POWER SWITCH BOARD = MDB-PART(2)

INTRRUPTING CAPACITY =

PANEL POTENTIAL = VL-L 380 VL-G 220

NUMBER OF PHASES = 3

NUMBER OF WIRES = 4

POWER FREQUENCY = 60 Hz

MAIN CIRCUIT BREAKER = 600 AT MCCB AF 3 POLES


CALCULATE
ADDITIONAL SETS (FOR FINAL NUMBER ESTIMATED GROUND VOLTAGE
PANEL NO. OF DIVERISTY CONNECTED CONNECTED DEMAND DEMAND Derating D NUMBER DESIGN CABLE SIZE % VOLTAGE
# PANEL ID VOLTAGE DROP NUMBER OF CABLE WIRE CB AT CB AF DROP
CB/AMP POLES FACTOR LOAD KVA LOAD AMPS LOAD LOAD AMPS factor OF AMPS/SET mm2 DROP
COMPENSATION) OF SETS WIRES/CT LENGTH mm2/CT (V/AMP*KM)
SETS/CT
CONNECTED PANELS

1 LP-GF 80 3 0.85 18.230 27.698 15.496 23.544 0.7 1 0 1 34 3PH+N 35 35 16 80 80 0.26 1.030

2 PP-GF 80 3 0.85 22.940 34.855 19.499 29.627 0.7 1 0 1 43 3PH+N 35 35 16 80 80 0.33 1.030

3 LP-FF 63 3 0.85 11.680 17.746 9.928 15.084 0.7 1 0 1 22 3PH+N 25 40 16 63 63 0.26 1.390

4 PP-FF 80 3 0.85 21.090 32.044 17.927 27.237 0.7 1 0 1 39 3PH+N 35 40 16 80 80 0.35 1.030

5 LP-RF 63 3 0.85 6.290 9.557 5.347 8.123 0.7 1 0 1 12 3PH+N 25 45 16 63 63 0.16 1.390

6 PP-RF 80 3 0.85 24.390 37.058 20.732 31.499 0.7 1 0 1 45 3PH+N 35 45 16 80 80 0.45 1.030

7 ACP2-RF 400 3 0.85 180.000 273.490 153.000 232.466 0.7 1 0 1 333 3PH+N 240 50 120 400 400 0.83 0.231

8 WATER TREATMENT PUMP 40 3 1 6.000 9.116 6.000 9.116 0.7 1 0 1 14 3PH+N 10 25 6 40 40 0.20 3.350

9 LIFT-1 63 3 1 9.000 13.674 9.000 13.674 0.7 1 0 1 20 3PH+N 16 30 10 63 63 0.23 2.140

10 LIFT-2 63 3 1 9.000 13.674 9.000 13.674 0.7 1 0 1 20 3PH+N 16 40 10 63 63 0.31 2.140

11 LIFT-3 63 3 1 9.000 13.674 9.000 13.674 0.7 1 0 1 20 3PH+N 16 45 10 63 63 0.35 2.140

12 CENTRAL WATER HEATER 40 3 1 6.000 9.116 6.000 9.116 0.7 1 0 1 14 3PH+N 10 50 6 40 40 0.40 3.350

13 SPARE 80 3 1 80 80

14 SPARE 100 3 1 100 100

15 SPARE 63 3 1 63 63

TOTAL DEMAND 290.620 491.704 247.927 426.837

ADDITIONA ESTIMATED
L SETS CABLE
CALCULATE (FOR LENGTH
FINAL GROUND VOLTAGE
NO. OF DEMAND CONNECTED D NUMBER VOLTAGE DESIGN CABLE SIZE % VOLTAGE
PANEL ID PANEL CB Derating factor NUMBER NUMBER OF WIRES/CT WIRE CB AT CB AF DROP
POLES LOAD Kw LOAD AMPS OF DROP AMPS/SET mm2 DROP
OF SETS mm2/CT (V/AMP*KM)
SETS/CT COMPENSA
TION)

MDB-PART(2) 600 3 247.927 426.837 0.75 1 0 1 570 3PH+N 300 10 150 600 MCCB 0.23 0.206

TOTAL LOAD Amperes= 427 A

TOTAL DEMAND LOAD Kw = 247.927 KVA

MAIN CIRCUIT BREAKER = 600 AT MCCB 3 POLES

SUPPLIED FROM PANEL SCECO METER