CUMMINS WEST AFRICA LIMITED

* Service Intervention Report*


Customer: ALEF RECYCLING AGBARA Date of Failure CESN (Job No):

Equipment Model: Customers Reported Problem


QSK 60 G
Genset Serial No: I19D004173

ESN: 33219877 Troubleshooting of GG1 L3 high temperature fault

Running Hours: 5445.3Hours

DIS/Comm. Date: 06/07/2023

Observation/symptoms:
Genset shuts down on high winding temperature (L 3)
Work carried out:
1. Troubleshooting associated fault codes.
2. Updating AUX 101(3), (4) and (5) boards.
3. Testing and re-termination of L3 RTD at alternator terminal connector.
4. Using Sepam to clear Active shutdown alarm on HV breaker unit.

Cummins Conclusion:
1. Genset was started with all parameters ok and later closed to bus with a shared load of 1025KW and
Windings indicated temperatures within limit as indicated above.

Arrival time on site: Departure time from site: Job start time: Job stop time:

Signed on behalf of CESN: Position: Date:


Ogheneochuko Udjor Service Engineer 06-07-2023

Counter signature Position: Date:


VILAS VIJAYAN Industrial Engineer power plant 06/07/2023

Note: This report requires one counter signature from the following group: - Field Service Manager,
Contract Manager, Technical Support Manager, Warranty Administrator, Head of Aftermarket (s)