7.

CONCLUSIONS:
7.1. Summary of most common stator winding testing techniques: Effectiveness, Advantages and Disadvantages.

Test Purpose Effectiveness Advantages Disadvantages

Insulation Resistance Detection of serious flaws, Little skill required, High influence of winding temperature
surface moisture or equipment in test results. No effective
IR (1min) Moderate.
contamination. Determine the inexpensive. temperature correction available.
previous status of the winding Less effective for Epoxy-mica
to carry out following High insulation.
voltage tests.
Polarization Index Detection of serious flaws, Effective Little skill required, If IR greater than 5G less significant
surface moisture or equipment meaning about the status of the
PI (10 min)
contamination. Determine the inexpensive. winding.
previous status of the winding
No temperature
to carry out following High
dependence.
voltage tests.
DC Reabsorption Detection of thermally ageing Low-Moderate Some skill required, Influenced by winding temperature
current (30min charge/1 groundwall insulation. equipment and superficial status of the winding.
min discharge). inexpensive. Less effective for Epoxy-mica
insulation.

DC Hi-Pot Detection of local weak points Moderate Little skill required, Test may cause an insulation
in the winding. Only finds equipment breakdown. It’s not a diagnostic test.
serious defects like partial inexpensive. Appears
cracks and punctures. to be better finding
defects in the overhang
area than AC Hi-Pot.
Detection of local weak points Moderate Provides more Requires experience to judge when to
in the winding. Only finds diagnostic information abort the test.
DC Step Graded or
serious defects like partial than the standard 1min
Ramp
cracks and punctures. Hi-Pot. Allows some
warning to the user
about when to abort
the test.

Page 30 of 35
AC Hi-Pot Detection of local weak points More effective Appears to be better Greater size and expensive
in the winding like cracks like than DC Hi-Pot finding defects in slot equipment needed. Promotes some
partial cracks and punctures. area than DC Hi-Pot. small ageing to insulation each test.
Dissipation Factor and Detection of thermally aged The test can also Less effective for epoxy-mica
Capacitance groundwall insulation and provide information insulation in terms of thermally and
Moderate
superficial moisture or partially about the contact load cycling ageing detection.
conductive contamination. status of the
semiconductive coating
in the slot area.
Dissipation Factor Detection of the global partial Moderate Well Known. Repetitive Influence by losses in the grading
discharge activity of the values coating, severe PD activity should be
Tip-Up
winding, mainly due to thermal present to be seen above this noise
Good for track ageing
and load cycling ageing. floor. Not allow detection of local
over time.
defects because it’s masked by
healthy winding section under test.
Off-Line Partial Detection of partial discharge Partly effective Allow detection of PD AC power supply free of PD activity
Discharge activity activity in areas close needed to energize the winding. No
to neutral (due to temperature and electromagnetic
mechanical defects). forces present during testing.
No external
interference present.
On-Line Partial Detection of partial discharge Partly Effective Temperature and Only sensitive to PD activity in
Discharge activity electromagnetic forces the High Voltage side of the
present. Real Voltage winding. External
distribution. Outage not interference present.
needed.
RF Porbe Detection of partial discharge Effective Pinpoints localized high There are safety concerns with
activity in stator slots levels of PD this test since it invloves
placing the RF probe
antenna close to a winding
energized with high voltage
Blackout or Ultraviolet Detection of surface partial Effective Identifies voltage stress Some safety concerns with the
Imaging discharge activity in stator control material defects blackout test since it
endwindings and contamination and involves applying high
inadeaquate spacing in voltage to the stator
endwindings and winding in a dark room.
connections Potential for over stressing
ground insulation if phase-

Page 31 of 35
to-phase voltage is applied.
Turn Surge Test Detection of weak turn Low No other Off-Line test Will not detect ageing or minor flaws.
to turn insulation in can detect turn-turn No effective in windings with large
windings with insulation weakness. number of turns in series. Experience
multiturn coils. needed for interpretation.

Page 32 of 35