LIFT PIT SUMP PUMP CALCULATION

Project No. 3481 Date 08/05/2023


Project Name SERENIA LIVING Prepared By AP
Checked By DW
Issue IFC

1 Basis

2 Sump Pump Flow Rate

System Demand per elevator = 11.4 m3/h


Flow Rate of the sump pump = 3.2 l/s

Flow Rate = 3.2 l/s

3 Pipe Size Selected & Pressure Drop

Pipe Size Selected = 65 mm


Velocity = 0.95 m/s
Frictional Loss / m = 0.052 mh/m
Total Pipe Length = 60.00 m
Total Frictional Loss = 3.12 m
Static Height = 6 m
Residual Pressure = 10.6 m

Total Pressure = 19.72 m

4 Pump & Pipe Material Selection

Flow design margin = 5.00 %


Pressure design margin = 10.00 %
Flow Rate = 3.33 l/s
Pump Pressure = 21.69 m = 2.17 bar
Pipe Size = 65 mm diameter
Pipe Material = uPVC Class E

Selection 1 duty

Pump arrangement = 1 Duty

Flow = 3.33 l/s

Head = 2.17 bar