Check physically condition of Belt (Damage, Change Belt if Damaged like cracks, wear
Pulley & V Belt Check Condition of Pully & To be run without
Sound and slipage cracks, wear out, broken or slipage,mis out, broken or slipage, etc). Lock nut to be Mr.Ashwani Fortnight
Assembly V-Belt sliping,sound
alignment etc). Loos of pully due to lock nut tighten . Alignment also to be done.
Loosness of padestal nut/bolt & grouting. Nut Loos fatners to be tighten. Replace the
Check Vibration Of Bearing Physically Check, Normal/
Vibration loos of Sleeve.Damage of bearing. Alignment bearing if damaged. Alignment also to be Mr.Ashwani Fortnight
Housing Abnormal
disturbed checked
Bearing Housing
(DS) Sleeve may be cut/loose, outer race may be Lubrication to be done, and other parts to be
Check Temperature Of
Minimum 50 ,Max 70.c High temprature rotate under housing, No sufficient lubricant replaced if found damaged . Alignment also to Mr.Ashwani Fortnight
Bearing Housing
and alignment disturbed. be checked
Loosness of padestal nut/bolt & grouting. Nut Loos fatners to be tighten. Replace the
I.D. Fan No.2 Check Vibration Of Bearing Physically Check Normal/
Vibration loos of Sleeve.Damage of bearing. Alignment bearing if damaged. Alignment also to be Mr.Ashwani Fortnight
Housing Abnormal
disturbed checked
Bearing Housing
(NDS)
Sleeve may be cut/loose, outer race may be Lubrication to be done, and other parts to be
Check Temperature Of
Minimum 50 ,Max 70.c Temprature high rotate under housing, No sufficient lubricant replaced if found damaged . Alignment also to Mr.Ashwani Fortnight
Bearing Housing
and alignment disturbed. be checked
Check physically condition of Belt (Damage, Change Belt if Damaged like cracks, wear
Pulley & V Belt Check Condition of Pully & To be run without
Sound and slipage cracks, wear out, broken or slipage,mis out, broken or slipage, etc). Lock nut to be Mr.Ashwani Fortnight
Assembly V-Belt sliping,sound
alignment etc). Loos of pully due to lock nut tighten . Alignment also to be done.
FD FAN
Loosness of padestal nut/bolt & grouting. Nut Loos fatners to be tighten. Replace the
Bearing Housing Check Vibration Of Bearing Physically Check, Normal/
Vibration loos of Sleeve.Damage of bearing. Alignment bearing if damaged. Alignment also to be Mr.Ashwani Fortnight
(DS) Housing Abnormal
disturbed checked
Sleeve may be cut/loose, outer race may be Lubrication to be done, and other parts to be
Bearing Housing Check Temperature Of
Minimum 50 ,Max 70.c Temprature high rotate under housing, No sufficient lubricant replaced if found damaged . Alignment also to Mr.Ashwani Fortnight
(DS) Bearing Housing
and alignment disturbed. be checked
Loosness of padestal nut/bolt & grouting. Nut Loos fatners to be tighten. Replace the
FD FAN No-1 Bearing Housing Check Vibration Of Bearing Physically Check, Normal/
Vibration loos of Sleeve.Damage of bearing. Alignment bearing if damaged. Alignment also to be Mr.Ashwani Fortnight
(NDS) Housing Abnormal
disturbed checked
Sleeve may be cut/loose, outer race may be Lubrication to be done, and other parts to be
Bearing Housing Check Temperature Of
Minimum 50 ,Max 70.c Temprature high rotate under housing, No sufficient lubricant replaced if found damaged . Alignment also to Mr.Ashwani Fortnight
(NDS) Bearing Housing
and alignment disturbed. be checked
Foundation bolts tighten,tighten of coupling
Check Condition of foundation bolts loose, damaged of tyre, loose
Coupling No sound and vibration Sound and vibration plate/tyre bolts,and re-alignment, change ture Mr.Ashwani Fortnight
Coupling of coupling plate/tyre bolts. Mis Alignment
if damaged
Loosness of padestal nut/bolt & grouting. Nut Loos fatners to be tighten. Replace the
Bearing Housing Check Vibration Of Bearing Physically Check, Normal/
Vibration loos of Sleeve.Damage of bearing. Alignment bearing if damaged. Alignment also to be Mr.Ashwani Fortnight
(DS) Housing Abnormal
disturbed checked
Sleeve may be cut/loose, outer race may be Lubrication to be done, and other parts to be
Bearing Housing Check Temperature Of
Minimum 50 ,Max 70.c Temprature high rotate under housing, No sufficient lubricant replaced if found damaged . Alignment also to Mr.Ashwani Fortnight
(DS) Bearing Housing
and alignment disturbed. be checked
Loosness of padestal nut/bolt & grouting. Nut Loos fatners to be tighten. Replace the
Bearing Housing Check Vibration Of Bearing Physically Check, Normal/
FD FAN No-2 Vibration loos of Sleeve.Damage of bearing. Alignment bearing if damaged. Alignment also to be Mr.Ashwani Fortnight
(NDS) Housing Abnormal
disturbed checked
Sleeve may be cut/loose, outer race may be Lubrication to be done, and other parts to be
Bearing Housing Check Temperature Of
Minimum 50 ,Max 70.c Temprature high rotate under housing, No sufficient lubricant replaced if found damaged . Alignment also to Mr.Ashwani Fortnight
(NDS) Bearing Housing
and alignment disturbed. be checked
Foundation bolts tighten,tighten of coupling
Check Condition of foundation bolts loose, damaged of tyre, loose
Coupling No sound and vibration Sound and vibration plate/tyre bolts,and re-alignment, change ture Mr.Ashwani Fortnight
Coupling of coupling plate/tyre bolts. Mis Alignment
if damaged
Seondary fan
Check Gear Box Physically check nut bolts Foundation bolt to be tightened if loose ,
Foundation bolt loose ,coupling star damaged&
Foundation Bolt Tightness & for tighting with spanner.Oil Sound & vibration rubber star to be changed if damaged,if oil Mr.Ashwani Fortnight
misalignment & oil leval low
oil leval leval checked throgh dipstic leval low then top up
Coal feeder Feeder-1 Check Condition of Lock nut of lovejoy coupling nut loose ,rubber Locknut tightned if loose & if rubber star
No sound and vibration Sound and vibration Mr.Ashwani Fortnight
Coupling star damaged ,misAlignment damaged ,thenchange ,and re-alignment,
Check Sprocket & Chain Physically check sprocket Lubrication not proper & sprocket teeth Chain lubrication to be done & sprocket
Sound & vibration Mr.Ashwani Fortnight
Condition and chain condition damaged & misalignment change if teeth depriciated & alignment done
Check Gear Box Physically check nut bolts Foundation bolt to be tightened if loose ,
Foundation bolt loose ,coupling star damaged&
Foundation Bolt Tightness & for tighting with spanner.Oil Sound & vibration rubber star to be changed if damaged,if oil Mr.Ashwani Fortnight
misalignment & oil leval low
oil leval leval checked throgh dipstic leval low then top up
Coal feeder Feeder-2 Check Condition of Lock nut of lovejoy coupling nut loose ,rubber Locknut tightned if loose & if rubber star
No sound and vibration Sound and vibration Mr.Ashwani Fortnight
Coupling star damaged ,misAlignment damaged ,thenchange ,and re-alignment,
Check Sprocket & Chain Physically check sprocket Lubrication not proper & sprocket teeth Chain lubrication to be done & sprocket
Sound & vibration Mr.Ashwani Fortnight
Condition and chain condition damaged & misalignment change if teeth depriciated & alignment done
Check Gear Box Physically check nut bolts Foundation bolt to be tightened if loose ,
Foundation bolt loose ,coupling star damaged&
Foundation Bolt Tightness & for tighting with spanner.Oil Sound & vibration rubber star to be changed if damaged,if oil Mr.Ashwani Fortnight
misalignment & oil leval low
oil leval leval checked throgh dipstic leval low then top up
Coal feeder Feeder-3 Check Condition of Lock nut of lovejoy coupling nut loose ,rubber Locknut tightned if loose & if rubber star
No sound and vibration Sound and vibration Mr.Ashwani Fortnight
Coupling star damaged ,misAlignment damaged ,thenchange ,and re-alignment,
Check Sprocket & Chain Physically check sprocket Lubrication not proper & sprocket teeth Chain lubrication to be done & sprocket
Sound & vibration Mr.Ashwani Fortnight
Condition and chain condition damaged & misalignment change if teeth depriciated & alignment done
Check Gear Box Physically check nut bolts Foundation bolt to be tightened if loose ,
Foundation bolt loose ,coupling star damaged&
Foundation Bolt Tightness & for tighting with spanner.Oil Sound & vibration rubber star to be changed if damaged,if oil Mr.Ashwani Fortnight
misalignment & oil leval low
oil leval leval checked throgh dipstic leval low then top up
Coal feeder Feeder-4 Check Condition of Lock nut of lovejoy coupling nut loose ,rubber Locknut tightned if loose & if rubber star
No sound and vibration Sound and vibration Mr.Ashwani Fortnight
Coupling star damaged ,misAlignment damaged ,thenchange ,and re-alignment,
Check Sprocket & Chain Physically check sprocket Lubrication not proper & sprocket teeth Chain lubrication to be done & sprocket
Sound & vibration Mr.Ashwani Fortnight
Condition and chain condition damaged & misalignment change if teeth depriciated & alignment done
Check Pump Bearing Check for Vibrations and Sleeve chuck nut loose ,lubrication not proper To be decide based on condition ,Lubrication
Vibration & sound Mr.Ashwani Fortnight
Condition Abnormal sound. or bearing damaged to be done or replacement.as condition
Check Pump Bearing Check for Vibrations and Sleeve chuck nut loose ,lubrication not proper To be decide based on condition ,Lubrication
Vibration & sound Mr.Ashwani Fortnight
Condition Abnormal sound. or bearing damaged to be done or replacement.as condition
Check Pump Bearing Check for Vibrations and Sleeve chuck nut loose ,lubrication not proper To be decide based on condition ,Lubrication
Vibration & sound Mr.Ashwani Fortnight
Condition Abnormal sound. or bearing damaged to be done or replacement.as condition
ESP
Check for abnormal sound,
Oil leval low.coupling rubber star brokened & Oil top up, as per condition check then furher
Check Gearbox Condition Oil level,Drive shaft coupling Vibration & sound Mr.Ashwani Fortnight
misalignment action to be taken
ESP ESP Assembly-1 etc.
Check Coupling & Star Check for Vibrations and lovejoj coupling Ruber star If damged then change further decesion taken
Vibration & sound Mr.Ashwani Fortnight
Condition Abnormal sound. brokened ,misalignment upon condition
Check for abnormal sound,
Oil leval low.coupling rubber star brokened & Oil top up, as per condition check then furher
Check Gearbox Condition Oil level,Drive shaft coupling Vibration & sound Mr.Ashwani Fortnight
misalignment action to be taken
ESP ESP Assembly-2 etc.
Check Coupling & Star Check for Vibrations and lovejoj coupling Ruber star If damged then change further decesion taken
Vibration & sound Mr.Ashwani Fortnight
Condition Abnormal sound. brokened ,misalignment upon condition
Stoker
Check for abnormal sound, Oil top up, Coupling friction cluch plate
Stoker Stoker Check Coupling Condition Oil level,Drive shaft cltuch Vibration & sound Oil leval low.Clutch plate damaged damaged then change & as per condition Mr.Ashwani Fortnight
plate etc. check then furher action to be taken
Check Sprocket & Chain Physically check sprocket Lubrication not proper & sprocket teeth Chain lubrication to be done & sprocket
Stoker Stoker Sound & vibration Mr.Ashwani Fortnight
Condition and chain condition damaged & misalignment change if teeth depriciated & alignment done
Coal plant
Check for abnormal sound,
Oil leval low.coupling rubber star brokened & Oil top up, as per condition check then furher
Coal Coveyor-01 Coal Coveyor-01 Check Gear Box Condition Oil level,Drive shaft coupling Vibration & sound Mr.Ashwani Fortnight
misalignment action to be taken
etc.
Check for abnormal sound,
Oil leval low.coupling rubber star brokened & Oil top up, as per condition check then furher
Coal Coveyor-02 Coal Coveyor-02 Check Gear Box Condition Oil level,Drive shaft coupling Vibration & sound Mr.Ashwani Fortnight
misalignment action to be taken
etc.
Check for abnormal sound,
Oil leval low.coupling rubber star brokened & Oil top up, as per condition check then furher
Coal Coveyor-03 Coal Coveyor-03 Check Gear Box Condition Oil level,Drive shaft coupling Vibration & sound Mr.Ashwani Fortnight
misalignment action to be taken
etc.
Check physically condition
Check physically condition of Belt (Damage, Change Belt if Damaged like cracks, wear
Check Pulley And V Belt of pully and Belt (Damage,
Vibrator Screen Vibrator Screen Sound and slipage cracks, wear out, broken or slipage,mis out, broken or slipage, etc). Lock nut to be Mr.Ashwani Fortnight
Condition cracks, wear out, broken,
alignment etc). Loos of pully due to lock nut tighten . Alignment also to be done.
etc).
Check physically condition
Check physically condition of Belt (Damage, Change Belt if Damaged like cracks, wear
Check Pulley And V Belt of pully and Belt (Damage,
Coal Crusher New Coal Crusher New Sound and slipage cracks, wear out, broken or slipage,mis out, broken or slipage, etc). Lock nut to be Mr.Ashwani Fortnight
Condition cracks, wear out, broken,
alignment etc). Loos of pully due to lock nut tighten . Alignment also to be done.
etc).
Loos fatners to be tighten. Replace the
Loosness of padestal nut/bolt & Nut loos of
Check Bearing Housing Bolt Physically check nut bolts bearing if damaged.Cover plate inner & outer
Coal Crusher New Coal Crusher New Sound & vibration Sleeve.Damage of bearing. Alignment Mr.Ashwani Fortnight
Tightness for tighting with spanner. change if damaged, Alignment also to be
disturbed ,cover plate inner & outer damaged
checked
SCREW COMPRE
Air Cooled Compressor Plant Air-1
Air Suction Fliter Suction Hose & Clamp Check Suction Hose & Clamp
Air Suction Fliter Check Suction Hose & Clamp Check Suction Hose & Clamp
Air Suction Fliter Check Suction Hose & Clamp Check Suction Hose & Clamp
Air Suction Fliter Check Suction Hose & Clamp Check Suction Hose & Clamp
Air End Check Coupling Condition Check Coupling Condition
Air Suction Fliter Check Suction Hose & Clamp Check Suction Hose & Clamp
Pressure Gauge Check Water Inlet line Pressure Check Water Inlet line Pressure
Air Suction Fliter Check Suction Hose & Clamp Check Suction Hose & Clamp
Pressure Gauge Check Water Inlet line Pressure Check Condition of Radiator Fins
Air Suction Fliter Check Suction Hose & Clamp Check Suction Hose & Clamp
Pressure Gauge Check Water Inlet line Pressure Check Condition of Radiator Fins
Air Suction Fliter Check Suction Hose & Clamp Check Suction Hose & Clamp
Pressure Gauge Check Water Inlet line Pressure Check Water Inlet line Pressure
SCREW COMPRESSOR
Specification/Standared Possible_Value
Filter dusty or Clean filter weekly & Replace if
3000 Running hrs. Dirty
chocked found chocked after cleaning.
Specification/Standared Possible_Value
Specification/Standared Possible_Value
Specification/Standared Possible_Value
2.5+/-0.5 kg/cm2 Pressure Low Inlet line strainer Clean in-line strainers weekly.
chocked,
Specification/Standared Possible_Value
2.5+/-0.5 kg/cm2 Pressure Low Inlet line strainer Clean in-line strainers weekly.
chocked,
Specification/Standared Possible_Value
2.5+/-0.5 kg/cm2 Pressure Low Inlet line strainer Clean in-line strainers weekly.
chocked,
Specification/Standared Possible_Value
2.5+/-0.5 kg/cm2 Pressure Low Inlet line strainer Clean in-line strainers weekly.
chocked,
engineer_name Periodicity
engineer_name Periodicity
Mr. Pravin FORTNIGHTLY
engineer_name Periodicity
engineer_name Periodicity
engineer_name Periodicity
engineer_name Periodicity
engineer_name Periodicity
engineer_name Periodicity
Return pit pump-02(HT) Pump assembly Check for Any abnormal Sound
Return pit pump-03(HT) Pump assembly Check for Any abnormal Sound
Gearbox Gear box assembly Check Gear box Alignment and Mounting bolt
Gearbox Gear box assembly Check Gear box Alignment and Mounting bolt
Cooling Tower-07(4MW)
Checklist_ID Task_ID Assembly Sub Assembly Check Description/Task
Gearbox Gear box assembly Check Gear box Alignment and Mounting bolt
Gearbox Gear box assembly Check Gear box Alignment and Mounting bolt
Gearbox Gear box assembly Check Gear box Alignment and Mounting bolt
Suction foot valve chocked, Pump Pump air trapped to be remove and
1.9+/-.2 kg/cm2 Pressure low priming to be done and check, Mr.Sanjay
air traped.
Suction footvalve to be cleane.
Coupling Allignment distrube, Coupling bush to be replace if wear
Physically check Not OK Pump bush wear out, Pump shaft out, Allignment to be done if Mr.Sanjay
wear out. missalligned, Coupling to be
replaced if damaged.
Mechenical seal to be replace with
Physically check Not OK Mechanical seal damaged Mr.Sanjay
new one.
Check bearing condition baced on
Bearing jam, low lubrication, that replace or lubricate same,
Physically check Vibration Coupling allignment distrube, Coupling allignmet check and Mr.Sanjay
Coupling damaged. correct same, Coupling replace if
found damaged.
Physically check Not OK Mechanical seal damaged Mechenical seal to be replace with Mr.Sanjay
new one.
Check bearing condition baced on
Physically check Coupling
Bearing jam, low lubrication, that replace or lubricate same,
allignment, Shaft of pump and Mr.Sanjay
Vibration Coupling allignment distrube, Coupling allignmet check and
motor , Bush wear and tear.&
Coupling damaged. correct same, Coupling replace if
beraing damage
found damaged.
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Periodicity
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
SCREW CHILLER
Sub Assembly Specification/ Observation
Check Description/Task Possible reason
Standared
Cooling water inlet Chocking of supply line filter, Inlet water pressure
28 to 31 deg Cel High
Temprature low, High temprature of supply water
Condensor
Condensor inlet line water
1.0 to 1.5 Kg/cm2 Low Chocking Inlet water line strainer
Pressure
Chillled water Outlet Chocking of inlet water filter, Chocking of
Evaporator 2.7 to 3 Kg/cm2 Low
Pressure evaporator tubes
Chillled water outline 2.8 to
Chilled water system Low Choaking of suction line filter or pr. Set point
pressure 3.2Kg/cm2(visual)
Chilled water supply Check Mech.seal leak Physically check Leakage Throtling of discharge valve, alignement issue, dry
Pump-1 run of pump,
Physically check,
Chilled water supply Check Pump Foundation bolt loose, spider or coupling
Shaft of pump and High Vibration
Pump-1 Alignment/Coupling damaged , foundation level,alignement issue
motor , Bush wear
Condition
and tear.
Physically check
Coupling allignment,
Shaft of pump and Bearing damageed, Foundation bolt loose, spider
Chilled water supply Check For Any abnormal Vibration/
motor , Bush wear or coupling damaged , foundation
Pump-1 sound abnormal sound
and tear.& beraing level,alignement issue
damage,foundation
bolt
Physically check
Coupling allignment,
Chilled water supply Check For Any abnormal Shaft of pump and Bearing damageed, Foundation bolt loose, spider
Vibration/ or coupling damaged , foundation
Pump-2 sound motor , Bush wear
abnormal sound level,alignement issue
and tear.& beraing
damage,foundation
bolt
ER
Action to be taken if standard beyond acceptance Status After engineer_name Periodicity
criteria action
Foundation bolt
CBD unit CBD PUMP-01(P1-VT) Check for Any Abnormal Sound condition,shaft/bush
Normal Vibration
damaged suction
choking, motor brg.
Physically check
Coupling allignment,
CBD unit CBD PUMP-02(P1-HT) Check for Any Abnormal Sound No vibration / abnormal Coupling
Vibration
sound &spider ,sleeve,Shaft of
pump and motor brg. , &
beraing sound
Check coupling physical
CBD unit CBD PUMP-02(P1-HT) ok OK/ Not OK condition, allignment and
rubber spider
Check Coupling Condition
CBD unit CBD PUMP-02(P1-HT) Physically check Leak/No Leak Physically check
CBD unit CBD PUMP-02(P1-HT) Check for Discharge Pressure 2.5+/-0.5kg/cm2 2.5+/-0.5kg/cm2 Physically check
Physically check
Coupling allignment,
CBD unit CBD PUMP-03(P1-HT) Check for Any Abnormal Sound No vibration / abnormal Coupling
Vibration
sound &spider ,sleeve,Shaft of
pump and motor brg. , &
beraing sound
CBD unit CBD PUMP-03(P1-HT) Physically check Leak/No Leak Physically check
CBD unit CBD PUMP-03(P1-HT) Check for Discharge Pressure 2.5+/-0.5kg/cm2 2.5+/-0.5kg/cm2 Physically check
Physically check ,Shaft of
CBD unit CBD PUMP-04(P3-VT) Check for Any Abnormal Sound Normal Vibration pump and motor brg. , &
beraing sound
CBD unit CBD PUMP-04(P3-VT) Check for Discharge Pressure 2.5+/-0.5kg/cm2 2.5+/-0.5kg/cm2 Physically check
CBD unit CBD PUMP-04(P3-VT) Physically check Leak/No Leak Physically check
CBD unit CBD PUMP-05(P3-HT) Physically check Leak/No Leak Physically check
CBD unit CBD PUMP-05(P3-HT) Check for Discharge Pressure 2.5+/-0.5kg/cm2 2.5+/-0.5kg/cm2 Physically check
Action to be taken if
Status After engineer_name Periodicity
standard beyond
action
acceptance criteria
Allignment to be done, If
shaft is damaged to be
repair or replace, Bush & Mr. sanjay dagar FORTNIGHTLY
brg.to be replace if found
not ok.
Allignment to be done, If
shaft is damaged to be
repair or replace, Bush & Mr. sanjay dagar FORTNIGHTLY
brg.to be replace if found
not ok.
If possible Start stand by
for instant to prevent
Mr. sanjay dagar FORTNIGHTLY
scrap of tyre. And then
resolve other pump issue
Allignment to be done, If
shaft is damaged to be
repair or replace, Bush & Mr. sanjay dagar FORTNIGHTLY
brg.to be replace if found
not ok. Check suction
condition and clean
Allignment to be done, If
shaft is damaged to be
repair or replace, Bush & Mr. sanjay dagar FORTNIGHTLY
brg.to be replace if found
not ok.
To be replace if found Mr. sanjay dagar FORTNIGHTLY
damaged.
Allignment to be done, If
shaft is damaged to be
repair or replace, Bush & Mr. sanjay dagar FORTNIGHTLY
brg.to be replace if found
not ok.
Allignment to be done, If
shaft is damaged to be
repair or replace, Bush & Mr. sanjay dagar FORTNIGHTLY
brg.to be replace if found
not ok.
4roll Calender TCU pump Calender-1 Any abnormal Normal Vibration/Abnormal sound
4roll Calender TCU pump Calender-2 Any abnormal Normal Vibration/Abnormal sound
4roll Calender TCU pump Calender-2 Discharge Pressure 3.5+/-0.5kg/cm2 Low
4roll Calender TCU pump Calender-3 Any abnormal Normal Vibration/Abnormal sound
3ROLL Calender TCU pump Roll-1 Any abnormal Normal Vibration/Abnormal sound
2ROLL Calender TCU pump (2 Roll Calender) Mechanical seal No leak Leak
2ROLL Calender TCU pump (2 Roll Calender) Any abnormal Normal Vibration/Abnormal sound
2ROLL Calender TCU pump (2 Roll Calender) Discharge Pressure 3.5+/-0.5kg/cm4 Low
2ROLL Calender Extruder pump-1 (2 Roll Calender) Mechanical seal No leak Leak
2ROLL Calender Extruder pump-1 (2 Roll Calender) Any abnormal Normal Vibration/Abnormal sound
2ROLL Calender Extruder pump-1 (2 Roll Calender) Discharge Pressure 3.5+/-0.5kg/cm4 Low
2ROLL Calender Extruder pump-2 (2 Roll Calender) Mechanical seal No leak Leak
2ROLL Calender Extruder pump-2 (2 Roll Calender) Any abnormal Normal Vibration/Abnormal sound
2ROLL Calender Extruder pump-2 (2 Roll Calender) Discharge Pressure 3.5+/-0.5kg/cm5 Low
2ROLL Calender Extruder pump-3 (2 Roll Calender) Mechanical seal No leak Leak
2ROLL Calender Extruder pump-3 (2 Roll Calender) Any abnormal Normal Vibration/Abnormal sound
2ROLL Calender Extruder pump-3 (2 Roll Calender) Discharge Pressure 3.5+/-0.5kg/cm6 Low
2ROLL Calender Extruder pump-4 (2 Roll Calender) Mechanical seal No leak Leak
2ROLL Calender Extruder pump-4 (2 Roll Calender) Any abnormal Normal Vibration/Abnormal sound
2ROLL Calender Extruder pump-4 (2 Roll Calender) Discharge Pressure 3.5+/-0.5kg/cm5 Low
2ROLL Calender Extruder pump-5 (2 Roll Calender) Mechanical seal No leak Leak
2ROLL Calender Extruder pump-5 (2 Roll Calender) Any abnormal Normal Vibration/Abnormal sound
2ROLL Calender Extruder pump-5 (2 Roll Calender) Discharge Pressure 3.5+/-0.5kg/cm6 Low
MP exd TCU pump (MP Extruder) Head Top Mechanical seal No leak Leak
MP exd TCU pump (MP Extruder) Head Top Any abnormal Normal Vibration/Abnormal sound
MP exd TCU pump (MP Extruder) Head Top Discharge Pressure 3.5+/-0.5kg/cm3 Low
MP exd TCU pump (MP Extruder) Head Top Coupling Ok Not OK
MP exd TCU pump (MP Extruder) Head Top Heat Exchanger No leak Leak
MP exd TCU pump (MP Extruder) Head Bottam Mechanical seal No leak Leak
MP exd TCU pump (MP Extruder) Head Bottam Any abnormal Normal Vibration/Abnormal sound
MP exd TCU pump (MP Extruder) Head Bottam Discharge Pressure 3.5+/-0.5kg/cm4 Low
MP exd TCU pump (MP Extruder) Head Bottam Heat Exchanger No leak Leak
MP exd TCU pump (MP Extruder) Barrle Mechanical seal No leak Leak
MP exd TCU pump (MP Extruder) Barrle Any abnormal Normal Vibration/Abnormal sound
MP exd TCU pump (MP Extruder) Barrle Discharge Pressure 3.5+/-0.5kg/cm5 Low
MP exd TCU pump (MP Extruder) Barrle Heat Exchanger No leak Leak
Duel exd TCU pump( Dual Extruder) Barrle Base Any abnormal Physically check Vibration/Abnormal sound
Duel exd TCU pump( Dual Extruder) Barrle Base Discharge Pressure Physically check 3.5+/-0.5kg/cm2
Duel exd TCU pump( Dual Extruder) Barrle Base Coupling Physically check Not OK
Duel exd TCU pump (Dual Extruder) Barrle Cap Discharge Pressure Physically check 3.5+/-0.5kg/cm2
Duel exd TCU pump (Dual Extruder) Barrle Cap Coupling Physically check Not OK
Duel exd TCU pump (Dual Extruder) Cusion Any abnormal Physically check Vibration/Abnormal sound
Duel exd TCU pump (Dual Extruder) Cusion Discharge Pressure Physically check 3.5+/-0.5kg/cm2
Duel exd TCU pump (Dual Extruder) Cusion Coupling Physically check Not OK
Duel exd TCU pump (Dual Extruder) Cusion Heat Exchanger Physically check (no Leak
leak) visual
Physically check (no
Duel exd TCU pump (Dual Extruder) Cap Mechanical seal Leak
leak) visual
Duel exd TCU pump (Dual Extruder) Cap Any abnormal Physically check Vibration/Abnormal sound
Duel exd TCU pump (Dual Extruder) Cap Discharge Pressure Physically check 3.5+/-0.5kg/cm2
Duel exd TCU pump (Dual Extruder) Cap Coupling Physically check Not OK
195 +/- 10 °C Less than 180°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
105 +/- 10 °C Higher than 112 °C Steam passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
105 +/- 10 °C Higher than 112 °C Steam passing through trap
170 +/- 10 °C Less than 160°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
170 +/- 10 °C Less than 160°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
170 +/- 10 °C Less than 160°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
105 +/- 10 °C Higher than 112 °C Steam passing through trap
170 +/- 10 °C Less than 160°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
170 +/- 10 °C Less than 160°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
170 +/- 10 °C Less than 160°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
105 +/- 10 °C Higher than 112 °C Steam passing through trap
170 +/- 10 °C Less than 160°C Condenset not passing through trap
195 +/- 10 °C Less than 180°C Condenset not passing through trap
170 +/- 10 °C Less than 160°C Condenset not passing through trap
160 +/- 10 °C Less than 160°C Condenset not passing through trap
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
WEEKLY
4mw
Assembly Sub Assembly Specification/ Observation
Check Description/Task Possible reason
Standared
Compressor suction
4MW Diesel Engine-1,2,3 Air receiver pressure 32+-1 Low filter choke, Air line
leakage
4MW Diesel Engine-1,2,3 Mini generator oil leval to be check Ok Not OK Oil leakage
4MW Diesel Engine-1,2,3 Mini generator togel switch in on position Ok Not OK Misobservation
Check suction
filtter ,nrv& coupling etc. Mr. Sanjay Monthly
& Drive motor
Mr.Rajeev Fornightly
Mr.Rajeev quartly
Mr.Rajeev Fornightly
Mr.Rajeev quartly
BANBURY NO 3
Assembly Sub Assembly Specification/ observation
Check Description/Task Possible reason
Standared
BANBURY NO 4 &5nos
Banbury no 4& 5nos booster poump for cooling Mech.seal leak to be check Ok Not OK Valve throtle, seal damaged
ac drive unit
Banbury no 4& 5nos Booster pump no 1 Any abnormal Normal Foundation bolt tightness &
Vibration
pump motor bearing
Banbury no 4& 5nos Booster pump no 1 Ok Not OK Coupling & spider damage,
mis-alignment
Coupling
water quality bad/ not
Banbury no 4& 5nos Booster pump no 1 Strainer to be check Clean choked
cleaned on time
Banbury no 4& 5nos Booster pump no 2 Ok Not OK Valve throtle, seal damaged
Mech seal leak to be check
Banbury no 4& 5nos Booster pump no 2 Any abnormal Normal Foundation bolt tightness &
Vibration
pump motor bearing
Banbury no 4& 5nos Booster pump no 3 Ok Not OK Valve throtle, seal damaged
Mech.seal leak to be check
Banbury no 4& 5nos Booster pump no 3 Any abnormal Normal Foundation bolt tightness &
Vibration
pump motor bearing
suction line filter chock,Gland
Banbury no 4& 5nos Booster pump no 3 Discharge Pressure 3+/-0.5kg/cm2 Low
seal leakage
Foundation bolt
Banbury no 4 slury pump Pump assembly Any abnormal Normal Foundation bolt tight &
Vibration tightness & pump
pump motor replace
motor bearing,
Status After engineer_name Periodicity
action
Booster Pump-
Pump assembly Gland leak to be check OK/NOT OK No leak
For Cooling roll
Booster Pump-
For Cooling roll Pump assembly Any abnormal Vibration Normal
Action to be taken if
Status After engineer_name Periodicity
standard beyond
action
acceptance criteria
If leakage Gland , m-seal
replace or shaft to be Mr.Rajeev FORTNIGHTLY
check
Foundation bolt tight & Mr.Rajeev FORTNIGHTLY
pump motor replace