Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

..

-
I B 32 150 3 -

RECEIVING • OPERATION • MAINTENANCE

"De-ion"
; • f AIR CIRCUIT BREAKER
Type DH
i

; -vji

m
!*
Type Kv Amps Kva
Vi

i i|
- -
50 DH 250 5.0 1200 250,000
50-DH-250 5.0 2000 250,000
/
75-DH- 150 7.5 600 150,000
- -
75 DH 150 7.5 1200 150,000
75-DH-250 7.5 1200 250,000
;
I
.?1 - -
75 DH 250 7.5 2000 250,000
'
'
' 2

- -
75 DH 500 7.5 1200 500,000
- -
75 DH 500 7.5 2000 500,000
150-DH- 150 15.0 600 150,000
3

150-DH-250 15.0 1200 250,000


150-DH-500 15.0 1200 500,000
- -
150 DH 500 15.0 2000 500,000

! . At
T,
:•

WESTINGHOUSE ELECTRIC CORPORATION


SWITCHGEAR AND CONTROL DIVISION
.
4

EAST PITTSBURGH WORKS EAST PITTSBURGH, PA


{ NEW INFORMATION EFFECTIVE OCTOBER , 1947
-
(R*p. 3 49 ) Printed In U S, A.

* Courtesy of NationalSwitchgear.com
A
e •
N
\
4

i
o

o
One of the outstanding improvements in modern power distribution has been
the “development of the air circuit breaker by Westinghouse for distribution
circuit voltages . On circuits where the duty on breakers is heavy, long life
-
with a minimum of maintenance makes the "De ion ' air breaker an outstanding
7

performer . In the type DH magnetic "De-ion" air circuit breakers, Westing


house offers a complete standard line for circuits from 2.3 to 15 kv. This
-
instruction book applies to breakers for the 7.5 and 15 kv classes and to 5 kv,
250,000 kva breakers which have the same class of insulation and general
construction .
Each of the type DH air circuit breakers is three- pole, electrically operated,
and is built as a complete horizontal drawout unit for metal-clad switchgear.
Breaker units of the same rating are interchangeable so that changing breakers
f
is a matter of minutes. Since they are drawn out horizontally, no lowering or
lifting is necessary . Steel barriers and automatic interlocks prevent contact
with live parts while the breakers are being changed .
As in the case of most high voltage electrical equipment, these breakers
should be inspected and maintained at regular intervals in order to obtain the
most dependable performance.
3
2
Courtesy of NationalSwitchgear.com
|

I
mm :1W -

.
I.B 32-150- 3
AIR CIRCUIT BREAKER

!1 DESCRIPTION
The type DH air circuit breaker is a three- pole, rier between personnel and live parts when the
electrically operated, horizontal drawout unit for unit is in the cell. This barrier assembly is in two
metal-clad switchgear. In the type designation, parts for convenience in handling.
the numbers preceding DH indicate the voltage
rating in hundreds of volts, and the numbers follow- *
ing DH indicate the maximum interrupting rating
in thousands of kva . The various ratings have A ARC CHUTE

similar structural features and many parts in


common . -i
P
l. *r
1
BLOWOUT
Fig. 1 shows a type 150DH250 breaker with - MAGNET
the main barrier assembly and one arc chute re- CONDENSER
moved . This shows clearly the arrangement of the - BUSHING
arc chutes and blowout magnet assemblies, the con- FINGER
CONTACTS
tacts and insulated operating rods, and the sole- A
noid operating mechanism . These components are MOVING
CONTACT ARM
supported in a welded steel frame mounted on
flanged wheels for guiding it into the metal-clad TRIPPING
OPERATING
ROD
cell. In the lower part of the frame also is located TRIGGER -
the levering- in device for moving the breaker into
final contact engagement. This device is inter-
locked with the mechanism to prevent inserting or SOLENOID
MECHANISM
withdrawing the breaker with the contacts closed.
Also located in the lower part of the frame are the
secondary contacts for automatically disconnecting
the control wiring when the breaker is withdrawn,
the auxiliary switch, and other auxiliary devices.
TRIP COIL
A barrier assembly is placed on the breaker
before it is rolled into its cell. The front sheet is of FIG . 1. Type 150 DH 250 Circuit Breaker with Main
one-eighth inch steel to form a grounded bar- Barrier and One Arc Chute Removed.

RECEIVING, HANDLING, STORING


All type DH breakers are completely assem
bled and given operating tests at the factory,
- damaged, file a claim immediately with the carrier
and notify the nearest Westinghouse Sales office.
after which they are carefully inspected and pre-
pared for shipment by workmen experienced in
HANDLING
the proper handling and packing of electrical
equipment. In order to afford maximum protection Remove the crating and packing carefully to
against damage, the main barrier assembly and the avoid damage from negligent handling of crowbars
arc chutes are removed from the breaker and or other tools. Use a nail puller for the uncrating.
packed separately. For each three- pole breaker Care must be used in handling the arc chutes,
there is one barrier assembly and three arc chutes. since the splitter plates within them are made
After the equipment has been unpacked, make of a ceramic material which may break if dropped .
a careful inspection for any damage which may have The base of the crate may be used as a skid for
occurred in transit. If the apparatus has been moving the breaker, or the breaker may be lifted

3
Courtesy of NationalSwitchgear.com
RECEIVING, HANDLING AND STORING.

with sling under the crate. If the breaker is to be STORING


lifted with slings, move it while it is still crated. The arcing chambers are shipped in separate
After the breaker is unpacked, the best way to containers to guard against damage from rough
move it is by rolling it on its own wheels. handling and for better protection from dust and
If it is necessary to lift the breaker after it is water or liquids. Store them in their shipping
i

uncrated, lift it without the arc chutes or barriers containers until ready for use.
in place. Slings may be placed under the breaker
frame or in holes provided in the frame. Use a Store all components of these breakers in a clean
spreader to prevent the cables from distorting the dry place. During the storage period, keep them
blowout magnets . sufficiently warm to prevent moisture condensation.

TABLE OF WEIGHTS ( POUNDS )

ARC CHUTE BARRIER ASSEMBLY


TYPE BREAKER UNIT ( Each)

75-DH- 150 1175 57 150


75-DH-250 1400 65 160
75- DH- 500 1600 105 160
150-DIM 50 1175 57 150
70 160
-
150- DH 250 1250
1450 105 160
150-DH- 500

INSTALLATION
With the exception of the arcing chambers and or excessive friction. As the contacts touch near the
barriers, these breakers are shipped completely end of the closing stroke, the force necessary to close
assembled and adjusted. No adjustments should be the breaker increases rapidly.
required and none should be made unless obviously .
2 With the breaker in the closed position, check
needed. the contacts to make certain that the adjustments
When the breaker has been removed from the have not been disturbed. Refer to Fig. 2 for proper
crate, remove the wooden clamp and angle iron settings. If adjustments are required, they may be
braces which support the blowout magnet pole made as described under OPERATION AND AD-
pieces during shipment and the breaker is ready JUSTMENTS.
for final assembly. A light film of grease is applied to both the arcing
Caution: Severe injury may be sustained and main contacts before the breaker is operated
if any part of the body is struck by the con - at the factory. This film is normally removed before
tact arms since they move very rapidly on the shipment. Before the breaker is placed in service,
opening stroke . Personnel working about the inspect the arcing contacts to see that they are free
breaker should stay clear of the space in which of oil or grease.
the contact arms move while breaker is .
3 The breaker is more easily handled with the
closed or is being closed . arc chutes and barriers removed; mount these parts
The following sequence of operations should be after the breaker has been moved near the metal-
performed in preparing the breaker for use: clad cell structure.
.
1 Breakers are usually shipped with the con- Before installing the arc chutes, play a stream of
tacts closed and with a tie on the trip lever to pre - dry compressed air through them from each end to
vent tripping. After the breaker is unpacked and remove any dust or foreign matter. Then examine
the shipping ties and braces removed, take off the the chutes to make certain that the vents and slots
tie on the trip lever and trip the breaker. Then close are open and free from foreign material. Assemble
-
the breaker carefully by hand, using the emergency
hand closing lever. Make certain that all parts are
functioning properly and that there is no binding
the arc chutes on the breaker by removing the re
taining straps from the front of the magnet pole
pieces and sliding the chutes into position, making o
4
Courtesy of NationalSwitchgear.com
INSTALLATION . I .B . 32-150-3
AIR CIRCUIT BREAKER

the top of the laminated pole faces. Connect the


STATIONARY
ARCING CONTACT |II TQ |11
MOVING shunt strap to the front arcing horn in the chute.
16 ' 16 ARCING CONTACT
ARCING ^ MOVING Tighten the lower connection of the shunt strap
CONTACT SPRINGS ^CONTACT ARM since it may have loosened during transit. The arc


/ STATIONARY
ARCING
^jCONTACT SHUNT
- V SECONDARY
MOVING
CONTACT
chute is now completely installed. Make a final
SECONDARY CONTACT check by operating the breaker slowly by hand to
PUFFER
)K CYLINDER see that there is no interference in the movement
of the moving contact.
SECONDARY . 4. Set the two sections of the barrier assembly
CONTACT SPRINGS '
UPPER STATIONARY
into position and bolt them in place. They are held
MAIN CONTACT *
MOVING MAIN
— by two bolts in the breaker frame at the bottom of
CONTACT BRIDGE
LOWER STATIONARY
— the barriers. The front sheets are held together at
MAIN CONTACT
the top by a single bolt .
o .
5 Thoroughly test the control wiring for possible
grounds and short circuits which may have devel-
LL oped during the installation period.
CONDENSER 7 INSULATING
BUSHING OPERATING ROD The breaker is now ready to be placed in the
-
metal clad cell and operated electrically.
FIG. 2. Contact Assembly.
Caution: When this drawout equipment is
put into the cell and moved in beyond the test
position , the high voltage parts of the breaker
will be energized . If the barrier is completely
sure that the rear arcing horn connectors engage assembled on the breaker , personnel will be
the contacts on the blowout coils. protected from contact with the live parts. If ,
After a chute has been placed in position, make however , the barrier assembly is left off and
sure (1) that it is centrally located so that there is the breaker rolled into the cell , live parts are
no interference with the travel of the moving con - exposed . The breaker should never be rolled
into an energized cell structure without
tacts and (2) that it is securely held in position by
the retaining strap with top of the chute parallel to having the complete barrier assembly in place .

OPERATION AND ADJUSTMENT


Before adjusting a circuit breaker, it is advan- circuit contacts in the cell. Above the arcing con -
tageous to become familiar with the construction tacts are located the blowout magnets and arc
and function of the various parts. The following chutes. The breaker is tripped by lifting the trip -
paragraphs describe the operation and the various ping trigger either manually, or electrically by
adjustments which can be made. This material means of the trip coil.
should be studied carefully before doing any work
on the breaker. OPERATING MECHANISM
The general arrangement of the breaker com - The solenoid operating mechanism with its trip -
ponents is shown in Fig. 1. The solenoid coil is
* built to exert a horizontal force on the mechanically-
free linkage is shown in Fig. 3. In this mechanism
the horizontal pull of the solenoid coil is transmitted
-
trip free linkage. This linkage, in turn, exerts
to the contact operating rods through a system of
an upward force on the pole unit insulating oper- links which rotates counter-clockwise about the
ating rods. The moving contact arms carry the
operating center. The linkage system consists of
main contact bridges, secondary contacts, and arc - four major links: the non-trip free lever, trip free
ing contacts. On opening, these contacts separate
lever, upper trip free link, and lower trip free link.
in the order named; on closing, they touch in the
These members are arranged as shown and are
reverse order.
held to form a rigid member by the cam link and
*
On the outer ends of the condenser bushings are tripping cam. The tripping cam is held fixed by
"C ' clusters of finger contacts for engaging the main the tripping latch.

5
Courtesy of NationalSwitchgear.com
OPERATION AND ADJUSTMENT

I
I

FIG . 3. Solenoid Operating Mechanism.

When the solenoid is energized, it pulls on the


junction of the non -trip free lever and the lower trip
.
release the tripping cam so that it is free to rotate
i
Without the restraining force of the cam and cam
free link, causing the system to rotate about the link, the major linkage collapses under the force of
operating center. The trip free lever then exerts the contact springs and the accelerating springs
an upward force on the operating rods through the
which are located in an air bumper attached to the
cross bar to close the breaker. The breaker is held
in this position by the closing latch and the tripping trip free lever. The junction of the upper and lower
latch. trip free links moves to the right and the trip free
The breaker is tripped either electrically or manu
ally by lifting the trigger which disengages the
- lever rotates clockwise, thus opening the breaker.
The position of the linkage is then that shown in
primary latch. This allows the tripping latch to Figure 3B.

6
Courtesy of NationalSwitchgear.com
OPERATION AND ADJUSTMENT, I.B. 32-150- 3
AIR CIRCUIT BREAKER

In moving to this position the roller on the lower MECHANISM ADJUSTMENTS


trip free link has disengaged the closing latch . The
retrieving springs now move the solenoid core The mechanism in the type DH air circuit breaker
which moves the linkage to the reset position as is adjusted at the factory and is designed to give
shown in Figure 3C. In this position the tripping long trouble-free performance. Do not make any
latch is reset and the breaker may be reclosed . adjustment unless faulty operation is observed.

MECHANISM PANEL -
Latch Checking Switch. If the breaker is
designed for automatic reclosing duty, there are
The mechanism panel is mounted on the front two switches mounted on the front panel. The lower
of the closing solenoid mechanism as shown in Fig. switch is the cut -off switch and the upper switch is
4. On it are mounted the following auxiliary de- the latch-checking switch . The latter prevents
vices included as standard on all breakers: energizing the solenoid to reclose the breaker until
Shunt Trip Magnet. This device may be the tripping latch has reset. This switch is adjusted
equipped with a coil for direct current or alternat - with the breaker in the open position . Turn the
i ing current or capacitor tripping.
adjusting screw until the contacts make and then
advanced two more turns. This switch should open
i Cut-Off Switch. This switch causes the supply early in the closing stroke and close when the
to the closing solenoid to be cut off after the breaker breaker is opened.
is closed .
Cut-Off Switch. If the circuit breaker cannot
Position Indicator. This device gives positive be closed electrically because *a fuse or breaker
indication of the position of the breaker contacts. has opened the supply to the closing solenoid, check
Operation Counter. This counter records each the cut-off switch. This switch interrupts the supply
operation of the breaker. to the solenoid when the breaker has closed .
The adjustment of the switch is made by means
The following special devices may also be
of a screw in the end of the cut -off switch operating
mounted on the mechanism panel when required: arm which extends through the mechanism panel
Undervoltage Trip Attachment. This de- as shown on Fig. 5. This screw may be adjusted by
vice may be equipped with either an a -c or d c - loosening the two lock nuts which lock it to the arm.
coil to trip the breaker on undervoltage . Special With the breaker in the closed position, adjust
-
a c and d-c coils are also available for use with time the screw until the switch makes contact and then
delay undervoltage tripping devices mounted in the turn the screw down two more turns. This gives
metal-clad cell.
Latch-Checking Switch. This switch is sup-
plied when the breaker is used for automatic re-
closing service. It prevents completion of the
closing circuit until the closing mechanism has
reset after being tripped .
r
SECONDARY
OPERATION
COUNTER
:
CONTACT f
.OCKING PIN

- i

\ _
1
POSITION
L INDICATOR

Rf’ -. m
#1
-
CUT OFF
SWITCH

' SHUNT TRIP MAGNET

:
FIG . 4. Mechanism Panel. FIG . 5. Cutoff Switch Adjustment .

7
Courtesy of NationalSwitchgear.com
OPERATION AND ADJUSTMENT.

FIG . 6. Tripping Latch Adjustment .

the switch the correct amount of overtravel. After


it is adjusted, tighten the two lock nuts. Check the
operation by closing the breaker slowly by hand . FIG . 7 Primary Latch and Trip Cora Adjustment .
The cut off switch should make contact near the
end of the closing stroke and should open when Primary Latch. The primary latch may be
the breaker is opened . readily observed from the front of the breaker.
This should be adjusted with the lower latching
Tripping Latch. If the breaker fails to close surface (on the trigger) extending slightly outward
on energizing of the closing coil, the cause may be from the surface on the tripping latch lever. See
faulty operation of the tripping latch . Examine the Fig. 7.
primary latch on the tripping trigger . If this latch
does not reset when the breaker is in the open
To adjust this latch, place the breaker in the
open position and hold the tripping latch lever down
J
position, then the difficulty may be due to improper against the trigger. Adjust the trigger stop until
clearance between the tripping latch and the trip- the front edges of the latching surfaces coincide
ping cam . This may be measured by removing the and then turn the screw down a half turn so that
horizontal panel which forms the seat of the chair - the lower surface extends slightly outward.
shaped breaker frame and is slotted to clear the
If this latch is not properly adjusted, the breaker
contact operating rods. The minimum clearance may trip from the impact of a normal closing opera -
between the roller and the cam with the breaker
tion. Note that this adjustment may require adjust -
open is one-thirty -second of an inch .
ment of the trip core as described below .
If this minimum clearance cannot be measured,
it can be obtained by adjusting the stop on the non- Trip Coil Core. Another possible cause of a
trip free lever . This stop is accessible after removing breaker tripping during a normal closing operation
the front panel on which the trip coil is mounted as is improper adjustment of the trip core. At the bot-
shown in Fig. 6. tom of the trip coil is a stop for the trip core. There
In order to remove this panel, first remove the should be a one thirty-second to one-sixteenth inch
nut which holds the trip core to the trigger and gap between the core and the stop with the trigger
then the spring from the operating arm of the opera - down against its stop. This may be adjusted by
tion counter. The panel bolts may then be loosened loosening the lock nut under the long hex nut im -
and the panel removed . The panel should be moved mediately below the trigger. The brass trip rod
as if on hinges at the left-hand edge to prevent may then be screwed in or out of the long hex nut
damage to the wires connecting to the cut-off switch to vary the gap.
and trip coil. There is no need to remove the wires.
BREAKER CONTACT ASSEMBLY
When the panel has been removed, loosen the lock -
ing nut and adjust the stop bolt until the clearance The breaker contact assembly for one pole is
between the roller and the cam is between one- and
three- thirty-seconds inches.
shown in Fig . 2. In this assembly the stationary
contacts are mounted on the condenser bushings 0
8
Courtesy of NationalSwitchgear.com
OPERATION AND ADJUSTMENT, - -
I .B. 32 150 3
AIR CIRCUIT BREAKER
and the moving contacts are mounted on the mov- When the arcing contacts have been properly
ing contact arm. There are three sets of contacts adjusted, they should touch on all three poles at
in the assembly called the main, secondary, and approximately the same time in the closing stroke.
arcing contacts. It is satisfactory, if , when the first pole touches, the
greatest distance between arcing contacts on other
The main contacts are of a silver-nickel alloy.
A bridge on the moving contact arm connects the poles is not greater than one-fourth inch .
two stationary main contacts giving a high-pressure
line contact. ARC CHUTES AND BLOWOUT MAGNETS

The secondary and arcing contacts are of a silver The arc chute on the type DH air circuit breaker
tungsten material with a high resistance to arc consists of an assembly of insulating refractory plates
burning. The stationary members are brazed to a enclosed in a rectangular Micarta tube or jacket.
In position on the breaker, the jacket is between the
single casting mounted on springs which are com
pressed when the breaker is closed. The travel of
- poles of the blowout magnet and the lower end is
this casting is restricted by stops which permit the immediately above the arcing contacts.
top to travel more than the bottom so that, on open- The refractory plates have inverted V-shaped
ing, the last point of contact is on the arcing contacts. slots starting immediately over the arcing contacts
In addition to the contacts, the moving contact so that the arc is drawn into these slots. The slots
arm also carries the puffer which supplies a puff of in the plates are alternately off center on opposite
air through the nozzle under the moving arcing sides to increase the length of the arc path as the
contact each time the breaker operates. This air arc progresses up the chute.
serves to speed circuit interruption at low currents Inside the front and rear surfaces of the chute

.
-
where the effect of the magnetic blow out coils is
lessened It has no appreciable effect in opening
are metallic arcing horns to which the arc transfers
from the arcing contacts. The front horn is con-
high currents . nected electrically to the moving contact, the rear
horn through the blowout coil to the stationary
CONTACT ADJUSTMENTS contact. Thus when the arc transfers to the horns ,
D Main Contacts. The main contact bridges are
the blowout coil is included in the circuit.
The action of the breaker in interrupting an arc
held in place on the moving contact arm by studs
is shown in Fig. 8. When the arcing contacts
which pass through the main contact springs. Ad-
separate, an arc is drawn between them without
justment of the main contacts is made, with the
breaker in the latched closed position, by setting the blowout coil carrying current as indicated by
position 1. The arc rises rapidly from this position
the stop nuts on these studs so that there will be
under the influence of magnetic forces and thermal
-
one sixteenth inch clearance between the face of
air currents. These cause the arc to impinge on
the nut and the back of the moving contact arm.
the arcing horns, thus including the blowout coil
If no clearance is present at these points, main in series with the arc.
contact pressure may be lacking or absent, thus
When current starts to flow in the blowout coil,
forcing load current through the intermediate and
arcing contacts. This can result in overheating and
the arc is driven very rapidly into the slots in the
damage to the contacts. If new contacts are being refractory plates by the magnetic field. Successive
positions of the arc are shown in Fig. 8.
installed or if the contacts have been smoothed, it
is well to operate the breaker electrically several Because the slots are staggered, the arc is
times so that the surfaces assume their permanent lengthened as it progresses up the chute by being
shape before this adjustment is made. extended laterally from one slot to the next. This
exposes a large part of the arc to the relatively cool
Arcing Contacts. To assure the proper com- surfaces of the plates and to the de-ionizing effect
pression in the arcing contact springs, these con-
of the blowout magnet field, which results in fast
tacts should be adjusted so that, with the breaker and positive interruption of the circuit.
closed, the dimension from the contact surface to
the front surface of the stud block is between lu/($
HORIZONTAL DRAWOUT ARRANGEMENT
and 1% inches. This adjustment is made by turn -
3 ing the nuts which attach the insulating operating
rod to the cross bar.
All type DH air circuit breakers are arranged
for use in metal-clad equipment from which they

9
Courtesy of NationalSwitchgear.com
OPERATION AND ADJUSTMENT

FIG , 8. Arc Chute and Blowout Coil.

may be drawn out horizontally. As may be seen the lower left-hand side of the breaker frame. This
in Fig. 9, all parts are supported on a steel frame -
permits the plug in connector to be extended 12
with four wheels with roller bearings to facilitate inches to the rear of its normal position so that the
moving the breaker, and flanges which engage with control circuits may be connected and the breaker
rails to align the breaker in the cell. operated electrically while the main contacts are
The main conductors project horizontally from
disengaged .
the rear of the breaker, and are supported and insu- This test position occurs at the outer limit of
lated from the steel back plate of the frame by breaker travel obtained by operation of the levering-
Micarta condenser bushings. On the ends of these
main conductors are circular clusters of contact
in device crank. If it is desired to connect the con
trol circuits when the breaker has been cranked to
-
fingers arranged to engage the circular bar con - this position, pull out the secondary contact locking
ductors in the cell. pin shown in Fig. 4. While holding this pin out,
The control circuit wiring also is arranged for push the secondary contact bracket toward the rear
drawout disconnection by means of an 18- point of the breaker until the secondary contacts engage.
connector block arranged to plug into a mating The main barriers may be removed and the breaker
block mounted on the cell. This secondary con - operated safely in this position since the main
nector block is mounted on a movable bracket on contacts are disconnected.

10
Courtesy of NationalSwitchgear.com
OPERATION AND ADJUSTMENT, . - -
I.B 32 150 3
AIR CIRCUIT BREAKER

When the breaker is in the cell far enough to be


connected to the high voltage bus, the frame work
of the breaker is effectively grounded by a special
connector located immediately above the secondary
plug-in connector block. This connector jaw en-
gages a copper bar which is mounted in the cell
and connected to the cell ground bus.

In order to move the breaker in or out of the


cell against the resistance of the contact fingers, a
levering-in device is provided on each breaker .
There is a lever on each side mounted on a common
* shaft across the back of the breaker. On each lever
is a roller which engages a groove on the side wall
of the cell. A removable crank engages another
shaft at the right front corner of the breaker which
turns the levers through a worm gear arrangement .

To move the breaker from the "test" position to


final contact engagement it is necessary only to
place the crank on the shaft, push until its slot
engages the shaft driving pin, and turn until the
breaker is in position. For safety, a mechanical
interlock prevents closing the breaker while the
crank is in position and also prevents cranking the
breaker while the breaker is closed. FIG . 9. Rear View of 150 DH 250 Circuit Breaker .

MAINTENANCE
Westinghouse power air breakers are durable rough guide for those with no previous experience
pieces of equipment and have a long life under with Westinghouse power air circuit breakers.
normal conditions of operation. However, condi -
tions vary widely and signs of wear may appear Note that for highly repetitive duty inspections
much more rapidly in some cases than others. In should be made at either 2500 or 5000 operations
central station service, barring abnormal condi- as indicated by the operation counter . If the breaker
tions, years of service may be expected before any is required to switch only normal load currents and
extensive parts replacement is required . moderate overloads, the 5000 figure may be used.
If the breaker is relayed to trip on system faults in
In highly repetitive service such as motor start - addition to being used for load switching, the 2500
ing or arc furnace switching, maintenance will be figure should be used. If faults occur often, more
determined by the number of operations, amount frequent maintenance may be required.
of dirt, grit or other harmful substances which
settles on breaker parts, and the care with which Arc Chutes. The insulating parts of the arc
the breaker is kept clean and in proper adjustment. chute remain in the circuit across the contacts at
all times. During the time that the contacts are open,
Experience on a given installation will prove to these insulating parts are subjected to the full po-
be the best guide for maintenance and parts re- tential across the breaker. Ability to withstand this
placement. The table on page 12 will serve as a potential depends upon the care given the insulation.

ii
Courtesy of NationalSwitchgear.com
MAINTENANCE,

On general inspections blow out the arc chute pitting on the main contact surfaces will not appre -
with dry compressed air by directing the stream ciably impair their current-carrying ability because
upward from the contact area and out through of the high contact pressure used. Any excessive
each of the slots between the arc splitter plates. roughness may be removed with a fine file or sand -
Also direct the dry air stream thoroughly over the paper. Emery cloth is not recommended for this
arc box shields. These are the ceramic liners in purpose. Be careful not to remove excessive amounts
the lower end of the chute where the arc is drawn . of contact material since this unnecessarily shortens
the life of the contacts.
The arc chutes may be removed periodically for
a thorough inspection. Remove any residue of dirt Operate the breaker slowly by hand to deter-
or arc products with a cloth or by a light sanding. mine whether the contact surfaces operate in the
Do not use a wire brush or emery cloth for this proper sequence. On opening the proper sequence
purpose because of the possibility of embedding is: (1) main contacts part, (2) secondary contacts
conducting particles in the ceramic material. part, (3) arcing contacts part. When the contacts
become worn to the point of changing this sequence,
Note: The ceramic material in the arc replace them.
chutes may have a dirty appearance
from re -
peated arc interruption and still have a high Mechanism. Apply a light lubricating oil to
dielectric strength. If in doubt, apply an a-c the various wearing surfaces throughout the breaker
test voltage of 25 kv for not more than one with the following exceptions. Do not oil the sur -
minute. When there is evidence of breakage faces listed below. Keep them free of dirt and grit:
or appreciable erosion of the slots in the
ceramic plates, the chutes should be replaced. .
1 All electrical contact surfaces, including main
bridges, arcing contacts, contact blade of rear arc
After an arc chute has been replaced, inspect it horn, and auxiliary switch contacts .
to make certain that the contact of the rear arcing
2 Trigger surfaces in operating mechanism.
.
horn has engaged the connector on the blowout
coil, that the upper edge of the jacket is substan - Wipe off the excess oil on the operating rods,
tially parallel to the magnetic pole faces, and that main condenser bushings, and other insulating sur -
the front arcing horn is securely connected to the faces. j
lower bushing by means of the shunt strap.
Contacts. Inspect the contacts periodically for Renewal Parts. A list of renewal parts recom-
evidence of excessive burning. Under normal con- mended to be kept in stock will be furnished upon
request. When ordering renewal parts, specify the
ditions the contacts should be usable for a large
number of operations within the rated interrupting name of the part, and include all of the information
given on the breaker nameplate.
capacity of the breaker . A moderate amount of

MAINTENANCE GUIDE
FREQUENCY OF OPERATION OUTY

OPERATION Moderate Heavy Very Heavy


Light
5 Oper. per day 15 Oper. par day .
30 Oper per day 60 Oper. per day

3 mos . 3 mos. 2 mos. 2500-5000 Oper.


Clean external surfaces
Blow out arc chutes and 2 mos. 2500-5000 Oper.
6 . 3 mos.
inspect contacts 2500-5000 Oper.
moB
12 mos. 6 mos. 4 mos.
Inspect mechanism

12
Courtesy of NationalSwitchgear.com

You might also like