Professional Documents
Culture Documents
Air Circuit Breaker
Air Circuit Breaker
-
I B 32 150 3 -
"De-ion"
; • f AIR CIRCUIT BREAKER
Type DH
i
; -vji
m
!*
Type Kv Amps Kva
Vi
i i|
- -
50 DH 250 5.0 1200 250,000
50-DH-250 5.0 2000 250,000
/
75-DH- 150 7.5 600 150,000
- -
75 DH 150 7.5 1200 150,000
75-DH-250 7.5 1200 250,000
;
I
.?1 - -
75 DH 250 7.5 2000 250,000
'
'
' 2
- -
75 DH 500 7.5 1200 500,000
- -
75 DH 500 7.5 2000 500,000
150-DH- 150 15.0 600 150,000
3
! . At
T,
:•
* Courtesy of NationalSwitchgear.com
A
e •
N
\
4
i
o
o
One of the outstanding improvements in modern power distribution has been
the “development of the air circuit breaker by Westinghouse for distribution
circuit voltages . On circuits where the duty on breakers is heavy, long life
-
with a minimum of maintenance makes the "De ion ' air breaker an outstanding
7
I
mm :1W -
.
I.B 32-150- 3
AIR CIRCUIT BREAKER
!1 DESCRIPTION
The type DH air circuit breaker is a three- pole, rier between personnel and live parts when the
electrically operated, horizontal drawout unit for unit is in the cell. This barrier assembly is in two
metal-clad switchgear. In the type designation, parts for convenience in handling.
the numbers preceding DH indicate the voltage
rating in hundreds of volts, and the numbers follow- *
ing DH indicate the maximum interrupting rating
in thousands of kva . The various ratings have A ARC CHUTE
3
Courtesy of NationalSwitchgear.com
RECEIVING, HANDLING AND STORING.
uncrated, lift it without the arc chutes or barriers containers until ready for use.
in place. Slings may be placed under the breaker
frame or in holes provided in the frame. Use a Store all components of these breakers in a clean
spreader to prevent the cables from distorting the dry place. During the storage period, keep them
blowout magnets . sufficiently warm to prevent moisture condensation.
INSTALLATION
With the exception of the arcing chambers and or excessive friction. As the contacts touch near the
barriers, these breakers are shipped completely end of the closing stroke, the force necessary to close
assembled and adjusted. No adjustments should be the breaker increases rapidly.
required and none should be made unless obviously .
2 With the breaker in the closed position, check
needed. the contacts to make certain that the adjustments
When the breaker has been removed from the have not been disturbed. Refer to Fig. 2 for proper
crate, remove the wooden clamp and angle iron settings. If adjustments are required, they may be
braces which support the blowout magnet pole made as described under OPERATION AND AD-
pieces during shipment and the breaker is ready JUSTMENTS.
for final assembly. A light film of grease is applied to both the arcing
Caution: Severe injury may be sustained and main contacts before the breaker is operated
if any part of the body is struck by the con - at the factory. This film is normally removed before
tact arms since they move very rapidly on the shipment. Before the breaker is placed in service,
opening stroke . Personnel working about the inspect the arcing contacts to see that they are free
breaker should stay clear of the space in which of oil or grease.
the contact arms move while breaker is .
3 The breaker is more easily handled with the
closed or is being closed . arc chutes and barriers removed; mount these parts
The following sequence of operations should be after the breaker has been moved near the metal-
performed in preparing the breaker for use: clad cell structure.
.
1 Breakers are usually shipped with the con- Before installing the arc chutes, play a stream of
tacts closed and with a tie on the trip lever to pre - dry compressed air through them from each end to
vent tripping. After the breaker is unpacked and remove any dust or foreign matter. Then examine
the shipping ties and braces removed, take off the the chutes to make certain that the vents and slots
tie on the trip lever and trip the breaker. Then close are open and free from foreign material. Assemble
-
the breaker carefully by hand, using the emergency
hand closing lever. Make certain that all parts are
functioning properly and that there is no binding
the arc chutes on the breaker by removing the re
taining straps from the front of the magnet pole
pieces and sliding the chutes into position, making o
4
Courtesy of NationalSwitchgear.com
INSTALLATION . I .B . 32-150-3
AIR CIRCUIT BREAKER
—
/ STATIONARY
ARCING
^jCONTACT SHUNT
- V SECONDARY
MOVING
CONTACT
chute is now completely installed. Make a final
SECONDARY CONTACT check by operating the breaker slowly by hand to
PUFFER
)K CYLINDER see that there is no interference in the movement
of the moving contact.
SECONDARY . 4. Set the two sections of the barrier assembly
CONTACT SPRINGS '
UPPER STATIONARY
into position and bolt them in place. They are held
MAIN CONTACT *
MOVING MAIN
— by two bolts in the breaker frame at the bottom of
CONTACT BRIDGE
LOWER STATIONARY
— the barriers. The front sheets are held together at
MAIN CONTACT
the top by a single bolt .
o .
5 Thoroughly test the control wiring for possible
grounds and short circuits which may have devel-
LL oped during the installation period.
CONDENSER 7 INSULATING
BUSHING OPERATING ROD The breaker is now ready to be placed in the
-
metal clad cell and operated electrically.
FIG. 2. Contact Assembly.
Caution: When this drawout equipment is
put into the cell and moved in beyond the test
position , the high voltage parts of the breaker
will be energized . If the barrier is completely
sure that the rear arcing horn connectors engage assembled on the breaker , personnel will be
the contacts on the blowout coils. protected from contact with the live parts. If ,
After a chute has been placed in position, make however , the barrier assembly is left off and
sure (1) that it is centrally located so that there is the breaker rolled into the cell , live parts are
no interference with the travel of the moving con - exposed . The breaker should never be rolled
into an energized cell structure without
tacts and (2) that it is securely held in position by
the retaining strap with top of the chute parallel to having the complete barrier assembly in place .
5
Courtesy of NationalSwitchgear.com
OPERATION AND ADJUSTMENT
I
I
6
Courtesy of NationalSwitchgear.com
OPERATION AND ADJUSTMENT, I.B. 32-150- 3
AIR CIRCUIT BREAKER
MECHANISM PANEL -
Latch Checking Switch. If the breaker is
designed for automatic reclosing duty, there are
The mechanism panel is mounted on the front two switches mounted on the front panel. The lower
of the closing solenoid mechanism as shown in Fig. switch is the cut -off switch and the upper switch is
4. On it are mounted the following auxiliary de- the latch-checking switch . The latter prevents
vices included as standard on all breakers: energizing the solenoid to reclose the breaker until
Shunt Trip Magnet. This device may be the tripping latch has reset. This switch is adjusted
equipped with a coil for direct current or alternat - with the breaker in the open position . Turn the
i ing current or capacitor tripping.
adjusting screw until the contacts make and then
advanced two more turns. This switch should open
i Cut-Off Switch. This switch causes the supply early in the closing stroke and close when the
to the closing solenoid to be cut off after the breaker breaker is opened.
is closed .
Cut-Off Switch. If the circuit breaker cannot
Position Indicator. This device gives positive be closed electrically because *a fuse or breaker
indication of the position of the breaker contacts. has opened the supply to the closing solenoid, check
Operation Counter. This counter records each the cut-off switch. This switch interrupts the supply
operation of the breaker. to the solenoid when the breaker has closed .
The adjustment of the switch is made by means
The following special devices may also be
of a screw in the end of the cut -off switch operating
mounted on the mechanism panel when required: arm which extends through the mechanism panel
Undervoltage Trip Attachment. This de- as shown on Fig. 5. This screw may be adjusted by
vice may be equipped with either an a -c or d c - loosening the two lock nuts which lock it to the arm.
coil to trip the breaker on undervoltage . Special With the breaker in the closed position, adjust
-
a c and d-c coils are also available for use with time the screw until the switch makes contact and then
delay undervoltage tripping devices mounted in the turn the screw down two more turns. This gives
metal-clad cell.
Latch-Checking Switch. This switch is sup-
plied when the breaker is used for automatic re-
closing service. It prevents completion of the
closing circuit until the closing mechanism has
reset after being tripped .
r
SECONDARY
OPERATION
COUNTER
:
CONTACT f
.OCKING PIN
- i
\ _
1
POSITION
L INDICATOR
Rf’ -. m
#1
-
CUT OFF
SWITCH
:
FIG . 4. Mechanism Panel. FIG . 5. Cutoff Switch Adjustment .
7
Courtesy of NationalSwitchgear.com
OPERATION AND ADJUSTMENT.
The secondary and arcing contacts are of a silver The arc chute on the type DH air circuit breaker
tungsten material with a high resistance to arc consists of an assembly of insulating refractory plates
burning. The stationary members are brazed to a enclosed in a rectangular Micarta tube or jacket.
In position on the breaker, the jacket is between the
single casting mounted on springs which are com
pressed when the breaker is closed. The travel of
- poles of the blowout magnet and the lower end is
this casting is restricted by stops which permit the immediately above the arcing contacts.
top to travel more than the bottom so that, on open- The refractory plates have inverted V-shaped
ing, the last point of contact is on the arcing contacts. slots starting immediately over the arcing contacts
In addition to the contacts, the moving contact so that the arc is drawn into these slots. The slots
arm also carries the puffer which supplies a puff of in the plates are alternately off center on opposite
air through the nozzle under the moving arcing sides to increase the length of the arc path as the
contact each time the breaker operates. This air arc progresses up the chute.
serves to speed circuit interruption at low currents Inside the front and rear surfaces of the chute
.
-
where the effect of the magnetic blow out coils is
lessened It has no appreciable effect in opening
are metallic arcing horns to which the arc transfers
from the arcing contacts. The front horn is con-
high currents . nected electrically to the moving contact, the rear
horn through the blowout coil to the stationary
CONTACT ADJUSTMENTS contact. Thus when the arc transfers to the horns ,
D Main Contacts. The main contact bridges are
the blowout coil is included in the circuit.
The action of the breaker in interrupting an arc
held in place on the moving contact arm by studs
is shown in Fig. 8. When the arcing contacts
which pass through the main contact springs. Ad-
separate, an arc is drawn between them without
justment of the main contacts is made, with the
breaker in the latched closed position, by setting the blowout coil carrying current as indicated by
position 1. The arc rises rapidly from this position
the stop nuts on these studs so that there will be
under the influence of magnetic forces and thermal
-
one sixteenth inch clearance between the face of
air currents. These cause the arc to impinge on
the nut and the back of the moving contact arm.
the arcing horns, thus including the blowout coil
If no clearance is present at these points, main in series with the arc.
contact pressure may be lacking or absent, thus
When current starts to flow in the blowout coil,
forcing load current through the intermediate and
arcing contacts. This can result in overheating and
the arc is driven very rapidly into the slots in the
damage to the contacts. If new contacts are being refractory plates by the magnetic field. Successive
positions of the arc are shown in Fig. 8.
installed or if the contacts have been smoothed, it
is well to operate the breaker electrically several Because the slots are staggered, the arc is
times so that the surfaces assume their permanent lengthened as it progresses up the chute by being
shape before this adjustment is made. extended laterally from one slot to the next. This
exposes a large part of the arc to the relatively cool
Arcing Contacts. To assure the proper com- surfaces of the plates and to the de-ionizing effect
pression in the arcing contact springs, these con-
of the blowout magnet field, which results in fast
tacts should be adjusted so that, with the breaker and positive interruption of the circuit.
closed, the dimension from the contact surface to
the front surface of the stud block is between lu/($
HORIZONTAL DRAWOUT ARRANGEMENT
and 1% inches. This adjustment is made by turn -
3 ing the nuts which attach the insulating operating
rod to the cross bar.
All type DH air circuit breakers are arranged
for use in metal-clad equipment from which they
9
Courtesy of NationalSwitchgear.com
OPERATION AND ADJUSTMENT
may be drawn out horizontally. As may be seen the lower left-hand side of the breaker frame. This
in Fig. 9, all parts are supported on a steel frame -
permits the plug in connector to be extended 12
with four wheels with roller bearings to facilitate inches to the rear of its normal position so that the
moving the breaker, and flanges which engage with control circuits may be connected and the breaker
rails to align the breaker in the cell. operated electrically while the main contacts are
The main conductors project horizontally from
disengaged .
the rear of the breaker, and are supported and insu- This test position occurs at the outer limit of
lated from the steel back plate of the frame by breaker travel obtained by operation of the levering-
Micarta condenser bushings. On the ends of these
main conductors are circular clusters of contact
in device crank. If it is desired to connect the con
trol circuits when the breaker has been cranked to
-
fingers arranged to engage the circular bar con - this position, pull out the secondary contact locking
ductors in the cell. pin shown in Fig. 4. While holding this pin out,
The control circuit wiring also is arranged for push the secondary contact bracket toward the rear
drawout disconnection by means of an 18- point of the breaker until the secondary contacts engage.
connector block arranged to plug into a mating The main barriers may be removed and the breaker
block mounted on the cell. This secondary con - operated safely in this position since the main
nector block is mounted on a movable bracket on contacts are disconnected.
10
Courtesy of NationalSwitchgear.com
OPERATION AND ADJUSTMENT, . - -
I.B 32 150 3
AIR CIRCUIT BREAKER
MAINTENANCE
Westinghouse power air breakers are durable rough guide for those with no previous experience
pieces of equipment and have a long life under with Westinghouse power air circuit breakers.
normal conditions of operation. However, condi -
tions vary widely and signs of wear may appear Note that for highly repetitive duty inspections
much more rapidly in some cases than others. In should be made at either 2500 or 5000 operations
central station service, barring abnormal condi- as indicated by the operation counter . If the breaker
tions, years of service may be expected before any is required to switch only normal load currents and
extensive parts replacement is required . moderate overloads, the 5000 figure may be used.
If the breaker is relayed to trip on system faults in
In highly repetitive service such as motor start - addition to being used for load switching, the 2500
ing or arc furnace switching, maintenance will be figure should be used. If faults occur often, more
determined by the number of operations, amount frequent maintenance may be required.
of dirt, grit or other harmful substances which
settles on breaker parts, and the care with which Arc Chutes. The insulating parts of the arc
the breaker is kept clean and in proper adjustment. chute remain in the circuit across the contacts at
all times. During the time that the contacts are open,
Experience on a given installation will prove to these insulating parts are subjected to the full po-
be the best guide for maintenance and parts re- tential across the breaker. Ability to withstand this
placement. The table on page 12 will serve as a potential depends upon the care given the insulation.
ii
Courtesy of NationalSwitchgear.com
MAINTENANCE,
On general inspections blow out the arc chute pitting on the main contact surfaces will not appre -
with dry compressed air by directing the stream ciably impair their current-carrying ability because
upward from the contact area and out through of the high contact pressure used. Any excessive
each of the slots between the arc splitter plates. roughness may be removed with a fine file or sand -
Also direct the dry air stream thoroughly over the paper. Emery cloth is not recommended for this
arc box shields. These are the ceramic liners in purpose. Be careful not to remove excessive amounts
the lower end of the chute where the arc is drawn . of contact material since this unnecessarily shortens
the life of the contacts.
The arc chutes may be removed periodically for
a thorough inspection. Remove any residue of dirt Operate the breaker slowly by hand to deter-
or arc products with a cloth or by a light sanding. mine whether the contact surfaces operate in the
Do not use a wire brush or emery cloth for this proper sequence. On opening the proper sequence
purpose because of the possibility of embedding is: (1) main contacts part, (2) secondary contacts
conducting particles in the ceramic material. part, (3) arcing contacts part. When the contacts
become worn to the point of changing this sequence,
Note: The ceramic material in the arc replace them.
chutes may have a dirty appearance
from re -
peated arc interruption and still have a high Mechanism. Apply a light lubricating oil to
dielectric strength. If in doubt, apply an a-c the various wearing surfaces throughout the breaker
test voltage of 25 kv for not more than one with the following exceptions. Do not oil the sur -
minute. When there is evidence of breakage faces listed below. Keep them free of dirt and grit:
or appreciable erosion of the slots in the
ceramic plates, the chutes should be replaced. .
1 All electrical contact surfaces, including main
bridges, arcing contacts, contact blade of rear arc
After an arc chute has been replaced, inspect it horn, and auxiliary switch contacts .
to make certain that the contact of the rear arcing
2 Trigger surfaces in operating mechanism.
.
horn has engaged the connector on the blowout
coil, that the upper edge of the jacket is substan - Wipe off the excess oil on the operating rods,
tially parallel to the magnetic pole faces, and that main condenser bushings, and other insulating sur -
the front arcing horn is securely connected to the faces. j
lower bushing by means of the shunt strap.
Contacts. Inspect the contacts periodically for Renewal Parts. A list of renewal parts recom-
evidence of excessive burning. Under normal con- mended to be kept in stock will be furnished upon
request. When ordering renewal parts, specify the
ditions the contacts should be usable for a large
number of operations within the rated interrupting name of the part, and include all of the information
given on the breaker nameplate.
capacity of the breaker . A moderate amount of
MAINTENANCE GUIDE
FREQUENCY OF OPERATION OUTY
12
Courtesy of NationalSwitchgear.com