Observation/symptoms:
Genset shuts down on high winding temperature (L 3)
Work carried out:
1. Troubleshooting associated fault codes.
2. Updating AUX 101(3), (4) and (5) boards.
3. Testing and re-termination of L3 RTD at alternator terminal connector.
4. Using Sepam to clear Active shutdown alarm on HV breaker unit.
Cummins Conclusion:
1. Genset was started with all parameters ok and later closed to bus with a shared load of 1025KW and
Windings indicated temperatures within limit as indicated above.