Old Lennox Application Design Guide MSAV and DX Coil Details
Old Lennox Application Design Guide MSAV and DX Coil Details
TABLE OF CONTENTS
Theory
Background……………………………………… 2
Bypass damper systems……………… 2
Multi-speed motors…………………..… 2
Variable Frequency Drives……………. 2
Multi-zone VS Single-zone VAV
systems………..………………………….. 2
What is MSAV® ………………………………..... 2
MSAV supply air blower option is available on System Overview...….……………………….…. 3
®
Energence 3 to 30 ton models, Landmark 7.5 Benefits of using MSAV Technology ………. 4
®
tons to 25 tons rooftop units, Strategos 10 to 24
TM
tons rooftop units, and T-Class 7.5 tons to 20 Energy Savings………………………….. 4
tons split systems Temperature and Humidity Control….. 5
Noise Reduction…………………….…... 5
Load Shedding………………………..…. 5
Increased Reliability……………………. 5
Compliance with Regulations………… 5
MSAV Limitations…….....……………..…….… 5
Application
How MSAV Technology Works..…….…...….. 6
Blower Speed Control………………… 6
VFD Bypass Option…………….……... 7
Phase and Voltage Protection……..… 7
Freeze Protection...……....................... 7
MSAV Application……….…….……….. 7
Duct Design…….……………………….. 7
Damper Setup...……………………....... 8
Applications…………………………….. 8
The facts and other material presented here are believed to be accurate. The final design and application of the product along with other components
used to make up a complete system is your responsibility. Lennox disclaims any responsibility for the application of the material presented.
Background
MSAV (Multi-Stage Air Volume) MSAV option is only for single zone, non 100%
MSAV is a Lennox single zone VAV System. outside air applications and, depending on the
control mode of the rooftop unit and the rooftop
For Energence RTUs 3 to 5 tons, multi-speed selected, MSAV can provide up to seven
motors are used to accomplish various airflows. blower speed settings:
On Energence RTUs, Strategos RTUs,
Landmark RTUs and T-Class split systems 7.5 4 cooling speeds
tons and above, VFDs are used to vary supply 1 heating speed
airflow. Landmark RTUs and T-Class Splits
1 ventilation or free cooling speed
stage the VFD based on cooling stages while
Energence RTUs and Strategos RTUs stage the 1 smoke speed
blower according to compressor stages, heating As the unit switches between different stages
demand, ventilation demand, or a smoke alarm. of cooling, the supply fan will either slow down
Table 1 summarizes the differences between or speed up to match the cooling demand.
MSAV single-zone systems and multi-zone/VAV
systems.
When occupied,
Static pressure
supply fan runs at
transducer modulates
Bypass Damper - Lowest upfront 100% constant
No damper in supply duct All RTUs
Multizone cost speed which results
bypassing air to the
in highest energy
return duct
consumption
Static pressure Most expensive
transducer modulates upfront cost.
VAV – Multizone Modulate supply Energence RTUs 20
Yes VFD; compressor Requires controls
(Variable Air Volume) fan saving energy tons and above
circuits staged based and systems
on discharge air integration
Multi-speed belt-
Multi-speed motors
drive motors have
Belt-Drive can handle
only 2 available Energence RTUs
significantly higher
Motors speeds: 6 poles low 3,4,5 tons
Supply fan stages external static than
speed and 4 poles
MSAV - either low or high PSC motors
high speed option.
Single-zone speed. First stage
(Multi- No cooling is low speed, ECM motors are
speed second stage cooling more efficient than
Motor) is high speed. Heating belt drive motors; ECM motors have a Energence RTUs
ECM Blower setpoints higher upfront cost
is high speed only. 3,4,5 tons
Motors can easily be than belt-drive
adjusted in field via motors
Prodigy Unit
Controller
Field installed option
Landmark
For Landmark and only for T- Class Landmark RTUs and
and T-
T-Class Splits, up splits; No heating T-Class splits 7.5
Class
to 2 fan speeds speeds, and no free tons and above
MSAV – Units
Supply fan stages up cooling speeds.
Single-
zone(Multi- and down based on For Energence
Yes Energence RTUs
Stage Air cooling circuits in use, and Strategos
Energence heating, or ventilation 7.5 tons and above
Volume) RTUs, up to 7 fan
and
speeds for Increased first cost Strategos RTUs 10
Strategos
different modes of tons and above
RTUs
operation and
energy savings.
Benefits of using MSAV Technology Figure 3- Reducing airflow reduces power consumption
exponentially, not linearly.
1. Energy Savings
According to the Department of Energy (DOE) In addition, HVAC systems are typically sized for
40-60% of all electricity used in US industry peak load conditions at full capacity, which only
today is consumed by Heating, Ventilation and occurs 1-5% of the annual operating hours. This
Air Conditioning (HVAC) systems making them means that while cooling, blower motors run at
the prime targets for energy-efficient initiatives. full speed unnecessarily 95-99% of the time.
MSAV units not only save energy by staging Utilizing the MSAV technology, staging of the
compressors based on cooling demands but also blower motor according to capacity helps the
offer the option of utilizing reduced fan speeds in rooftop unit lower operational energy
multiple modes of operation. The MSAV option consumption year round. As shown in Figure 4,
controls blower speed based on cooling, heating Energence units equipped with MSAV blower
(select models only), and ventilation demands option are capable of achieving up to 27% higher
(select models only). part-load ratings.
MSAV Limitations
Figure 4- IEER ratings of Energence 7.5-ton to 25-ton
CAV and MSAV units. In the HVAC industry, there are three main
evaporator coil arrangements: face-split, row-
2. Temperature and Humidity Control split and intertwined. At full load, all coil
By staging the blower according to compressor configurations have the same performance,
stages and cooling demand, units with MSAV are however, at part-load, performance and airflow
capable of removing more moisture than CAV allowances differ. Depending on the coil type,
equivalent units. airflow ranges for MSAV will have different
limitations. Below are guidelines, advantages
3. Noise Reduction and disadvantages of each of the different coils.
One of the main sources of sound in HVAC units For a summary of Lennox RTU coil
is supply fan operation. The faster the fan rotates configurations, see Table 2.
the more sound the system produces. Since a
unit with MSAV varies the fan speed as needed 1. Face-Split
by space conditions, the fan will run at lower Figure 5 shows
speeds most of the time producing on average the horizontal or
less noise. face-split
configuration. In
4. Load Shedding (Strategos and Energence this arrangement,
Only) each coil has an
MSAV technology provides the ability to run units independent
in part-load when load shedding is required. circuit on the top
Since MSAV units stage their blowers in part- and the bottom.
load operation, MSAV RTUs will have a lower Each circuit is
energy demand than the equivalent CAV RTUs.
equal in size and Figure 5- Face-Split evaporator
capacity. coil configuration
5. Increased Reliability- Smooth Speed
During stage 1,
Transitions
compressor 1 energizes and drives refrigerant
When a motor is started, it draws much higher
through coil 1; for stage 2, compressor 2
current than during normal operation. This inrush
energizes coil 2… etc. Refrigerant circuits are
current can be three to ten times the full-load
energized and de-energized as the
operating current for the motor, generating both
corresponding compressors are cycled on and
heat and stress in the motor’s components, belts,
off. In this configuration part-load conditions are
bearings, and pulleys. This high inrush causes
achieved by turning off individual sections.
unnecessary wear and tear, possibly leading to a
Therefore, air passing through an inactive
shortened motor, belt, bearings, and pulley life
section is unconditioned and mixed with
span.
conditioned air to arrive at the supply air
However when using a unit with VFD, the VFD
temperature and humidity set point. One of the
controls the inrush ampacity to the motor,
advantages of this arrangement is that, at part-
gradually ramping up until the unit runs at normal
load, air travels through multiple coil rows
operating conditions. As a result of reducing the
providing extra moisture removal. At part-load
inrush current, the blower motor, pulleys,
face-split coils provide the greatest energy
bearings, and belts should have an extended life
efficiency, however, as air velocity through the
span and increased reliability.
coil decreases, the risk of freezing the coil
Ventilation – Optional
Damper Position 3