PCS-931S - X - Selection Guide - EN - Overseas General - X - R1.10

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 51

Copyright © 2020 NR. All rights reserved.

NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and
benefits afforded under P.R. China and international copyright and patent laws in its products,
including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is
licensed to use this document as well as all intellectual property rights owned or held by NR
Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how,
trade secrets, trademarks and trade names, service marks, design rights, database rights and
rights in data, utility models, domain names and all similar rights.

The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.

To the extent required the products described herein meet applicable IEC and IEEE standards,
but no such assurance is given with respect to local codes and ordinances because they vary
greatly.

Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered
sufficiently for your purposes, please do not hesitate to contact us.
Preface

Preface

About This Manual

The selection guide describes the application overview and the summary of protection, automation,
control and supervision functions of PCS-931S. Moreover, it provides the explanation about the
application option, the firmware option, the software option, the hardware option and etc., and can
be used to indicate how to order a PCS-931S based on expected configurations.

Warranty

This product is covered by the standard NR 10-year warranty. For warranty details, please consult
the manufacturer or agent for warranty information.

Document Structure

This guide is mainly for the overview of the application and the functions about PCS-931S, and it
provides the configuration of software and hardware information for ordering. An overview of each
manual section and section topics follows.

1 Functions and Application


Introduces the summary functions of this device, such as the protection, the automation, the
control and the supervision. Briefly introduces the typical application schemes of PCS-931S.

2 Introduction to PCS-Torch
Introduces the main functions of PCS-Torch, including create new project, create new device,
export MOT and Manage MOT library, MOT configuration interface and the structure of the
ordering code.

3 MOT Information
Introduces the meaning and options of each field, and gives a detailed description about the
selection rule for the application, the firmware, the software, the hardware, the chassis structure
and so on.

Document Revision History

PN: ZL_PCS-931S_X_Selection Guide_EN_Overseas General_X

Current version: R1.10

PCS-931S Line Differential Relay I


Date: 2020-07-29
Preface

Corresponding Version
Release Date Description of change
Document Software

R1.00 R1.00 2019-01-31 ⚫ Form the original manual.

⚫ Modify the section "Functions and Applications"

⚫ Update the section "Typical Applications"


R1.10 R1.30 2020-07-29
⚫ Add the section "Introduction to PCS-Torch"

⚫ Update the options and descriptions of all MOT fields

II PCS-931S Line Differential Relay


Date: 2020-07-29
1 Functions and Applications

1 Functions and Applications


1
Table of Contents

1.1 Overview........................................................................................................... 1-1


1.2 Protection ......................................................................................................... 1-2
1.3 Control .............................................................................................................. 1-6
1.4 Synchrophasor Measurement ........................................................................ 1-7
1.5 Measurement ................................................................................................... 1-7
1.6 Recording ......................................................................................................... 1-7
1.7 Supervision ...................................................................................................... 1-8
1.8 Pilot Channel Scheme ..................................................................................... 1-8
1.9 Communication................................................................................................ 1-8
1.10 Digital Interface .............................................................................................. 1-8
1.11 User Interface ................................................................................................. 1-9
1.12 Miscellaneous ................................................................................................ 1-9
1.13 Typical Applications .................................................................................... 1-10

List of Figures

Figure 1.1-1 Functional overview of PCS-931S ........................................................................ 1-1

Figure 1.10-1 Typical application of single circuit breaker in single busbar ...................... 1-10

Figure 1.10-2 Typical application of double circuit breakers ............................................... 1-11

Figure 1.10-3 Typical application of single circuit breaker in double busbars .................. 1-12

PCS-931S Line Differential Relay 1-a


Date: 2020-07-29
1 Functions and Applications

1-b PCS-931S Line Differential Relay


Date: 2020-07-29
1 Functions and Applications

1.1 Overview

PCS-931S protect overhead and underground lines, feeders and cables on all voltage levels with 1
highest selectivity possible. The large number of protective and automatic functions available
permits their utilization in all areas of line protection. The devices contain all important auxiliary
functions that are necessary today for safe network operation. This includes control, measurement
and monitoring functions. The large number of communication interfaces and communication
protocols satisfies the requirements of communication-based selective protection and of
automated operation. Their modular structure permits line protection devices always to be adapted
flexibly to the individual requirements.

The functional overview of the device is shown in Figure 1.1-1.

Busbar

3VT

52

85 21 67P 67G 67Q 32R 49P 50DZ 46BC 62P D 50BF 37 PMU 59P
3CT
*

87L 21D 50/51P 50/51G 50/51Q FR 59Q

78 FL

Data transmit/Rec eiv e


SOTF 59G

81O 27P

81U 81R

87STB (Only for one and a half breakers arrangement)


1VT
25 79

Line

Figure 1.1-1 Functional overview of PCS-931S

PCS-931S is a high-speed transmission line differential relay featuring single-pole and three-pole
tripping and reclosing with synchronism check. The device features extensive metering and data
recording including high-resolution data capture and reporting. PCS-931S features expanded
control equation programming for easy and flexible implementation of custom protection and
control schemes.

A simple and robust hardware design features efficient digital signal processing. Combined with
extensive self-testing, these features provide device reliability and enhance relay availability.

PCS-931S can be configured to support single circuit breaker application or double circuit
breakers application by PCS-Studio. If the device is applied to double circuit breakers mode, all

PCS-931S Line Differential Relay 1-1


Date: 2020-07-29
1 Functions and Applications

protection functions related to the number of circuit breaker will be affected.

1.2 Protection
1
ANSI Protection functions Remark

⚫ DPFC current differential element (2 stages)

⚫ Steady-state current differential element (2 stages)

87 Current differential protection ⚫ Neutral current differential element (1 stage)

⚫ CT saturation detection

⚫ Capacitive current compensation

⚫ Independent pilot zone (forward direction and reverse

direction, mho or quadrilateral characteristics)

⚫ PUTT, POTT, Blocking, Unblocking, Zone Extension


Pilot distance protection
⚫ Current reversal logic

⚫ Weak infeed echo or echo&trip

85 ⚫ Open breaker echo

⚫ Directional zero-sequence comparison element for

pilot scheme
Pilot directional earth-fault
⚫ PTT, Blocking and Unblocking
protection
⚫ Current reversal logic

⚫ Open breaker echo

⚫ Up to 6 zones

⚫ 3 independent phase-to-ground distance elements for

each zone

⚫ 3 independent phase-to-phase distance elements for

21L Distance protection each zone

⚫ Selectable quadrilateral characteristics or mho

characteristics

⚫ Independent impedance settings and time delays for

each zone

1-2 PCS-931S Line Differential Relay


Date: 2020-07-29
1 Functions and Applications

⚫ Zero-sequence current compensation for

phase-to-ground distance element

⚫ Selectable forward direction, reverse direction or


1
non-direction (except zone 1 that is fixed as forward

direction)

⚫ Load encroachment for each zone

⚫ Power swing blocking and releasing for each zone

⚫ Faulty phase selection for each zone

⚫ Fixed forward direction

21D DPFC distance protection ⚫ High-speed operation

⚫ Supplementary for zone 1 of distance protection

78 Out-of-step protection ⚫ Easy to set and independent of system parameters

⚫ Up to 6 stages with independent logic

⚫ Voltage control element for each stage

⚫ Optional direction element for each stage, including

67P forward direction, reverse direction or non-direction


Phase overcurrent protection
50/51P ⚫ Optional definite-time characteristics and inverse-time

characteristics for each stage

⚫ Trip purpose or alarm purpose for each stage

⚫ Harmonic control element for each stage

⚫ Up to 6 stages with independent logic

⚫ Optional direction element for each stage, including

forward direction, reverse direction or non-direction

67G ⚫ Optional definite-time characteristics and inverse-time


Earth fault protection
50/51G characteristics for each stage

⚫ Selectable trip purpose or alarm purpose for each

stage

⚫ Harmonic control element for each stage

67Q Negative-sequence overcurrent ⚫ Up to 2 stages with independent logic

PCS-931S Line Differential Relay 1-3


Date: 2020-07-29
1 Functions and Applications

50/51Q protection ⚫ Optional direction element for each stage, including

forward direction, reverse direction or non-direction


1 ⚫ Optional definite-time characteristics and inverse-time

characteristics for each stage

⚫ Via distance measurement elements

SOTF Switch onto fault ⚫ Via dedicated earth fault element

⚫ Via phase overcurrent element

⚫ Up to 2 stages with independent logic

49P Thermal overload protection ⚫ Selectable trip purpose or alarm purpose for each

stage

⚫ Up to 2 stages with independent logic

⚫ Optional definite-time characteristics and inverse-time

characteristics for each stage

59P Phase overvoltage protection ⚫ Optional phase voltage or phase-to-phase voltage

⚫ Optional “1-out-of-3” logic or “3-out-of-3” logic

⚫ Selectable trip purpose or alarm purpose for each

stage

⚫ Up to 2 stages with independent logic

⚫ Optional definite-time characteristics and inverse-time

characteristics for each stage

⚫ Optional phase voltage or phase-to-phase voltage

⚫ Optional “1-out-of-3” logic or “3-out-of-3” logic


27P Phase undervoltage protection
⚫ Blocked by instantaneous VT circuit failure

⚫ Selectable trip purpose or alarm purpose for each

stage

⚫ Optional auxiliary criterion, including CB position check

and current check

Negative-sequence overvoltage ⚫ Up to 2 stages with independent logic


59Q
protection ⚫ Selectable trip purpose or alarm purpose for each

1-4 PCS-931S Line Differential Relay


Date: 2020-07-29
1 Functions and Applications

stage

⚫ Up to 2 stages with independent logic


1
59G Residual overvoltage protection ⚫ Selectable trip purpose or alarm purpose for each

stage

⚫ Up to 4 stages with independent logic


81O Overfrequency protection
⚫ Voltage control element

⚫ Up to 4 stages with independent logic


81U Underfrequency protection
⚫ Voltage control element

Rate of change of frequency ⚫ Up to 4 stages with independent logic


81R
protection ⚫ Voltage control element

⚫ Up to 2 stages with independent logic

32R Reverse power protection ⚫ Selectable trip purpose or alarm purpose for each

stage

⚫ Optional auxiliary criterion, including CB position check

and current check


37 Undercurrent protection
⚫ Selectable trip purpose or alarm purpose for each

stage

⚫ Phase-segregated re-trip and three-phases re-trip

⚫ Optional current criterion (phase overcurrent element,

zero-sequence overcurrent element,


50BF Breaker failure protection
negative-sequence overcurrent element)

⚫ Optional circuit breaker position check

⚫ Two time delays

⚫ Protect the T-zone in one-and-a-half breaker and ring


87STB Stub differential protection
breaker arrangements

⚫ Clear the dead zone faults between CT and the circuit


50DZ Dead zone protection
breaker

⚫ Adopt the ratio of negative-sequence current to


46BC Broken conductor protection
positive-sequence current (Ι2/Ι1) to detect the broken

PCS-931S Line Differential Relay 1-5


Date: 2020-07-29
1 Functions and Applications

conductor.

⚫ Initiated by three auxiliary contacts of phase-segregate


1
circuit breaker
62PD Pole discrepancy protection
⚫ Optional auxiliary criterion (zero-sequence current

element or negative-sequence current element)

⚫ Independent logic for auto-reclosing and manually


25 Synchrocheck
closing

⚫ One shot or multi-shot

⚫ 1-pole AR, 3-pole AR or 1/3-pole AR

79 Auto-reclosing ⚫ Optional trigger mode, including protection operating

and external binary input

⚫ Support synchro-check and voltage check

⚫ Compatible with IEEE C37.118-2005, IEEE

PMU Phasor measurement unit C37.118.1-2011, IEEE C37.118.2-2011 and IEEE

C37.118.1a-2014.

⚫ Single-ended impedance-based method

FL Fault location ⚫ Zero-sequence mutual coupling compensation for

parallel lines

⚫ Single-ended travelling-wave-based method


TWFL Travelling-Wave fault location
⚫ Double-ended travelling-wave-based method

DPFC is the abbreviation of deviation of power frequency component.

1.3 Control

⚫ Circuit breaker & disconnector control (Remote/local)

⚫ Synchronism check for remote and manual closing

⚫ Voltage selection

1-6 PCS-931S Line Differential Relay


Date: 2020-07-29
1 Functions and Applications

1.4 Synchrophasor Measurement

⚫ Synchronize with the GPS time by IRIG-B time source 1


⚫ Calculate synchronized phasors, including: Ua, Ub, Uc, U1, U2, U0, Ia, Ib, Ic, I1, I2, I0

⚫ Calculate analog values, including: active power (P), reactive power (Q), frequency,
ROCOF (df/dt)

⚫ Transmit binary status of the IED to PDC (Phasor Data Concentrator) according to IEEE
C37.118 standard

⚫ Realize high accurate measurement of the phasors and analogs according to the IEEE
C37.118.1-2011 and IEEE C37.118.1a-2014 standard.

⚫ Communicate with PDC according to IEEE C37.118-2005 and IEEE C37.118.2-2011

⚫ Supporting P Class or M Class measurement (user selectable)

⚫ Measurement of up to 32 binary status (user configurable)

⚫ Output of synchrophasor with timestamp, support of multiple protocols (TCP, TCP-UDP,


UDP) and multiple data rates (2f0, f0, f0/2) for maximum 4 clients (PDC)

1.5 Measurement

⚫ Current and voltage measurement at a 2.4KHz sampling rate

⚫ Current and voltage measurement at a 9.6KHz sampling rate

⚫ Travelling wave current measurement at a 1MHz sampling rate

⚫ Energy metering (active and reactive energy are calculated in import respectively export
direction)

⚫ Power (Apparent/Real/Reactive)

⚫ Power factor

⚫ Frequency

1.6 Recording

⚫ Event Recorder including 1024 disturbance records, 1024 binary events, 1024
supervision events, 256 control logs and 1024 device logs.

⚫ 64 disturbance waveforms records (The file format of disturbance recorder is compatible


with international COMTRADE file.)

⚫ 64 travelling wave fault location (TWFL) records (The file format of disturbance recorder
is compatible with international COMTRADE file.)

PCS-931S Line Differential Relay 1-7


Date: 2020-07-29
1 Functions and Applications

⚫ 64 high-frequency waveforms records (The file format of disturbance recorder is


compatible with international COMTRADE file.)

1 1.7 Supervision

⚫ VT circuit supervision

⚫ CT circuit supervision

⚫ Trip/Close coil supervision

⚫ Self-diagnostic

⚫ Pilot communication channel supervision

⚫ DC power supply supervision

⚫ Channel status statistic

⚫ System frequency supervision

1.8 Pilot Channel Scheme

⚫ Optional single- or dual- pilot channels (fiber optic)

⚫ Support G.703 and C37.94

1.9 Communication

⚫ Up to four 10Base-T/100Base-TX copper Ethernet ports using IEC 61850, DNP3.0 or


IEC 60870-5-103 over TCP/IP

⚫ Up to four 100Base-FX optical Ethernet ports using IEC 61850, DNP3.0 or IEC
60870-5-103 over TCP/IP

⚫ Two RS-485 serial ports using IEC 60870-5-103 or Modbus

⚫ One RS-485 serial port for clock synchronization

⚫ Support GOOSE communication module using IEC 61850-8-1 GOOSE

⚫ Full compatibility between IEC 61850 Editions 1 and 2

⚫ Redundancy protocols PRP, HSR and RSTP

⚫ One front RJ-45 port and one rear RJ-45 port for debugging

1.10 Digital Interface

⚫ Support IEC 61850 MMS Server via extendable electrical or optical Ethernet port

1-8 PCS-931S Line Differential Relay


Date: 2020-07-29
1 Functions and Applications

⚫ Support IEC 61850-8-1 GOOSE via extendable electrical or optical Ethernet port

⚫ Support IEC 61850-9-2LE SV via extendable electrical or optical Ethernet port


1
1.11 User Interface

⚫ Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and
set-point adjustment

⚫ Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management

⚫ 4 Programmable operator push-buttons with user-configurable labels

⚫ Up to 18 programmable target LEDs with user-configurable labels

⚫ 1 RS-232 rear ports for printer

⚫ Language switchover—English + selected language

⚫ Configuration tool—PCS-Studio

1.12 Miscellaneous

⚫ User programmable logic

⚫ Fault phase selection

⚫ Switching system phase sequences function (ABC or ACB)

⚫ Clock synchronization

 IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface

 PPS: Pulse per second (PPS) via RS-485 differential level or binary input

 PPM: Pulse per minute (PPM) via RS-485 differential level or binary input

 IEEE 1588: Clock message based on IEEE 1588 via optical fiber interface

 SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network

 SNTP (BC): Broadcast SNTP mode via Ethernet network

 Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol,


Modbus protocol and DNP3.0 protocol

⚫ Cyber security

 NERC CIP

 IEC 62351

 IEC 62443

PCS-931S Line Differential Relay 1-9


Date: 2020-07-29
1 Functions and Applications

 IEEE 1686

1.13 Typical Applications


1
There are several typical applications for different application situation.

⚫ 2-terminal transmission line

Busbar

1VT
52

3VT

85 21 67P 67G 67Q 32R 49P 50DZ 46BC 62P D 50BF 37 PMU 59P
3CT
*

87L 21D 50/51P 50/51G 50/51Q FR 59Q

78 FL

Data transmit/Rec eiv e


SOTF 59G

81O 27P

81U 81R

87STB (Only for one and a half breakers arrangement)

25 79
52

Figure 1.13-1 Typical application of single circuit breaker in single busbar

1-10 PCS-931S Line Differential Relay


Date: 2020-07-29
1 Functions and Applications

52 52
1VT
3CT

* 3VT
1
52 52

3CT
*

1VT

52 52

1VT

85 21 67P 67G 67Q 32R 49P 50DZ 46BC 62P D 50BF 37 PMU 59P

87L 21D 50/51P 50/51G 50/51Q FR 59Q

78 FL

Data transmit/Rec eiv e


SOTF 59G

81O 27P

81U 81R

87STB (Only for one and a half breakers arrangement)

25 79

Figure 1.13-2 Typical application of double circuit breakers

PCS-931S Line Differential Relay 1-11


Date: 2020-07-29
1 Functions and Applications

Busbar 1

3VT
Busbar 2

1 52
3VT

85 21 67P 67G 67Q 32R 49P 50DZ 46BC 62P D 50BF 37 PMU 59P
3CT
*

87L 21D 50/51P 50/51G 50/51Q FR 59Q

78 FL

Data transmit/Rec eiv e


SOTF 59G

81O 27P

81U 81R

87STB (Only for one and a half breakers arrangement)


1VT
25 79
52

Figure 1.13-3 Typical application of single circuit breaker in double busbars

1-12 PCS-931S Line Differential Relay


Date: 2020-07-29
2 Introduction to PCS-Torch

2 Introduction to PCS-Torch

Table of Contents

2.1 Overview........................................................................................................... 2-1 2


2.2 Create New Project .......................................................................................... 2-1
2.3 Create New Device........................................................................................... 2-2
2.4 Project Management........................................................................................ 2-4
2.5 MOT Configuration Interface .......................................................................... 2-5
2.6 Ordering Code.................................................................................................. 2-7
2.7 Export MOT ...................................................................................................... 2-8
2.8 MOT Library Management ............................................................................. 2-10

List of Figures

Figure 2.1-1 Project navigation when ordering IEDs............................................................... 2-1

PCS-931S Line Differential Relay 2-a


Date: 2020-07-29
2 Introduction to PCS-Torch

2-b PCS-931S Line Differential Relay


Date: 2020-07-29
2 Introduction to PCS-Torch

2.1 Overview

The PCS-Torch is an auxiliary ordering tool for the PCS S series products of NR Electric. It is
recommended to run on a MS Windows 7/10 operating system. This tool helps to create a
complete order code with detailed specifications based on the selection of functional options such
as software and hardware. This tool supports engineering methods to create models of various 2
types of the PCS S series protection, measurement and control devices in power substations, and
can view or select device hardware and software configurations before sales. Meanwhile, it could
preview device rear modules, and import or export the device configuration results in the form of
Excel table. The model library of all the types of device could be updated online automatically or
offline manually to facilitate the access of the latest functions of PCS S series devices.

2.2 Create New Project

PCS-Torch manages a project according to the structure of "Project (Substation)"→"Voltage


Level"→"Bay"→"Device" as shown in Figure 2.2-1, however, it also supports to create a new
device under the node of "Substation" or "Voltage Level" directly.

Click the button “New” to create a new


Project (Substation)
project sorted by substation name

Right-click the menu “New voltage


Voltage Level
level...” to create a new voltage level

Right-click the menu “New bay...” to


Bay
create a new bay

Right-click the menu “New device...” to


Device
create a new device

Right-click the menu “New device...” to


Device
create a new device

Right-click the menu “New device...” to


Device create a new device

Figure 2.2-1 Project navigation when ordering IEDs

⚫ Create several voltage levels or devices under the project node

PCS-931S Line Differential Relay 2-1


Date: 2020-07-29
2 Introduction to PCS-Torch

⚫ Create several bays or devices under the voltage level node

⚫ Create several devices under the bay node

2.3 Create New Device

Button Remark

Create a new project

Open an existing project

Save the current project

Update the MOT library online

Import the MOT library locally

Right-click the menu "New device..." under the node of project, voltage level or bay to create a
new device. There are two methods to create new device:

1. By MOT lib

2-2 PCS-931S Line Differential Relay


Date: 2020-07-29
2 Introduction to PCS-Torch

By the pop-up dialog box, enter the device name and select the device type.

⚫ Based main MOT version to create MOT configuration

If check the "MOT version", please select main MOT version (R1, R2……) in the dropdown box
"Version". When PCS-Torch creates MOT configuration of the device, it will automatically search
the latest archived firmware version corresponding to main MOT version, and creates MOT
configuration based on the latest archived firmware version.

Main MOT version is compatible with all firmware versions that begin with
main MOT version (except disabled firmware version). For example, if main
MOT version is "R1", R1 is compatible with all firmware version R1.**.

⚫ Based on specified firmware version to create MOT configuration

If check the "Firmware version", please input required firmware version according to the correct
format in the textbox "Version". PCS-Torch will create MOT configuration of the device according
to the input firmware version automatically except that the input firmware version is disabled or
does not exist, and PCS-Torch will issue related prompt message.

Finally, click the button "OK" to finish creating MOT information of the device.

2. By MOT code

PCS-931S Line Differential Relay 2-3


Date: 2020-07-29
2 Introduction to PCS-Torch

If no specific firmware version is designated (as shown in the red box), when PCS-Torch creates
2 MOT configuration of the device, it will automatically search the latest archived firmware version
corresponding to main MOT version, and creates MOT configuration based on the latest archived
firmware version.

If a specific firmware version is designated (as shown in the red box), PCS-Torch will create MOT
configuration of the device according to the input firmware version automatically except that the
input firmware version is disabled or does not exist, and PCS-Torch will issue related prompt
message.

2.4 Project Management

PCS-Torch can export MOT information of the whole substation, and support copy, paste, rename
function under any node.

It should be noted that PCS-Torch can only manage one project


(substation), so the project's (substation) copy and paste needs to open
multiple instances of PCS-Torch.

2-4 PCS-931S Line Differential Relay


Date: 2020-07-29
2 Introduction to PCS-Torch

Right-click menu under the project (substation) node, and select the menu item "Export Station
Information", an excel file that includes MOT codes and boards configuration information of all
devices in the project will be generated, as shown below.

2.5 MOT Configuration Interface

In the MOT configuration interface, the integral ordering code is displayed at the top. The detailed
MOT information is shown in a row/column format. The first column indicates MOT item, the
second column indicates the board type corresponding to the option, the third column indicates
available options with the ordering code corresponding to each item, and the fourth column
indicates the description about the chosen option.

Double-click the cell in the "Option" column to switch the option from drop-down box. When the
contents of the cell in the "Option" column is changed, the corresponding contents of the
"Description" and "Board Type" columns in the same row are changed synchronously, and the
corresponding bit of ordering code is also changed synchronously. There is possibly a mandatory

PCS-931S Line Differential Relay 2-5


Date: 2020-07-29
2 Introduction to PCS-Torch

binding rule or mutual exclusion rule among MOT items. The option will be chosen fixedly if an
option's mandatory binding rule is activated. The option will be hidden if an option's mutual
exclusion rule is activated. For the option that cannot be selected, PCS-Torch sets the row as gray.

There is a corresponding relationship between MOT item and the ordering code. When one bit of
the ordering code is chosen, the corresponding MOT item will be highlighted. When one MOT item
is chosen, the corresponding bit of ordering code will be highlighted.

2-6 PCS-931S Line Differential Relay


Date: 2020-07-29
2 Introduction to PCS-Torch

Click the button "Default", all options will be chosen as default value directly. Click the button
"Import excel", an existing MOT file (*.xls or *.xlsx) can be directly imported into the
corresponding device type of PCS-Torch. Click the button "Import code", an existing MOT code
can be directly imported into the corresponding device type of PCS-Torch.

2.6 Ordering Code

The ordering code of a MOT consists of 9 parts, including:

⚫ Device type: indicates the device type

⚫ U field: indicates application scenario

⚫ A field: indicates firmware type, which can be standard version or regional version

PCS-931S Line Differential Relay 2-7


Date: 2020-07-29
2 Introduction to PCS-Torch

⚫ R field: indicates firmware version

⚫ S field: indicates software functions

⚫ C field: indicates chassis structure and installation

⚫ PWR field: indicates the voltage level of power supply plug-in module


2 H field: indicates plug-in module configuration

⚫ MOT version: indicates MOT version

The display format is shown as below:

H field MOT version

PWR field

C field

S field

R field

A field

U field

Device type

2.7 Export MOT

After finishing MOT (Market Ordering Table) configuration, click the button "Complete" to display
the currently selected configuration information, including the ordering code and the device′s
hardware configuration, is shown as below:

2-8 PCS-931S Line Differential Relay


Date: 2020-07-29
2 Introduction to PCS-Torch

There are four function buttons, their usages are shown in the following table.

Button Remark

Copy ordering code based on selected information to the clipboard

Display device′s rear view based on selected information


2
Export MOT (Market Ordering Table) and device′s hardware configuration in Excel file format

Close the current window

Both MOT and device′s hardware configuration can be exported in Excel file format, as shown in
figures below.

⚫ Exported MOT

PCS-931S Line Differential Relay 2-9


Date: 2020-07-29
2 Introduction to PCS-Torch

⚫ Exported device′s hardware configuration

After finishing MOT configuration, the rear view of the device based on selected information can
be displayed. The device′s hardware configuration is displayed graphically (including Slot No.,
Module ID, and total slot numbers), as shown in the figure below.

2.8 MOT Library Management

The latest MOT library is included when PCS-Torch is released. The MOT library contains MOT
templates of each device, which are stored in the directory according to the device type. Each
directory contains all historical versions of the device for the MOT template. The path of MOT
library is "installation directory→PCS-Torch→motLib". There are two methods to upgrade the
MOT library.

2-10 PCS-931S Line Differential Relay


Date: 2020-07-29
2 Introduction to PCS-Torch

1. Update the MOT library online

Firstly, PCS-Torch reads a list of MOT templates for all devices from the server, and compares
them with local MOT library. The user can select the MOT template that needs to be updated, and
PCS-Torch downloads the corresponding MOT template file from the server.

2. Import the MOT library locally

It takes a long time to update the MOT library by connecting to the server, and the user can directly
import the latest MOT library if the network conditions are not good (The latest MOT template
library can be gained by mail firstly).

PCS-931S Line Differential Relay 2-11


Date: 2020-07-29
3 MOT Information

3 MOT Information

Table of Contents

3.1 Device Type ...................................................................................................... 3-1


3.2 Application Scenario (U Field) ........................................................................ 3-1
3.3 Firmware Type (A Field) .................................................................................. 3-1
3
3.4 Firmware Version (R Field) ............................................................................. 3-1
3.5 Software Functions (S Field) .......................................................................... 3-1
3.5.1 Software ............................................................................................................................... 3-1

3.5.2 Language.............................................................................................................................. 3-2

3.5.3 Protocol ................................................................................................................................ 3-2

3.5.4 Sampling Mode..................................................................................................................... 3-3

3.6 Chassis Structure and Installation (C Field) ................................................. 3-3


3.6.1 Case Size ............................................................................................................................. 3-3

3.6.2 Installation Mode .................................................................................................................. 3-4

3.6.3 Front Side Protection Class ................................................................................................. 3-8

3.6.4 Harsh Environment Conformal Coating ............................................................................... 3-8

3.6.5 I/O Terminal .......................................................................................................................... 3-9

3.7 Power Supply Plug-in Module (PWR Field) ................................................... 3-9


3.8 Plug-in Module Configuration (H Field) ....................................................... 3-10
3.8.1 Communication Ports & Time Synchronization Mode ........................................................ 3-10

3.8.2 Optical Fiber Protection Signalling Channel Interface ....................................................... 3-10

3.8.3 PRP/HSR............................................................................................................................ 3-11

3.8.4 Slot02.................................................................................................................................. 3-11

3.8.5 Slot03.................................................................................................................................. 3-12

3.8.6 Slot04.................................................................................................................................. 3-12

3.8.7 Slot05~Slot14 ..................................................................................................................... 3-13

3.9 MOT Version ................................................................................................... 3-13

PCS-931S Line Differential Relay 3-a


Date: 2020-07-29
3 MOT Information

3-b PCS-931S Line Differential Relay


Date: 2020-07-29
3 MOT Information

PCS S series device can select the hardware configuration and software functions of the device
through the auxiliary tool “PCS-Torch”, and a corresponding MOT (Market Ordering Table) serial
code will be generated.

3.1 Device Type

For a specific device, the device type is fixed, such as PCS-931S, so it is not need to be chosen.

3.2 Application Scenario (U Field)

The corresponding application scenarios are selected according to the actual protected objects by 3
the device. Only one kind of application is available, so it is chosen as "A: 2 terminal line" fixedly.

3.3 Firmware Type (A Field)

The firmware type is used to select between the standard version program and the regional
version program. Only the standard version program is available, so it is chosen as "AA:
Standard" fixedly.

3.4 Firmware Version (R Field)

The firmware version is used to select required program version. If there is no special version
requirement, the latest version can be chosen, i.e., "Latest version". Otherwise, the specified
version can be chosen.

3.5 Software Functions (S Field)

The software functions are determined by four parts: "Software", "Language", "Protocol" and
"Sampling mode".

3.5.1 Software

The option is used to select the required protection functions, which is used in conjunction with the
application scenario option. Different options correspond with different combinations of protection
functions, which can be viewed through the button "Software Functions" in PCS-Torch.
PCS-931S provides two kinds of functions combination, "A: Basic": and "C: Basic + PMU".

If "C: Basic + PMU" is chosen, "Sampling Mode" only can be "A:


Conventional instrument transformer".

PCS-931S Line Differential Relay 3-1


Date: 2020-07-29
3 MOT Information

3.5.2 Language

The option is used to select other supported language. "Chinese" is supported fixedly. "C:
English", "F: English + French", "R: English + Russian" or "S: English + Spanish" is available.

3.5.3 Protocol

The option is used to select the supported protocol for communication with SCADA system. There
are four kinds of protocols, including IEC103, DNP3.0, Modbus and IEC61850.

"A: Basic (IEC 60870-5-103 + DNP3.0 + Modbus)": includes IEC 60870-5-103, DNP3.0 and
Modbus

3-2 PCS-931S Line Differential Relay


Date: 2020-07-29
3 MOT Information

"B: Basic + IEC 61850 (Editions 1.0 or Edition 2.0)": includes IEC 60870-5-103, DNP3.0,
Modbus and IEC 61850, and full compatibility between IEC 61850 Editions 1.0 and 2.0.

3.5.4 Sampling Mode

The option is used to select sampling mode, and conventional sampling mode or digital sampling
mode is available.

"A: Conventional instrument transformer": conventional sampling mode

"B: Non-conventional instrument transformer": digital sampling mode based on IEC


61850-9-2LE
3
3.6 Chassis Structure and Installation (C Field)

The chassis structure and installation are determined by five parts: "Case Size", "Installation
Mode", "Front Side Protection Class", "Harsh Environment Conformal Coating" and "I/O
Terminal".

3.6.1 Case Size


The option is used to select the case size. The device supports two kinds of case sizes.

"B: 6U 1/2 19": 6U height, 1/2 width, 19-inch chassis

"C: 6U 1/1 19": 6U height, Full width, 19-inch chassis

1. Choose "B: 6U 1/2 19"

The device can support five kinds of installation modes.

The device can be equipped with 18 configurable LEDs, 1 CPU module, 1 AI module, 3 I/O
modules ("Slot4"~"Slot6") and 1 PWR module.

2. Choose "C: 6U 1/1 19"

The device only can support two kinds of installation modes. ("A: Flush" and "C: Rack")

The device can be equipped with 18 configurable LEDs, 1 CPU module, 1 AI module, 10 I/O

PCS-931S Line Differential Relay 3-3


Date: 2020-07-29
3 MOT Information

modules ("Slot5"~"Slot14") and 1 PWR module. "Slot4" will be always fixed as "X: Not required"
and "Slot7"~"Slot14" in the H field are activated.

The panels of 1/2 and 1/1 chassis are as below:

6U 1/2 19" 6U 1/1 19"

3.6.2 Installation Mode

The device supports 5 installation modes. This option is used to select the desired installation
mode, so that the manufacturer can provide the corresponding installation accessories.

"A: Flush": flush mounting

"B: Semi-flush": semi-flush mounting

"C: Rack": rack mounting

"D: Wall": wall mounting

"E: Surface": surface mounting

When the installation mode chooses "E: Surface", the front side of the device can support two
kinds of protection class (IP52 and IP54). For other installation modes, only IP52 is supported, and
"Front Side Protection Class" will be always fixed as "A: IP52".

When the installation mode chooses "C: Rack", please communicate with the manufacturer to
confirm the installation accessories because the installation accessories are different for single 6U,
1/1 × 19'' device, single 6U, 1/2 × 19'' device and dual 6U, 1/2 × 19'' devices.

1. Flush mounting

3-4 PCS-931S Line Differential Relay


Date: 2020-07-29
3 MOT Information

2. Semi-flush mounting

3. Rack mounting

⚫ Single 6U, 1/1 × 19''

PCS-931S Line Differential Relay 3-5


Date: 2020-07-29
3 MOT Information

⚫ Single 6U, 1/2 × 19''

⚫ Dual 6U, 1/2 × 19''

3-6 PCS-931S Line Differential Relay


Date: 2020-07-29
3 MOT Information

4. Wall mounting

5. Surface mounting

⚫ Front side protection class: IP52

PCS-931S Line Differential Relay 3-7


Date: 2020-07-29
3 MOT Information

3
⚫ Front side protection class: IP54

3.6.3 Front Side Protection Class

There are two kinds of protection classes for the front side of the device: IP52 and IP54. If the
protection class is selected as IP54, the manufacturer will provide the corresponding accessories.

3.6.4 Harsh Environment Conformal Coating

For some harsh operating conditions, such as petrochemical project (chemical plant, refinery),
underground project (metro, underground pipe gallery, coal mine), coastal areas (such as Hong
Kong, offshore wind power), high-humidity-hot areas (such as Southeast Asia, Africa), the device
is often in the windy, dusty or hot-and-humid environment, there are risks such as short circuit,
corrosion, module damage, etc., so the tri-proof treatment is often needed.

The option is used to select whether or not the conformal coating is needed. If "A: Required" is
selected, the conformal coating for the whole device will be done before delivery.

3-8 PCS-931S Line Differential Relay


Date: 2020-07-29
3 MOT Information

3.6.5 I/O Terminal

The option is used to select the I/O terminal type, including the binary input, binary output and
device power supply terminals. The device supports three types of I/O terminal:

⚫ "A: 0.8~4mm2 lead (26-pin connector, ring ferrule, IP10)": 0.8~4mm2 lead, 26-pin screw
terminal with ring ferrule and protection class IP10

⚫ "B: 0.8~4mm2 lead (26-pin connector, ring ferrule, IP20)": 0.8~4mm2 lead, 26-pin screw
terminal with ring ferrule and protection class IP20

⚫ "C: 0.8~2.5mm2 lead (36-pin connector, pin ferrule, IP20)": 0.8~2.5mm2 lead, 36-pin (two
18-pin) screw terminal with pin ferrule and protection class IP20 3
The appearance of the terminals are as below.

IP10 (0.8~4mm2) IP20 (0.8~4mm2)

IP20 (0.8~2.5mm 2)

3.7 Power Supply Plug-in Module (PWR Field)

The option is used to select the voltage level of the power supply for the device. The power supply
module support external power supply input of 110Vdc, 125Vdc, 220Vdc, 250Vdc or 100Vac,
110Vac, 115Vac, 120Vac, 127Vac, 220Vac, 230Vac, 240Vac, 250Vac, and provides 2 binary inputs
with independent negative supply, 7 binary inputs with common negative supply and 6 binary
outputs (5NO+1NC, NC contact is output contact of the device failure). The board type is different
based on different I/O terminal.

PCS-931S Line Differential Relay 3-9


Date: 2020-07-29
3 MOT Information

3.8 Plug-in Module Configuration (H Field)

The plug-in module configuration is used to select hardware resources, such as the number of
communication ports, the number of binary inputs and outputs, the number of AC analogs, and so
on. Different case size can support different hardware resources. Please refer to Section 3.6 for
details.

3.8.1 Communication Ports & Time Synchronization Mode

The option is used to select the number and type of communication ports and time synchronization

3 mode.

⚫ "A: 2 × 10Base-T/100Base-TX (RJ45) + 2 × RS-485 + RS-485 (IRIG-B or PPS)": 2 RJ45


Ethernet ports for Ethernet communication, 2 RS-485 serial ports for communicating with
SCADA system, 1 RS-485 serial port for clock synchronization (IRIG-B or PPS)

⚫ "B: 4 × 10Base-T/100Base-TX (RJ45) + 2 × RS-485 + RS-485 (IRIG-B or PPS)": 4 RJ45


Ethernet ports for Ethernet communication, 2 RS-485 serial ports for communicating with
SCADA system, 1 RS-485 serial port for clock synchronization (IRIG-B or PPS)

⚫ "C: 2 × 10Base-T/100Base-TX (RJ45) + 2 × 100Base-FX (LC-Connector) + 2 × RS-485 +


RS-485 (IRIG-B or PPS)": 2 RJ45 Ethernet ports for Ethernet communication, 2 optical fibre
ports for Ethernet communication (LC type), 2 RS-485 serial ports for communicating with
SCADA system, 1 RS-485 serial port for clock synchronization (IRIG-B or PPS)

⚫ "G: 4 × 100Base-FX (LC-Connector) + 2 × RS-485 + RS-485 (IRIG-B or PPS)": 4 optical


fibre ports for Ethernet communication (LC type), 2 RS-485 serial ports for communicating
with SCADA system, 1 RS-485 serial port for clock synchronization (IRIG-B or PPS)

3.8.2 Optical Fiber Protection Signalling Channel Interface

The option is used to select the number and type of optical fiber channel interface for protection
signal.

⚫ "X: Not required": Do not use optical fiber channel interface

⚫ "A: 1310nm, SM, FC-Connector, dual channels (up to 60km or via MUX)": 1310nm wave
length, single mode, FC type, dual channels, Max. transmission distance is 60km via direct
optical link or further distances via MUX

⚫ "B: 850nm, MM, ST-Connector, dual channels (up to 2km or via MUX)": 850nm wave
length, multi-mode, ST type, dual channels, Max. transmission distance is 2km via direct
optical link or further distances via MUX

⚫ "C: 1550nm, SM, FC-Connector, dual channels (up to 120km)": 1550nm wave length,
single mode, FC type, dual channels, Max. transmission distance is 120km via direct optical
link

⚫ "D: 1310nm, SM, FC-Connector, channel 1 (up to 60km or via MUX) + 850nm, MM,
ST-Connector, channel 2 (up to 2km or via MUX)": 1310nm wave length, single mode, FC

3-10 PCS-931S Line Differential Relay


Date: 2020-07-29
3 MOT Information

type, Max. transmission distance is 60km via direct optical link or further distances via MUX
(channel 1), and 850nm wave length, multi-mode, ST type, Max. transmission distance is 2km
via direct optical link or further distances via MUX (channel 2)

⚫ "E: 1550nm, SM, FC-Connector, channel 1 (up to 120km) + 850nm, MM, ST-Connector,
channel 2 (up to 2km or via MUX)": 1550nm wave length, single mode, FC type, Max.
transmission distance is 120km via direct optical link (channel 1), and 850nm wave length,
multi-mode, ST type, Max. transmission distance is 2km via direct optical link or further
distances via MUX (channel 2)

3.8.3 PRP/HSR

The option is used to determine whether or not PRP/HSR networking mode is supported. Only up 3
to 1 group of PRP or 1 group of HSR is available.

The module type in slot No.01 is determined by three options,


"Communication Ports & Time Synchronization Mode", "Optical Fiber
Protection Signalling Channel Interface", "PRP/HSR".

3.8.4 Slot02

The option is used to select the number of analog channels and digital channels based on different
sampling mode.

When "Sampling Mode" is chosen as "A: Conventional instrument transformer", four kinds of
analog channels are available.

⚫ "A: 4CT/4VT (1A/5A)": 4 AC current inputs and 4 AC voltage inputs, secondary rated current
is adaptive between 1A and 5A.

⚫ "B: 6CT/6VT (1A/5A)": 6 AC current inputs and 6 AC voltage inputs, secondary rated current
is adaptive between 1A and 5A.

⚫ "C: 7CT/5VT (1A/5A)": 7 AC current inputs and 5 AC voltage inputs, secondary rated current
is adaptive between 1A and 5A.

⚫ "D: 4CT/7VT (1A/5A)": 4 AC current inputs and 7 AC voltage inputs, secondary rated current
is adaptive between 1A and 5A.

When "Sampling Mode" is chosen as "B: Non-conventional instrument transformer", four


kinds of digital channels are available.

⚫ "X: Not Required"

⚫ "E: 12 × 100Base-FX (LC-Connector)": 12 100Mbit/s optical fibre interface (LC type)


receiving SV

⚫ "F: 8 × 100Base-FX (LC-Connector)": 8 100Mbit/s optical fibre interface (LC type) receiving
SV

PCS-931S Line Differential Relay 3-11


Date: 2020-07-29
3 MOT Information

⚫ "G: 4 × 100Base-FX (LC-Connector)": 4 100Mbit/s optical fibre interface (LC type) receiving
SV

3.8.5 Slot03

Currently, the option is used as reserved bit and it is chosen as "Not required" fixedly.

3.8.6 Slot04

When "Case Size" is chosen as "B: 6U 1/2 19", the option is used to select the extended I/O
module located in slot No.4.

⚫ "X: Not required": the extended I/O module located in slot No.4 is not required.
3
⚫ "A: 25 BI (Common negative supply)": 25 binary inputs share the common negative input of
power supply, and the rated voltage of binary input can be 24Vdc~250Vdc, 110Vac or 220Vac,
which can be set through the settings.

⚫ "B: 13 BO (Normal, NO)":13 normal binary outputs, normally open contact (NO).

⚫ "C: 4 BO (Heavy-capacity, NO) + 4 BO (Normal, NO)": 4 large-capacitor binary outputs (its


breaking capacity is 10A), normally open contact, and 4 normal binary outputs, normally open
contact.

⚫ "D: 13 BO (Normal, 11 NO + 2 NC)":13 normal binary outputs, the first 11 BOs are normally
open contact and the last 2 BOs are normally closed contact.

⚫ "E: 32 BI (2 groups, each group share 1 common negative supply)": 32 binary inputs with
two 18-pin connectors, BI01~BI16 share one common negative input of power supply and
BI17~BI32 share another common negative input of power supply.

⚫ "F: 17 BO (Normal, 15 NO + 2 NC/NO)": 17 normal binary outputs, the first 15 BOs are
normally open contact. The last 2 BOs are normally closed/open contacts, and each BO has 3
terminals, and the normally open contact and normally closed contact share one common
terminal.

⚫ "G: 4 BO (Heavy-capacity, NO) + 4 BO (Normal, NO)": 4 large-capacitor binary outputs (its


breaking capacity is 10A), normally open contact, and 4 normal binary outputs, normally open
contact.

For "Slot04"~"Slot14", there are different I/O modules chosen based on


different I/O terminal.

When "I/O Terminal" is chosen as "A: 0.8~4mm2 lead (26-pin connector,


IP10)" or "B: 0.8~4mm2 lead (26-pin connector, IP20)", these items, "X:
Not required", "A: 25 BI (Common negative supply)", "B: 13 BO
(Normal, NO)", "C: 4 BO (Heavy-capacity, NO) + 4 BO (Normal, NO)"
and "D: 13 BO (Normal, 11 NO + 2 NC)", are activated.

3-12 PCS-931S Line Differential Relay


Date: 2020-07-29
3 MOT Information

When "I/O Terminal" is chosen as "C: 0.8~2.5mm2 lead (36-pin


connector, IP20)", these items, "X: Not required", "E: 32 BI (2 groups,
each group share 1 common negative supply)", "F: 17 BO (Normal, 15
NO + 2 NC/NO)" and "G: 4 BO (Heavy-capacity, NO) + 4 BO (Normal,
NO)", are activated.

When "Case Size" is chosen as "C: 6U 1/1 19", the option is used to select TWFL module located
in slot No.4.

⚫ "X: Not required": the TWFL module located in slot No.4 is not required.

⚫ "T: Travelling wave fault location (Communication channel bandwidth should be


2Mbit/s)": travelling-wave fault location, which must adopt the channel bandwidth with the 3
communication rate of 2Mbit/s.

3.8.7 Slot05~Slot14

They are used to select the extended I/O module located in slot No.5~slot No.14. Please refer to
Slot04.

3.9 MOT Version

It indicates the version of MOT. For different versions, the corresponding options may be different.

PCS-931S Line Differential Relay 3-13


Date: 2020-07-29
3 MOT Information

3-14 PCS-931S Line Differential Relay


Date: 2020-07-29
3 MOT Information

PCS-931S Line Differential Relay 1