Advanced Cooling Systems Design

Report

HVAC system design project for refrigeration and air


conditioning building workshops
Building No. (18) Ground Floor

Supervision / Engineer Turki Al-Maliki

Trainees names:
‫أحمد منير العتيبي‬
‫أحمد اليامي‬
‫أحمد الشراري‬
‫فيصل جالل‬
‫ممدوح موسى‬
‫ريان الثقفي‬
‫حسن سالمي‬
‫وليد الكعبي‬
Project requirements
1- Calculation of heat loads.
2- Selection of the air conditioning system.
3- Design of the air distribution system.

Additional project details

Lighting:
15 W/ 𝑚2 Reassessed Vented - From ASHRAE Standard 90.1 For Workshop

Students:
20 Students per workshop. In Corridor 2 Students / 𝑚2 .
Windows:
Window with Double Glass Panels.
CALCULATION OF HEAT LOADS

Location
Weather

Schedule
Walls
Windows

Doors
Space

Systems
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5 (Corridor)
Selection of The Air Conditioning System

Equipment Type: Packaged Unit


System Type: Constant Air Volume (CAV) Single Zone

Zone 1and 3
Zone 2,4, and 5 (Corridor)
Design of the air distribution system

Zone 1

Flow rate Velocity Diameter


Dimensions No. Diffuser
𝐿 ⁄𝑠 𝑚 ⁄𝑠 𝑚𝑚
766 550 x 300 4.65 - -
640 475 x 300 4.49 - -
600 450 x 300 4.44 - -
450 375 x 300 4.0 - -
300 275 x 300 3.6 - -
150 225 x 225 2.96 - -
126 200 x 225 3.2 225 1
75 175 x 175 2.4 190 8
20 100 x 110 1.8 125 2

Total Pressure Loss: 128.1 Pa


Zone 2

Flow rate Velocity Diameter


Dimensions No. Diffuser
𝐿 ⁄𝑠 𝑚 ⁄𝑠 𝑚𝑚
937 650 x 300 4.8 - -
791 600 x 300 4.4 - -
645 500 x 300 4.3 - -
499 400 x 300 4.16 - -
353 300 x 300 3.9 - -
207 250 x 250 3.3 - -
119 200 x 200 3.0 - -
88 175 x 200 2.5 -
73 175 x 175 2.4 190 10
44 140 x 140 2.2 125 4
31 125 x 125 2.0 125 1

Total Pressure Loss: 277.8 Pa


Zone 3

Flow rate Velocity Diameter


Dimensions No. Diffuser
𝐿 ⁄𝑠 𝑚 ⁄𝑠 𝑚𝑚
797 600 x 300 4.43 - -
704 550 x 300 4.3 - -
664 500 x 300 4.4 - -
498 450 x 300 4.2 - -
332 300 x 300 3.7 - -
166 225 x 250 3.0
93 175 x 200 3.0 200 1
83 175 x 175 2.7 200 8
20 100 x 110 1.8 125 2

Total Pressure Loss: 107.3 Pa


Zone 4

Flow rate Velocity Diameter


Dimensions No. Diffuser
𝐿 ⁄𝑠 𝑚 ⁄𝑠 𝑚𝑚
1007 700 x 300 4.8 - -
907 650 x 300 4.65 - -
807 600 x 300 4.48 - -
663 500 x 300 4.42 - -
519 400 x 300 4.33 - -
375 325 x 300 4.85 - -
231 250 x 275 3.4 - -
200 250 x 250 3.2 - -
100 175 x 200 2.9 - -
72 175 x 175 2.7 190 8
50 140 x 150 2.4 160 8
31 125 x 125 2.0 125 1

Total Pressure Loss: 260.4 Pa


Zone 5 (Corridor)

Flow rate Velocity Diameter


Dimensions No. Diffuser
𝐿 ⁄𝑠 𝑚 ⁄𝑠 𝑚𝑚
672 500 x 300 4.48 - -
588 450 x 300 4.36 - -
504 400 x 300 4.2 - -
420 350 x 300 4.0 - -
336 300 x 300 3.73 - -
252 275 x 275 3.33 - -
168 225 x 250 3.0 - -
84 175 x 175 2.74 200 -

Total Pressure Loss: 130.6 Pa