Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

Centum Science Park, 79, Centum jungang-ro, Haeundae-gu, Busan 48058, Korea

Changing Solenoid
Tel : +82 52 204 7878 Valve
/ FAX: +82Type for
52 204 7801 TRO
/ Web Sampling Line E-MAIL : service@hyundai-gs.com
: http://www.hyundai-gs.com/

Service Letter

Date : July 11, 2019


Ref. No.: HGS-EES3-SL-19-0001
Subject : Hyundai ACB Retrofit
Type : HiAN ACB

Dear Our Valued Clients,

We appreciate your unwavering support and cooperation rendered to our Hyundai Electric
businesses.

As you may be aware, the production for HiAN ACB has been discontinued since 2013.
In this regard, HiAN ACB needs to be replaced with UAN or HGN retrofit typed ACB in case
partial repair is not available any longer.
The retrofit ACB is including the relevant cradle which means any modification for BUSBAR is
not required.
When placing order the mentioned retrofit ACB, following information is required.

A. Photo for ACB name plate to confirm serial no.


B. OCR setting parameter or OCR front photo

Contact points ;
For Genuine Hyundai ACB : sales@hyundai-gs.com
For Service engineers for replacing ACB(s): service@hyundai-gs.com

We hope our guidance will be of service to you.

Faithfully yours,

GY,Oh, General Manager

Machinery Service Department


EnClosure : HiAN-UAN Cradle Retrofit Manual http://www.hyundai-gs.com/
U-Series ACB

HiAN Cradle Retrofit


Installation Manual
! 주 의
■ 제품을 설치하기 전 주의사항을 반드시 읽고 설명에 따라 설치하여 주십시오.
■ 차단기의 설치 및 보수는 유자격자(전기공사자)가 행하여 주십시오. 잘못된
xd설치로 인한 오동작 또는 사고가 발생할 위험이 있습니다.

! CAUTION
■ Before installation, be sure to read the manual carefully to ensure proper
aaoperation.
■ Installation, maintenance and inspection of the circuit breaker should be
aaperformed by persons who are qualified for electric work.

! CUIDADO
■ Antes da instalação, certifique-se de ler atentamente o manual e entender os
procedimentos para o funcionamento adequado
■ A instalação, manutenção e inspeção do disjuntor deve ser realizada por
pessoas qualificadas para o trabalho elétrico.

! PRECAUCION
■ Antes de la instalación , asegúrese de leer el manual cuidadosamente y
00comprenda los procedimientos para la apropiada operación
■ La Instalación, mantenimiento e inspección del interruptor automático 00debe
ser realizada por personas cualificadas para el trabajo eléctrico.

! ПРЕДУПРЕЖДЕНИЕ
■ Перед установкой, внимательно прочтите инструкцию по
00эксплуатации и ознакомьтесь с порядком выполнения 00необходимых
условий и процедур для корректной работы 00оборудования.
■ Установка, ремонт и осмотр автоматического выключателя
00должен выполняться квалифицированным специалистом по
00электрооборудованию.

NAME installation manual


▶ Installation
SUMMRY
- High function and breaking performance of UAN ACB is applied with existing installd ACB Cradle
by adapting distance of between phase, pole, ground and size of terminals.

- Quality and function is stable by application with high function and breaking performance of UAN ACB.

- When replacement is required, it is possible that compatibility with appliance of standard ACB body.

Notice before installation

1. Appearance comparison of HiAN ACB and UAN RETROFIT ACB

Note.
1) Mounting hole of bottom
In case of HiAN 40, before installation of retrofit cradle,
you have to drill the new mounting hole structurally.
Before fastening the terminals, mark the applicable positions and then do post-process.

RETROFIT CRADLE installation manual


2. Notice of wiring work
1) Before the replacement, please check the length of wire
and prepare for beforehand work of wiring and then do the wiring work.
In case of HiAN type, there are two wiring types.

3. Door treatment for the front view projection


1) Once installed with retrofit ACB type, it was positioned with inside of the origin panel.
It has some problem regarding IP specification, should be assemble the special
Dust cover for retrofit ACB.
2) If you want to assemble projection type, contact to our service center.

FIG ?

RETROFIT CRADLE installation manual


Installation Procedure

1. Remove existing ACB

1) The existing ACB should be drawn out at first.


2) The cradle installation bolts should be released on the switchboard panel.
3) Remove installation bolts of Cradle main busway terminal and busbar.
4) Remove control jock unit positioned top of cradle and auxiliary S/W unit.

RETROFIT CRADLE installation manual


2. RETROFIT ACB installation

1) UAN Retrofit Cradle Should be matched with origin ACB Cradle


that both origin terminal mounting hole and bottom mounting hole.
In case of HiAN 4000A, bottom mounting hole does not matched with retrofit cradle.
After matching origin terminal mounting hole, mark the position
of bottom mounting hole and then drill the hole.
2) If the both hole was matched properly, tighten those installation bolts

RETROFIT CRADLE installation manual


3. Control circuit connection

1) Should be connected properly the circuit number HiAN ACB to UAN ACB like below table
2) Depanding on Switchgear wiring method, the control cable length should be check
in advance.

RETROFIT CRADLE installation manual


ACB Control terminal connection
(HiAN>UAN)
Terminal No. of HiAN ACB UAN ACB No.
1 1 No. 1 of U-ACB
Charging Motor
2 2 No. 2 of UAN ACB
3 3 No. 3 of U-ACB
Closing Coil
4 4 No. 4 of UAN ACB
7 7 No. 7 of UAN ACB
Shunt coil
8 8 No. 8 of UAN ACB

In case Inst type : No. 9 of U-ACB


9
in case Delay type
UVT COIL in put
* Inst Type : 9 : Common No. 11 & No.13 of HiAN ACB
( = UVT controller out put)
* Delay Type ⇒ No. 1(U1) of UVT Time delay module for U-ACB
10
: U1 ⇒ C1 ⇒ 9 ⇒ No. 17(C1) of UVT Time delay module
(No. 1 of UVT CONT.) ⇒ No. 9 of U-ACB
Control
** UVT Control power OPEN S/W
Source 11
: 11(T1) of UVT Time delay module for U-ACB
UVT control source 1st in-put
In case Inst type : No. 10 of U-ACB
12
in case Delay type
* Inst Type : 10 : Common No. 12 & No.14 of HiAN ACB
* Delay Type ⇒ No. 3(U2) of UVT Time delay module for U-ACB
13
: U2 ⇒ C2 ⇒ 10 ⇒ No. 19(C2) of UVT Time delay module
UVT controller 1st in-put (No. 3 of UVT CONT.) ⇒ No. 10 of U-ACB
** UVT Control power OPEN S/W
14
: 13(T2) of UVT Time delay module for U-ACB

15 15 No. 15 of U-ACB
Charging Complete contact
16 16 No. 16 of U-ACB
19 Add the control power sorce at No. 19 of U-ACB
OCR In-put Source Power
OCR 20 Add the control power sorce at No. 20 of U-ACB
APR-1L-GL Alarm contact common 22 No. 22 of U-ACB
LTD / STD / Inst / GFT Contact 23 Common No. 21 / 24 / 26 of U-ACB
19 19 No. 19 of U-ACB
OCR In-put Source Power
20 20 No. 20 of U-ACB
22 22 No. 22 of U-ACB
OCR Trip pre alarm contact
24 23 No. 23 of U-ACB
APR-1L-GS
25 22 No. 22 of U-ACB
APR-2L-GS LTD / STD / Inst Contact
26 21 & 24 Common No. 21 & 24 of U-ACB
27 22 No. 22 of U-ACB
GFT Contact
28 26 No. 26 of U-ACB
19 19 No. 19 of U-ACB
OCR In-put Source Power
20 20 No. 20 of U-ACB
OCR
Alarm contact common 22 22 No. 22 of U-ACB
APR-1S-AS
Trip pre alarm contact 24 23 No. 23 of U-ACB
APR-2S-AS
LTD Contact 25 21 No. 21 of U-ACB
STD / Inst Contact 26 24 No. 24 of U-ACB
31 51 No. 51 of U-ACB
AUX S/W "b" contact b1
32 52 No. 52 of U-ACB
33 41 No. 41 of U-ACB
AUX S/W "a" contact a1
34 42 No. 42 of U-ACB
35 43 No. 43 of U-ACB
AUX S/W "a" contact a2
36 44 No. 44 of U-ACB
37 53 No. 53 of U-ACB
AUX S/W "b" contact b2
38 54 No. 54 of U-ACB
AUX S/W
39 45 No. 45 of U-ACB
AUX S/W "a" contact a3
40 46 No. 46 of U-ACB
41 55 No. 55 of U-ACB
AUX S/W "b" contact b3
42 56 No. 56 of U-ACB
43 47 No. 47 of U-ACB
AUX S/W "a" contact a4
44 48 No. 48 of U-ACB
45 57 No. 57 of U-ACB
AUX S/W "b" contact b4
46 58 No. 58 of U-ACB

RETROFIT CRADLE installation manual


* UVT CIRCUIT CONNECTION

RETROFIT CRADLE installation manual


4. TEST

1) Based on their origin circuit diagram, it should be verified with OCR function at first
and then be connected to power system
2) For test, Refer to UAN ACB installation Manual

5. ACB Door handling in Switchgear

1) When the installation was completed, the Dust Cover for it's own Retrofit
can be assembled like below

RETROFIT CRADLE installation manual

You might also like