Professional Documents
Culture Documents
MDB Part
MDB Part
INTRRUPTING CAPACITY =
NUMBER OF PHASES = 3
NUMBER OF WIRES = 4
POWER FREQUENCY = 60 Hz
1 LP-GF 80 3 0.85 18.230 27.698 15.496 23.544 0.7 1 0 1 34 3PH+N 35 35 16 80 80 0.26 1.030
2 PP-GF 80 3 0.85 22.940 34.855 19.499 29.627 0.7 1 0 1 43 3PH+N 35 35 16 80 80 0.33 1.030
3 LP-FF 63 3 0.85 11.680 17.746 9.928 15.084 0.7 1 0 1 22 3PH+N 25 40 16 63 63 0.26 1.390
4 PP-FF 80 3 0.85 21.090 32.044 17.927 27.237 0.7 1 0 1 39 3PH+N 35 40 16 80 80 0.35 1.030
5 LP-RF 63 3 0.85 6.290 9.557 5.347 8.123 0.7 1 0 1 12 3PH+N 25 45 16 63 63 0.16 1.390
6 PP-RF 80 3 0.85 24.390 37.058 20.732 31.499 0.7 1 0 1 45 3PH+N 35 45 16 80 80 0.45 1.030
7 ACP2-RF 400 3 0.85 180.000 273.490 153.000 232.466 0.7 1 0 1 333 3PH+N 240 50 120 400 400 0.83 0.231
8 WATER TREATMENT PUMP 40 3 1 6.000 9.116 6.000 9.116 0.7 1 0 1 14 3PH+N 10 25 6 40 40 0.20 3.350
12 CENTRAL WATER HEATER 40 3 1 6.000 9.116 6.000 9.116 0.7 1 0 1 14 3PH+N 10 50 6 40 40 0.40 3.350
13 SPARE 80 3 1 80 80
15 SPARE 63 3 1 63 63
ADDITIONA ESTIMATED
L SETS CABLE
CALCULATE (FOR LENGTH
FINAL GROUND VOLTAGE
NO. OF DEMAND CONNECTED D NUMBER VOLTAGE DESIGN CABLE SIZE % VOLTAGE
PANEL ID PANEL CB Derating factor NUMBER NUMBER OF WIRES/CT WIRE CB AT CB AF DROP
POLES LOAD Kw LOAD AMPS OF DROP AMPS/SET mm2 DROP
OF SETS mm2/CT (V/AMP*KM)
SETS/CT COMPENSA
TION)
MDB-PART(2) 600 3 247.927 426.837 0.75 1 0 1 570 3PH+N 300 10 150 600 MCCB 0.23 0.206