Wiring diagram code

TPA

This data applies to:


Multi-turn actuators SA 07.2 – SA 16.2; SAR 07.2 – SAR 16.2
SAEx 07.2 – SAEx 16.2; SAREx 07.2 – SAREx 16.2
SA 25.1 – SA 48.1; SAR 25.1 – SAR 30.1
SAEx 25.1 – SAEx 40.1; SAREx 25.1 – SAREx 30.1
Part-turn actuators SQ 05.2 – SQ 14.2; SQR 05.2 – SQR 14.2
SQEx 05.2 – SQEx 14.2; SQREx 05.2 – SQREx 14.2
SG 05.1 – SG 12.1; SGR 05.1 – SGR 12.1
SGExC 05.1 – SGExC 12.1

Extract of wiring diagram code


Posi- 1 2 3 4 5 6 7 8 9 10 11 12 13 14
tion
Position TPA 0 0 R 1 A A - 1 0 1 - 0 0 0
00 AUMA 3-ph AC motor

1+2 01 AUMA 1-ph AC motor for SA .2/SQ .2

16 1-ph AC motor for SG .1

R Clockwise closing
3
L Counterclockwise closing

1 1 thermoswitch 140 ° C (NC)


4
2 1 Kaltleiter

0 Without torque switches (MWG)

5 A 2 single switches (standard)

B 2 tandem switches

0 Without limit/intermediate switches (MWG)

6 A 2 single switches (standard) for end positions

B 2 tandem switches for end positions

7 - Reserve

0 Without signalling

1 With blinker transmitter


8 With blinker transmitter and manual operation
2
switch
Without blinker transmitter and manual
3
operation switch
0 Without position transmitter

A Precision potentiometer
1)
9 C Electronic position transmitter 2-wire system (EWG/RWG)

E1) Electronic position transmitter 3-wire or 4-wire system (EWG/RWG)

I2) Absolute encode for limit and torque sensing (MWG)

0 Without heater
10 110 V – 250 V (without controls)
1
24 V (with controls)
11 - Reserve

12 – 14 000 Without special units

Notes on table
1) C, E When combined with SAEx 25.1 – SAEx 40.1; SAREx 25.1 – SAREx 30.1, valid for 2-wire RWG 5020 (Ex i) only
2) I Only possible for SAEx 25.1 – SAEx 40.1/SAREx 25.1 – SAREx 30.1 in FM (US) version
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.