STORM WATER DISCHARGE PUMP CALCULATION

Project No. 3481 Date 08/05/2023


Project Name SERENIA LIVING Prepared By AP
Checked By DW
Issue IFC

1 Basis

Flow rate is calculated separately

2 Pump Flow Rate

Flow Rate calculated = 44.49 l/s

Consider the emptying rate to be half of the incoming flow rate

Flow Rate = 22.25 l/s

3 Pipe Size Selected & Pressure Drop

Pipe Size Selected = 160 mm


Velocity = 1.4 m/s
Frictional Loss / m = 0.012 mh/m
Total Pipe Length = 162.55 m
Total Frictional Loss = 1.95 m
Static Height = 4 m
Residual Pressure = 10 m

Total Pressure = 16.15 m

4 Pump & Pipe Material Selection

Flow design margin = 5.00 %

Pressure design margin = 10.00 %

Flow Rate = 23.36 l/s

Pump Pressure = 17.77 m = 1.78 bar

Pipe Size = 160 mm diameter

Pipe Material = uPVC Class E

Selection - 1 Duty, 1 Assist & 1 Standby

Pump arrangement = 1 Duty + 1 Assist + 1 Standby

Flow = 11.68 l/s (each)

Head = 1.78 bar