Pm210011-Nui900-Rl5-00015 - 02 - Slab On Grade Plan - (261-B203) Operators B...
Pm210011-Nui900-Rl5-00015 - 02 - Slab On Grade Plan - (261-B203) Operators B...
NOTES :-
LEGEND:-
PLANT
T 3600 2200 3300
NORTH NO RU 02 1. ALL DIMENSIONS ARE IN MILLIMETERS AND ELEVATIONS ARE IN METERS
RT E
NN H UNLESS OTHERWISE NOTED.
GB GRADE BEAM
300
DN
2. FOR GENERAL NOTES FOR CONCRETE AND STRUCTURE REFER TO
DWG. NO. PM210011-NUI900-RD2-00028, 00029, 00030.
SOG SLAB ON GRADE
02
TOC EL +0.000
3. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ARCHITECTURE, 02
WALL FOOTINGS
PREVAILING ELECTRICAL AND MECHANICAL DRAWINGS AND DOCUMENTS.
1765
WIND
RAMP DOWN TOC TOP OF CONCRETE
4. ALL REINFORCING STEEL SHALL BE HOT ROLLED HIGH TENSILE
1200
MECCA S-SB-02 DEFORMED BILLET STEEL BARS CONFORMING TO ASTM A-615
EL ELEVATION
3265
150 150 THK. PLINTH GRADE 60 (420MPa) REINFORCEMENT SHALL BE FUSION BONDED EPOXY
PROTECTION PCC COATED (ONLY FOR BELOW GROUND CONCRETE FOUNDATIONS, PILES,
SOG SOLID SLAB THICKNESS
4 PILECAP & UNDERGROUND STRUCTURES AND DO NOT REQUIRE FOR ABOVE 4
150
GROUND CONCRETE STRUCTURE)
TOC EL +0.250 DN DOWN
02 5. GRADE OF CONCRETE SHALL BE CLASS B FOR BELOW GRADE
1505
1500
1000 x 2250 STRUCTURES AND CLASS C FOR ABOVE GRADE STRUCTURES WITH
WALL OPENING OPENING
01 MINIMUM CYLINDRICAL COMPRESSIVE STRENGTH OF 31 N/mm² @ 28 days.
200
200
FALSE FLOOR
of Air Products and must not be used, copied, reproduced, or disclosed to others in whole or in part, without proper authorization. This drawing may not be reproduced or used for purposes other than that for which it was supplied.
620
FROM SOG.
7. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ELECTRICAL DWG#
5 REFER DRAWING. NO.
PM210011-NUI900-TL5-00005, PM210011-NUI900-EC9-00011 &
GB1 GB1 PM210011-NUI900-RD2-00029.
500 1000 PM210011-NUI900-EL5-00027.
50
50
200
50
50 50
DETAIL - X
S-SB-02
4300
GB1
GB1
150 S-SB-02
GB1
150
1500
TOC EL +0.250
TOC EL +0.250
01
1500 1300 800
F
REFERENCE DRAWINGS
RD2-00026
125
125
GB1 RAFT FOUNDATION PLAN PM210011-NUI900-RF2-00005
GB3
4 ROOF FRAMING PLAN PM210011-NUI900-RL5-00016
02
125
125
COLUMN AND AXES PLAN PM210011-NUI900-RL5-00014
TOC EL +0.250
F S-SB-02 RAFT FOUNDATION SECTION, COLUMN & WALL DETAILS PM210011-NUI900-RD2-00025
RD2-00026
2275
3 150 SLOPE : 2% 3
GB3
SLAB ON GRADE / GRADE BEAM SCH, SEC & DETAILS PM210011-NUI900-RD2-00026
TOC EL +0.000 (TYP.)
1500
S-SB-02 ROOF FRAMING / ROOF BEAM SCH, SEC & DETAILS PM210011-NUI900-RD2-00027
800
560 1200 150
4000
GB3
F F 02
TOC EL -0.300
RD2-00026 RD2-00026
GB1
1600
B C 02
1300 800
RD2-00026 RD2-00026
200
200
H PLANT T
NORTH NORUE
RT
900-B 923
3 GB2* RD2-00026
3600
26.4 o
WALL OPENING
RAMP DOWN
550 M2
SHED
900-B 910
100
900-B 911
56
100
1050
2870 M2
GB2
PREVAILING
16600
T SF -2
WIND
1000 x 2250
MEP MATERIAL
4235 M2
S-SB-02 S150
RD2-00026
2
900-B908
150
GB3
RD2-00026
GB3
TOC EL -0.300
900-B919
300 900-B 907 900- B906
K K
900-B 912 900-B 913
4000
GB1
RD2-00026 RD2-00026 02
TOC EL +0.000
800
S-SB-02 2 0
.5
6
RAMP DOWN
WALL OPENING
900- B 901
7 0
.5
3
2
150
3600
2200 x 2250
tT
2200
1000
150 RD2-00026
RD2-00026
200
200
TOC EL +0.250
GB3 GB1
2
300 200-B 220
525
5
50
50
3260
1050
2 G G 2
O
HDL
1335
1335
E
100-B101
1500
RD2-00026 RD2-00026
TOC EL +0.250
TOC EL +0.250
GB3
GB3
GB1
2200
3000
REFER DWG # 150 150 261-B203 (OPERATOR BLDG-AMMONIA)
DN
261-B203
PM210011-NUI900-DL5-00009 600
2400
2400
PDC
02
D ISSUE FOR CONSTRUCTION
1500 RD2-00026 3872
650
AP REVIEW STAMP
50
50
W1 H
RD2-00026
200
200
2372
D
(TYP.)
1500
RD2-00026 CODE 4: Reviewed by Air Products - NO COMMENTS, No Further Submittal Required 02 ISSUED FOR CONSTRUCTION 14/08/2023 MS CP HB
02 Unless Drawing/Document is Revised.
WATER SUPPLY 01 REVISED AS PER COMMENTS 24/06/2023 SS CP HB
REFER DWG # 00 ISSUE FOR REVIEW 20/03/2023 SS AK HB
PM210011-NUI900-OL5-00039 CODE 5 : ACCEPTED FOR INFORMATION ONLY REV.NO. DESCRIPTION DATE DRAWN CHECKED APPROVED
INSTRUMENTATION 3 NOS. ERTHING CABLE LV CABLE 4 NOS. LV CABLE 4 NOS.
REVISION HISTORY
REFER DWG # REFER DWG # REFER DWG # REFER DWG #
PM210011-NUI900-DL5-00009 PM210011-NUI900-EL5-00027 PM210011-NUI900-EC9-00011 PM210011-NUI900-EC9-00011
02 Contractor/Sub-Contractor/Vendor are not relieved of their responsibilities for accuracy of
COMMUNICATION 4 NOS. 3400 5400 INSTRUMENTATION S-SB-02
dimensions, performance, design, design of details or any code requirement. Further, review
REFER DWG # REFER DWG # 150 by Air Products does not relieve Contractor/Sub-Contractor/Vendor of responsibilities
W1
PM210011-NUI900-TL5-00005 8800 PM210011-NUI900-DL5-00009 or liabilities, or fromfurnishing material in conformance with the contract, purchase order, or
1 other agreement. Air Products' review shall not be constructed as an Approval by Air Products
1
ERTHING CABLE
REFER DWG # of such documents or an opinion by Air Products that such documents are true and accurate.
02 C B A PM210011-NUI900-EL5-00027
C Air Products and Chemicals, Inc.
GB1
C1 SLAB ON GRADE PLAN 02 Lead Reviewer's Signature: Date: Project No: PM210011 NEOM GREEN HYDROGEN ELEMENTS (NGHE) PROJECT
GB1
SCALE 1 : 50
Area 90 - Common Building Unit 900 - Common Building
PROPRIETARY DATA:
RL5-00015 STRUCTURAL
PO Number: N/A PO Date N/A Title LOCATION LAYOUTS
261-B203 OPERATOR BUILDING (AMMONIA)
Vendor / Contractor SLAB ON GRADE PLAN
Name NESMA UNITED INDUSTRIES
DETAIL - X - TYPICAL FILLER BOARD DETAIL Vendor / Contractor PM210011-NUI900-RL5-00015 Drawing No: PM210011-NUI900-RL5-00015 Rev: 02
SCALE 1 : 10 Document No.:
RL5-00015 Contractor
Contractor SAP ID N/A ORG Code NUI Tag No(s): 261-B203 Scale: 1:50 Size : A1
A B C D E F G H