Technician Settings Operating Manual

1. Set-point temperature limits, Temperature scale, offset for temperature 2. Turning the thermostat ON or OFF
reading, Heater type, Heat pump configuration, and Compressor delay. - Press the [On] button to turn the thermostat ON or OFF – “ON” or "OFF" will
- Adjust the temperature to 10oC (50oF). appear on display.
- Press and hold the [Select] button until “COOL” appears on display and the 3. Selecting Modes and Auto Fan
temperature flashes. - Press the [Select] button – the mode will flash.
- Using the [+] or [-] buttons adjust the temperature limit for COOL - Using the [+] and [-] buttons select between COOL, HEAT, AUTO CHANGE
(range 10..30oC (50..88oF), default 10oC (50oF)). OVER (Cool & Heat appear on display) or FAN ONLY MODE.
- Press the [Select] button again - “HEAT” will appear on display. - Press the [Select] button again – “Auto Fan” or “Fan” will flash.
- Using the [+] or [-] buttons adjust the temp. limit for HEAT - Using the [+] and [-] buttons select with or without Auto Fan.
(range 10..30oC (50..88oF), default 30oC (88oF)). With Auto Fan - the fan will work only during demand for cool or heat. In Oil/Gas
- Press the [Select] button again – “C” or “F” will appear on display. systems, the fan will never work).
- Using the [+] or [-] buttons select between: Without Auto Fan - the fan will work continuously.
Celsius – “C” flashing. - Press the [Select] button again to return to normal display.
Fahrenheit – “F” flashing. 4. Economy mode
- Press the [Select] button again – the offset temperature will appear on display - Press and hold the [On] button (5 seconds) to activate economy mode – “EC”
(the offset is used for calibration of the measured temperature when needed). will appear on display.
- Using the [+] or [-] buttons adjust offset (range -6…+6oC/F, default 0oC/F). - Press and hold the [On] button again to return to normal display.
- Press the [Select] button again – “HP” or “HC” will appear on display. Note: In economy mode, the set-point temperature for cooling = 29oC (85oF) and
- Using the [+] or [-] buttons select between: the set-point temperature for heating = 13oC (55oF).
Heat pump configuration – “HP” flashing. 5. Emergency heat
Heat/Cool configuration – “HC” flashing. - Make sure the set-point temperature is different than 10oC (50oF).
- Press the [Select] button again – “EO” will appear on display. - Press and hold the [Select] button to activate emergency heat - "EH" will
- Using the [+] or [-] buttons select between: appear on display.
Electric heater – “E” flashing. - Press and hold the [Select] button again to deactivate emergency heat – “EH” 24Vac 0 C
(In this configuration, when Auto Fan is active, the fan will work only will appear on display. input ~ RC
during demand) When the Emergency Heat is active, the compressor will stop and only the heat
Oil/Gas heater – “O” flashing. element will be used for heating. The display will alternate between “EH” and the RH
(In this configuration, when Auto Fan is selected, the fan will never work) temperature.
Fan G
The following selection in enabled only when Heat Pump system has been
6. Low temperature alarm indication
selected previously:
When the measured temperature is less than 6oC (45oF) “AL” will flash on
Heat Element 2 W2
- Press the [Select] button again – “HC” will appear on display.
display. H. Element 1 / Heat Pump W1
- Using the [+] or [-] buttons select between:
The indication will automatically disappear when the measured temperature is
Heat pump active in heat (B) – “H” flashing.
higher than 8oC (48oF).
Compressor 2 Y2
Heat pump active in cool (O) – “C” flashing.
Compressor 1 Y1
- Press the [Select] button again – “30” will appear on display.
- Using the [+] or [-] buttons select between:
With 3 minutes compressor delay – “3” flashing.
Without compressor delay – “0” flashing (For testing purposes only !).
- Press the [Select] button again – the thermostat display will return to normal.
Rear View of thermostat

Print name: FMT24; OUT-FMT24 Drawn: P.Rechtman


meitav-tec Title:
FMT24-SUPER Software: FTSUPN03 Checked: S.Lukin
Tel: +972-3-9626462
Fax: +972-3-9626620 Checksum: 9249 Approved: E.Roy
Date: 16 Mar 2008
e-mail: support@meitavtec.com 1 Original 16 Mar 2008 File name: FMT24-SUPER.VSD