
at zero when no flow is detected. The empty tube zero feature shall be enabled
automatically when the transmitter detects no flow or manually through a contact
input.
Physical:
a. Transmitter shall be suitable for surface or pipe stand mounting.
b. Enclosure shall be NEMA 4X (IP65).
c. A/C power will be as specified in Section 13300.
Manufacturer:
a. ABB Instruments MagMaster Transmitter.
b, Krohne Optiflux IFC 300.
c. Rosemount Series 8712.
d. OrEqual.
2.3 THERMAL DISPERSION FLOW SWITCHES
AL Type:
2.
Thermal dispersion flow switch with integral electronics enclosure.
Inline with flow body or insertion type as indicated on the Drawings or in the
Instrument Device Schedule.
B. Function/Performance
Range: 1 to 125 ft/s (0.3 to 38 m/s) in air.
2. Process Operating Temperature: ~40 to 170 degrees C.
3. Operating Temperature for Electronics: -40 to 60 degrees C.
4. Accuracy: Plus or minus 5 percent of reading.
com
Biological Sludge Thickening Faciity lnstrumentation and Contol Systems Instruments - Flow Devices,
June 2008
19341 -35. Repeatability: Plus or minus 0.5 percent of reading.
6. Output: DPDT contacts rated 6 A at 120 VAC adjustable over the range of the
instrument.
C. Physical:
1. Wetted parts to be 316 stainless steel.
2. Electronics head to be NEMA 4X (IP65) for non-hazardous process gases and
explosion proof approved for Class 1, Division 1, Groups C and D (Ex d TIC) for
hazardous process gases or where located in a hazardous area.
3. A/C power will be as specified in Section 13300.
D. Accessories Required:
1. For insertion type flow elements a hot tap assembly including a ball valve and packing
gland that will allow removal of the sensor without shutdown of the process, shall be
provided. ‘The hot tap assembly shall be installed in a welded fitting on the pipe.
FE, Manufacturer(s):
1. Fluid Components International FLT93-F.
2. Equal.
PART3 EXECUTION
3.1 GENERAL
A. See execution requirements specified in Section 13300.
END OF SECTION