Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

TRANSMISSION COMPANY OF NIGERIA (TCN).

Technical Specifications – Instrument Transformers

Page VII.VII-1

1 TECHNICAL DATA SCHEDULES


1.1 CAPACITOR VOLTAGE TRANSFORMER 330 kV

TECHNICAL DATA SCHEDULE


CAPACITOR VOLTAGE TRANSFORMER 330 kV
CODE NO: 4132

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 Manufacturer
1.1 Type - -
1.2 Model no - -
1.3 Country of Origin - -
Equipment that
are compliant
with KEMA,
KERRI or CESSI
Certifications
Only.
(Attach
Certificates and
Type Tests
report from STL
Members only)

2.0 Nominal characteristics


2.1 Voltage
2.1.1 Rated voltage kV 330
2.1.2 Rated voltage class KV 362
2.2 Rated frequency Hz 50
2.3 Network neutral grounding - Effective
2.4 Rated voltage factor for 30 s - 1,5
2.5 Rated lightning impulse withstand kV 1175
2.6 Chopped lighting impulse withstand (3 s) kV 1290
2.7 Switching impulse withstand (wet) kV 950
2.8 Power frequency withstand voltage (1 min) kV 450
2.9 Creepage distance mm/kV 31
2.10 Max. radio interference voltage at 0,5 MHz V 2500

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-2

TECHNICAL DATA SCHEDULE


CAPACITOR VOLTAGE TRANSFORMER 330 kV
CODE NO: 4132

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED


per IEC 694
2.11 Capacitance C1 and C2 pf 4400
2.12 Series reactor
- inductance range mH 0.2
- resistance range ohms -
2.13 Transformation ratio - 330kV/3
: 0,11kV/3
: 0,11kV/3
(: 0,11kV/3)

2.14 Transformer characteristics


- HV/LV turn ratio range - -
- Normal operating flux density tesla -
2.15 Primary voltage kV 330/3
2.16 Secondary voltage V 110/3
2.17 Winding accuracy:

- metering class - 0,2


- protection class - 3P

- burden ( on each winding) VA 50

2.18 Number of secondary winding - 2 (3)


2.19 Winding conductor - Cu

2.20 Circuit Diagram - To be enclosed


with bid
2.21 HV Terminal connector for - TBA

3.0 Weights and Dimensions


3.1 Weight for operation kg -
3.2 Weight for transport kg -
3.3 Height m -

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-3

TECHNICAL DATA SCHEDULE


CAPACITOR VOLTAGE TRANSFORMER 330 kV
CODE NO: 4132

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

3.4 Shipping dimensions (H x W x D) m -


3.5 Outline drawing number - To be enclosed
with bid
4.0 Type tests reports N - To be enclosed
with bid
5.0 Standards - IEC 60044-5
IEC 60694
IEC 60947-1
6.0 Quality control - ISO -----------

7.0 Installation - Outdoor,


Substation
Switchyard
8.0 Installation - Outdoor in
substation
switchyard

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-4

1.2 CAPACITOR VOLTAGE TRANSFORMER 132KV

TECHNICAL DATA SCHEDULE


CAPACITOR VOLTAGE TRANSFORMER 132 kV
CODE NO: 4133

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 Manufacturer -
Equipment that
are compliant
with KEMA,
KERRI or CESSI
Certifications
Only.
(Attach
Certificates)
1.1 Type - -
1.2 Model no - -
2.0 Nominal characteristics
2.1 Voltage
2.1.1 Rated voltage kV 132
2.1.2 Rated voltage class kV 145
2.2 Rated frequency Hz 50
2.3 Network neutral grounding - Effective
2.4 Rated voltage factor for 30 s - 1,5
2.5 Rated lightning impulse withstand kV 650
2.6 Power frequency withstand voltage (1 min) kV 275
2.7 Creepage distance mm/kV 31
2.8 Capacitance C1 and C2 pf 8800
2.9 Series reactor
- inductance range mH 0.2
- resistance range ohms -
2.10 Transformation ratio - 132kV/3
: 0,11kV/3
: 0,11kV/3
(: 0,11kV/3)
2.11 Transformer characteristics
- HV/LV turn ratio range - -
- Normal operating flux density tesla -

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-5

TECHNICAL DATA SCHEDULE


CAPACITOR VOLTAGE TRANSFORMER 132 kV
CODE NO: 4133

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.12 Primary voltage kV 132/3


2.13 Secondary voltage V 110/3
2.14 Winding accuracy:
- metering class - 0,2
- protection class - 3P
- burden ( on each winding) VA 50
2.15 Number of secondary winding - 2 (3)
2.16 Winding conductor - Cu
2.17 Circuit Diagram - To be enclosed
with bid
2.18 HV Terminal Connector for - TBA
3.0 Weights and Dimensions
3.1 Weight for operation kg -
3.2 Weight for transport kg -
3.3 Height m -
3.4 Shipping dimensions (H x W x D) m -
3.5 Outline drawing number - To be enclosed
with bid
4.0 Type tests reports N - To be enclosed
with bid
5.0 Standards - IEC60186
IEC 60694
IEC 60947-1
IEC 60044-5
6.0 Quality control - ISO-------------
7.0 Installation - Outdoor, in
substation
switchyard

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-6

1.3 CURRENT TRANSFORMER, 330KV, 300/600/800/1600A

TECHNICAL DATA SCHEDULE


CURRENT TRANSFORMER 330 kV, 300/600/800/1600A
CODE NO: 4134

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 Manufacturer -
Equipment that are
compliant with
KEMA, KERRI or
CESSI Certifications
Only.
(Attach Certificates
and Type Tests
report from STL
Members only)
1.1 Type - Oil
1.2 Model no - -

2.0 Nominal characteristics


2.1 Voltage
2.1.1 Rated max. operating voltage kV 330
2.1.2 Rated voltage class KV 362
2.2 Rated frequency Hz 50
2.3 Network neutral grounding - effective
2.4 Heating limit at 30C ambient temperature C 55
2.5 Rated current A 1600/800/600/300
2.6 Short-circuit current capability (1 s) kA 31.5
2.7 Rated lightning impulse withstand kV 1175
2.8 Switching impulse withstand voltage kV 950
2.9 Power frequency withstands voltage (1 kV 450
min.)
2.10 Creepage distance mm/kV 31
2.11 Max. radio interference voltage at 0,5 MHz V 2500
as per IEC694
2.12 Primary rated current A 300/600/800/1600
2.13 Secondary rated current A 1

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-7

TECHNICAL DATA SCHEDULE


CURRENT TRANSFORMER 330 kV, 300/600/800/1600A
CODE NO: 4134

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.14 Number of windings - 4


2.15 Accuracy class:
Metering
core No. 1 class- 0,2
Burden 20VA
ISF ≤5

- Core: 2 & 3 (PS) - (5P20)


- Core: 4 (class x)
- burden - 20 VA
-Knee point volt(Vk) 30(Rct+36):core 2&3
40(Rct+75):core 4
2.16 Winding conductor - Cu
2.17 Transient performance
- class - TPX or TPY
- rated S.C. current factor p.u. 20
- primary time constant ms 45
- secondary C.T. time constant ms -
- Duty cycle - C-0,075s-0-0,3s-C-
0,075s-0
- resistive burden ohms 2,5
- secondary C.T. resistance ohms -
- transient dimensioning factor - -
- remanence factor - -
- equivalent limiting secondary EMF V -
- saturation curve - to be enclosed with
bid
2.18 HV Terminal Connector for - TBA
2.19 LV Terminal Voltage Limiting Device - Yes
3.0 Weights and Dimensions
3.1 Weight for operation kg -
3.2 Weight for transport kg -
3.3 Height m -
3.4 Shipping dimensions (H x W x D) m -
3.5 Outline drawing number - To be enclosed with
bid

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-8

TECHNICAL DATA SCHEDULE


CURRENT TRANSFORMER 330 kV, 300/600/800/1600A
CODE NO: 4134

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

4.0 Type tests reports N - To be enclosed with


bid
5.0 Standards - IEC 600815
IEC 60867
IEC 61869-5
IEC 61869-1
6.0 Quality control - ISO9001,140001,
18001
Manufacturer’s test
lab shall be
accredited to ISO
17025 for accuracy.
7.0 Installation - Outdoor in substation
switchyard
The max. tan delta
allowed for the
capacitor column is
0.0020

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-9

1.4 CURRENT TRANSFORMER, 132KV, 300/400/600/800 A

TECHNICAL DATA SCHEDULE


CURRENT TRANSFORMER 132 kV, 300/400/600/800A
CODE NO: 4135

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 Manufacturer -
Equipment that are
compliant with
KEMA, KERRI or
CESSI Certifications
Only.
(Attach Certificates)
1.1 Type - Oil
1.2 Model no - -

2.0 Nominal characteristics


2.1 Voltage
2.1.1 Rated max. operating voltage kV 132
2.1.2 Rated voltage class KV 145
2.2 Rated frequency Hz 50
2.3 Network neutral grounding - effective
2.4 Heating limit at maximum ambient C 55
temperature
2.5 Rated current A 300/400/600/800
2.6 Short-circuit current capability (1 s) kA 31.5
2.7 Rated lightning impulse withstand kV 650
2.8 Power frequency withstands voltage (1 kV 275
min.)
2.9 Creepage distance mm/kV 31
2.10 Primary rated currents A 300/400/600/800
2.11 Secondary rated current A 1
2.12 Number of windings - 4
2.13 Accuracy class:
metering
- Core No. 1 - 0,2

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-10

TECHNICAL DATA SCHEDULE


CURRENT TRANSFORMER 132 kV, 300/400/600/800A
CODE NO: 4135

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

-Burden 20 VA
-ISF ≤5
- Core No. 2 & 3 (Protection) - (5P20)
- Core No.4 Class X
- burden - 20 VA
-Knee point Volts(Vk) 30(Rct+36):core 2&3
40(Rct+7):core 4
2.14 Winding conductor - Cu

2.15 Transient performance


- class - TPX or TPY
- rated S.C. current factor p.u. 20
- primary time constant ms 45
- secondary C.T. time constant ms -
- Duty cycle - C-0,075s-0-0,3s-C-
0,075s-0
- resistive burden ohms 2,5
- secondary C.T. resistance ohms -
- transient dimensioning factor - -
- remanence factor - -
- equivalent limiting secondary EMF V -
- saturation curve - to be enclosed with
bid
2.16 HV Terminal Connector for - TBA
2.17 LV Terminal Voltage Limiting Device - Yes
3.0 Weights and Dimensions
3.1 Weight for operation kg -
3.2 Weight for transport kg -
3.3 Height m -
3.4 Shipping dimensions (H x W x D) m -
3.5 Outline drawing number - To be enclosed with
bid
4.0 Type tests reports N - To be enclosed with
bid

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-11

TECHNICAL DATA SCHEDULE


CURRENT TRANSFORMER 132 kV, 300/400/600/800A
CODE NO: 4135

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

5.0 Standards - IEC 600815


IEC 60867
IEC 61869-5
IEC 61869-1
6.0 Quality control - ISO9001,140001,
18001
Manufacturer’s test
lab shall be
accredited to ISO
17025 for accuracy
7.0 Installation - Outdoor in substation
switchyard
The max. tan delta
allowed for the
capacitor column is
0.0020

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-12

1.5 VOLTAGE TRANSFORMER 33KV

TECHNICAL DATA SCHEDULE


VOLTAGE TRANSFORMER 33 kV
CODE NO: 4137

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 Manufacturer -

1.1 Type - -
1.2 Model no - -
1.3 Country of origin - -
Equipment that
are compliant
with KEMA,
KERRI, CESSI or
any other
member of STL
group
Certifications.
(Attach
Certificates)
2.0 Nominal characteristics
2.1 Voltage
2.1.1 Rated voltage kV 33
2.1.2 Rated maximum voltage class kV 36
2.2 Rated frequency Hz 50
2.3 Network neutral grounding - Effective
2.4 Rated voltage factor for 30 s - 1,5
2.5 Rated lightning impulse withstand kV 170
2.6 Power frequency withstand voltage (1 min) kV 70
2.7 Creepage distance mm/kV 31
2.8 Design - Inductive
2.9 Transformation ratio: - 33kV/3
: 0,11kV/3
: 0,11kV/3
2.10 Transformer characteristics
- HV/LV turn ratio range - -
- Normal operating flux density tesla -

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-13

TECHNICAL DATA SCHEDULE


VOLTAGE TRANSFORMER 33 kV
CODE NO: 4137

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.11 Primary voltage kV 33/3


2.12 Secondary voltage V 110/3
2.13 Winding accuracy:
- metering class - 0,2
- protection class - 3P
- burden (simultaneous on each winding) VA 50
2.14 Number of secondary winding - 2
2.15 Winding conductor - Cu
2.16 Circuit Diagram - To be enclosed
with bid
2.17 HV Terminal Connector for - TBA
3.0 Weights and Dimensions
3.1 Weight for operation kg -
3.2 Weight for transport kg -
3.3 Height m -
3.4 Shipping dimensions (H x W x D) m -
3.5 Outline drawing number - To be enclosed
with bid
4.0 Type tests reports N - To be enclosed
with bid
5.0 Standards - IEC60186
IEC 60694
IEC 60947-1
6.0 Quality control - ISO--------
7.0 Installation - Outdoor, in
substation
switchyard

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-14

1.6 CURRENT TRANSFORMER, 33KV, 400/600/800/1200 A

TECHNICAL DATA SCHEDULE


CURRENT TRANSFORMER 33KV, 400/600/800/1200 A
CODE NO: 4135

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 Manufacturer -

1.1 Type - Oil

1.2 Model no - -
1.3 Country of origin - -
Equipment that are
compliant with
KEMA, KERRI, CESSI
or any other
member of STL
group Certifications.
(Attach Certificates)
2.0 Nominal characteristics
2.1 Voltage
2.1.1 Rated max. operating voltage kV 33
2.1.2 Rated voltage class KV 36
2.2 Rated frequency Hz 50
2.3 Network neutral grounding - effective
2.4 Heating limit at maximum ambient C 55
temperature
2.5 Rated current A 400/600/800/1200

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-15

TECHNICAL DATA SCHEDULE


CURRENT TRANSFORMER 33KV, 400/600/800/1200 A
CODE NO: 4135

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.6 Short-circuit current capability (1 s) kA 25


2.7 Rated lightning impulse withstand kV 170
2.8 Power frequency withstands voltage (1 kV 70
min.)
2.9 Creepage distance mm/k 31
V
2.10 Primary rated current A 400/600/800/1200
2.11 Secondary rated current A 1
2.12 Number of windings - 4
2.13 Accuracy class:
-Metering
- Core No. 1 Class 0,2
- Core No. 2 & 3 (protection) - 5P20
-Core No. 4 5P20
- burden - 20 VA

2.14 Winding conductor - Cu

2.15 Transient performance


- class - TPX or TPY
- rated S.C. current factor p.u. 20
- primary time constant ms 45
- secondary C.T. time constant ms -
- Duty cycle - C-0,075s-0-0,3s-C-
0,075s-0
- resistive burden ohms 2,5
- secondary C.T. resistance ohms -
- transient dimensioning factor - -
- remanence factor - -
- equivalent limiting secondary EMF V -
- saturation curve - to be enclosed with
bid
2.16 HV Terminal Connector for - TBA
2.17 LV Terminal Voltage Limiting Device - Yes
3.0 Weights and Dimensions

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-16

TECHNICAL DATA SCHEDULE


CURRENT TRANSFORMER 33KV, 400/600/800/1200 A
CODE NO: 4135

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

3.1 Weight for operation kg -


3.2 Weight for transport kg -
3.3 Height m -
3.4 Shipping dimensions (H x W x D) m -
3.5 Outline drawing number - To be enclosed with
bid
4.0 Type tests reports N - To be enclosed with
bid
5.0 Standards - IEC 60044
IEC 60694
IEC 60947-1
IEC 60376
6.0 Quality control - ISO---------
7.0 Installation - Outdoor in
substation
switchyard

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE
TRANSMISSION COMPANY OF NIGERIA (TCN).
Technical Specifications – Instrument Transformers

Page VII.VII-17

DOCUMENT TS 4130 REV. 2 TCN (SUPPLY OF EQUIPMENT & MATERIALS) FOR 2015-2016
GRID MAINTENANCE