7.1: Three (30 + j30) Ω identical impedances are connected in Delta and supplied by a 173V 3-phase
system through three lines each having impedance of (0.8 + j0.6) Ω. Find:
1) the current magnitude in each of the delta-connected impedances, and
2) the voltage cross each of Delta impedance.
7.2: A 415V, 50 HZ, 4-wire three-phase balanced power supply with sequence RYB is connected to the
following loads:
A single resistance of 12 between R phase and neutral;
An inductive impedance of (2 + j8) between B phase and neutral;
A capacitor of 120F between R and Y phase;
A three-phase, delta connected induction motor operating at 10kW and 0.75 p.f. lagging.
Calculate:
1) the magnitude and phase angle of the current in the four lines of the supply, and
2) the total power from the supply.
7.3: The figure below shows the per-phase per-unit network of a 4-bus power system. Develop
Thevenin equivalent circuits as viewed
1) from bus 4 and ground, and
2) from bus 2 and ground.
j 0.10
8.1: The phase voltages at a bus of an unbalanced power system are V 100 , V 1 900 , V 21350
a b c
. Find the sequence voltages of three unbalanced voltages and prove that: V V 0 V1 V 2 .
a a a a
8.2: The component parameters of the following system are given in Table. The power rating for each
apparatus is 200MVA. Sketch the sequence networks and find the Thevenin equivalent reactance of
each sequence network seen from bus 4. Assume that pre-fault voltage at bus 4 is 100 pu. (Exercise:
the same question for Bus 5)
j 0.03pu
8.3: Part of a power system is shown in the figure. Vf= 100 pu . XN=5%. For a bolted double line-to-
ground fault occurs on phase b and c at bus 1, the three-phase currents out of G 1:
I a 0.4008900 pu , I b 6.1817152.86 pu , I c 6.181727.140 pu
0
Currents Ifb and Ifc from bus 1 to ground: I 7.8104157.250 pu and I 7.810422.750 pu .
fb fc
a) Calculate per-unit sequence currents of phase a
flowing from delta side of transformer T1 to
bus 1.
jX N
b) Calculate per-unit three-phase currents flowing
from bus 2 to Y side of T 1. 100MVA
13.8kV
X 1 0.15 pu 100MVA
13.8kV /138kV Y
X 2 0.17 pu X 0.10 pu
X 0 0.05 pu
Tutorial 9: Fault Analysis
9.1: The one-line diagram for a power system is given in the following figure. The parameters of
the generators and transformers are given as:
G1 and G2: 100MVA, 20kV, X 1 X 2 20%, X 0 6% and X N =5%
Transformers T1 and T2: 100MVA, 20 / 345Y kV and X=10%
Line (on bases 100MVA, 345kV): X 1 X 2 10%, X 0 25%
A bolted single line-to-ground fault occurs on phase a at bus 2. Vf=100 pu.
Transmission Line
jX N
9.2: A bolted double line-to-ground fault between phase b and c occurs at bus 2 in the power
system shown in question 9.1.
a) Calculate per unit sequence currents at the fault point.
b) Calculate the per unit phase voltages at bus 3.
9.3 (Homework) A double line fault between phase b and c with the fault impedance Xf=0.1pu
occurs at bus 1 in the power system shown in question 9.1.
a) Calculate the per unit sequence currents through transmission line.
b) Calculate the per unit sequence voltages at bus 3.
3
Tutorial 10: Overcurrent Protection
10.1: A 50-Hz radial distribution system and the data are shown in the figure. The maximum and minimum fault
levels at bus A are 200 MVA and 150 MVA, respectively. The maximum and minimum loads for each of the three
load points are 5 MVA and 3MVA, respectively. The power factors of the loads are the same. The CO-8 relays are
selected to protect load and lines. The coordination time interval (CTI) for two adjacent relays is 0.3s. Ignore
transmission losses when calculate the maximum load current. Ignore the operating time of the breakers.
1) Select the CT ratio for the related relay at each bus.
2) Select current plug settings (PSs) for all the relays.
3) Select time dial settings (TDSs) for the phase relays R2 at bus B and R3 at bus C.
4) Calculate the operating time of R2 and R3 if a three phase to ground fault occurs at 10 miles to Bus C on line3
for the minimum system capacity.
A
CB1 CB2 CB3 CB4
10 miles 20 miles 30 miles
10.2: A 3.5 MVA rated load is supplied from 33 kV system bus through a 40MVA and 33Δ/11Y kV transformer
with a leakage reactance of 15%. The fault level at 33 kV is 2000MVA. The relays R1 and R2 are IDMT relays with
5A rating. The time-current curve of the relay is represented by 0.14 . The TDSs are from 0.1 to 1 in
t 0.02 TDS
M 1
the step of 0.1. The plug settings are from 50% to 200% of the relay rating in the step of 25%. The CT ratios for
CT1 and CT2 are 400:5 and 300:5 respectively.
a. Determine the PSs and the TDSs of the phase relays if the required discrimination time or CTI between R2 and
R1 is 0.4s.
b. Find the fault location and the minimum operating time of R2 based on the relay settings from part a.
CT2 T
CT1
3.5MVA
CB2 CB1
11 kV
R2
4
Tutorial 11: Differential Protection
Δ
CT CT System:
B
G 230kV
F1 F2 100MVA
33kV 33/230kV XS1= XS2=5%
150MVA 150MVA XS0=10%
XG1= XT1= XT2=
XG2=30% XT0=15%
XG0=40%