Annual Avg kw/tr kw/tr 1.

4
RAK Plant Capacity T 375 Capacity 375
Design Power kw 525 Design Power 525
Total Hours 8760 Total Hours 8760
Annual power profile considered drift % 0.95
Power Bin % Time kwh
5 1.00 2,300
10 1.00 4,599 Load Profile
15 2.00 13,797 25
20 20.00 183,960
20
25 22.00 252,945
30 15.00 206,955 15

% Time
35 10.00 160,965 10
40 12.00 220,752
5
45 8.00 165,564
50 4.00 91,980 0
5 10 15 20 25 30 35 40 45
55 2.00 50,589
60 3.00 82,782 % Load
65 0.00 -
70 0.00 -
Total KWH 1,437,188 hrs tr $/kwh Savings
8760 375 0.120
kw/tr 1.4 1.33
Power cost/ kwh USD 0.120 kwh 172,463 392,486 - 220,024
annual consump USD 172,463
15% savings USD 25,869
Chiller Savings AED 94,423 60

Invest 73,000
Payback 0.7731 0.07 kw/tr
kwh

kw/tr
kwh
5% 26.25
10% 52.5
15% 78.75
20% 105
Load Profile 25% 131.25
30% 157.5
35% 183.75
40% 210
45% 236.25
50% 262.5
55% 288.75
60% 315
20 25 30 35 40 45 50 55 60 65 70 65% 341.25
70% 367.5
% Load 75% 393.75
80% 420
85% 446.25
90% 472.5
95% 498.75
100% 525

hrs tr $/kwh Savings


3840 1400 0.077
1.4 1.33
181104 172048.8 9055.2

hrs tr $/kwh Savings


8000 1400 0.077
1.4 1.33
377300 358435 18865

22000 5060
kw/tr 1.33
Micro synergy Daikin Chillers capcity tr 1400
Design Power kw 1862 Design Power 1862
Total Hours 8760 Total Hours 8760
Annual power profile considered
Power Bin % Time kwh
5 1.00 8,156
10 1.00 16,311 Load Profile
15 2.00 48,933
25
20 20.00 652,445
25 22.00 897,112 20
30 15.00 734,000 15

% Time
35 10.00 570,889
10
40 12.00 782,934
45 8.00 587,200 5

50 4.00 326,222 0
5 10 15 20 25 30 35 40 45 50 55 60 65
55 2.00 179,422
60 3.00 293,600 % Load
65 0.00 -
70 0.00 -
Total KWH 5,097,225

Power cost/ kwh Dinars


Power cost/ kwh USD 0.077
annual consump USD 392,486
10% savings USD 39,249
Chiller Savings AED 143,258

Invest 55,000
Payback #REF!
5% 93.1
10% 186.2
15% 279.3
20% 372.4
d Profile 25% 465.5
30% 558.6
35% 651.7
40% 744.8
45% 837.9
50% 931
55% 1024.1
60% 1117.2
65% 1210.3
0 35 40 45 50 55 60 65 70
70% 1303.4
Load 75% 1396.5
80% 1489.6
85% 1582.7
90% 1675.8
95% 1768.9
100% 1862
Simple payback calculation for IPC Integrated plant controller

Annual Avg kw/tr 1.4


RAK Plant Capacity Tr 375
Design Power kw 525
Total Hours 8760
Annual Load profile
Power Bin % Time kwh
5 1.00 2,300
10 1.00 4,599
15 2.00 13,797
20 20.00 183,960
25 22.00 252,945
30 15.00 206,955
35 10.00 160,965
40 12.00 220,752
45 8.00 165,564
50 4.00 91,980
55 2.00 50,589
60 3.00 82,782
65 0.00 -
70 0.00 -
Total KWH 1,437,188

Power cost/ kwh USD 0.120


annual consump USD 172,463
15% savings USD 25,869
Chiller Savings AED 94,423
Invest AED 73,000
Payback Yrs 0.7731