Professional Documents
Culture Documents
MZX Fire Alarm Control Panels-T2000: From Firmware Versions 20 To 22
MZX Fire Alarm Control Panels-T2000: From Firmware Versions 20 To 22
Control Panels-
T2000
From Firmware versions
20 to 22
User manual
120.515.921_MZX-P-U-
T2000
Contents
3 Functions ....................................................................................................................... 13
3.1 Access Levels ............................................................................................................................. 13
3.1.1 Logging On ............................................................................................................................................................................................... 15
3.2 Valid Values................................................................................................................................. 15
3.3 Using the Menus......................................................................................................................... 15
3.3.1 Network and Non-Network Addresses .......................................................................................................................................... 17
2 Operating Instructions
2.1 Indicators and Controls Key Usage
The front panel is shown in Fig. 1. The numbered items in Used to enter the number 2 or letters A, B or
the figure are explained in the following paragraphs. Your 2
ABC C.
panel version may not match the figure exactly, but the Similarly for the rest of the number keys.
....
same items will be present, although perhaps not in the
positions shown.
WXYZ
9
Function Keys
Use these keys (F1 to F5) to carry out the functions
6 displayed on the bottom line of the LCD display. These
functions vary between the different display screens.
4
5 Enable Keyswitch
This can only be changed using a key.
You need to switch this from 0 (OFF – disabled) to 1 (ON –
Fig. 1: MZX Front Panel (example T2000)
enabled) before you can use most of the Control keys
1 –LCD Display
2 –Alphanumeric keypad (below), and the menus. (Note that which of the menu
3 –Function keys items you can use is also controlled by your level of access.
4 –Enable Keyswitch For details see section 3.1 “Access Levels” on page 13.)
5 –Control keys
6 –Status LEDs
Control Keys
Note: Fig. 1 is for illustration purposes only.
There are seven control keys, as follows:
LCD display SILENCE BUZZER - used to silence the internal buzzer.
A 640 character backlit LCD alphanumeric display, SILENCE/RESOUND - used to silence/resound
arranged in 16 rows of 40 characters. external sounders and other types of annunciators.
This is used to display user interaction information, such as RESET - used to reset the system after an alarm has
alarms, status messages and responses to user input. been resolved.
DAY/NIGHT - used to switch between Day mode
Alphanumeric Keypad (DAY MODE LED lit) and Night mode (DAY MODE
LED not lit).
Alphanumeric keys used for entering access codes, text
strings or general information. INVESTIGATE DELAY - used to end signalling delay
time and start the investigation time.
Key Usage SPARE - configurable to customer requirements.
Used to enter the number 0 or a space. FIRE ALARM- indicates that the system is in fire alarm
0
condition. The responses are found in the fire alarm
procedure for the vessel or installation. Typically the fire
Used to enter the number1 or special alarm annunciators, such as sounders and beacons,
1* symbols. activate.
Table 2: Alphanumeric keys and arrow keys
Status LEDs
The status LEDs light to alert you to unusual conditions Thorn Security panel
(apart from POWER ON which should normally be lit). Mon, 15-Mar-10
They are arranged in the following groups: 14:51
The format of the fault message in Fig. 4 is as follows: To do this press the More (F5) key, to see the
The top line shows the Zone and point number in fault “unaccepted” events. These are events that you have
condition. not yet acknowledged that you are aware of. You might
also see earlier events that you have left unaccepted as
The second line shows the zone description.
a reminder of an issue that still needs resolving. (Details
The third line shows the point description. of accepting events are provided below.)
The fourth line shows the type of fault. These events are shown in categories, with various
To see these next two lines, you might have to press the priorities (for details of the categories see 4.5.3 “Filter”
Info (F2) key to clear the general information: on page 24). Press the More again to step to the next
The fifth line shows the date and time. category. Press the All (F4) key to see all the
unaccepted events (the All key label may take a second
The sixth line shows the device type.
or two to appear).
The seventh line always shows Unaccepted. Details of
4 Try to resolve the situation. Do this by, for example,
what this means are provided below.
restoring the mains supply, or de-isolating an isolated
point.
If there is a fault that cannot be cured, contact your local
2.5 Event Operator Actions supplier and arrange for a service visit.
DANGER 5 Repeat from step 2 in case there are any more active
Incorrect responses to event alerts events.
may lead to death, serious injuries or 6 Accept the events that you have resolved (as a double
damage to property. check you will be again reviewing the events as part of
For example it is important that alerts the accepting process). You use the Accept Events
for mains failure faults are acted upon. menu option. For details see section 4.1 “Accept
(The battery backup will maintain Events” on page 18.
panel operation for a period, but this Note that the Operator Window will continue to display
will eventually fail.) an unaccepted event, if one exists, so the “normal”
This guide includes step by step display will only be shown once all events are accepted.
instructions on carrying out
operations on the panel, but users
must ensure the operation is Even if an event is still “active”, accepting it will
appropriate, according to the local remove it from the Operator Window (but it will
site procedures. still contribute to the “count” displayed in the
General Window, so this count is the best
indication of any outstanding problems).
For details of handling pre-alarm warning events, alarm
warning events and alarm events, see section 2.7 “Alarm
Operator Actions” on page 10. The remainder of this 2.6 Alarm Panel Behaviour
section covers non-alarm events.
Depending on the configuration, the panel may respond in
stages to device activations, as described below.
How to respond if you are alerted to an event
1 Optionally press the SILENCE BUZZER key.
2.6.1 Alarm Warnings
2 Check whether there are any other “active” (not clear)
events. These may be related, helping you gain an You may see an Alarm Warning type message (as well as
overview of the situation, or they may be more urgent. the internal buzzer sounding).
(Although note that there is a priority based selection for This will be because the control panel has been configured
the event shown in the Operator window.) for a partial alarm response if only one detector is in alarm.
To see the active events press the Not Clr (F4) key. You The panel will be waiting for another device to alarm, before
now see, for example, mains failure events that have not issuing an alarm.
been “cleared” by a restoration of the mains supply.
These are shown as the Unrestored Events list.
2.6.2 Pre-Alarm Warnings
3 Check whether there are any other events that may not
be active, but might have been active in the past and You may see a a Pre Alarm Warning type message (as
cleared themselves. Again these may be related. well as the internal buzzer sounding).
This will be because, for example, a detector has identified In an alarm situation, follow the local site procedures.
a build-up of smoke or heat that might be the result of a fire,
but the alarm threshold has not yet been reached.
The panel will be waiting for the alarm threshold to be DANGER
reached, before issuing an alarm. In an alarm situation, inappropriate
use of the panel functions may lead to
death, serious injuries or damage to
2.6.3 Alarm property.
The panel issues an alarm as follows: This guide includes step by step
The internal buzzer sounds continuously. instructions on carrying out
The red FIRE LED lights. operations on the panel. However you
must ensure the operation is
The (SOUNDERS) ACTIVATED LED lights.
appropriate for the circumstances,
The (SIGNALLING) ACTIVATED LED may light (see according to the local site procedures.
section 2.7.1 “Alarm Investigate Option” on page 10).
The LCD displays a message in the format shown in
Fig. 5. 2.7.1 Alarm Investigate Option
The First Fire window shows the first fire to occur, In Day mode you can delay the fire alarm signalling. This
including details of the zone number and description, gives you time to investigate the alarm, and cancel the
and the point address. signalling if you discover the alarm is a false one (for full
The Last Fire window shows the same information, but details see section 2.3 “Selecting Day or Night Mode” on
is dedicated to the last zone that entered alarm. page 8).
This window is zonally based because it is more There is no delay option, and the signalling immediately
important to know that a fire has spread to another zone activates, in these circumstances:
than to know that the fire has spread to a second Night mode is active.
detector in the first “on fire” zone. A call point was activated.
To fulfil this requirement, the window updates to show There is a sounder fault.
the last fire, but only if this is the first fire to occur in its
zone.
The number of alarms (002) is displayed at the right DANGER
hand side of line 5 in the fire window. When investigating an area of a
(There may be other event alerts, that you can see using building protected by a CO detector
the More (F5) key, for example. For details see 2.7 that has raised an alarm, there is a
“Alarm Operator Actions” on page 10.) particular danger of fires not being
First Fire
detected, leading to possible death,
Zone 002 B002 serious injuries or damage to
1st Floor Corridor property.
Heat Sensor Device
Last Fire 002 This is because CO detectors are liable
Zone 001 B005 to raise an alarm earlier than other
Stock room
Photo Sensor Device types of detector, so as no other
General Information detectors are in alarm you might
dismiss this as a false alarm. The CO
detector may also have alarmed
before the fire is visible (this applies
particular to fires in hard-to-access
Menu Passcode Not Clr More areas, such as between tightly packed
materials or in cupboards and storage
Fig. 5: Alarm Window rooms, or in areas far away from the
detector).
You should take care in your
2.7 Alarm Operator Actions investigation, and not clear an area as
This section gives options for responding to pre-alarm being safe until you are absolutely
warnings, alarm warnings and alarms. sure.
How to investigate an alarm conditions. This is not permanent, as you can re-activate the
1 On the alarm occurring, follow the procedure specified sounders if necessary.
for the vessel or installation. If you have configured an
investigation delay before the signalling indicator is lit, How to silence the sounders
proceed with steps 2-5.
1 Insert the key into the Enable Keyswitch, and turn to the
2 Optionally silence the buzzer and/or sounders using ON (1) position.
the SILENCE BUZZER and SILENCE/RESOUND
Press the SILENCE/RESOUND key.The system
keys.
responds as follows:
3 In the LCD General Window, note the Del mm:ss
– The sounders are silenced.
(minutes:seconds) indication. Before this delay counts
down to 0, press the INVESTIGATE DELAY key. – The (SOUNDERS) ACTIVATED LED goes out.
Note that you now see an Inv mm:ss – All other outputs remain activated.
(minutes:seconds) countdown of the remaining The LCD display remains on and shows the alarm
investigation time (updates in 5 second steps). Once type and the complete zone identification. A Sound
this reaches 0 the signalling activates. SIL message appears.
4 You can now determine the cause of the alarm and
carry out the necessary measures. If you need to re-activate the sounders, press the
SILENCE/RESOUND key again.
Note that you can investigate any other current events
using the More and All keys, as you can with non-alarm
events. For more information see steps 2 and 3 in 2.7.4 Resetting the Panel
section 2.5 “Event Operator Actions” on page 9. Resetting the panel “cancels” the alarm, returning the panel
5 If you confirm there is a fire, you can override the delay to the state prior to the alarm (apart from the alarm now
and activate signalling by pressing the FIRE ALARM being logged as an event).
key or by activating a call point.
6 If you determine there is a false alarm, you can reset the How to reset the panel
control panel, as described in section 2.7.4 “Resetting 1 Silence the sounders as described above.
the Panel” on page 11. 2 Press the RESET key. The display will show a
“resetting” message for approximately 20 seconds,
after which the reset will be complete.
2.7.2 Fire Alarm key
If there are no faults or other abnormal conditions, the
With the Enable Keyswitch set to ON, pressing the
LCD display will now show the normal screen, as shown
FIRE ALARM key will produce the same response as an
in Fig 2 on page 7.
alarm (see 2.6 “Alarm Panel Behaviour” on page 9).
The exception is that the LCD will display the type of screen
shown in Fig. 6.
2.8 Auxiliary Display Devices
First Fire
Zone 000 RB002R12 2.8.1 General
System Zone
Evacuate Button The system may be fitted with printers and repeaters.
d
General
001 Information
2.8.2 Repeaters
A repeater allows the controller to be operated from a
General Not Available remote location and provides remote indications of the
state of the controller. The front panel of the repeater is
identical to that of the controller (see Fig. 1 on page 6) and
all controller operations may be performed at the repeater
Menu Info Passcode Not Clr More panel.
3 Functions
The control panel functions allow you to view the event log, Customer Operator 7
set the date and time, and so on. ....
Customer Operator 1
Automatic Log off Select the menu options by their number (press the
You are automatically logged off after a period appropriate number key). Each option leads to a further
of inactivity. screen, which may present further options.
Details of the menu screens are provided in section 4
“Menu Details” on page 18.
In using the menus you always use combinations of the
3.2 Valid Values same basic methods – to navigate between the various
When using the menus you will be entering various values, settings in a screen for example. To avoid repetition this
such as point numbers. guide does not provide full step by step details for each
In general, you can set these to any value, including invalid screen. Instead, the illustration below serves as an example
values. If you make an invalid setting there will be an audible of how you use the basic methods. The illustration is based
or on screen warning. on discovering the status of a point.
As an example if you enter a loop address of “A132”, and a
device has not been configured into this address, you will How to discover the status of a point
see an “Invalid entry!” message. 1 Enter your passcode to display the Main Menu (this is
If you are in a position to use a particular option, you will not strictly necessary when viewing status, and is only
probably know which are the valid values, that you will included for the purposes of the illustration):
using.
2 Press the 2 key to display the View Status menu: 5 The loop setting (A) does not need changing.
You press the >> key (F2) to move the highlight to the
View Status
Thorn Security panel point number:
Mon, 15-Mar-10 1 - Point View Status
14:51 2 - Point I/P only Thorn Security panel
3 - Point O/P only
High Street Office 4 - Zone Mon, 15-Mar-10 Point
5 - Zone Maps 14:51 Loop
General 6 - Network Status Loop Point
7 - Commis. O/View High Street Office A 001
General
Back
3 Press the 1 key to display the next menu: Fig. 12: View Status Point Highlighted
View Status
Thorn Security panel 6 Press the + key (F4) to increment the point number (or
press the 2 key):
Mon, 15-Mar-10 Point
14:51 1 - Loop Point View Status
2 - RBus Point Thorn Security panel Point
High Street Office 3 - Local I/O Point Panel
Thu, 18-Aug-11 01
General 11:27
Loop Point
High Street Office A 002
General
Flt P 011
Back
Fig. 14: View Status Point Fig. 15: View Status – Panel Number
4 Menu Details
A typical Main Menu screen is shown in Fig. 16. View Status
For information on accessing this, see section 3.1.1 Thorn Security panel
“Logging On” on page 15 (this section also explains how Mon, 15-Mar-10 1 - Point
you may not be able to see all the menu options). 14:51 2
3
-
-
Point I/P only
Point O/P only
High Street Office 4 - Zone
Main Menu 5 - Zone Maps
Thorn Security panel General 6 - Network Status
1 - Accept Events 7 - Commis. O/View
Mon, 15-Mar-10 2 - View Status
14:51 3 - Isolate/De-Isol
4 - Time / Date
High Street Office 5 - Event Log
6 - View/Print Data
General 7 - Service
8 - Configuration Back
9 - Test Buzzer,
LEDs & Display Fig. 18: View Status
Alarm Count: 0021
Accept Events
Thorn Security panel
Mon, 15-Mar-10 Zone 000 R10
14:51 System Zone
Battery Fault IP Back
High Street Office
BATTERY FAULT Fig. 19: View Status, point
General
15-Mar-10 14:01:02
Fault 02 Digital Input Select the option for the type of point, as appropriate. The
types of point are as follows:
Loop Point: Points on the addressable loop.
1000
RBus Point: Points on the Remote Bus, such as I/O
Back Accept << >>
expansion boards.
Fig. 17: Accept Events Local I/O Point: Local points that are not on the
Remote Bus or addressable loop.
information includes the point’s zone number and Specify the appropriate Point and RBus numbers. Select
description, the sector description (if applicable), the device the Category option according to what you want to
description and the loop ID. For input devices, the Output interrogate at your specified numbers. Select from this list
column is not applicable and will always be blank. Similarly, of options:
for output devices the Input column will be blank. Real: Physical items (as opposed to “logical” items), that
View Status are directly connected at the RBus point.
Thorn Security panel XBus: Further expansion hardware.
Mon, 15-Mar-10 Point Pseudo: “Logical” items (as apposed to “physical”
14:51 Zone 006 A007
Zone 06 items), such as diagnostic status indications.
High Street Office Call alarm in room
CP 820
General Input Output Local I/O Points
Normal After selecting the Local I/O option in Fig. 19 above, you
see the type of screen shown in Fig. 21 above, but without
the RBus item.
Back For Category, the same options are available, but with the
addition of these options:
Fig. 20: View Status Point Details Timer: Timed events such as switching events
between Day and Night modes.
The status for input devices can be one of the following: Menu: Additional menu items that may have been
Normal configured into the panel. These can be enabled or
Fault
disabled.
Active
Pre-Alarm 4.2.2 Point I/P only
This Point I/P only option refers to input points on the
The status for output devices can be one of the following: loop, which are, for example, call points and detectors.
On
If you specify an output point address, this will be indicated
as “invalid”.
Off
Pulse 1
4.2.3 Point O/P only
Pulse 2
This Point O/P only option refers to output points on the
loop, such as sounders.
RBus Point
If you specify an input point address, this will be indicated as
After selecting the RBus option in Fig. 19 above, you see “invalid”.
the type of screen shown in Fig. 21.
View Status
Thorn Security panel 4.2.4 Zone
Mon, 15-Mar-10
14:51 Point Use this Zone option to see a summary for a set of
conditions (Alarm, Fault, Isolate and Walk Test)
High Street Office RBus Category
00 Real assessed on all points in the zone.
General
Point
After entering the zone number, you see the type of screen
01 shown in Fig. 22.
Fig. 22: Selecting Zone Fig. 24: Current status - Zone Maps
The status might be: The screen shows all the zones. The zones with your
Either: Yes or No (one or more points have the chosen condition are marked (with an A in this example, for
condition, or no points have the condition). “Alarm”).
Or one of: None, All or Partial (no points have the The zones are in a table, where columns correspond to
condition, or all points have the condition, or more than “units” and rows correspond to “10s” (so the first item in the
one but not all points have the condition). “40” row is zone “40”, the next is “41” and so on).
The zones have a condition if any of their points have the
condition (so zone 41 is in Alarm if any of the points in zone
4.2.5 Zone Maps 41 are in Alarm).
Use this Zone Maps option for a quick overview of the For the 3 - Test option the condition is only marked if you
state of the zones. Fig, 23 shows the type of screen set the Area option of the Walk Test to All (see page 29).
displayed.
The options 5, 6 and 7 of Fig. 23 are similar to the first four,
Zone Maps except they relate to outputs. For these you choose a status
Thorn Security panel condition from Active, Faulty or Isolated. The zone map
Mon, 15-Mar-10 1 - Alarm display will be similar to the one for the first four options.
14:51 2 - Fault
3 - Test
High Street Office 4 - Isolated Inputs
5 - Protection Eqp. 4.2.6 Network Status
General 6 - Sounders
7 - Plant Equipment Use this Network Status option to check the
communications with other control panels in the network.
This option may not be available, depending on the
configuration of your control panel. Fig, 25 shows the type
of screen displayed.
Back
Network Status
Fig. 23: Zone Maps, choose item Thorn Security panel
Nodes 0123456789
Mon, 15-Mar-10 0 Mm.......
The options 1 to 4 relate to status conditions for inputs. 14:51 10 ..........
Choose the condition option you are interested in, to see a 20 ..........
High Street Office 30 ..........
screen of the type shown in Fig. 24. 40 ..........
General 50 ..........
60 ..........
70 ..........
80 ..........
90 ..........
Back
Note that in the “Customer Operator” access levels, only 4.3.4 By Function
points on the addressable loop can be isolated or de- Using this By Function option you can isolate or de-isolate
isolated. multiple devices of the same function in one operation.
As an illustration, the steps required to isolate a point are How to use the By Function option
provided below.
1 From the Isolate/De-Isolate screen select 4 - By
Function.
How to isolate a point 2 Select the function. You can choose from:
1 From the Isolate/De-Isolate screen select 1 - Point. – Detectors
2 Specify the point type and address. This is described in – Callpoints
the example in section 3.3 “Using the Menus” on
– Alarm I/Ps (combination of “Detectors” and
page 15.
“Callpoints”)
You see the type of screen shown in Fig, 28.
– Sounders
Isolate/De-Isolate
Thorn Security panel
These remaining items refer to any interfaces to
Point external equipment that may be fitted to the loops.
Mon, 15-Mar-10
14:51 Zone 01 - 1st Floor – Protection Eqp.
Corridor
High Street Office – Extinguishing
CO Device
General 811PC – Plant Equipment
Status IP: Normal
3 Specify the zone in which to isolate or de-isolate (for
example 001).
1 - Isolate
4 Choose Isolate Opts (options) or De-Isolate Opts.
5 If isolating, choose one of the “isolate options”. These
Back
are All, In Fault, Active and Not Normal
Fig. 28: Point Isolate (combination of “Active” and “In Fault”).
Some of these may not be available. For Sounders for
3 Press the 1 key to isolate. The text 1 - Isolate changes example, only All and In Fault are available.
to 2 - De-Isolate (both immediately, and also when you If de-isolating, choose one of the “de-Isolate” options.
return to this screen to de-isolate the point. Follow the These are All or Normal.
same steps to return to the screen).
Isolations count
To confirm your changes press the Save (F5) key.
When isolating you may see a Matches and a
To cancel your changes press the Back (F1) key and
Successes number indicated.
respond with a “No” to the “save changes” prompt.
For example you might use All SND, and see:
Matches 24
Successes 23 4.4.2 Summer/Winter
Here Matches is the number of units The panel automatically adjusts to stay synchronised with
(sounders) which were liable to be isolated, British Summer Time.
and Successes is the number of units that Use this Summer/Winter option to review the settings.
actually became isolated (the two numbers Fig. 30 shows the type of screen that will be displayed.
being different because a sounder was already Fig. 30 is showing the dates on which the time will be
isolated). advanced, and by how much, at the start of summertime.
Press the Winter (F5) key to see the dates on which the
time will be retarded, at the end of summertime (F5 then
4.4 Time/Date changes to Summer so you can switch back).
Use this Time/Date option to make the time and date and Summer/Winter
settings, and review the daylight saving adjustment Thorn Security panel
Summertime
settings. Mon, 15-Mar-10 29-Mar-09 +1h
14:51 28-Mar-10 +1h
27-Mar-11 +1h
4.4.1 Set Time/Date High Street Office 25-Mar-12
31-Mar-13
+1h
+1h
Use this Set Time/Date option to set the time and date. General 30-Mar-14 +1h
29-Mar-15 +1h
Fig. 29 shows the type of screen that will be displayed. 27-Mar-16 +1h
26-Mar-17 +1h
Time / Date 25-Mar-18 +1h
Thorn Security panel
Date : 15-Mar-10
Mon, 15-Mar-10 Time : 14:15:17 Back Winter
14:51
General
4.5.3 Filter
Use this Filter option to view or print events, selected
according to their category. You use the type of screen
shown in Fig. 34. The screen lists the events in descending Points Isolated
order of priority. Thorn Security panel Input
Total : 004
Event Log Mon, 15-Mar-10 Zone 001 -001 B
Thorn Security panel 14:51 Point Text
1 - Fire + --------------------
Wed, 01-Jan-09 2 - Gas Alert + High Street Office 001 -002 B
14:51 3 - Pre Alarm - Point Text
4 - Supervisory - General
Company Name 5 - Fault -
6 - Isolate -
General 7 - Test Mode -
8 - Warning -
9 - Information -
Fig. 34: Event Log – Filter To switch between viewing isolated inputs and isolated
outputs, press the “Output” key (F2).
To include an item for printing, note its number and press Points that are both input and output points can appear in
this key. For the item, this changes the – to a + (as for 1- Fire either list, or both lists, depending on the function(s) that are
and 2 - Gas Alert in Fig. 34). Press the number key again if isolated.
you need to change back to a –.
4.6.2 Points Untested/Failed
Use this Points Untested/Failed option during a Walk
4.6 View/Print Data Test. For more information see section 4.7.1 “Walk Test” on
Use this View/Print Data option to see status type page 28.
information, either displayed on the screen or printed. The option is abbreviated to Pts Unt./Failed on the
Fig. 35 shows the type of screen that will be displayed. screen.
Start by selecting the category of information you want to
see. You might then need to specify an address.
4.6.3 Point Values
View/Print Data
Thorn Security panel Use this Point Values option to see a screen of information
1 - Points Isolated on the point. For both the loop and point number, you can
Mon, 15-Mar-10 2 - Pts Unt./Failed
14:51 3 - Point Values set specific values or opt for All. Fig. 37 shows the type of
4 - View Faults screen displayed. The screen shows the device type,
High Street Office 5 - Loop Point Ctrs
operating mode and so on.
General 7 - Active Points
8 - By Function Point Values
Thorn Security panel
Zone 003 A023
Mon, 15-Mar-10 Zone 03
14:51 Heat Sensor Device
801 H
Back High Street Office Real: 801H
Mode: Std R.o.(21)
General Sens: N/A
Fig. 35: View/Print Data 22 ºC (073)
Fig. 36 shows the type of screen that will be displayed. Fig. 37: Point Values
The << (F3) and >> (F4) keys are only available if you
selected the All option.
The raw values sent by the device, before conversion to
meaningful values, are displayed in brackets.
For devices not sending a value, this is shown as (000) and If no faults are found, the type of screen shown in Fig. 39 is
converted to a pre-programmed value (such as -8 °C for displayed.
temperature).
Loop Point Counters
Thorn Security panel
Counter
Contamination up to 20 % Mon, 15-Mar-10 Loop : A
14:51 PASSED
Values in the range up to 20 % do not Configured : 010
necessarily relate to contamination but can High Street Office
occur due to the calibration and the new General
environmental conditions.
General
Back
DANGER
Back While Walk Test mode is active, fires
may go undetected, leading to
Fig. 44: By Function possible death, serious injuries or
damage to property.
Note that Fire Inputs are callpoints and detectors,
whereas a Non-Fire input is, for example, the open/closed This is because the normal response
state of a fire door that the panel controls. (triggering an alarm) to activations in
one or more devices is overridden.
After selecting a function, you see a screen for selecting the
status, as shown in Fig. 45. You should use Walk Test with
caution, and only use Walk Test for as
Fire Inputs short a time as possible.
Thorn Security panel
Now set the options in the screen. As you set the options, Now start to make your tests – by applying smoke, for
other displayed options may change. The options are: example. Alternatively, automatic testing starts.
Panel: Only applies to networked panels. Set this to the While any device is in Walk Test, the Test LED is lit.
panel network address.
Area: Use this to specify the scope of the test. You can
Walk Test
choose All, or Zone (an individual zone) or Point (an Thorn Security panel
individual point). All Inputs
Mon, 15-Mar-10 Selected : 007
Type: For “multiple device” Area settings (such as All), 14:51 Excluded : 000
this is a “filter” setting that you use to specify the type of Been Active : 005
High Street Office Been Clear : 007
detectors to be in test. Choose between Input, Successful : 005
Detectrs, Callpnts, Alarm I/Ps or Sounders. General Curr.Active : 000
There are separate Input and Alarm I/P (input) options TestZ 001
because not all inputs are alarm inputs. Alarm inputs are
detectors and call points, while a non-alarm input might
be used to monitor the open/closed state of a panel-
controlled fire door, for example. Back Details Settings End
With Sounders selected, you can set Loop to All + Fig. 48: Walk test example
FIM. This also permits the inspection of two sounders
connected to the FIM. Sounders’ status is not shown on If you need a reminder of the settings you made, press
the display (see below). The selected sounders will be Settings (F3).
activated in a pulsing mode. As you make the tests, the Fig. 48 screen dynamically
Loop: Use this to (optionally) narrow the scope of the updates. with a summary of the results. There is also a
test to a specific loop, or to specify the loop part of a screen dedicated to individual point results – see Fig. 50 on
point address. page 30.
Mode: Make one of the following settings: The items in the Fig. 48 screen are as follows:
– MANUAL: Apply the test yourself. Selected: Number of devices in Walk Test.
– AUTOMATIC: Use the self-test facility of devices. Excluded: Number of isolated devices in the “scope” of
The self-test is automatically triggered by the control the test, for example.
panel. For more information see the section “Devices Been Active: Number of devices that have been in the
Supporting Automatic Test” on page 30. active state since the test was started.
– 813P: Use this mode instead of “Automatic” to test Been Clear: Number of devices that have been in the
813P detectors (813P detectors do not support the clear state (that is the “not active” state) since the test
Automatic mode). Use the 813P mode in the same was started. This will most probably match the
way as the Automatic mode. The 813P mode is only “Selected” value, as all devices will probably start in the
available if there is at least one 813P detector clear state. (You are unlikely to start the Walk Test with
configured into the system. devices active.)
If the 813P detector fails the test, you are advised to Successful: Number of devices that have switched
perform a manual walk test on the unit. This is from the “clear” to the “active” states. This will increase
because occasionally the 813P test produces a false as you test devices, and the test is successful. Again, this
negative (that is it fails the test when it is actually OK). will most probably match the “Been Active” value, as all
Multisensor: This option applies to multi-sensor devices will probably start in the “clear” state.
devices (that are also configured for multi-sensor Curr.Active: Devices currently active.
mode). Select Full if you only want the device to pass as
TestZ: Number of zones with a device in Walk Test.
“Successful” if your test activates all the sensors,
otherwise select Part.
You can only select either Automatic mode (above), or To summarize, if all the devices pass, the Selected and
one of the Multisensor options. Successful values will be the same, and they will also most
probably match the Been Active and Been Clear values.
(But for the results you mainly use the untested or failed
Press the Start (F5) key to enter Walk Test mode.The type status screen, of the type shown in Fig. 50.)
of screen shown in Fig. 48 is displayed.
For a single device test, you see a status screen of the type
shown in Fig. 49.
Back Print
Project Numbers
Menu Points
Use this Project Numbers option to see information
Use this Menu Points option to operate any menu points
relating to the configuration of the panel (the project
that might be configured into the system. Fig. 57 shows the
type of screen that will be displayed. Press the appropriate
number key, to switch from OFF and ON (repeat for ON to
OFF).
High Street Office Choose the type of text you want to change. You may then
General need to specify a particular item (point address for
example).
You see a screen of the type shown in Fig. 60.
Point Text Modify
Thorn Security panel
Back Zone 255 -007 A
Mon, 15-Mar-10
Fig. 58: Configuration 14:51 Old text
Callp. alarm room
High Street Office
New text
4.8.1 Change Text General
Step through the number and letter characters on a key Point Text
with quick repeated presses. Pause after reaching the Use this Point Text option to change the descriptive text
required character. for a point. Follow the steps above.
Press the scroll up key ( ) to switch to upper case text
(capitals).
Zone Text
Press the scroll down key ( ) to switch to lower case text.
Use this Zone Text option to change the descriptive text
When finished press Enter. You will then see a Save data? for a zone. Follow the steps above.
prompt, with Yes (confirm) or No (cancel) options.
To abandon your changes, press the Back key (F1) and
Sector Text
respond with “No” to “Save changes?”.
Use this Sector Text option to change the descriptive text
If you save your changes. you briefly see a “please wait”
for a sector. Follow the steps above.
message. You then see a screen similar to the “Change
Text” screen above, but only allowing changes to the same
type of text. Panel Text
After making all your text changes, select Back (F1), to Use this Panel Text option to change the text that appears
display the type of screen shown in Fig. 61: as High Street Office in the screen examples above.
Follow the steps above.
Configuration
Thorn Security panel
Back
Different editing for info text
Fig. 61: Configuration, Back For info text you automatically start editing the
existing text – you do not need to copy the text
Again you can make more text changes, but only for the using the >> key. Using the >> key deletes all
same type as previously. the text.
Select 9 - Restart to restart the panel, allowing the
changes to take effect.
Test Buzzer, LEDs & Display
Selecting this should momentarily activate the internal
CAUTION
buzzer, all the pixels of the LCD and all the LEDs.
Never use the Back option to avoid
If any of these do not happen there is a fault.
committing changes when the menu option
9 - Restart is displayed. If you do not want to
commit changes, turn the Enable Keyswitch to
OFF.
Failure to comply with these restrictions may
lead to unpredictable effects or system
instability.
5 Routine Checks
5.1 General CAUTION: Follow the regular fire tests procedure for the
vessel or installation. Warn personnel that the fire alarm
In order to comply with the requirements of British Stand- audible and visual annunciators, for example sounders
ard BS 5839 Part 1 or the equivalent local code of practice and beacons, might activate.
for fire detection and fire alarm systems, the installation
must be checked on a regular basis by a responsible mem- 2 Activate a device (either a callpoint or detector).
ber of staff. 3 Check that the system responds as follows:
This is to confirm that the fire alarm control panel and all The control panel’s buzzer sounds in a continuous
ancillary devices are operating correctly. The required rou- tone.
tine checks are described in the following paragraphs. The (GENERAL) FIRE LED on the control panel front
lights.
The appropriate red ZONE STATUS LED flashes.
5.2 Daily Checks The sounders operate as specified in the fire alarm
procedure.
How to do a daily check The LCD display shows the location of the alarm.
1 Ensure the front panel of the fire alarm control panel is 4 Record the device used to initiate the test in the site log
indicating a normal condition (i.e. no alarm or fault LEDs book and reset the fire alarm control panel.
are lit and the LCD is displaying the date and time). 5 Check the condition of the printout on any printers
If the panel is not indicating a normal condition record attached to the system and replace the ribbon if it is
the condition in the log book and take any necessary becoming feint.
action. 6 Ensure that each printer has an adequate supply of
2 Check that any fault recorded on the previous day has paper.
received attention. Record any defect in the log book and take the appropriate
action to remedy this.
Index
A I
Access Levels 13 Indicators 6
Accept Events 18 Info Text menu option 33
Active point - definition 27 Information paragraphs 6
Active Points (View/Print Data) menu option 25 Input – difference to Alarm I/P 28
Alarm INVESTIGATE DELAY key 6
Investigating 10 Isolate/De-Isol menu option 21
Operator response 10 isolated points - discovering 25
Panel behaviour 9 isolating 21
Alarm I/P – difference to Input 28
Alarm Warning 9
Auxiliary Display Devices 11 K
Keypad 6
B
Battery Test menu option 31 L
By Function (Isolate/De-isol) menu option 21 LCD Display 7
By Function (View/Print Data) menu option 25 Fire Window 7
Main Window 7
Softkey Window 8
C Status Window 8
Change Text menu option 32 LCD Repeaters12
Configuration menu option 32 Local I/P Points (Status) menu option 19
Control Keys 6 Logging off 15
Controls 6 Logging on 15
Loop Point Ctrs (View/Print Data) menu option 25
D
Day Mode 8 M
DAY/NIGHT key 8 Main Menu 15, 18
de-isolating 22 Maint. Request menu option 30
Display LEDs 7 Maintenance menu option 30
Menu point
Enabling/disabling 31
E List of 31
Enable Keyswitch 6 Menus - using 15
Entering Passcodes 15 More key 9
Event Log
menu option 23
size 8 N
Network Status (Status) menu option 20
Night Mode 8
F Non-Fire Input - definition 27
Fault Normal operation 7
Operator response 9 Not Clr key 9
Panel behaviour 8
Filter menu option 24
Fire Cycle Count menu option 30 P
Fire Input - definition 27 Panel Text menu option 33
Firmware - covered by guide 5 passcodes – entering 15
Firmware version 31 Point I/P Only (Isolate/De-isol) menu option 19
Function keys 6 Point I/P only (Status) menu item 19
R V
View Event Log menu option 24
RBus point (Status) menu option 19
View Faults (View/Print Data) menu option 26
Repeaters 11
View Status menu option 18
RESET key 6
View/Print Data menu option 25
S W
S/W Versions menu option 31
Walk test
Sector Text menu option 33
Ending 28
Service menu option 28
Setting scope 28
Set Time/Date menu option 23
Starting 28
SILENCE BUZZER control key 6
Walk Test menu option 28
SILENCE/ RESOUND control key 6
Warnings formats 5
Sounders
Silenced indication 11
Silencing 11 Z
SPARE control key 6
Zone (Status) menu option 7
Summer/Winter menu option 23
Zone Display LEDs 7
Zone Maps (Status) menu option 20
Zone Text menu option 33
Company stamp