EXISTING COOLING PIPE SYSTEM

COOLING PUMP, 30M3/H (~ 8,33 l/s), 40mH2O

q V L h=i*L h
Pipe number D [mm] i
[l/s] [m/s] [m] [m] [kg/cm2]

1 8.33 65 2.51 0.100 200 20.0 2.0


Total pressure drop for existing cooling pipe 20.0 2.0
Total pressure drop for existing pipe fitting (30% of Pipe) 6.0 0.6
Grand - Total pressure drop for all system 26.0 2.6
Hight difference 10.0 1.0
Total Pressure Required 36.0 3.6

NEW COOLING PIPE SYSTEM COOLING


PUMP, 30M3/H (~ 8,33 l/s), 40mH2O

q V L h=i*L h
Pipe number D [mm] i
[l/s] [m/s] [m] [m] [kg/cm2]

1 8.33 65 2.51 0.100 280 28.0 2.8


Total pressure drop for existing cooling pipe 28.0 2.8
Total pressure drop for existing pipe fitting (30% of Pipe) 8.4 0.8
Grand - Total pressure drop for all system 36.4 3.6
Hight difference 10.0 1.0
Total Pressure Required 46.4 4.6