Professional Documents
Culture Documents
SOP of UPS Battery Replacement
SOP of UPS Battery Replacement
SOP of UPS Battery Replacement
STANDARD OPERATING
PROCEDURE
BATTERY REPLACEMENT PROCEDURE (UNINTERRUPTIBLE POWER SUPPLY)
1. Document Records
Version Date Description Prepared By Approved By
No.
1
2. TABLE OF CONTENTS
1. Document Records 1
2. Table of Contents 2
3. Introduction 3
4. Objective 3
6. Quality Control 3
9. Supplementary Information 5
2
1. INTRODUCTION
The basic component that differentiates an UPS system from a power conditioner is the battery. If the batteries fail
before the backup generators come on line, the critical power goes down. Improperly installed, poorly maintained,
and inadequately tested batteries are common happenings. In order to make the UPS Battery replacement, inspection
and preventive maintenance shall be conducted regularly. The procedures required for battery replacement must be
defined and carried out by compete person without withstanding the instructions described in this procedure.
2. OBJECTIVE
The main purpose of this standard operating procedure is to stipulate means, measures, responsibility for inspection,
testing and maintenance of UPS, followed by enabling responsible person to carry out battery replacement.
4. QUALITY CONTROL
1. Rubber Glove
2. Safety Hat
3. Safety Boot
4. Goggle
5. Screw Driver
6. Spanner box
7. Multimeter
8. Current Tester
9. Other necessary tools
Inspection is normally performed by the owner or occupant, or any designated responsible personnel. Maintenance
and recharging shall be performed by competent persons of an approved organization authorized by the relevant
3
authority and having available the proper types of tools, recharge materials, lubricants, and manufacturer's
recommended replacement parts.
2 Check Battery • Check and record the overall float voltage at the battery
terminals (not at the rectifier charger)
• Measure the pilot cell voltage
• Check total battery voltage
• If the battery condition is abnormal, see at content
No. 6
5 Check electrical parameters • Record input voltage, input current, input frequency of each
before replace battery (User module.
Interface) • Record output voltage, output current, output frequency of each
module.
• Record bypass voltage of each module
• Record and check load percentage and conditions of each
module
• Check and record battery information on UPS monitoring screen
• Make sure no alarm is generated from UPS
4
6 Battery Replacement • Before replace battery, comply WORK SAFETY, HEALTY AND
(Abnormal Condition) ENVIRONMENT at article 3.
• Make sure to change manual bypass mode or brake down the
whole of system (Load size) or switch off the isolated circuit
breaker of battery cabinet.
• When system shut down is not available, need auxiliary power
supply source to load size.
• Make sure to check replaced battery conditions before
replacement.
• If battery is in good condition, no need to make boost charge or
if not, need to make boost charge.
• Check the replaced battery terminal don’t have corrosion
• Remove abnormal battery (remove negative cable before
remove positive cable to preventive electric shock)
• Make sure the positive and negative cable do not touch each
other.
• Check the replaced battery specifications to meet the old battery
• Secure the new battery to the bracket of the cabinet
• Reconnect the positive cable first and the negative cable next
• Scure the battery cable terminal correctly
• Before reactivated the normal operation, ensure system fault
alarm does not occur.
• Upon battery replacement, change manual bypass mode to
normal mode or resume system to normal operation or switch on
the isolated circuit breaker of battery cabinet.
7 Check electrical parameters • Record input voltage, input current, input frequency of each
after replace battery (User module.
Interface) • Record output voltage, output current, output frequency of each
module.
• Record bypass voltage of each module
• Record and check load percentage and conditions of each
module
• Check and record battery information on UPS monitoring screen
• Make sure no alarm is generated from UPS
7. SUPPLEMENTARY INFORMATION
No Role No. of person (min:)
1 Maintenance In-charge 1
2 Maintenance Engineer 1
3 Certified workers 3
5
6