Download as pdf or txt
Download as pdf or txt
You are on page 1of 25

SDEC SMART Project eNodeB Hardware MTS

Cabinet

Installation Highlight V1

Security Level:
Mode 4 (Wireless Site):Grid, 3500W, 8hours backup time

Load information

Load type RAN,Microwave,CCTV…

Load power
3500W
consumption

battery back up time 8 hours

DCDU

BBU Configuration

RTN
MTS9304A &
Router
MTS9300A
MTS9304A-HA16A1*1 Installation
Equipment Cabinet
Switch Dimensions
IVS

MTS9300A-XA10A3*1
Battery Cabinet

Rectifier module R4875G5*4


220/380Vac
Battery capacity 48V,100AH*8

MTS9300A-XA10A3 *1 units(500Ah)
MTS9304A-HA16A1 * 1 unit(500Ah) 650mm x 650mm x 1000mm
650mm x 650mm x 1600mm Base: 650 mm x 650 mm x 100 mm
MTS Cabinet Layout – (for END Sites)

DC/AC Invertor

DCDU
BBU
MW IDU/TX
Router
POE Switch

PDU
Space for IVS 1800
Battery
(CCTV only)
Battery
Battery
Battery
Battery
Battery
Battery
Battery
3 Huawei Confidential
Power Rectifier

2Path *63A

DCDU

Grounding
4 Huawei Confidential
DCDU Rectifier Equipment
LOAD0 Sector 1 & Sector 2 – RRU
2300Mhz
LOAD1 Sector 1 & Sector 2 – RRU
2300Mhz
LOAD2 Sector 3 – RRU 2300Mhz
LOAD3 Sector 3 – RRU 2300Mhz
LOAD4 Sector 1 – RRU 1800Mhz
LOAD5 Sector 2 - RRU 1800Mhz
LOAD6 Sector 3 – RRU 1800Mhz
LOAD7
LOAD8 BBU1
LOAD9 BBU2

5 Huawei Confidential
ODM03D Installed on Tower

6 Huawei Confidential
ODM03D Power Cable

Two Cable One Cable


from DCDU to RRU

7 Huawei Confidential
Power Rectifier – DC/AC Invertor for IVS
125A

DC/AC Invertor

DCDU
BBU
MW IDU/TX
POE Switch
Router

Space for IVS 1800


(CCTV only)

Battery

Battery

Battery

8 Huawei Confidential
Monitor Cable

RS485/RS232 port on the SMU

MON1 port on BBU

9 Huawei Confidential
External Alarm Cable from BBU
Dry Contact Silkscreen Associated Alarm
Type
Dry contact ALM1 AC failure
outputs
The default ALM2 DC overvoltage, DC ultra overvoltage, DC undervoltage, DC ultra undervoltage
setting (closed:
alarm; open: ALM3 Rectifier fault, rectifier protection, communication failure, multi-rectifier fault
normal) can be
modified. ALM4 AC SPD faults, DC SPD faults

ALM5 Load fuse break, battery fuse break

ALM6 Battery high temperature, battery very high temperature, battery low
temperature, battery very low temperature, ambient high temperature, ambient
very high temperature, ambient low temperature,
ALM7 Door Open Alarm

ALM8 Heater fault alarm, Air conditioner fault alarm, Fan fault alarm

10 Huawei Confidential
External Cabinet Alarm Termination
• Identify UIM02C board in Rectifier Unit
• Use Alarm Cable (BoM: 04080054) or FE cable – 2pcs
• Connect from BBU UPEU-19 EXT-ALM 0 and EXT-ALM 1
to UIM02C board
BBU3900

UPEU
EXT-ALM0 Slot 19
EXT-ALM1
UIM02

11 Huawei Confidential
Alarm Cable pairing for Internal
UPEU RJ-45 Pin Color UIM02C Remarks

Cabinet Alarm Termination


Slot 19
1&2 White Orange/Orange ALM1 +, ALM1 - ALM 1 – Mains Failure (internal cabinet)

3&4 White Green/Green ALM2 +, ALM2 - ALM 2 – DC over/under voltage


EXT-ALM0
(Bottom 5&6 White Blue/Blue ALM3 +, ALM3 - ALM 3 – Rectifier Fault
UPEU)
7&8 White Brown/Brown ALM4 +, ALM4 - ALM 4 – AC/DC SPD Fault

1&2 White Orange/Orange ALM5 +, ALM5 - ALM 5 – Load Fuse/Battery Fuse

Slot 19 3&4 White Green/Green ALM6 +, ALM6 - ALM 6 – Battery over/under Temperature
EXT-ALM1
(Bottom 5&6 White Blue/Blue ALM7 +, ALM7 - ALM 7 – Door Status Alarm (cabinet)
UPEU)
7&8 White Brown/Brown ALM8 +, ALM8 - ALM 8 – Cabinet Temperature/Fan Fault
Alarm

12 Huawei Confidential
• Scenario
1.2300Mhz 4T4R
2.2300Mhz 8T8R
3.1800MHz 4T4R
4.1800MHz 8T8R
5.2300Mhz 64T64R

13 Huawei Confidential
Scenario 1(2300MHz 4T4R) CPRI Connection

UBBP, Port 0,2

14 Huawei Confidential
14
• Scenario 1(2300MHz 4T4R) Jumper • Scenario 1(2300MHz 4T4R) Jumper
Connection Connection
• Sector 1 & Sector2 share 1 RRU • Sector 3

15 Huawei Confidential
Scenario 2(2300MHz 8T8R) 1 Sector use 1 RRU & 1
Antenna, CPRI Connection

UBBP, Port 0,1,2

16 Huawei Confidential
16
• Scenario 2(2300MHz 8T8R) 1 Sector use 1 RRU & 1 Antenna
Jumper connection

17 Huawei Confidential
Scenario 3, 1800MHz 4T4R CPRI Connection

UBBP, Port 3,4,5

18 Huawei Confidential
18
Scenario 3, 1800MHz 4T4R
Jumper & RET Cable Connection for RRU5818(2300Mhz) 4T4R

19 Huawei Confidential
19
• Scenario 4(1800MHz 8T8R) 1 Sector use 1 RRU & 1 Antenna, Jumper
Connection

20 Huawei Confidential
• Scenario 4 1800MHz 8T8R CPRI Connection

UBBP, Port 3,4,5

21 Huawei Confidential
21
• Scenario 5(AAU5363)

22 Huawei Confidential
GPS
• No Hole to install GPS bracket. Have to install on cable ladder/gantry.

23 Huawei Confidential
Antenna Installation
1. Azimuth
➢ Refer to TSSR and use compass to confirm the actual
direction Remarks:
Mechanical Tilt for each sector
Antenna is 2º

2. Mechanical Tilt
➢ Refer to TSSR and use anchor meter to confirm the
actual mechanical tilt

24 Huawei Confidential
Antenna Installation
3. Antenna Height
➢ Refer to TSSR (Usually 75m AGL for L2300, 72m AGL for L1800)
From the top of the antenna

25 Huawei Confidential

You might also like