Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

Doc. No.

: 26071-100-V1E-JV09-50021

Job No. : 26071 Rev.000

CERTIFICATE

PROJECT : Engineering, Procurement and Construction (EPC) Inside


Battery Limits (ISBL) and Outside Battery Limits (OSBL) for
the Refinery Development Master Plan (RDMP) Project
RU V Balikpapan
LOCATION : Refinery Unit V Balikpapan, East Kalimantan,Indonesia
OWNER : PT PERTAMINA (Persero)
PO NO. : 26071-100-POE-JV09-00001

J.M.An J.M.An

000 10 APR 23 ISSUED FOR CONDTRUCTION CHAN STEVEN KELVIN

00A 27 MAR 23 ISSUED FOR APPROVAL CHAN STEVEN KELVIN

REV. DATE DESCRIPTION PREPARED CHECKED APPROVED

VALVES.COM PTE LTD

Page 1
Certificate

Doc No – 26071-100-V1E-JV09-50021
P O No – 26071-100-POE-JV09-0013

CONTENTS :
1. SOLENOID VALVE
Versa ( Page 3 – 18 )
Maxseal ( Page 19 – 26 )

2. LIMIT SWITCH
Topworx ( Page 27 – 40 )

Page 2
Certificate of Compliance
Certificate: 0002203795 Master Contract: 154085

Project: 80030993 Date Issued: 2020-05-26

Issued To: Versa Products Company, Inc.


22 Spring Valley Rd
Paramus, New Jersey, 07652
United States

Attention: Jesse Hui

The products listed below are eligible to bear the CSA Mark shown with
adjacent indicators 'C' and 'US' for Canada and US or with adjacent
indicator 'US' for US only or without either indicator for Canada only.

Issued by: Thong Tong


Thong Tong

PRODUCTS
CLASS - C322801 - VALVES For Hazardous Locations
CLASS - C322881 - VALVES For Hazardous Locations - Certified to US Standards

CLASS 3228 01- VALVES - For Hazardous Locations

Note: the Solenoid Operators below are certified to CSA Std. 139 and UL Std. 429 when mounted to
Pneumatic Valve bodies, Series A, Series B, Series B (316), Series C, Series C (316), Series E, Series K,
Series M, Series R, Series T, Series V and Series V (316).

Class I, Div. 1, Groups B, C, D; Class II, Div 1, Groups E, F and G; Class III:

Series E4-3198-xxXT-xxxx, E4-3198-xxXU-xxxx and E4-3198-xxXV-xxxx Solenoid Operated Valves; supply


input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 3
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; MWP 120 psi (LZ coil (0.50W) –dc),
MWP 150 psi (LV Coil (0.85W) – dc), MWP 200 psi (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –
55 Deg. C to +90 Deg. C, Temperature Coded based on ambient range and construction options; Type 4X and 6P;
IP66; installed per Installation Instructions INS-XR-1.

Series E4-3198-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85
Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts
or 230 Vac, 50/60 Hz, 4.0 W; MWP 120 psi (LZ coil (0.50W) –dc), MWP 150 psi (LV Coil (0.85W) – dc), MWP
200 psi (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –55 Deg. C to +90 Deg. C, Temperature Coded
based on ambient range and construction options; Type 4X and 6P; IP66; installed per Installation Instructions
INS-XDB-1.

Class I, Div. 2, Groups A, B, C, D; Class II, Div 1, Groups E, F and G; Class III:

Series E4-3198-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85
Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts
or 230 Vac, 50/60 Hz, 4.0 W; MWP 120 psi (LZ coil (0.50W) –dc), MWP 150 psi (LV Coil (0.85W) – dc), MWP
200 psi (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –55 Deg. C to +90 Deg. C, Temperature Coded
based on ambient range and construction options; Type 4X and 6P; IP66; installed per Installation Instructions
INS-XDB-1.

(Non incendive) Class I, Div. 2, Groups A, B, C, D:

Series E4-3198-xx-LV-NI-XDBT-303D-D024 Solenoid Operated Valves; supply input rated 24Vdc, 0.85 Watts,
with Diode (P-1005-70D) , MWP 150 psi (LV Coil (0.85W) – dc); Tamb: –55 Deg. C to +90 Deg. C,
Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66; non-incendive
when installed per Installation Instructions
INS-XDB-2.

Ex db IIC:
DIP A21 T85C, T100C, T135C, T200C:

Series E4-3198-xxXS-xxxx, E4-3198-xxXT-xxxx, E4-3198-xxXU-xxxx and E4-3198-xxXV Solenoid Operated


Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts
or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W;
MWP 120 psi (LZ coil (0.50W) –dc),MWP 150 psi (LV Coil (0.85W) – dc), MWP 200 psi (LX Coil (1.8W) or
Standard (4W) – ac and dc); Tamb: –55 Deg. C to +90 Deg. C, Temperature Coded based on ambient range and
construction options; Type 4X and 6P; IP66; installed per Installation Instructions INS-XR-1.

Series E4-3198-xx-XDBS-xxxx and E4-3198-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24
Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or
120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; MWP 120 psi (LZ coil (0.50W) –dc), MWP 150 psi
(LV Coil (0.85W) – dc), MWP 200 psi (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –55 Deg. C to
+90 Deg. C, Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66;
installed per Installation Instructions INS-XDB-1.

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 4
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

Note: the Solenoid Operators below are certified to CSA Std. 139 and UL Std. 429 when mounted to
Pneumatic Valve bodies, Series E4SM.

Class I, Div. 1, Groups B, C, D; Class II, Div 1, Groups E, F and G; Class III:

Safety Valves-

Series E4-2198-xxXT-xxxx, E4-2198-xxXU-xxxx and E4-2198-xxXV-xxxx Solenoid Operated Valves; supply


input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60
Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil
(0.85W) – dc), see Pressure Table for MWP (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C
to +90 Deg. C, Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66;
installed per Installation Instructions INS-XR-1.

Series E4-2198-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85
Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts
or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil (0.85W) – dc), see Pressure Table for MWP
(LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C, Temperature Coded based on
ambient range and construction options; Type 4X and 6P; IP66; installed per Installation Instructions INS-XDB-1.

General Purpose Valves-


Series E4-xx98-xxXT-xxxx, E4-xx98-xxXU-xxxx and E4-xx98-xxXV-xxxx Solenoid Operated Valves; supply
input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60
Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil
(0.85W) – dc), see Pressure Table for MWP (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C
to +90 Deg. C, Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66;
installed per Installation Instructions INS-XR-1.

Series E4-xx98-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85
Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts
or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil (0.85W) – dc), see Pressure Table for MWP
(LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C, Temperature Coded based on
ambient range and construction options; Type 4X and 6P; IP66; installed per Installation Instructions INS-XDB-1.

Ex db IIC:
DIP A21 T85C, T100C, T135C, T200C:

Safety Valves-
Series E4-2198-xxXS-xxxx, E4-2198-xxXT-xxxx, E4-2198-xxXU-xxxx and E4-2198-xxXV-xxxx Solenoid
Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc,
4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see
Pressure Table for MWP (LV Coil (0.85W) – dc), see Pressure Table for MWP (LX Coil (1.8W) or Standard
(4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C, Temperature Coded based on ambient range and
construction options; Type 4X and 6P; IP66; installed per Installation Instructions INS-XR-1.

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 5
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

Series E4-2198-xx-XDBS-xxxx and E4-2198-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24
Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or
120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil (0.85W) – dc),
see Pressure Table for MWP (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C,
Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66; installed per
Installation Instructions INS-XDB-1.

General Purpose Valves-


Series E4-xx98-xxXS-xxxx, E4-xx98-xxXT-xxxx, E4-xx98-xxXU-xxxx and E4-xx98-xxXV-xxxx Solenoid
Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc,
4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see
Pressure Table for MWP (LV Coil (0.85W) – dc), see Pressure Table for MWP (LX Coil (1.8W) or Standard

(4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C, Temperature Coded based on ambient range and
construction options; Type 4X and 6P; IP66; installed per Installation Instructions INS-XR-1.

Series E4-xx98-xx-XDBS-xxxx and E4-xx98-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24
Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or
120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil (0.85W) – dc),
see Pressure Table for MWP (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C,
Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66; installed per
Installation Instructions INS-XDB-1.

Ratings and Coverage: Gas Valves

1. Valves with Type LZ Coil (0.50W) - dc, MWP of up to 120 psi depending on orifice size (Seal: FKM,
BUNA, LT BUNA, EP, FVMQ).
2. Valves with Type LV Coil (0.85W) – dc, see Pressure Table for MWP (Seal: FKM, BUNA, LT BUNA,
EP, FVMQ).
3. Valves with Type LV Coil (0.85W) – dc, MWP of up to 500 psi depending on orifice size and wattage;
(Seal: FKM, BUNA, LT BUNA, FVMQ).
4. Valves with Type LX Coil (1.8W) or Standard (4W) – ac and dc, see Pressure Table for MWP (Seal:
FKM, BUNA, LT BUNA, EP, FVMQ).
5. Valve body is made of stainless steel of different configuration ported for E4 operators having the same
construction on the operator cavity. The operators may be used with aluminum manifold or brass body
having the same construction on the operator cavity.
6. Valves with “-PLR” suffix (Seal LT Buna, Compound NB800-104) may be used at -55°C to +65°C
ambient temperature range.

Ratings and Coverage: Hydraulic Valves

1. Valves with Type LV Coil (0.85W) – dc, see Pressure Table for MWP.
2. Valves with Type LX Coil (1.8W) or Standard (4W) coil – ac or dc, see Pressure Table for MWP

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 6
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

3. Valves LV, LX and Standard (4W) are for use with #1 Oil at -15 Deg. C to +48 Deg. C ambient; or
Hydraulic Oil (AWG 46) at -15 Deg. C to +95 Deg. C ambient.
4. Valve body is made of stainless steel of different configuration ported for E4 operators having the same
construction on the operator cavity. The operators may be used with aluminum manifold having the same
construction on the operator cavity.

Nomenclature

Model E4-ab98-cdXe-ffff where

a = Function; 2 (2-way), 3 (3-way), 7 (7-way diverter), 8 (8 –way Multi-purpose)


b = 1 (normally closed); 2 (normally open)
c = Bottom Seat Orifice; 0, 1, 2, 3, 4, 5, 6, 7, 8
d = Top Seat Orifice; 0, 1, 2, 3, 4, 5, 6
e = Conduit Thread, S, T, U, V
f = Voltage Code; A006 to A480, D005 to D300, E006 to E480

Model E4-ab98-cdXDBe-ffff where

a = Function; 2 (2-way), 3 (3-way), 7 (7-way diverter), 8 (8 –way Multi-purpose)


b = 1 (normally closed); 2 (normally open)
c = Bottom Seat Orifice; 0, 1, 2, 3, 4, 5, 6, 7, 8
d = Top Seat Orifice; 0, 1, 2, 3, 4, 5, 6
e = Conduit Thread, S, T,
f = Voltage Code; A006 to A480, D005 to D300, E006 to E480

CLASS 3228 81- VALVES - For Hazardous Locations - CERTIFIED TO U.S. STANDARDS

Note: the Solenoid Operators below are certified to CSA Std. 139 and UL Std. 429 when mounted to
Pneumatic Valve bodies, Series A, Series B, Series B (316), Series C, Series C (316), Series E, Series K,
Series M, Series R, Series T, Series V and Series V (316).

Class I, Div. 1, Groups B, C, D; Class II, Div 1, Groups E, F and G; Class III:

Series E4-3198-xxXT-xxxx, E4-3198-xxXU-xxxx and E4-3198-xxXV-xxxx Solenoid Operated Valves; supply


input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60
Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; MWP 120 psi (LZ coil (0.50W) –dc),
MWP 150 psi (LV Coil (0.85W) – dc), MWP 200 psi (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –
55 Deg. C to +90 Deg. C, Temperature Coded based on ambient range and construction options; Type 4X and 6P;
IP66; installed per Installation Instructions INS-XR-1.
Series E4-3198-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85
Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts
or 230 Vac, 50/60 Hz, 4.0 W; MWP 120 psi (LZ coil (0.50W) –dc), MWP 150 psi (LV Coil (0.85W) – dc), MWP
200 psi (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –55 Deg. C to +90 Deg. C, Temperature Coded

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 7
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

based on ambient range and construction options; Type 4X and 6P; IP66; installed per Installation Instructions
INS-XDB-1.

Class I, Div. 2, Groups A, B, C, D; Class II, Div 1, Groups E, F and G; Class III:

Series E4-3198-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85
Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts
or 230 Vac, 50/60 Hz, 4.0 W; MWP 120 psi (LZ coil (0.50W) –dc), MWP 150 psi (LV Coil (0.85W) – dc), MWP
200 psi (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –55 Deg. C to +90 Deg. C, Temperature Coded
based on ambient range and construction options; Type 4X and 6P; IP66; installed per Installation Instructions
INS-XDB-1.

(Non incendive) Class I, Div. 2, Groups A, B, C, D:

Series E4-3198-xx-LV-NI-XDBT-303D-D024 Solenoid Operated Valves; supply input rated 24Vdc, 0.85 Watts,
with Diode (P-1005-70D) , MWP 150 psi (LV Coil (0.85W) – dc); Tamb: –55 Deg. C to +90 Deg. C,
Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66; non-incendive
when installed per Installation Instructions NS-XDB-2.

AEx db IIC:
AEx tD 21 T85C, T100C, T135C, T200C:

Series E4-3198-xxXS-xxxx, E4-3198-xxXT-xxxx, E4-3198-xxXU-xxxx and E4-3198-xxXV-xxxx Solenoid


Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc,
4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; MWP 120
psi (LZ coil (0.50W) –dc), MWP 150 psi (LV Coil (0.85W) – dc), MWP 200 psi (LX Coil (1.8W) or Standard

(4W) – ac and dc); Tamb: –55 Deg. C to +90 Deg. C, Temperature Coded based on ambient range and
construction options; Type 4X and 6P; IP66; installed per Installation Instructions INS-XR-1.

Series E4-3198-xx-XDBS-xxxx and E4-3198-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24
Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or
120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W A; MWP 120 psi (LZ coil (0.50W) –dc), MWP 150
psi (LV Coil (0.85W) – dc), MWP 200 psi (LX Coil (1.8W) or Standard (4W) – ac and dc) ; Tamb: –55 Deg. C
to +90 Deg. C, Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66;
installed per Installation Instructions INS-XDB-1.

Ratings and Coverage: Gas Valves

1. Valves with Type LZ Coil (0.50W) – dc, 120 psi differential pressure (Seal: FKM, BUNA, LT BUNA,
EP, FVMQ).
2. Valves with Type LV Coil (0.85W) – dc, 150 psi differential pressure (Seal: FKM, BUNA, LT BUNA,
EP, FVMQ).
3. Valves with Type LX Coil (1.8W) or Standard (4W) – ac and dc, 200 psi differential pressure (Seal:
FKM, BUNA, LT BUNA, EP, FVMQ).

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 8
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

4. Valve body is made of stainless steel of different configuration ported for E4 operators having the same
construction on the operator cavity. The operators may be used with aluminum manifold or brass body
having the same construction on the operator cavity.
5. Valves with “-PLR” suffix (Seal LT Buna, Compound NB800-104) may be used at -55°C to +65°C
ambient temperature range.

Ratings and Coverage: Hydraulic Valves

1. Valves with Type LV Coil (0.85W) – dc, 150 psi differential pressure.
2. Valves with Type LX Coil (1.8W) or Standard (4W) coil – ac or dc, 200 psi differential pressure.
3. Valves LV, LX and Standard (4W) are for use with #1 Oil at -15 Deg.C to +48 Deg.C ambient; or
Hydraulic Oil (AWG 46) at -15 Deg. C to +95 Deg. C ambient.
4. Valve body is made of stainless steel of different configuration ported for E4 operators having the same
construction on the operator cavity. The operators may be used with aluminum manifold having the
same construction on the operator cavity.

Nomenclature

Model E4-3198-abXc-dddd, where

a = Bottom Seat Orifice; 0, 1, 2,3,4,5,6,7,8


b = Top Seat Orifice; 0,1,2,3,4,5,6
c = Conduit Thread; S, T, U, V
d = Voltage Code; A006 to A480, D005 to D300, E006 to E480

Model E4-3198-ab-XDBc-dddd, where

a = Bottom Seat Orifice; 0, 1, 2,3,4,5,6,7,8


b = Top Seat Orifice; 0,1,2,3,4,5,6
c = Conduit Thread; S, T
d = Voltage Code; A006 to A480, D005 to D300, E006 to E480

Note: the Solenoid Operators below are certified to CSA Std. 139 and UL Std. 429 when mounted to
Pneumatic Valve bodies, Series E4SM.

Class I, Div. 1, Groups B, C, D; Class II, Div 1, Groups E, F and G; Class III:
Safety Valves-
Series E4-2198-xxXT-xxxx, E4-2198-xxXU-xxxx and E4-2198-xxXV-xxxx Solenoid Operated Valves; supply
input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60
Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil
(0.85W) – dc), see Pressure Table for MWP (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C
to +90 Deg. C, Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66;
installed per Installation Instructions INS-XR-1.

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 9
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

Series E4-2198-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85
Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts
or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil (0.85W) – dc), see Pressure Table for MWP
(LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C, Temperature Coded based on
ambient range and construction options; Type 4X and 6P; IP66; installed per Installation Instructions INS-XDB-1.

General Purpose Valves-


Series E4-xx98-xxXT-xxxx, E4-xx98-xxXU-xxxx and E4-xx98-xxXV-xxxx Solenoid Operated Valves; supply
input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60
Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil
(0.85W) – dc), see Pressure Table for MWP (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C
to +90 Deg. C, Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66;
installed per Installation Instructions INS-XR-1.

Series E4-xx98-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85
Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts
or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil (0.85W) – dc), see Pressure Table for MWP
(LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C, Temperature Coded based on
ambient range and construction options; Type 4X and 6P; IP66; installed per Installation Instructions INS-XDB-1.

AEx db IIC:
AEx tD 21 T85C, T100C, T135C, T200C:

Safety Valves-
Series E4-2198-xxXS-xxxx, E4-2198-xxXT-xxxx, E4-2198-xxXU-xxxx and E4-2198-xxXV-xxxx Solenoid
Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc,
4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see
Pressure Table for MWP (LV Coil (0.85W) – dc), see Pressure Table for MWP (LX Coil (1.8W) or Standard
(4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C, Temperature Coded based on ambient range and
construction options; Type 4X and 6P; IP66; installed per Installation Instructions INS-XR-1.

Series E4-2198-xx-XDBS-xxxx and E4-2198-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24
Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or
120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil (0.85W) – dc),

see Pressure Table for MWP (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C,
Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66; installed per
Installation Instructions INS-XDB-1.

General Purpose Valves-


Series E4-xx98-xxXS-xxxx, E4-xx98-xxXT-xxxx, E4-xx98-xxXU-xxxx and E4-xx98-xxXV-xxxx Solenoid
Operated Valves; supply input rated 24 Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc,
4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or 120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see
Pressure Table for MWP (LV Coil (0.85W) – dc), see Pressure Table for MWP (LX Coil (1.8W) or Standard

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 10
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

(4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C, Temperature Coded based on ambient range and
construction options; Type 4X and 6P; IP66; installed per Installation Instructions INS-XR-1.

Series E4-xx98-xx-XDBS-xxxx and E4-xx98-xx-XDBT-xxxx Solenoid Operated Valves; supply input rated 24
Vdc, 0.50 Watts or 24Vdc, 0.85 Watts or 24 Vdc, 1.8 Watts or 48 Vdc, 4.0 Watts or 120 Vac, 50/60 Hz, 1.8 W, or
120 Vac, 50/60 Hz, 4.0 Watts or 230 Vac, 50/60 Hz, 4.0 W; see Pressure Table for MWP (LV Coil (0.85W) – dc),
see Pressure Table for MWP (LX Coil (1.8W) or Standard (4W) – ac and dc); Tamb: –40 Deg. C to +90 Deg. C,
Temperature Coded based on ambient range and construction options; Type 4X and 6P; IP66; installed per
Installation Instructions INS-XDB-1.

Ratings and Coverage: Gas Valves

1. Valves with Type LZ Coil (0.50W) - dc, MWP of up to 120 psi depending on orifice size (Seal: FKM,
BUNA, LT BUNA, EP, FVMQ)
2. Valves with Type LV Coil (0.85W) – dc, see Pressure Table for MWP (Seal: FKM, BUNA, LT BUNA,
EP, FVMQ)
3. Valves with Type LV Coil (0.85W) – dc, MWP of up to 500 psi depending on orifice size and wattage;
(Seal: FKM, BUNA, LT BUNA, FVMQ)
4. Valves with Type LX Coil (1.8W) or Standard (4W) – ac and dc, see Pressure Table for MWP (Seal:
FKM, BUNA, LT BUNA, EP, FVMQ)
5. Valve body is made of stainless steel of different configuration ported for E4 operators having the same
construction on the operator cavity. The operators may be used with aluminum manifold or brass body
having the same construction on the operator cavity.
6. Valves with “-PLR” suffix (Seal LT Buna, Compound NB800-104) may be used at -55°C to +65°C
ambient temperature range.

Ratings and Coverage: Hydraulic Valves

1. Valves with Type LV Coil (0.85W) – dc, see Pressure Table for MWP.
2. Valves with Type LX Coil (1.8W) or Standard (4W) coil – ac or dc, see Pressure Table for MWP
3. Valves LV, LX and Standard (4W) are for use with #1 Oil at -15 Deg. C to +48 Deg. C ambient; or
Hydraulic Oil (AWG 46) at -15 Deg. C to +95 Deg. C ambient.
4. Valve body is made of stainless steel of different configuration ported for E4 operators having the same
construction on the operator cavity. The operators may be used with aluminum manifold having the same
construction on the operator cavity.

Nomenclature

Model E4-ab98-cdXe-ffff where

a = Function; 2 (2-way), 3 (3-way), 7 (7-way diverter), 8 (8 –way Multi-purpose)


b = 1 (normally closed); 2 (normally open)
c = Bottom Seat Orifice; 0, 1, 2, 3, 4, 5, 6, 7, 8
d = Top Seat Orifice; 0, 1, 2, 3, 4, 5, 6
e = Conduit Thread, S, T, U, V

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 11
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

f = Voltage Code; A006 to A480, D005 to D300, E006 to E480

Model E4-ab98-cdXDBe-ffff where

a = Function; 2 (2-way), 3 (3-way), 7 (7-way diverter), 8 (8 –way Multi-purpose)


b = 1 (normally closed); 2 (normally open)
c = Bottom Seat Orifice; 0, 1, 2, 3, 4, 5, 6, 7, 8
d = Top Seat Orifice; 0, 1, 2, 3, 4, 5, 6
e = Conduit Thread, S, T,
f = Voltage Code; A006 to A480, D005 to D300, E006 to E480

Maximum Working Pressure Table

Solenoid Power
Seat Std. LX LV LZ
Size (4.0 Watts) (1.8 Watts) (0.85 Watts) (0.5 Watts)
Function Code Bottom Top AC/DC AC/DC DC DC only
2-Way 21 2 0 500 400 250 120
Normally 3 0 400 300 150 60
Closed 4 0 200 200 80 N/A
6 0 100 100 N/A N/A
8 0 60 50 N/A N/A

2-Way 22 0 2 400 300 175 N/A


Normally Open 0 3 200 150 100 N/A
0 4 125 100 N/A N/A
0 6 75 50 N/A N/A

3-Way 31 2 2 200 200 150 120


Normally 3 3 175 175 125 60
Closed 3 4 175 175 100 N/A
4 4 150 125 75 N/A
6 4 100 75 50 N/A
6 6 75 50 25 N/A
8 4 30 N/A N/A N/A

3-Way 32 2 2 150 150 125 N/A


Normally Open 3 3 125 75 100 N/A
4 4 100 60 60 N/A
6 4 75 50 N/A N/A
6 6 50 25 N/A N/A

72 2 2 300 250 110 N/A

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 12
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

3 3 250 200 100 N/A


7-Way
4 4 175 150 80 N/A
(Diverter)
6 4 80 120 N/A N/A

8-Way (Multi- 82 2 2 150 150 125 N/A


purpose) 3 3 100 75 100 N/A
4 4 75 60 40 N/A
6 4 50 30 N/A N/A
6 6 30 20 N/A N/A

Temperature codes and ambient ranges

The ambient temperature range and temperature code tables are amended as shown in BOLD below. The tables
below show the various ambient temperature ranges for each coil material and power rating.

Ambient Ranges for X(TAB) models with F-class coils


Configuration Temperature Code
Power O-ring Material T6 T5 T4 T3
1.80 W & EPDM -40°C to +42°C -40°C to +57°C -40°C to +60°C -40°C to +60°C
0.85 W & LT Buna -40°C to +42°C -40°C to +52°C -40°C to +52°C -40°C to +52°C
0.50 W Buna -20°C to +42°C -20°C to +57°C -20°C to +60°C -20°C to +60°C
FKM -20°C to +42°C -20°C to +57°C -20°C to +87°C -20°C to +97°C
4W EPDM -40°C to +31°C -40°C to +46°C -40°C to +60°C -40°C to +60°C
LT Buna -40°C to +31°C -40°C to +46°C -40°C to +52°C -40°C to +52°C
Buna -20°C to +31°C -20°C to +46°C -20°C to +60°C -20°C to +60°C
FKM -20°C to +31°C -20°C to +46°C -20°C to +60°C -20°C to +60°C

Ambient Ranges for X(TAB) models with H-class coils


Configuration Temperature Code
Power O-ring Material T6 T5 T4 T3
1.80 W & EPDM -55°C to +42°C -55°C to +57°C -55°C to +60°C -55°C to +60°C
0.85 W & LT Buna -40°C to +42°C -40°C to +52°C -40°C to +52°C -40°C to +52°C
0.50 W Buna -20°C to +42°C -20°C to +57°C -20°C to +60°C -20°C to +60°C
FKM -20°C to +42°C -20°C to +57°C -20°C to +87°C -20°C to +105°C
4W EPDM -55°C to +31°C -55°C to +46°C -55°C to +60°C -55°C to +60°C
LT Buna -40°C to +31°C -40°C to +46°C -40°C to +52°C -40°C to +52°C
Buna -20°C to +31°C -20°C to +46°C -20°C to +60°C -20°C to +60°C
FKM -20°C to +31°C -20°C to +46°C -20°C to +76°C -20°C to +105°C

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 13
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

Ambient Ranges for XDB(TAB) models with F-class coils


Configuration Temperature Code
Power O-ring Material T6 T5 T4 T3
1.80 W & EPDM -40°C to +55°C -40°C to +70°C -40°C to +80°C -40°C to +90°C
0.85 W & LT Buna -40°C to +55°C -40°C to +60°C -40°C to +60°C -40°C to +60°C
0.50 W Buna -20°C to +55°C -20°C to +70°C -20°C to +80°C -20°C to +90°C
FKM -20°C to +55°C -20°C to +70°C -20°C to +90°C -20°C to +90°C
4W EPDM -40°C to +42°C -40°C to +57°C -40°C to +60°C -40°C to +60°C
LT Buna -40°C to +42°C -40°C to +46°C -40°C to +52°C -40°C to +52°C
Buna -20°C to +42°C -20°C to +56°C -20°C to +56°C -20°C to +56°C
FKM -20°C to +42°C -20°C to +57°C -20°C to +80°C -20°C to +80°C

Ambient Ranges for XDB(TAB) models with H-class coils


Configuration Temperature Code
Power O-ring Material T6 T5 T4 T3
1.80 W & EPDM -55°C to +55°C -55°C to +70°C -55°C to +80°C -55°C to +90°C
0.85 W & LT Buna -40°C to +55°C -40°C to +60°C -40°C to +60°C -40°C to +60°C
0.50 W Buna -20°C to +55°C -20°C to +70°C -20°C to +80°C -20°C to +90°C
FKM -20°C to +55°C -20°C to +70°C -20°C to +90°C -20°C to +90°C
4W EPDM -55°C to +42°C -55°C to +57°C -55°C to +60°C -55°C to +60°C
LT Buna -40°C to +42°C -40°C to +56°C -40°C to +56°C -40°C to +56°C
Buna -20°C to +42°C -20°C to +57°C -20°C to +60°C -20°C to +60°C
FKM -20°C to +42°C -20°C to +57°C -20°C to +87°C -20°C to +90°C

APPLICABLE REQUIREMENTS

CAN/CSA-C22.2 No. 0-M91 - General Requirements – Canadian Electrical Code, Part II


C22.2 No. 25-1966 - Enclosures for Use in Class II, Groups E, F and G Hazardous
Locations
C22.2 No. 30-M1986 - Explosion-Proof Enclosures for Use in Class I Hazardous Locations
CAN/CSA-C22.2 No. 94-M91 - Special Purpose Enclosures
C22.2 No. 139-1982 - Electrically Operated Valves
C22.2 No. 213-16 - Nonincendive electrical equipment for use in Class I and II, Division 2
and Class, Divisions 1 and 2 hazardous (classified) locations
CAN/CSA-C22.2 No. 60079-0:07 - Electrical apparatus for explosive gas atmospheres - Part 0: General
requirements
CAN/CSA-C22.2 No. 60079-1:16 - Electrical apparatus for explosive gas atmospheres - Part 1:
Flameproof enclosures "d"
CAN/CSA-C22.2 No. 60529:05 - Degrees of protection provided by enclosures (IP Code)
CAN/CSA-E61241-1-1:02 - Electrical apparatus for use in the presence of combustible dust – Part
1-1: Electrical Apparatus protected by enclosures and surface
temperature limitation – Specification for apparatus

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 14
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

UL 50 (11th Ed.) - Enclosures for Electrical Equipment


UL 429 (5th Ed.) - Electrically Operated Valves
UL 1203 (4th Ed.) - Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use
in Hazardous (Classified) Locations
ANSI/ISA -12.12.01-2015 - Nonincendive electrical equipment for use in Class I and II, Division 2
and Class, Divisions 1 and 2 hazardous (classified) locations
ANSI/UL 60079-0:05 - Electrical Apparatus for Explosive Gas Atmospheres - Part 0: General
Requirements
ANSI/UL 60079-1:15 - Electrical Apparatus for Explosive Gas Atmospheres - Part 1:
Flameproof Enclosures “d”
ANSI/IEC 60529:2004 - Degrees of Protection Provided by Enclosures (IP Code)
ANSI/ISA-61241-0 (12.10.02)- - Electrical Apparatus for Use in Zone 20, Zone 21 and Zone 22
2006 Hazardous (Classified) Locations – General Requirements
ISA-61241-1 (12.10.03)-2006 - Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous
(Classified) Locations – Protection by Enclosures “tD”

MARKINGS

The manufacturer is required to apply the following markings:


• Products shall be marked with the markings specified by the particular product standard.
• Products certified for Canada shall have all Caution and Warning markings in both English and French.

Additional bilingual markings not covered by the product standard(s) may be required by the Authorities Having
Jurisdiction. It is the responsibility of the manufacturer to provide and apply these additional markings, where
applicable, in accordance with the requirements of those authorities.

The products listed are eligible to bear the CSA Mark shown with adjacent indicators 'C' and 'US' for Canada and
US (indicating that products have been manufactured to the requirements of both Canadian and U.S. Standards) or
with adjacent indicator 'US' for US only or without either indicator for Canada only.

Nameplate adhesive label material approval information:

Markings are etched or engraved onto a minimum 0.02 inch thick metal nameplate, which is mechanically secured
to the enclosure cover clips. Refer to Drawings E4-110-XS-SF, E4-110-XT-SF and E4-110-XV-SF (Model X
Series) and to Drawings E4-110-XDBS and E4-110-XDBT (Model XDB Series),

The following marking details appear:

- CSA Monogram with C US Indicator;


- Company name;
- Model number;
- Serial number or Date Code

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 15
Certificate: 0002203795 Master Contract: 154085
Project: 80030993 Date Issued: 2020-05-26

- Certificate reference (“CSA 2009 2203795”)


- Hazardous Location designation: “Class I, Div. 1, Groups B, C, D Tx; Class II, Div. 1, Groups E, F, G;
Class III”; “Class I, Zone 1 A/Ex db IIC Tx”, “DIP A21 TxxC” and “Class II, Zone 21 AEx tD 21 TxxC”
(Additionally for model Series E4-3198-xx-XDBT-xxxx the following marking must appear on the label
“Class I, Div. 2, Groups A – D” for model Series E4-3198-xx-LV-NI-XDBT-303D-D024 the following
must appear on the marking label “N.I. Cl. I, Div. 2 per dwg INS-XDB-2 REV A (11-16).
- Ambient Temperature
- The statement: “Conduit seal is required within 2 inches of conduit entry” (appears on referenced
Installation Drawing).
- The statement: “WARNING – Do not open while energized” (appears on referenced Installation
Drawing)
- The statement: “WARNING – Check nameplate for correct voltage and classification” (appears on
referenced Installation Drawing)
- Statement re. use of proper conduit thread lubricant (appears on referenced Installation Drawing).
- Statement re. use of proper crimping tool for internal ground wire termination (appears on referenced
Installation Drawing).

Note - Jurisdictions in Canada may require these markings to also be provided in French language. It is the responsibility of
the manufacturer to provide bilingual marking, where applicable, in accordance with the requirements of the Provincial
Regulatory Authorities. It is the responsibility of the manufacturer to determine this requirement and have bilingual wording
added to the "Markings".

ALTERATIONS

Markings as above.

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.
Page 16
Supplement to Certificate of Compliance

Certificate: 0002203795 Master Contract: 154085

The products listed, including the latest revision described below,


are eligible to be marked in accordance with the referenced Certificate.

Product Certification History

Project Date Description

80030993 2020-05-26 Update to Certificate 2203795 to introduce a lower temperature version of


the valve (-55°C to 65°C temperature range).

000070173123 2018-12-03 Updating the existing CSA N.A. report 2203795 for Change of material on
the sleeves on solenoids model E4 (XDB and XV).

000070106720 2016-11-25 Update to cover part no. correction to E4-3198-xx-LV-NI-XDBT-303D-


D024

000070085370 2016-09-29 CSA c-us certification of solenoid operated valve, series E4-3198-xx-
XDBT, for use in Cl. I, Div. 2 and as non incendive for use in Cl. I, DIv. 2.

000070073114 2016-07-29 Addition of alternate seals to Certificate 2203795 (one new size and three
different compounds and one additional compound to the existing size listed
in the file)

000070023102 2015-09-14 Variation to CSA 2203795 As an alternative to the existing Varistor, add
diodes P-1005-70D-1 and P-1005-70T-TAB as an option.

0002663982 2013-12-06 Update to report 2203795 to include half watt version of actuator, and to
update report to include minor corrections and updating drawings to latest
revision.

0002447513 2011-10-07 Update to cover addition of IP x8 rating; evaluation/testing of additional


solenoid oriface & function;and increase in pressure rating (MWP) of the
LV (0.85W) versions of the Hydraulic valves from 115 psi to 150 psi.

0002356448 2011-01-07 Update of report 2203795 to cover increase to process pressure for 0.85
Watt LV option; evaluation of alternative enclosure surface for Corrosion
protection.

0002203795 2010-03-29 Series E4-3198-xxXS-xxxx, E4-3198-xxXT-xxxx, E4-3198-xxXU-xxxx,


E4-3198-xxXV, E4-3198-xx-XDBS-xxxx and E4-3198-xx-XDBT-xxxx
Solenoid Operated Valves for hazardous locations.

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 17
000070023102 2010-03-20 Variation to CSA 2203795 As an alternative to the existing Varistor, add
diodes P-1005-70D-1 and P-1005-70T-TAB as an option.

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved.

Page 18
Page 19
Page 20
Page 21
IECEx Certificate
of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

Certificate No.: IECEx CML 16.0035X Issue No: 1 Certificate history:


Issue No. 1 (2019-02-25)
Status: Current Issue No. 0 (2016-06-03)
Page 1 of 4
Date of Issue: 2019-02-25

Applicant: Thompson Valves


17 Balena Close
Creekmoor
Poole
Dorset
BH17 7EF
United Kingdom

Equipment: ICO3 Solenoid Valves


Optional accessory:

Type of Protection: Intrinsic safety

Marking:
Ex ia IIC T6/T4 Ga or Ex ib IIC T6/T4 Gb
Ex iaD IIIC T180°C Da or Ex ibD IIIC T180°C Db
Up to -60°C to +69°C (dependant on T classification, ambient temperature and seals fitted)
See description in annex for specific marking details

Approved for issue on behalf of the IECEx H M Amos MIET


Certification Body:

Position: Certification Manager

Signature:
(for printed version)

Date:
February 25, 2019

1. This certificate and schedule may only be reproduced in full.


2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.

Certificate issued by:


Certification Management Limited
Unit 1, Newport Business Park
New Port Road
Ellesmere Port, CH65 4LZ
United Kingdom

Page 22
IECEx Certificate
of Conformity
Certificate No: IECEx CML 16.0035X Issue No: 1

Date of Issue: 2019-02-25


Page 2 of 4

Manufacturer: Thompson Valves


17 Balena Close
Creekmoor
Poole
Dorset
BH17 7EF
United Kingdom

Additional Manufacturing location(s):

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended.

STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply
with the following standards:

IEC 60079-0 : 2011 Explosive atmospheres - Part 0: General requirements


Edition:6.0
IEC 60079-11 : 2011 Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
Edition:6.0

This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the

Standards listed above.

TEST & ASSESSMENT REPORTS:


A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

Test Report:

GB/CML/ExTR16.0052/00

Quality Assessment Report:

GB/CML/QAR19.0002/00

Page 23
IECEx Certificate
of Conformity
Certificate No: IECEx CML 16.0035X Issue No: 1

Date of Issue: 2019-02-25


Page 3 of 4

Schedule

EQUIPMENT:
Equipment and systems covered by this certificate are as follows:

The ICO3 Intrinsically Safe Solenoid Valve is an electrically operated control valve consisting of a solenoid which operates a
poppet valve connected to the solenoid enclosure.

See Annex for full description and Conditions of Manufacture

SPECIFIC CONDITIONS OF USE: YES as shown below:

See Annex for Conditions of Certification

Page 24
IECEx Certificate
of Conformity
Certificate No: IECEx CML 16.0035X Issue No: 1

Date of Issue: 2019-02-25


Page 4 of 4

DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):

Issue 1

This Issue introduced the following changes:

1. To update QAR reference only

Annex:

Certificate Annex IECEx CML 16.0035X Issue 1.pdf

Page 25
Annexe to: IECEx CML 16.0035X Issue 1
Applicant: Thompson Valves Ltd
Apparatus: ICO3 Solenoid Valves

Description of equipment

The ICO3 Intrinsically Safe Solenoid Valve is an electrically operated control valve consisting of a
solenoid which operates a poppet valve connected to the solenoid enclosure.

The solenoid consists of a cast stainless steel cylindrical enclosure (solenoid pot) and a top
threaded cover. The top cover provides access to the terminal compartment and is fitted with an O-
ring interface seal. The solenoid pot housing has a perpendicular raised flat boss moulded onto the
side, which has an external earth connection point and a threaded conduit entry point. The solenoid
enclosure contains an encapsulated circuit and an intrinsically safe solenoid cartridge consisting of
a magnetic steel case which houses a coil encapsulated with epoxy resin.

Intrinsic safety is achieved by adequately rated diodes that suppress the inductance of the coil,
segregation, encapsulation and the connection integrity of the solenoid/diode assembly.

The valve operates using electromagnetic force in the solenoid coil to actuate an armature which
passes through the solenoid pot base; both these are manufactured from magnetic steel. The
armature then operates the valve, therefore, controlling the flow of media through the valve.

Safety Description

Ui = 28V Li = 0
Ii = 300mA Ci = 0
Pi = 1.3W
Marking

Ex ia IIC T4/T6 Ga or Ex ib IIC T4/T6 Gb and Ex iaD IIIC T180°C Da or Ex ibD IIIC T180°C Db
Ta -60°C to 69°C (T4) Ta -60°C to 69°C
Ta -60°C to 50°C (T6)

Conditions of Manufacture
i. Where the product incorporates certified parts or safety critical components the
manufacturer shall ensure that any changes to those parts or components do not affect
the compliance of the certified product that is the subject of this certificate.
ii. The equipment shall be capable of withstanding an electric strength test using a test
voltage of 500 Vac applied between the circuit and earth for 60 s. Alternatively, a voltage
of 20% higher may be applied for 1 s. There shall be no evidence of flashover or
breakdown and the maximum current flowing shall not exceed 5 mA.

Conditions of Certification
i. The ICO3 solenoid valves shall only be installed in accordance with IEC 60079-14 and the
manufacturer’s instructions.

1 of 1

Page 26
CERTIFICATE OF COMPLIANCE
Certificate Number E125326
Report Reference E125326-20000121
Issue Date 2020-JANUARY-31

Issued to: TOPWORX INC


3300 FERN VALLEY RD
LOUISVILLE, KY 40213-3528 USA

This certificate confirms that TELEMETERING EQUIPMENT FOR USE IN HAZARDOUS


representative samples of LOCATIONS
(See Addendum for Additional Information.)

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL 913, Intrinsically Safe Apparatus and Associated


Apparatus for Use in Class I, II, and III, Division 1,
Hazardous (Classified) Locations
UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical
Equipment for Use in Hazardous (Classified) Locations.
CSA-C22.2 No. 14, Industrial Control Equipment.
CSA-C22.2 No. 30, Explosion-Proof Enclosures for Use in
Class I Hazardous Locations.
CAN/CSA C22.2 No. 157-92, Intrinsically Safe and Non-
Incendive Equipment for Use in Hazardous Locations
Additional Information: See the UL Online Certifications Directory at
https://iq.ulprospector.com for additional information.

This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.

Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 4

Page 27
CERTIFICATE OF COMPLIANCE
Certificate Number E125326
Report Reference E125326-20000121
Issue Date 2020-JANUARY-31

This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.

Addendum -

Models:

USL, CNL - Class I, Division 1, Groups A, B, C and D Hazardous Locations (Intrinsically Safe).

Valve Monitor/Indicator - Model DXS/DXP- followed by F, B, C, or J, followed by 1, 2, 3 4, or X


followed by 0, followed by letter or number, followed by S, N, 1, 2, M or R, followed by any number or
letter, followed by B, V, E, or S, followed by Blank, 1, 2, 3, 4, 5 or 6, followed by Blank, A, S, 6, B or R,
followed by Blank or any number or letter, followed by Blank or any number or letter. Model Ex, Fx, Bx,
Cx or Jx, intrinsically safe when connected in accordance with Topworx installation wiring diagram,
Drawing Nos. S-K136, or ES-03847-1.

Valve Monitor/Indicator - Model DXS/DXP- followed by L, followed by 1 2, or X, followed by 0, followed


by letter or number, followed by S, N, 1 2, M or R, followed by any number or letter, followed by B, V, E,
or S, followed by Blank, 1, 2, 3, 4, 5 or 6, followed by Blank, A, S, 6, B or R, followed by Blank or any
number or letter, followed by Blank or any number or letter. Model Lx, intrinsically safe when connected
in accordance with Topworx installation wiring diagram, Drawing Nos. S-K127 and S-K127A.

Valve Monitor/Indicator – Model DXP/DXS – followed by L, followed by 3 or 4, followed by 0, followed


by any number or letter, followed by S, N, 1, 2, M or R, followed by any number or letter, followed by B,
V, E or S, followed by Blank, 1, 2, 3, 4, 5, 6, 7, 8 or 9, followed by Blank, A, S, 6, B, R, followed by
Blank or any number or letter, followed by Blank or any number or letter. Model Lx, intrinsically safe
when connected in accordance with TopWorx installation wiring diagram, Drawing No. ES-01416-1.

Valve Monitor/Indicator – Model DXP/DXS – followed by 3 or V, followed by 1, 2, 3, 4, or X, followed by


0, followed by any number or letter, followed by S, N, 1, 2, M or R, followed by any number or letter,
followed by B, V, E or S, followed by Blank, 1, 2, 3, 4, 5 or 6, followed by Blank, A, S, 6, B, R, followed
by Blank or any number or letter, followed by Blank or any number or letter. Model Lx, intrinsically safe
when connected in accordance with TopWorx installation wiring diagram, Drawing No. ES-01410-1.

Valve Monitor/Indicator – Model DXP/DXS – followed by M or K, followed by 1, 2, or X, followed by 0,


followed by any number or letter, followed by S, N, 1, 2, M or R, followed by any number or letter,
followed by B, V, E or S, followed by Blank, 1, 2, 3, 4, 5 or 6, followed by Blank, A, S, 6, B, R, followed
by Blank or any number or letter, followed by Blank or any number or letter. Model Mx or Kx,
intrinsically safe when connected in accordance with TopWorx installation wiring diagram, Drawing No.
ES-01413-1.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 2 of 4
Page 28
CERTIFICATE OF COMPLIANCE
Certificate Number E125326
Report Reference E125326-20000121
Issue Date 2020-JANUARY-31

Valve Monitor/Indicator – Model DXP/DXS – followed by M or K, followed by 3, 4, 5 or 6, followed by 0,


followed by any number or letter, followed by S, N, 1, 2, M or R, followed by any number or letter,
followed by B, V, E or S, followed by Blank, 1, 2, 3, 4, 5 or 6, followed by Blank, A, S, 6, B, R, followed
by Blank or any number or letter, followed by Blank or any number or letter. Model Mx or Kx,
intrinsically safe when connected in accordance with TopWorx installation wiring diagram, Drawing No.
ES-01414-1.

Valve Monitor/Indicator – Model DXP/DXS – followed by T, followed by 2 or X, followed by 0, followed


by any number or letter, followed by S, N, 1, 2, M or R, followed by any number or letter, followed by B,
V, E or S, followed by Blank, 1, 2, 3, 4, 5 or 6, followed by Blank, A, S, 6, B, R, followed by Blank or any
number or letter, followed by Blank or any number or letter. Model Tx, intrinsically safe when connected
in accordance with TopWorx installation wiring diagram, Drawing No. ES-01417-1.

Valve Monitor/Indicator – Model DXP/DXS – followed by 8, followed by 1, 2, 3, 4, or X, followed by 0,


followed by any number or letter, followed by S, N, 1, 2, M or R, followed by any number or letter,
followed by B, V, E or S, followed by Blank, 1, 2, 3, 4, 5 or 6, followed by Blank, A, S, 6, B, R, followed
by Blank or any number or letter, followed by Blank or any number or letter. Model 8x, intrinsically safe
when connected in accordance with TopWorx installation wiring diagram, Drawing No. ES-01418-1.

Valve Monitor/Indicator - Model DXS/DXP- followed by Z, followed by 1, 2, 3 4, or X, followed by 0,


followed by letter or number, followed by S, N, 1, 2, M or R, followed by any number or letter, followed
by B, V, E, or S, followed by Blank, 1, 2, 3, 4, 5 or 6, followed by Blank, A, S, 6, B, R, 1, 2, 4, 5 or 7,
followed by Blank or any numbers or letters, followed by Blank or any number or letter. Model Zx,
intrinsically safe when connected in accordance with Topworx installation wiring diagram, Drawing Nos.
ES-01743-1 and ES-01744-1.

Valve Monitor/Indicator - Model DXS/DXP- followed by R, followed by 2 or 4, followed by 0, followed by


letter or number, followed by S, N, 1, 2, M or R, followed by any number or letter, followed by B, V, E, or
S, followed by Blank, 1, 2, 3, 4, 5 or 6, followed by Blank, A, S, 6, B or R, followed by Blank or any
number or letter, followed by Blank or any number or letter. Intrinsically safe when connected in
accordance with Topworx installation wiring diagram, Drawing Nos. S-K087 and S-K087A and ES-
01735-1.

Valve Monitor/Indicator - Model DXS/DXP - followed by E or 0, followed by 1, 2, 3, 4, X or H, followed


by 0, followed by any letter or number, followed by S, N, 1, 2, M, or R, followed by any number or letter,
followed by B, V, E, or S, followed by Blank, 1, 2, 3, 4, 5, or 6, followed by Blank, A, S, 6, B, or R,
followed by Blank or any number or letter, followed by Blank or any number or letter except T and U,
followed by blank or any number or letter. model Ex, intrinsically safe when connected in accordance
with Topworx installation wiring diagram, Drawing Nos. S-K136, ES-03847-,1, ES-06502-1, and ES-
06505-1.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 3 of 4
Page 29
CERTIFICATE OF COMPLIANCE
Certificate Number E125326
Report Reference E125326-20000121
Issue Date 2020-JANUARY-31

Valve Monitor/Indicator – Model DXP/DXS – followed by 0H, HK, , HL, or HM, followed by 0, followed
by any number or letter, followed by S, N, 1, 2, M or R, followed by any number or letter, followed by B,
V, E or S, followed by Blank, 1, 2, 3, 4, 5 or 6, followed by Blank, A, S, 6, B, R, followed by Blank or any
number or letter, followed by Blank or any number or letter. Model Mx or Kx, intrinsically safe when
connected in accordance with TopWorx installation wiring diagram, Drawing No. ES-06502-1.

Valve Monitor/Indicator – Model DXP/DXS – followed by K, L or M, followed by H, followed by 0,


followed by any number or letter, followed by S, N, 1, 2, M or R, followed by any number or letter,
followed by B, V, E or S, followed by Blank, 1, 2, 3, 4, 5 or 6, followed by Blank, A, S, 6, B, R, followed
by Blank or any number or letter, followed by Blank or any number or letter. Model Mx or Kx,
intrinsically safe when connected in accordance with TopWorx installation wiring diagram, Drawing No.
ES-06855-1.

USL, CNL -Class I, Division 1, Groups C and D Hazardous Locations (Explosion-Proof)

Valve Monitor/Indicator - Model DXS/DXP - followed by 0, M, E, T, K, 4, 5 or V; followed by 1, 2, 3, 4, 5,


6, A, C, B, D or X or H, followed by 1, followed by a letter or number, followed by S, N, 1, 2, M or R,
followed by any number or letter, followed by B, V, E, or S, followed by Blank, 1, 2, 3, 7, 8 or 9, followed
by Blank, A, S, 6, B or R, followed by Blank or any number or letter, followed by Blank or any number or
letter, may be followed by any four letters or numbers.

USL, CNL -Class I, Division 1, Groups C and D; Class I, Division 2, Groups A, B, C or D; and Class II,
Division 2, Groups F and G Hazardous Locations.

Valve Monitor/Indicator - Model DXS/DXP - followed by 0, E, L, R, P, Z, 4, 5, 7 or V, followed by 1, 2, 3,


4, 5, 6, N, S, X or H, followed by 1 or 2, followed by a letter or number, followed by S, N, 1, 2, M or R
followed by any number or letter, followed by B, V, E, or S, followed by Blank, 1, 2, 3, 7, 8 or 9, followed
by Blank, A, S, 6, B or R, followed by Blank or any number or letter, followed by Blank or any number or
letter.

USL, CNL -Class I, Division 2, Groups A, B, C and D; Class II, Division 2, F and G Hazardous
Locations.

Valve Monitor/Indicator - Model DXR - followed by 0, L, R, P, 7, E, F, B, C, J, V, N Z, 4 or 5; followed by


0, 1, 2, 3, 4, 5, 6, N, S, X, or H, followed by 2, followed by a letter or number, followed by S, N, 1,2, M,
or, R followed by any letter or number, followed by S or E, followed by Blank, 1, 2, 3, 4, 5, 6, 7, 8 or 9,
followed by Blank, A, S, or 6, followed by Blank or any number or letter, followed by Blank or any
number or letter, followed by N004

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 4 of 4
Page 30
1 EU-TYPE EXAMINATION CERTIFICATE
2 Equipment intended for use in Potentially Explosive Atmospheres Directive 2014/34/EU
3 Certificate Number: Sira 07ATEX1273X Issue: 15
4 Equipment: Type DXP and Type DXS Switchboxes
5 Applicant: Topworx Inc.
6 Address: 3300 Fern Valley Road, Louisville, Kentucky 40213, USA
7 This equipment and any acceptable variation thereto is specified in the schedule to this certificate and
the documents therein referred to.
8 CSA Group Netherlands B.V., notified body number 2813 in accordance with Articles 17 and 21 of
Directive 2014/34/EU of the European Parliament and of the Council, dated 26 February 2014, certifies
that this equipment has been found to comply with the Essential Health and Safety Requirements relating
to the design and construction of equipment intended for use in potentially explosive atmospheres given
in Annex II to the Directive.
The examination and test results are recorded in the confidential reports listed in Section 14.2.
9 Compliance with the Essential Health and Safety Requirements, with the exception of those listed in the
schedule to this certificate, has been assured by compliance with the following documents:
EN IEC 60079-0:2018 incl. A/C:2020 EN IEC 60079-1:2014 incl. AC:2018 EN 60079-31:2014
10 If the sign ‘X’ is placed after the certificate number, it indicates that the equipment is subject to Specific
Conditions of Use identified in the schedule to this certificate.
11 This EU-Type Examination Certificate relates only to the design and construction of the specified
equipment. If applicable, further requirements of this Directive apply to the manufacture and supply of
this equipment.
12 The marking of the equipment shall include the following:

II 2GD
Marking for Group IIC/IIB+H2 Marking for Group IIIC
Ex db IIC T6 Gb or Ex db IIB+H2 T6 Gb Ex tb IIIC T85°C Db
Ta = -60°C to +60°C Ta = -50°C to +60°C
Ex db IIC T5 Gb or Ex db IIB+H2 T5 Gb Ex tb IIIC T100°C Db
Ta = -60°C to +75°C Ta = -50°C to +75°C
Ex db IIC T4 Gb or Ex db IIB+H2 T4 Gb Ex tb IIIC T135°C Db
Ta = -60°C to +110°C Ta = -50°C to +110°C
Ex db IIC T3 Gb or Ex db IIB+H2 T3 Gb
Ta = -60°C to +175°C

Signed: M Halliwell

Title: Director of Operations

Project Number 80147060


This certificate and its schedules may only be reproduced in its entirety and without change
CSA Group Netherlands B.V. Utrechtseweg 310, Building B42, 6812AR Arnhem, The Netherlands
DQD 544.09 Issue Date: 2022-04-14 Page 1 of 6

Page 31
SCHEDULE

EU-TYPE EXAMINATION CERTIFICATE Sira 07ATEX1273X


Issue 15

13 DESCRIPTION OF EQUIPMENT
The Type DXP switchbox comprises a rectangular base and cover manufactured in aluminium. The base
and cover has a boss with a bronze sleeve bearing, through which passes the switch shaft. Cams with
magnets are attached to the shaft to operate sensors within the enclosure. The enclosure is provided
with either a flat flange joint or a serrated joint for gas group IIB + H 2 or group IIC applications
respectively. The cover securing bolts are Grade A2-70 stainless steel.
The rectangular base and cover can be manufactured from stainless steel to form a Type DXS Switchbox;
and the sleeve bearing is not provided.
The enclosure may contain a combination of switches, a fieldbus module, pilots and terminal strips up to
the maximum thermal dissipation of 10 W. The pilots provide feedback to control a pneumatic valve
attached to the side of the enclosure.
The switch box is rated up to 240 V, 15 A.
The enclosure fasteners are stainless steel M8x1.25 – 6H, reduced shank A2-70 grade fasteners.
When marked for dust, the enclosures have an IP66/IP67 rating.
Variation 1 - This variation introduced the following changes:
i. To permit the use within a combustible dust laden atmospheres in accordance with the requirements
of IEC 60079-0:2007 and IEC 61241-1:2004.
Variation 2 - This variation introduced the following changes:
i. The recognition of minor drawing modifications; these amendments, which are fully described in
the associated Sira report, are administrative or involve changes to the design that do not affect the
aspects of the product that are relevant to explosion safety.
ii. The external valve block pressure was increased, the special condition for safe use being modified
accordingly.
Variation 3 - This variation introduced the following changes:
i. To permit the metal enclosures to be given an IP67/66 ingress protection rating. The marking in
Section 12 was amended accordingly.
ii. Following appropriate re-assessment, IEC 61241-1:2004 was replaced by EN 60079-31:2009.
Variation 4 - This variation introduced the following changes:
i. The introduction of an alternative internal arrangement which is designated the Type FF 2.0 Module.
ii. Minor drawing modifications were recognised.
Variation 5 - This variation introduced the following changes:
i. The equipment was permitted to be used in an ambient temperature up to 175°C, the marking is
amended accordingly and a Special condition for safe use was added to reflect the change.

Project Number 80147060


This certificate and its schedules may only be reproduced in its entirety and without change
CSA Group Netherlands B.V. Utrechtseweg 310, Building B42, 6812AR Arnhem, The Netherlands
DQD 544.09 Issue Date: 2022-04-14 Page 2 of 6

Page 32
SCHEDULE

EU-TYPE EXAMINATION CERTIFICATE Sira 07ATEX1273X


Issue 15

Variation 6 - This variation introduced the following changes:


i. Following appropriate assessment, EN 60079-0:2006 was replaced with EN 60079-0: 2012, the
marking in Section 12 was amended accordingly.
ii. The ambient temperature range has been extended to -60°C for category 2G only.
iii. The requirement for routine overpressure testing has been removed for enclosures suitable for
a -50°C ambient temperature limit, in addition, a routine overpressure testing requirement for
enclosures suitable for -60°C was added.
iv. The DXP can be fitted with the following switch types:
SPDT - 250 V ac at 1.5 A NO Proximity - 250 V ac at 0.2A
SPDT - 250 V ac at 0.5 A NO Proximity - 60 V dc at 0.2 A
DPDTh - 110 V ac at 6 A NC Proximity - 8 V dc at 3 mA
PNP Proximity - 30 V dc at 0.2 A
Variation 7 - This variation introduced the following change:
i. The removal of routine overpressure testing on model variants with stainless steel housings was
endorsed.
ii. Clarification of the special fastener head, on drawing numbers ES-00238-1, was approved.
iii. The recognition of minor drawing modifications; the leading edge of the bushing from 0.5 mm x 30°
to 1.0 mm x 10° to aid assembly, these amendments are administrative or involve changes to the
design that do not affect the aspects of the product that are relevant to explosion safety.
Variation 8 - This variation introduced the following change:
i. The introduction of two additional manufacturing locations:
Emerson Machinery Equipment (Shenzhen) Co. Ltd. Emerson Process Management Magyarorszag Kft.
Fisher Controls Division Fisher Controls International LLC
Bao Heng Technology Industry Park H-8001 Székesfehérveár
North Hong Long 2nd Road Berenyi U
District 68 Bao’an District Shenzhen 518101, China 72-100, Hungary
Variation 9 - This variation introduced the following change:
i. The introduction of an advanced HART protocol module variant, HART v7 Model ES-04900-1, to be
used in various HART module assemblies.
ii. Following appropriate assessment to demonstrate compliance with the latest technical knowledge;
EN 60079-0:2012, EN 60079-1:2007 and EN 60079-31:2009 were replaced by
EN 60079-0:2012/A11:2013, EN 60079-1:2014, and EN 60079-31:2014. The markings and
specific conditions of use are updated according to recognise the latest standards.
iii. Numerous drawing changes have been made.
a. Drawing updates to the following scheduled drawings:
i. ES-00238-1 revision 12 to 15;
ii. S-S01-0006 revision 2 to 4;
iii. S-S01-0008 revision 18 to 23;
iv. Drawing ES-01141-1 at revision 9 has been replaced rev 12 to include the HART v7
Module ES-04900-1, and updates to the other module assemblies it can be used in;
Project Number 80147060
This certificate and its schedules may only be reproduced in its entirety and without change
CSA Group Netherlands B.V. Utrechtseweg 310, Building B42, 6812AR Arnhem, The Netherlands
DQD 544.09 Issue Date: 2022-04-14 Page 3 of 6

Page 33
SCHEDULE

EU-TYPE EXAMINATION CERTIFICATE Sira 07ATEX1273X


Issue 15

v. The following nameplate drawings have been updated to include revised markings that are
required by the standards upgrade: CERT-ES-01148-1; CERT-ES-01149-1; CERT-ES-
03278-1; CERT-ES-03279-1; and CERT-ES-03288-1.
vi. The following nameplate drawings have become obsolete and removed from the list of
scheduled drawings: CERT-ES-03440-1; CERT-ES-03442-1; CERT-ES-03443-1; and CERT-
ES-03444-1.
vii. Drawing S-S01-0007 rev 25 to rev 27 has been updated for various minor changes,
detailed in the assessment report.
viii. Drawing S-S01-0012 rev 22 to rev27 has been updated for various minor changes,
detailed in the assessment report.
Variation 10 - This variation introduced the following change:
i. The change of manufacturing location;
From: To:
Emerson Process Management ASCO Numatics Sp.z o.o.
Magyarorszag Kft. Kurczaki 132
Fisher Controls International LLC, 93 331 Lodz
H-8001 Székesfehérveár, Poland
Berenyi U, 72-100,
Hungary
Variation 11 - This variation introduced the following change:
i. The change to the name of the facility in Poland was recognised;
From: To:
ASCO Numatics Sp. z o.o. Emerson Automation Fluid Control & Pneumatics Poland Sp. z o.o.
Variation 12 - This variation introduced the following change:
i. Addition of an alternative hall effect sensor connected to HART v7, Model ES-04900-1 module
certified under IECEx SIR 16.0107U and Sira 16ATEX2342U.
Variation 13 - This variation introduced the following changes:
i. Addition of an alternate construction of the external indicator.
ii. Manufacturer address change for Shenzhen location
Variation 14 - This variation introduced the following changes:
i. After appropriate assessment, the listed standard for Issue 13 were updated to the latest issues.
EN 60079-0:2012/A11:2013 was updated to IEC EN 60079-0:2018 incl. A/C:2020, EN 60079-
1:2014 was updated to EN 60079-1:2014 incl. AC:2018, EN 60079-31:2014 remains unchanged.
ii. References to factory locations were removed from the certificate, leaving the applicants name
and address only.
Variation 15 - This variation introduced the following changes:
i. Revision to manufacturer drawings. These amendments are administrative or involve changes to the
design that do not affect the aspects of the product that are relevant to explosion safety.
Project Number 80147060
This certificate and its schedules may only be reproduced in its entirety and without change
CSA Group Netherlands B.V. Utrechtseweg 310, Building B42, 6812AR Arnhem, The Netherlands
DQD 544.09 Issue Date: 2022-04-14 Page 4 of 6

Page 34
SCHEDULE

EU-TYPE EXAMINATION CERTIFICATE Sira 07ATEX1273X


Issue 15

ii. Modification to stopping plugs PS-00177-1 to PS-00177-7. Introduction of new stopping plug, PS-
00177-8.
14 DESCRIPTIVE DOCUMENTS
14.1 Drawings
Refer to Certificate Annexe.
14.2 Associated Reports and Certificate History
Issue Date Report number Comment
0 10 April 2008 R51A15997A The release of the prime certificate.
1 21 May 2009 R51L18967A The introduction of Variation 1.
2 25 November 2011 R25807A/00 The introduction of Variation 2.
3 23 March 2012 R25461A/00 The introduction of Variation 3 (report R25461A/00)
R25661A/00 and Variation 4 (report R25661A/00).
4 01 August 2012 R25661B/00 The introduction of Variation 5.
5 11 December 2012 R21191A/00 The introduction of Variation 6.
R28146A/00
6 02 December 2013 R30951A/00 The introduction of Variation 7.
7 07 May 2014 R70005505A The introduction of Variation 8.
8 12 June 2018 R70095234A This Issue covers the following changes:
• EC Type-Examination Certificate in accordance
with 94/9/EC updated to EU Type-Examination
Certificate in accordance with Directive
2014/34/EU. (I n accordance with Article 41 of Directive
2014/ 34/ EU, EC Type-Examination Certificates referring to
94/ 9/ EC that were in existence prior to the date of
application of 2014/ 34/ EU (20 April 2016) may be referenced
as if they were issued in accordance with Directive
2014/ 34/ EU. Variations to such EC Type-Examination
Certificates may continue to bear the original certificate
number issued prior to 20 April 2016.)
• The introduction of Variation 9.
9 07 March 2019 R70209081A The introduction of Variation 10.
10 15 October 2019 0449 Transfer of certificate Sira 07ATEX1273X from Sira
Certification Service to CSA Group Netherlands B.V.
11 30 July 2020 R80050077A The introduction of Variation 11.
12 15 February 2021 R80054407A This Issue covers the following changes:
• The introduction of Variation 12.
• The Applicant details for the Hungary location
were deleted to retrospectively align with the
change introduced at Variation 10.
13 04 October 2021 R80082520A The introduction of Variation 13.
14 08 June 2022 R80103684A The introduction of Variation 14.
15 27 February 2023 R80147059A The introduction of Variation 15.

Project Number 80147060


This certificate and its schedules may only be reproduced in its entirety and without change
CSA Group Netherlands B.V. Utrechtseweg 310, Building B42, 6812AR Arnhem, The Netherlands
DQD 544.09 Issue Date: 2022-04-14 Page 5 of 6

Page 35
SCHEDULE

EU-TYPE EXAMINATION CERTIFICATE Sira 07ATEX1273X


Issue 15

15 SPECIFIC CONDITIONS OF USE (denoted by X after the certificate number)


15.1 The IIC enclosures are excluded from use in carbon disulphide atmospheres.
15.2 The air pressure to the valve block, when fitted, shall not exceed 10.0 bar.
15.3 For ambient temperatures above 110°C, the degrees of ingress protection IP66 and IP67 are not
endorsed by Sira.
15.4 The slotted hexagonal head cover screws are not of standard form; they shall only be replaced with
identical screws sourced from the equipment manufacturer.
15.5 The hexagonal head cover screws are to be replaced only with stainless steel A2-70 or A4-80 screws to
ISO 35061
15.6 Cover fasteners are to be tightened to a torque value of 10.85 Nm (8ft/lbs) minimum.
15.7 Only suitably certified cable entry devices or conduit shall be used for connections and unused openings
shall be blanked off using a suitable ATEX certified plug.
15.8 Under certain extreme circumstances, the non-metallic parts orporated in the enclosure of this
equipment may generate an ignition-capable level of electrostatic charge. Therefore the equipment shall
not be installed in a location where the external conditions are conducive to the build-up of electrostatic
charge on such surfaces. In addition, the equipment shall only be cleaned with a damp cloth.
16 ESSENTIAL HEALTH AND SAFETY REQUIREMENTS OF ANNEX II (EHSRs)
The relevant EHSRs that are not addressed by the standards listed in this certificate have been identified
and individually assessed in the reports listed in Section 14.2.
17 CONDITIONS OF MANUFACTURE
17.1 The use of this certificate is subject to the Regulations Applicable to Holders of CSA Group Netherlands
B.V. certificates.
17.2 Holders of EU-Type Examination Certificates are required to comply with the conformity to type
requirements defined in Article 13 of Directive 2014/34/EU.
17.3 The manufacturer shall conduct a routine overpressure test on each unit to be marked with a -60°C
ambient, unless manufacture from stainless steel, at the following pressures; for at least 10 s as required
by clause 16.1 of EN 60079-1:2014. There shall be no permanent damage or deformation to the
enclosure.
Gas group IIC Gas group IIB+H2
28 bar 19.1 bar

Project Number 80147060


This certificate and its schedules may only be reproduced in its entirety and without change
CSA Group Netherlands B.V. Utrechtseweg 310, Building B42, 6812AR Arnhem, The Netherlands
DQD 544.09 Issue Date: 2022-04-14 Page 6 of 6

Page 36
Certificate Annexe
Certificate Number: Sira 07ATEX1273X
Equipment: Type DXP and Type DXS Switchboxes
Applicant: Topworx Inc.

Issue 0
Drawing No. Sheets Rev. Date Description
ES-01141-1 1 of 1 3 03.19.08 General Assembly - DXP
S-AV1-0003 1 of 1 13 03.13.08 General Assembly – DXS Valve
S-S01-0008 1 of 1 12 02.05.08 Upper Casting -DXP
S-S01-0007 1 of 1 21 03.14.08 Lower Casting -DXP With Ports
S-S01-0012 1 of 1 17 03.14.08 Lower Casting -DXP Without Ports
S-S01-SS08 1 of 1 5 02.05.08 Upper Casting -DXS
S-S01-SS07 1 of 1 11 03.14.08 Lower Casting -DXS With Ports
S-S01-SS12 1 of 1 10 03.14.08 Lower Casting -DXS Without Ports
ES-00746-1 1 of 1 2 11.07.07 Serration Joint Details - Lower Casting
ES-00747-1 1 of 1 2 11.07.07 Serration Joint Details – Upper Casting
ES-01068-1 1 of 1 1 03.25.08 Serration Joint Match Details
ES-00157-1 1 of 1 3 06.13.07 Switch Shaft Assembly
S-S01-0016 1 of 1 7 01.18.08 Switch Shaft - Standard
S-S01-0017 1 of 1 7 01.18.08 Switch Shaft - Universal
S-S01-0006 1 of 1 1 09.19.03 Bushing
S-S01-0013 1 of 1 5 12.10.07 Sinter
ES-00238-1 1 of 1 6 03.19.08 Cover Bolt
PS-00177-1 1 of 1 3 03.12.08 Blanking Plug
ES-00874-1 1 of 1 1 05.11.07 EDS Cube Assembly
S-A01-0001-M 1 of 1 10 01.15.08 Switch Assembly - SPDT
S-A01-0030 1 of 1 12 06.28.07 Switch Assembly - DPDT
S-A01-0032 1 of 1 9 10.11.07 Switch Assembly – L2
S-A01-0001-F 1 of 1 8 01.16.08 Switch Assembly – P & F
S-A01-0010 1 of 1 5 02.01.05 Target Assembly
ES-00973-1 1 of 1 3 01.31.08 Nameplate
ES-01149-1 1 of 1 1 12.11.07 Nameplate Artwork – IIC
ES-01147-1 1 of 1 2 03.28.08 Certification Label Details – IIC
ES-01148-1 1 of 1 2 03.26.08 Nameplate Artwork – IIB + H2
ES-01146-1 1 of 1 3 03.28.08 Certification Label Details – IIB + H2
Issue 1
Drawing Sheets Rev. Date (Sira stamp) Description
ES-01141-1 1 of 1 4 14 May 09 DXP/DXS IIC cert Drawing
ES-00973-1 1 of 1 6 14 May 09 Nameplate
ES-01146-1 1 of 1 6 14 May 09 Certification Label Details – IIB + H2
ES-01147-1 1 of 1 4 14 May 09 Certification Label Details - IIC
ES-01148-1 1 of 1 4 14 May 09 Nameplate Artwork – IIB + H2
ES-01149-1 1 of 1 2 14 May 09 Nameplate Artwork – IIC
Issue 2
Drawing Sheets Rev. Date (Sira stamp) Title
ES-00746-1 1 of 1 3 29 Sep 11 Serration Joint Casting - Lower Casting
ES-00238-1 1 of 1 8 29 Sep 11 Cover Bolt
S-S01-0008 1 of 1 16 29 Sep 11 Upper Casting - DXP
S-S01-SS07 1 of 1 14 29 Sep 11 Lower Casting - DXS With Ports
ES-01146-1 1 of 1 11 29 Sep 11 Certification Label Details - IIB + H2
ES-01147-1 1 of 1 8 29 Sep 11 Certification Label Details - IIC
Project Number 80147060
This certificate and its schedules may only be reproduced in its entirety and without change
CSA Group Netherlands B.V. Utrechtseweg 310, Building B42, 6812AR Arnhem, The Netherlands
DQD 544.09 Issue Date: 2022-04-14 Page 1 of 4

Page 37
Certificate Annexe
Certificate Number: Sira 07ATEX1273X
Equipment: Type DXP and Type DXS Switchboxes
Applicant: Topworx Inc.

Drawing Sheets Rev. Date (Sira stamp) Title


S-AV1-0003 1 of 1 15 29 Sep 11 General Assembly - DXS Valve
S-A01-0001-M 1 of 1 14 29 Sep 11 Switch Assembly - SPDT
S-S01-SS08 1 of 1 6 29 Sep 11 Upper Casting - DXS
S-S01-0016 1 of 1 9 29 Sep 11 Switch Shaft - Standard
S-S01-0017 1 of 1 9 29 Sep 11 Switch Shaft - Universal
S-S01-0012 1 of 1 20 29 Sep 11 Lower Casting - DXP Without Ports
S-S01-0007 1 of 1 23 29 Sep 11 Lower Casting - DXP With Ports
ES-01148-1 1 of 1 8 29 Sep 11 Nameplate Artwork - IIB + H2
ES-01149-1 1 of 1 5 29 Sep 11 Nameplate Artwork - IIC
ES-01141-1 1 of 1 6 29 Sep 11 General Assembly - DXP
S-S01-0006 1 of 1 2 29 Sep 11 Bushing
S-A01-0030 1 of 1 17 29 Sep 11 Switch Assembly - DPDT
S-A01-0032 1 of 1 12 29 Sep 11 Switch Assembly – L2
S-A01-0001-F 1 of 1 11 29 Sep 11 Switch Assembly – P & F
ES-00747-1 1 of 1 4 29 Sep 11 Serration Joint Details – Upper Casting
ES-00973-1 1 of 1 7 04 Oct 11 Nameplate
ES-00874-1 1 of 1 2 29 Sep 11 EDS Cube Assembly
ES-00157-1 1 of 1 6 29 Sep 11 Switch Shaft Assembly
S-S01-SS12 1 of 1 14 29 Sep 11 Lower Casting – DXS Without Ports
Issue 3
(Report R25461A/00)
Drawing Sheets Rev. Date (Sira stamp) Title
CERT-ES-01148-1 1 of 1 9 06 Dec 11 Assembly, Nameplate DXP/DXS IIB+H2
CERT-ES-01149-1 1 of 1 6 06 Dec 11 Assembly, Nameplate DXP/DXS IIC
PS-00177-1 1 of 1 5 05 Dec 11 Plug, Hole
(Report R25661A/00)
Drawing Sheets Rev. Date (Sira stamp) Title
SK-1256 1 of 1 C 06 Jan 12 General Assembly – FF2.0 Module
ES-01141-1 1 of 1 7 06 Jan 12 DXP/DXS IIC Certification Drawing
Issue 4
Drawing Sheets Rev. Date (Sira stamp) Title
ES-01141-1 1 of 1 9 23 Jul 12 DXP/DXS IIC Certification Drawing
CERT-ES-01148-1 1 of 1 10 23 Jul 12 Nameplate Artwork [IIB+H 2]
CERT-ES-01149-1 1 of 1 7 23 Jul 12 Nameplate Artwork [IIC]
CERT-ES-03278-1 1 of 1 1 23 Jul 12 Nameplate Artwork [IIB+H 2/IIIC T6/T5/T4-Silicone
S7426-60 O-Ring]
CERT-ES-03279-1 1 of 1 1 23 Jul 12 Nameplate Artwork [IIC/IIIC T6/T5/T4-Silicone S7426-
60 O-Ring]
CERT-ES-03288-1 1 of 1 1 23 Jul 12 Nameplate Artwork [IIC/IIB+H 2 T3]
Issue 5
Drawing Sheets Rev. Date (Sira stamp) Title
CERT-ES-03278-1 1 of 1 2 10 Nov 12 Artwork, Nameplate DXP/DXS IIB+H2 T6/T5/T4
CERT-ES-03279-1 1 of 1 2 10 Nov 12 Artwork, Nameplate DXP IIC T6/T5/T4
CERT-ES-03288-1 1 of 1 2 10 Nov 12 Artwork, Nameplate DXP/DXS IIB+H2/IIC T3
Project Number 80147060
This certificate and its schedules may only be reproduced in its entirety and without change
CSA Group Netherlands B.V. Utrechtseweg 310, Building B42, 6812AR Arnhem, The Netherlands
DQD 544.09 Issue Date: 2022-04-14 Page 2 of 4

Page 38
Certificate Annexe
Certificate Number: Sira 07ATEX1273X
Equipment: Type DXP and Type DXS Switchboxes
Applicant: Topworx Inc.

Drawing Sheets Rev. Date (Sira stamp) Title


CERT-ES-01148-1 1 of 1 11 10 Nov 12 Assembly, Nameplate & Artwork DXP/DXS IIB+H2
CERT-ES-01149-1 1 of 1 8 10 Nov 12 Assembly, Nameplate & Artwork DXP/DXS IIC
S-S01-0007 1 of 1 25 06 Dec 12 Lower Casting - DXP With Ports
S-S01-0012 1 of 1 22 06 Dec 12 Lower Casting - DXP Without Ports
S-S01-0008 1 of 1 18 06 Dec 12 Upper Casting - DXP
CERT-ES-03440-1 1 of 1 1 06 Dec 12 Nameplate Artwork – IIB+H2, -60°C
CERT-ES-03442-1 1 of 1 1 06 Dec 12 Nameplate Artwork – IIB+H2, -60°C to +75°C
CERT-ES-03443-1 1 of 1 1 06 Dec 12 Nameplate Artwork – IIC, -60°C to +75°C
CERT-ES-03444-1 1 of 1 1 06 Dec 12 Nameplate Artwork – IIB+H2/ IIC, -60°C to +175°C
ES-01506-1 1 of 1 3 06 Dec 12 Enclosure specification
Issue 6
Drawing Sheets Rev. Date (Sira stamp) Title
ES-00238-1 1 of 1 12 18 Nov 13 Cover bolt
ES-00157-1 1 of 1 7 18 Nov 13 Switch shaft assembly
S-S01-0016 1 of 1 11 18 Nov 13 Switch shaft - Standard
S-S01-0017 1 of 1 11 18 Nov 13 Switch shaft - Universal
S-S01-SS07 1 of 1 15 18 Nov 13 Lower Casting – DXP With Ports
S-S01-SS12 1 of 1 15 18 Nov 13 Lower Casting – DXS Without Ports
S-A01-0030 1 of 1 20 18 Nov 13 Switch Assembly – DPDT
Issue 7
Drawing Sheets Rev. Date (Sira stamp) Description
CERT-ES-01148-1 1 of 1 12 07 May 14 Nameplate
CERT-ES-01149-1 1 of 1 9 07 May 14 Nameplate
CERT-ES-03278-1 1 of 1 3 07 May 14 Nameplate
CERT-ES-03279-1 1 of 1 3 07 May 14 Nameplate
CERT-ES-03288-1 1 of 1 3 07 May 14 Nameplate
CERT-ES-03440-1 1 of 1 2 07 May 14 Nameplate
CERT-ES-03442-1 1 of 1 2 07 May 14 Nameplate
CERT-ES-03443-1 1 of 1 2 07 May 14 Nameplate
CERT-ES-03444-1 1 of 1 2 07 May 14 Nameplate
Issue 8
Drawing Sheets Rev. Date (Sira stamp) Title
ES-00238-1 1 of 1 15 16 May 18 Bolt, Housing DXP/S Enclosure
S-S01-0006 1 of 1 4 16 May 18 Bushing, Oil impregnated
S-S01-0008 1 of 1 23 16 May 18 Casting, Upper DXP,
ES-01141-1 1 of 1 12 16 May 18 DXP/DXS-Series Master Assembly,
CERT-ES-01148-1 1 of 1 14 08 Jun 18 Nameplate DXP/DXS IIB+H2
CERT-ES-01149-1 1 of 1 10 08 Jun 18 Nameplate DXP/DXS IIC
CERT-ES-03278-1 1 of 1 5 08 Jun 18 Nameplate DXP/S IIB+H2 T6/T5/T4 Silicone
CERT-ES-03279-1 1 of 1 5 08 Jun 18 Nameplate DXP/S IIC T6/T5/T4 Silicone
CERT-ES-03288-1 1 of 1 5 08 Jun 18 Nameplate DXP/S IIB+H2/IIC T3 Silicone
S-S01-0007 1 of 1 27 16 May 18 Lower casting DXP with ports
S-S01-0012 1 of 1 27 07 Jun 18 Lower casting DXP without ports
ES-04900-1* 1 of 1 4 15 May 17 HART Module Assembly

Project Number 80147060


This certificate and its schedules may only be reproduced in its entirety and without change
CSA Group Netherlands B.V. Utrechtseweg 310, Building B42, 6812AR Arnhem, The Netherlands
DQD 544.09 Issue Date: 2022-04-14 Page 3 of 4

Page 39
Certificate Annexe
Certificate Number: Sira 07ATEX1273X
Equipment: Type DXP and Type DXS Switchboxes
Applicant: Topworx Inc.

Issue 9
Drawing Sheets Rev. Date (Sira stamp) Title
CERT-ES-01148-1 1 OF 1 15 13 Feb 19 NAMEPLATE
CERT-ES-01149-1 1 OF 1 11 13 Feb 19 ASSEMBLY, NAMEPLATE
CERT-ES-03288-1 1 OF 1 6 17 Jan 19 NAMEPLATE, markings
CERT-ES-03278-1 1 OF 1 6 17 Jan 19 NAMEPLATE, markings
CERT-ES-03279-1 1 OF 1 6 17 Jan 19 NAMEPLATE, markings
Issues 10 and 11 - No new drawings were introduced.
Issue 12
Drawing # Sheets Rev. Date (Stamp) Title
ES-08221-1 1 of 1 AA 02 Dec 20 Schematic AH8503 Hall Effect Sensor
ES-08619-1 1 to 2 AA 02 Dec 20 Assembly Drawing AH8503 Hall Effect Sensor
ES-08220-1 1 to 2 AA 02 Dec 20 PCB AH8503 Hall Effect Sensor
ES-03278-1 1 of 1 7 02 Dec 20 Nameplate, Markings DXP/S IIB+H2, T6/T5/T4, Silicone
ES-03288-1 1 of 1 7 02 Dec 20 Nameplate, Markings DXP/S IIB+H2/IIC, T3, Silicone
ES-01148-1 1 of 1 16 02 Dec 20 Nameplate, Markings DXP/DXS Ex db IIB+H2
ES-01149-1 1 of 1 12 02 Dec 20 Assembly, Nameplate & Artwork DXP/DXS IIC
ES-08605-1 1 of 1 AA 02 Dec 20 Lower Casting, DXP Base With Valve Ports
ES-08752-1 1 of 1 AA 02 Dec 20 Lower Casting, DXP Base Without Valve Ports
ES-04311-1 1 to 5 AA 02 Dec 20 D-SERIES Master Assy Ex d, Ex ia, Ex e & Ex nA nC
Enclosure
ES-08567-1 1 of 1 AA 02 Dec 20 Contactless Positioner Hall Effect Sensor Board Housing
ES-08568-1 1 of 1 AA 02 Dec 20 CPS Magnet Holder Hall Effect Sensor Magnet Lid
ES-08569-1 1 of 1 AA 02 Dec 20 CPS Magnet Holder Hall Effect Sensor Magnet Holder
ES-08570-1 1 of 1 AA 02 Dec 20 Contact Position Sensor Assembly
ES-08599-1 1 of 1 AA 02 Dec 20 CPS Ring Magnet
Issue 13
Drawing Sheets Rev. Date (Stamp) Title
CERT-ES-04311-1 1 to 5 AB 18 Jun 21 D-SERIES MASTER ASSY
Issue 14 - No new drawings were introduced.
Issue 15
Drawing Sheets Rev. Date (Stamp) Title
CERT-ES-01148-1 1 of 1 16 05 Dec 22 NAMEPLATE Markings, DXP/DXS Ex db IIB+H2
CERT-ES-01149-1 1 of 1 12 07 Dec 22 ASSEMBLY, NAMEPLATE & ARTWORKDXP/DXS IIC
ES-00746-1 1 of 1 6 18 Nov 22 MODIFICATION, CASTING IIC
ES-00747-1 1 of 1 7 18 Nov 22 MODIFICATION, CASTING IIC
PS-00177-1 1 of 1 AD 15 Feb 23 PLUG, HOLE
S-S01-0007 1 of 1 AD 18 Nov 22 LOWER CASTING, DXP BASE WITH VALVE PORTS
S-S01-0008 1 of 1 AC 18 Nov 22 UPPER CASTING, DXP LID
S-S01-0012 1 of 1 AE 18 Nov 22 LOWER CASTING, DXP BASE WITHOUT VALVE PORTS
S-S01-0013 1 of 1 8 18 Nov 22 FLAME ARRESTOR, DXP
S-S01-0016 1 of 1 13 18 Nov 22 SHAFT, STANDARD
S-S01-0017 1 of 1 14 18 Nov 22 SHAFT, NAMUR
S-S01-SS07 1 of 1 16 18 Nov 22 LOWER CASTING, DXS W/PORTS
S-S01-SS08 1 of 1 13 18 Nov 22 UPPER CASTING, DXS

Project Number 80147060


This certificate and its schedules may only be reproduced in its entirety and without change
CSA Group Netherlands B.V. Utrechtseweg 310, Building B42, 6812AR Arnhem, The Netherlands
DQD 544.09 Issue Date: 2022-04-14 Page 4 of 4

Page 40