Ground2021-PE BJS

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

GROUND2020/21 International Conference on Grounding

&
& Lightning Physics and Effects

9th LPE Belo Horizonte, Brazil - June, 2021

GEOELECTRIC MODELING FOR THE RETROFIT OF THE GROUNDING SYSTEM OF THE BOM
JARDIM DA SERRA WINDFARM

Paulo Edmundo da F. Freire, Neimar Rodrigo Alves da Silva, Jonas Zanelatto Minatto, Camila Schweig, Patricia de
Lugão, Berthold Kriegshäuser, Jorge Luis Porsani
PAIOL Engenharia, Energimp, Geoanalisys, Strataimage, USP

Abstract - Windfarms are wide-area generating plants, with


dimensions of the order of kilometers, which require a deep 1 DESCRIPTION OF THE WINDFARM COMPLEX
geoelectric model for the proper design of its grounding system.
In 2019 the Bom Jardim da Serra windfarm started a wide retrofit,
for the substitution of its 62 old aerogenerators by new ones. The Bom Jardim da Serra Windfarm Complex occupies an
Considering the high exposition of the windfarm to lightning and area of about 28 km² and consists of four windfarms with
the complex regional geology, both associated with the 62 towers. Each generating unit has 1.5 MW with three 30
geographic location of the site, the review of the grounding system meters blades, supported by towers between 60 to 100
was considered an important item of the retrofit. meters in height. The interference-free maneuvering yards
The Bom Jardim da Serra windfarm is situated on the southeast are 60 meters in diameter and the towers are spaced
edge of the Santa Catarina Plateau, the border of the Serra Geral about 380 m on average.
Formation, 1400 m above sea level. This plateau is bordered by
huge and beautiful canyons, which are very close to some
aerogenerators' towers, and was produced by the extensive Excluding the Santo Antônio windfarm, which has only two
fissural volcanism that 130 million years ago flooded 75% of the towers, the other three windfarms have each one 20
entire Paraná Basin, South of Brazil, with 800,000 km³ of lava. towers, interconnected with the substation through an
These geologic events formed volcanic layers with an average aerial double-circuit 34.5 kV line, with an average length of
thickness of about 800 m, but also up to 1500 m in the axis of the 7.3 km. The groundings of the towers are interconnected
Paraná Basin. Moisture is very high in the area and the basalt by the shield wires of the medium voltage lines, or by a 70
basement is covered by a less than one-meter thick layer of mm² bare copper cable directly buried in the ground, which
organic soil (black peat). There are basalt outcrops everywhere in
this area and they are well-intact in some places, in others quite
accompanies the medium voltage cables in the
altered. underground stretches of the lines.
The typical grounding project is based on shallow, double-layered
geoelectric models, developed from Wenner soundings, with Figure 1.1 shows a Google Earth image that illustrates the
electrode openings limited to about 100 m and with no correction entire Windfarm Complex, with the location of the towers
of the galvanic deviations. and of the 22 stations where geophysical soundings were
A geoelectric model was developed in an unprecedented way, carried out. In each station, it was done an
with the use of three different geophysical sounding methods. The audiomagnetotelluric (AMT) sounding and a Vertical
combination of the measured geophysical dataset, with some
known geological constraints, allowed for the construction of a 1D
Electrical Sounding (VES) with the Wenner arrangement.
deep geoelectrical model down to about 1 km depth, compatible Four Time-Domain Electromagnetic (TDEM) soundings
with the dimension of the windfarm. were carried out in stations A2, C3, C5 and B8.
The 1D geoelectric model shows that, in the area of the wind farm,
the volcanic package is superimposed over a layer of low
resistivity pre-volcanic sediments. Despite the basaltic basement
that dominates the entire area, the resistivities obtained are lower
than what could be expected, which indicates that the basalts in
the area are well fractured and water-saturated. The 1D
geoelectric model is compatible with the geological structure
expected for the border of the canyons and was used to simulate
the towers' groundings, which resulted in calculated impedances
(25 kHz) that are similar to the average of the measured
impedances at the aerogenerators towers.
This pioneering design approach, based in extensive geophysical
surveys, is compared to the traditional usual grounding design
based on simple and shallow geoelectric models, developed from
Wenner soundings, with openings of the current probes limited to
about 100 m wide and with no static-shift adjustment.
This is a multidisciplinary paper that applies electrical engineering
and geophysics knowledge for the solution of an engineering
problem. The paper presents the methodology used for the
construction of the average 1D deep geoelectric model of the
windfarm area, which is a unidimensional model of the subsurface
structure, composed of horizontal ground layers of different
electrical resistivities and thicknesses.
Figure 1.1: towers of the Bom Jardim da Serra Windfarm,
geophysical stations Wenner/AMT and TDEM (A2, C3, C5
and B8), and lines of the AMT profiles (red).
2 EXPOSITION OF WINDFARMS TO LIGHTNING
The survey included the measurement of the grounding
Windfarms can be classified as extremely exposed impedance of 22 towers, with a high-frequency ground
installations to lightning strikes, usually subject to a tester (25 kHz), which revealed an average impedance of
combination of several critical conditions, such as [1]:
open areas, sometimes very exposed to lightning; v
high towers, which allow for the formation of ground- but indicators of the electrical performance of the existing
cloud electrical discharges; grounding system, allowing for an evaluation of the
high resistivity grounds, which make it difficult to obtain geoelectric model obtained, based on the simulations of
a good low resistance grounding; the grounding system of the complete windfarm.
connections with long medium-voltage overhead lines.
3.1 The Vertical Electrical Soundings (VES)
The grounding of a wind turbine tower can be analyzed
considering two parameters: The shallow soundings were done by Geoanalisys at 22
impulsive impedance - response of the ground to a stations distributed within the windfarm complex, with a
current impulse, typical of an atmospheric discharge, Terrameter ABEM SAS 4000 resistivimeter, with the
which is the impedance presented by the grounding at Wenner array spaced 1, 2, 4, 8, 16, 32, 64 and 128 m.
t = 0+, immediately after the lightning strike; and Figure 2.1 shows the 22 apparent resistivity curves
dispersion resistance - valid for low frequencies, such calculated from these measurements, as well as the
as a short-circuit to the ground in the medium voltage geometric average curve (red). In this graph, some values
network, which can be also associated with the were eliminated because they were considered not
resistance that the grounding presents to the tail of the representative of the regional apparent resistivity range -
impulse, after the transient of the lightning wavefront. higher than 10,000 m.

The application of a high-frequency sinusoidal current in The analysis of this set of curves reveals a significant
the grounding, either for a field measurement or for a variation of the apparent resistivities, of almost a decade,
computer simulation, is a simplified way for the estimate of for each sounding spacing. Although the variability of the
the response of the tower grounding to the wavefront of shallow ground is expected, part of this variation can be
lightning [2]. For this assessment, the 10/350 impulse is attributed to static-shift deviations, which affect all the
used, which, according to the IEC 62305-1: 2010 geophysical soundings based on the measurement of the
standard, is characteristic of the first positive polarity electric field on the soil surface.
discharge, typical of lightning generated on top of tall and
thin structures. These discharges are only 1% of the The average apparent resistivity curve was considered as
lightning, but they are one of the most critical conditions to representative of the typical shallow ground in the
which the wind generator can be submitted. The windfarm windfarm area. The final segment of this curve indicates
towers can be ground-to-cloud an upward trend of the apparent resistivity, but the last
lightning, which present return discharges with higher point (128 m spacing) was calculated from the average of
peak and energy values, the latter associated with the long only 4 wide-open soundings. Due to these reasons, the
tail of the current impulse. shallow geoelectric model will be considered well-defined
only after the joint analysis with the near-surface
Hand [3] presents the calculation of the magnetic field in soundings (TDEM/AMT).
the nacelle of a wind generator, with the COMSOL
Multiphysics software, produced by the injection of a
current of 200 A @ 25 kHz on the tip of one blade,
simulating a lightning strike. The sine wave at the
frequency of 25 kHz has a period of 40 µs (T = 1/freq.),
which takes the same 10 µs that the 10/350 µs pulse takes
to reach the peak value. The frequency range from 1 to 40
kHz concentrates the highest energy content of the
standard impulses, after its decomposition by the Fourier
transform. Therefore, the grounding response to the 25
kHz frequency emulates the response to an impulse with
a 10 µs wavefront [4].

3 GEOPHYSICAL SURVEYS
Figure 2.1: VES apparent resistivity curves (Wenner array).
Three geophysical surveys were carried out over the
windfarm complex, using different electrical and 3.2 The Audiomagnetotelluric Soundings (AMT)
electromagnetic methods for probing the resistivity
distribution of the subsurface. The ground was probed by The AMT soundings were done by Strataimage with
22 collocated VES + AMT soundings - the VES with Phoenix Geophysics equipment, with magnetic sensors in
Wenner arrangement and spacings up to 128 m (for the frequency range 1 - 10 kHz. The Phoenix Geophysics
probing the upper tens of meters); the AMT soundings for MTU-5A receiver records five time-series channels - two
probing the so-called near-surface, with a depth of for the electric field and three for the magnetic field. The
investigation of about one kilometer. Four complimentary soundings were done for periods of 30 minutes.
TDEM soundings were done, which is another method of
near-surface survey.
The telluric channels (electric fields Ex and Ey) were These deviations are not random, which means that there
measured using non-polarized porous lead-chloride is no Gaussian distribution of errors. The consequence is
electrodes, with 100 m dipoles in a cross configuration and that the invariants of the apparent resistivity curves of a
component X always directed towards magnetic north. regional MT survey may be all displaced up or down (more
Data processing transforms the raw data-series into an often downward) by different factors, which are constant
Electronic Data Interchange file (EDI), containing apparent for each curve in the log-log scale. This means that, in
resistivity and phase information as a function of general, the invariant of the apparent resistivity curves
frequency, in addition to other parameters (impedance, (1D) of different MT stations will present lower values than
tipper, skew, coherence, induction vectors). The dipoles the real ones, which results in an average 1D regional
orientation was corrected for the regional true magnetic model more conductive than the real [7, 8].
North in the pre-processing of the data, considering the
magnetic declination according to NOAA National In the AMT transfer function, the vertical displacement of
Oceanic and Atmospheric Organization. The AMT curves the apparent resistivity curve occurs by a factor
calculated for each sounding station were rotated to align independent of the frequency, with no corresponding
with the dominant regional strike. change in the phase curve. This effect is especially
common in volcanic environments, such as the Bom
Figure 2.2 shows the two sets of 22 invariant (1D) curves Jardim da Serra Complex, where changes in resistivity can
of apparent resistivities and phases. The invariant of each occur over short horizontal distances due to the variability
of the 22 AMT sounding stations was calculated, for each of the resistivity of lava flows and/or the fracture level of
frequency, from the geometric average of the apparent the basaltic surface packages.
resistivities and the arithmetic average of the phases, for
the XY and YX values. This figure also shows the average 3.3 The Time Domain Electromagnetic Soundings
curves (red), which are representative of the regional 1D
geoelectric model of the near-surface ground layers of the The TDEM soundings were done by USP, using a 100 m
Bom Jardim da Serra windfarm complex. side transmitting square loop configuration, with a
receiving coil in the center of the loop (central loop). The
acquisition was done with a Protem-D recorder (Geonics,
1994) and a transmitting source TEM57-MK2 (Geonics,
1998), with frequencies of 30 Hz, 7.5 Hz and 3 Hz, which
allows reaching down to ~ 1000 m in depth, depending on
the electrical conductivity of the subsurface materials.

Figure 2.3 shows the four apparent resistivity curves


calculated from the TDEM technique (A2, C3, C5 and B8),
which are very consistent with each other and were
reduced to a geometric average curve (red),
representative of the near-surface geoelectric structure of
the Bom Jardim da Serra windfarm complex. The TDEM
curves show a much smaller vertical spread than what is
observed in the Wenner and AMT curves, which can be
attributed to the fact that this electromagnetic technique
does not measure the electric field on the soil surface and,
therefore, is not affected by the static-shift.

Figura 2.2: AMT apparent resistivity and phase curves.

Figure 2.4: four apparent resistivity curves calculated from


Berdichevsky [6] proposed the construction of the 1D the TDEM technique and the geometric average curve,
average regional geoelectric model of a region using the representative of the regional basement.
geometric average of the invariant of the MT impedances,
calculated from a large number of MT soundings within the
area under study. MT soundings measure electric fields on Many techniques have been proposed to correct the static-
the soil surface and, in the same way of the shift observed in the apparent resistivity curves of the
electroresistivity soundings, can be affected by galvanic Wenner and AMT soundings. One of the most traditional
deviations due to heterogeneities in the resistivity of approaches is the use of TDEM soundings as a reference
shallow ground layers, which introduce distortions in the for the near-surface resistivity layers [9, 10], disregarding
parameters of the MT impedance matrix. aspects of topographic variation, which means the
premise of a flat region.
4 THE COMBINED GEOELECTRIC MODEL

The ideal procedure for the combination of the different


surveys into a single geoelectric model would be by the
simultaneous inversion of the Wenner and/or AMT curves
with the TDEM curves. Considering that this software is
not available, before the inversion of each set of curves, it
was adjusted the leveling of the Wenner and AMT
apparent resistivity curves affected by the static deviation.
This leveling was achieved by plotting the three 1D
average curves in the same graph, using the empirical
conversion factors proposed by Meju [11].

Figure 3.1 shows the average apparent resistivity curves


Wenner (red), TDEM (light blue) and AMT (dark blue)
plotted on the same graph. The spacing of the average Figure 3.2: average Wenner apparent resistivity curve
Wenner curve and the times of the average TDEM curve adjusted with the divisor factor 2 (black) and inferred curve
were converted to period (in seconds) using Meju's (red) with the 3-layer model (blue line and table).
empirical expressions [2005]. These three curves are
vertically displaced, which can be seen in the overlap This model neglected the existence of a superficial layer
interval of the curves, between the periods of 10 -4 s and of soil of slightly lower resistivity and less than one meter
10-2 s. For the combination of the Wenner and AMT curves thick. The final segment of this curve is not well
in a single geoelectric model, valid from the ground surface characterized, only indicating the trend of increasing
to about a kilometer depth, an adjustment of the vertical resistivity. The final segment of the red curve does not
offset is necessary, which can be applied to both curves, follow the average curve (black), reflecting the adjustment
considering that both may be affected by the static-shift. obtained for the transition layer between the Wenner and
Assuming that the average TDEM curve is not affected by AMT curves, from the inversion of the AMT curves
any galvanic deviation, this curve can be used as a constrained by the shallow ground layers of the Wenner
reference for the average Wenner and AMT curves. model.

Figure 3.1 also shows the average curves of apparent Figure 3.3 shows the result of the inversion of the average
resistances Wenner and AMT vertically displaced - AMT curves adjusted by the multiplicative factor 1.3. The
Wenner (/2, orange) and AMT (x 1.3, purple). The two shallower layers were constrained by the result of the
adjustments were applied in an interactive process that inversion of the Wenner curve divided by 2. The blue line
simultaneously adjusted the correction factors for both and the table show the average geoelectric model
curves (Wenner and AMT), taking as reference the obtained, with 6 layers, considered as representative of
the entire area of the Bom Jardim da Serra Windfarm.
periods 10-3 if 10-2 s). This graph also includes the Wenner
curve adjusted by the divisor factor 3 (green), which would
correspond to the areas of the windfarm complex where
the resistivity of the shallow layers is lower. This is the
case of the two towers of Santo Antônio Windfarm, where
the impedance measurements at the base of the towers
revealed an

Figure 3.2 shows the average Wenner apparent resistivity


curve after the adjustment with the divisor factor 2 (black)
and the inferred curve (red) after inversion, with the 1D soil
model stratified in 3 layers (blue line and table).

Figure 3.3: AMT 1D invariant curves (apparent resistivities


Figure 3.1: average apparent resistivity curves original and phases) adjusted by the multiplicative factor 1.3 (black)
TDEM (light blue), Wenner (red) and AMT (dark blue), and and inferred curve (red), with the imposition of the shallow
vertically adjusted curves (orange, green and purple). ground model (blue line and table, with h in km).
The simulations of the isolated tower reveal that both the
According to this model, the shallow ground layers, down
to a depth of 44 m, show resistivity variations within the as seen from the base of the tower, present very similar
area of the windfarm, justifying the different grounding values, which can be explained by the extremely close grid
provided by the tower foundation. The grounding
characterizes the average regional basement, valid for the resistance seen from the base of the tower or seen from
entire area of the windfarm. The depth of about 660 m the foot of the post However,
(around 0.1 seconds) is compatible with the average the grounding impedance as seen at the foot of the post
thickness expected for the Serra Geral formation in the concerning the same parameter
Bom Jesus da Serra region. as was verified
that in the case of the isolated tower, the arrestors located
Below the 660 m depth are the pre-volcanic ground layers, on the top of the post are not as well-grounded as those
where the AMT signal presents lower quality, without, located in the cubicle at the base of the tower.
however, prejudice of the geoelectric model, because at
this depth the ground layers do not affect the performance The grounding impedance calculated at the base of the
of the grounding system of the windfarm. of the
central tower of the complete park (9.5 both reproduce
5 THE PERFORMANCE OF THE GROUNDINGS very well the performance of the average grounding
the high-
The grounding system of each windfarm consists of the frequency (25 kHz) is confined to the tower where the
following interconnected elements: lightning strikes, not spreading to the rest of the park.
the base of each tower including the two rings of
copper cable with 70 mm² interconnected to the We performed a sequence of simulations to calculate the
resistance (60 Hz) and impedance (25 kHz) of the
bare copper cable with 70 mm², connecting the base grounding of a central tower of Parque Púlpito. In each
of the tower with the 2.4 m coppersteel rod at the base simulation, the depth of the geoelectric model was
of the post of the 34.5 kV line (about 60 m long); reduced, with the elimination of the last ground layer. The
the , model was reduced from 6 layers to 4 layers with no
interconnecting the groundings of the towers. significant change of the two parameters monitored.
ground layer was eliminated,
The Púlpito Windfarm is one of the three windfarms with remaining only the basalt
20 towers and was selected to assess the performance of basement, the grounding resistance
the grounding system, as it is considered representative of elevation of 8.5%, which means that the grounding system
the typical windfarm of the Bom Jesus da Serra Complex. of the park can see more than 700 m deep, thus confirming
the importance of a deep geoelectric model, about 1 km
Performance evaluations of the grounding system were deep. The grounding impedance of the tower increased by
carried out based on simulations using the MultiGroundZ only 2% with this last model, more than expected for such
program, developed by SES - Safe Engineering Services a high frequency (25 kHz).
& technologies ltd (www.sestech.com), a Canadian
research company founded in 1978 by Prof. Farid P. The simulations with the complete park reveal that the
Dawalibi, developer of the computational package CDEGS tower grounding resistance is significatively reduced, to
- Current Distribution, Electromagnetics, Grounding and less than 10% of the value of the isolated tower. The
Soil Structure Analysis. interconnection of the bases through the ground
wire of the medium voltage transmission lines guarantees,
Table 4.1 presents the measured and calculated therefore, the manufacturers d tower grounding
grounding resistances and impedances for a current resistance less than 10 . In medium or low resistivity soils
injection at the base of the tower and at the foot of the post (below 10 foundation
of the medium voltage line, at the arrival of the tower, reinforcements as grounding elements may be enough to
considering two conditions: achieve resistances and
isolated tower no grounding connection with the rest However, in high-resistivity grounds
of the park, and the base of the tower is interconnected only with the integration of the windfarm groundings it is
to the foot of the medium voltage line post by a 70 mm² possible to achieve grounding resistances
bare copper cable directly buried in the ground; and
In the case where a conductivity enhancement product is
at the central tower of the windfarm connected to the
used to improve the grounding of the tower-post
groundings of the other towers through the ground wire
interconnection cable since it is applied along the entire
of the medium voltage line.
length of the cable trench, the simulations of the isolated
tower reveal that the grounding resistance seen from the
The table also shows the effect of the treatment of the
post has a reduction of about 10%, however, the
bottom of the trench, where it is buried in the cable tower-
grounding impedance is halved, demonstrating that this
post, with a product that enhances the soil conductivity.
measure is important for improving the performance of the
The effect of this product was simulated by a larger
arresters located there. Therefore, this measure is
diameter conductor ( 15 cm). It is noteworthy that if the
important in the case of isolated towers or when the
treatment was simulated by a 15 cm diameter conductive
shallow ground presents high-resistivity and high
tube, the treated trench diameter shall be larger, and it is
exposure to lightning strikes, as is the case of the Bom
necessary to observe the product manufacturer's
Jardim da Serra Complex.
guidelines.
6 CONCLUSIONS the TDEM soundings are performed as a support for
the AMT soundings and allow for the best adjustment
The main finding of this study is that the use of only of the static-shift deviations.
shallow soundings (Wenner) would result in a geoelectric
model with higher resistivities than those that occur in the 7 REFERENCES
surveyed area and with an infinite high-resistivity
basement, which could lead to a very conservative [1] IEC-TR61400-24 - Wind Turbine Generator Systems - Part
evaluation and thus to expensive measures. The 24: Lightning Protection
importance of complex geoelectric modeling was [2] Hand J. Lightning-proof Wind Turbines.
demonstrated, using different geophysical sounding www.comsol.com/electrical. June/2012.
techniques for probing different ground layers, which are [3] Freire PEF. & Pane E. Sistemas de Aterramento de Parques
then combined into a single geoelectric model. Despite the Eólicos. Rio de Janeiro. Brazil WindPower agosto/2012.
basalt basement that dominates the entire area, the final [4] Freire PEF. Costanzo A. Villarreal M. Pane E. Parque Eólico
geoelectric model shows lower resistivities than expected, Água Doce Medições de Resistividade do solo e de
which indicates that the basalts in the area are well- Resistências de Aterramento. Rio de Janeiro, Brazil
fractured and water-saturated. The 1D geoelectric model WindPower agosto/2013.
obtained is compatible with the expected geological [5] Freire PEF. Medição de Aterramentos com o Terrômetro de
structure of the border of the canyons and was used for Alta-frequência Aplicação a Parques Eólicos. São Paulo,
ENIE agosto/2014.
[6] Berdichevsky MN. Vanyan LL. Kuznetsov VA. Levadny VT.
Mandelbaum MM. Nechaeva GP. Ukulessky BA. Shilovsky
The complete windfarm grounding system was simulated PP. Shpak IP. Geoelectrical model of the Baikal region.
with the CDEGS MultiGroundZ software, allowing for the Physics of the Earth and Planetary Interiors, Vol. 22, Issue
grounding impedance at the 1, pp. 1-11, April 1980.
frequencies of 60 Hz and 25 kHz. The average of the [7] Árnason K. The static-shift problem in MT soundings.
measured impedance of the tower groundings Proceedings World Geothermal Congress. Melbourne,
(at 25 kHz), almost the same value calculated for the Australia. April 2015.
impedance of a tower located in the central area of the [8] Rung-Arunwan T. Siripunvaraporn W. Utada H. On the
windfarm . This excellent match demonstrates the Berdichevsky average. Physics of The Earth and Planetary
success of the proposed methodology for the construction Interiors. February 2016.
of the deep geoelectric model of the windfarm, despite all [9] Sternberg BK. Washburne JC. Pellerin L. Correction for the
the uncertainties that do exist in this kind of modeling. static-shift in magnetotellurics using transient
electromagnetic soundings. Geophysics 53, pp. 1459 1468,
1988.
The following conclusions can be derived from the
geoelectric modeling procedure here proposed: [10] Pellerin LD. & Hohmann GW. Transient electromagnetic
inversion; a remedy for magnetotelluric static shifts.
if only the average of the Wenner soundings were Geophysics 55, pp. 1242 1250, 1990.
used, the average shallow geoelectric model would [11] Meju MA. Simple relative space-time scaling of electrical and
result in a more resistive geoelectric model, due to the electromagnetic depth sounding arrays: implications for
upward deviation produced by galvanic deviations and electrical static-shift removal and joint DC-TEM data
to the use of a geoelectric model that does not show inversion with the most-squares criterion. Geophysics
the low resistivity layer below the basalt ground layer; Prospecting 53, pp. 463-479, 2005.
the addition of the AMT soundings provides near-
surface resistivity information and allows for a first-
approach adjustment of the 1D geoelectric model;

Table 4.1: measured and calculated resistances (60 Hz) and impedances (25 kHz) for the tower and post.

Place of the Current Resistance Impedance


Configuration
Injection (60 Hz) (25 kHz)

The average value measured at 22 towers Base of the tower - 9,3


Insulated tower Base of the tower 8,6 9,0
Insulated tower Base of the post 8,6 17
Complete windfarm Base of the tower 0,7 9,3
Complete windfarm Base of the post 0,7 11
Insulated tower with the application of a product for the improvement
Base of the tower 7,9 8
of the conductivity of the cable tower-post
Insulated tower with the application of a product for the improvement
Base of the post 7,9 8,4
of the conductivity of the cable tower-post
Complete windfarm with the application of a product for the
Base of the tower 0,7 7,5
improvement of the conductivity of the cable tower-post
Complete windfarm with the application of a product for the
Base of the post 0,6 7
improvement of the conductivity of the cable tower-post

You might also like