04 August DC Riyadh
04 August DC Riyadh
A/C units No. CRAC-01 CRAC-02 CRAC-03 CRAC-04 CRAC-05 CRAC-06 CRAC-07 CRAC-08
Current Alarms
Current Alarms
Generator Readings
Ground Floor:
1. Rectifier Readings
Electrical Room:-
UPS Readings
UPS No. Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 Power Power
(kW) (kVA)
UPS-A1 379 380 380 220 220 219 72 61 61 40.2 40.6
Current Alarms NO
Last
Alarms PMR 23-07-2023
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
UPS No. Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
UPS-A2 380 380 381 219 219 219 64 55 54 38.3 38.7
Current Alarms NO
Last
Alarms PMR 23-07-2023
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
UPS No. Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
UPS-A3 379 380 380 219 220 220 67 56 56 41.8 42.4
Current Alarms NO
Last
Alarms PMR 23-07-2023
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
UPS No. Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
UPS-B1 380 380 380 219 219 220 46 47 43 29.3 29.7
Current Alarms NO
Last
Alarms PMR 23-07-2023
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
UPS No. Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
UPS-B2 380 380 380 219 220 219 46 45 43 29.6 30.3
Current Alarms NO
Last
Alarms PMR 23-07-2023
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
UPS No. Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
UPS-B3 379 379 380 220 219 219 46 45 43 29.1 29.5
Current Alarms NO
Last
Alarms PMR 23-07-2023
PPC Readings
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
PPC No: Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
PPC-A1 373 374 376 216 215 216 25 36 23 19 19
PPC-B1 376 374 376 216 215 217 10 16 15 7 7
PPC-A2 377 375 377 217 217 217 38 31 22 19 19
Current Alarms NO
Last
Alarms NO
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
PPC No: Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
PPC-B2 374 374 376 216 215 215 34 38 23 19 20
PPC-A3 373 374 375 217 217 218 61 42 53 32 34
PPC-B3 377 377 378 217 216 216 51 31 48 27 28
Current Alarms NO
Last
Alarms NO
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
PPC No: Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
PPC-STS-01 380 380 380 220 220 220 - - - - -
PPC-STS-02 380 380 380 220 220 220 - - - - -
Current Alarms
Last
Alarms Power On Feb 15 2023
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
PPC No: Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
PPC-A4 373 377 374 216 217 217 11 3 4 4 4
PPC-B4 375 376 376 216 216 216 5 1 3 2 2
Current Alarms
Last
Alarms Power On Feb 15 2023
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
PPC No: Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
PPC-A5 373 374 376 215 214 216 64 54 25 31 32
PPC-B5 376 374 374 215 215 215 54 70 46 34 35
Current Alarms NO
Last NO
Alarms
ATS READING
Ground floor:-
Current Alarms NO
Last
Alarms
PMR 23-07-2023
Current Alarms NO
Last
Alarms
PMR 23-07-2023
MESB READING
Electrical Room
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
MESB No. Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
MESB-A 378 379 379 218 218 219 548 534 525 334 352
Visual Check OK
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
MESB No. Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
MESB-B 378 379 379 219 219 219 497 507 497 310 327
Visual Check OK
UPSDB READING
Electrical Room
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
UPSDB No. Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
UPSDB -A 381 380 380 219 220 220 198 177 176 120 121
Visual Check OK
Line to Line Voltage (V) Line to neutral Voltage (V) Current (A) Active Apparent
UDP No. Power Power
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3 (kW) (kVA)
UPSDB -B 380 380 381 219 220 220 140 135 132 89 89
Visual Check OK
Fire Alarm
FM200 Cylinders
Status Remarks
Location Reference Number
OK/Not OK
Zone 1 CYL1-4 OK -
Zone 2 CYL 5-8 OK -
Electrical Room CYL 9-11 OK -
Lamps replacement
All lights
Total number of Number of lights
Location Rows Remarks
lights changed
Checked
Zone 1 115 OK
Zone 2 120 OK
Electrical Room 36 OK
Staging Area 12 OK