1. Design Data
Observations Symbol Air (Cold) Unit Water (Before Overhaul) Unit
Inlet Temperature °C 40 °C 95 °C
Outlet Temperature °C 50 °C 73 °C
Mass Flow Rate m 63360 kg/hr 6600 kg/hr
Specific Heat Cp 1 kJ/kg°C 4.187 kJ/kg°C
Thermal Conductivity K 0.024 W/mK 0.66 W/mK
Density ρ 1.1 kg/m³ 1 kg/L
Tube
Material : Carbon Steel Tubing (ASME SA179)
OD 12.7 mm
ID 9.398 mm
Wall thk 1.651 mm
Overall Heat Transfer Coefficient (U) for air cooled ranges from 300-450 W/m²K (1)
Assume U 350 W/m²K
Energy Balance
(mCp)h(Thi-Tu)=((mCp)c(Tce-Tci)
6600x4.187x(95-73) = 63360x1x(40-Tci)
Tci = 49.60 °C
So, Outlet temperature of Water is : 49.60 °C (2)
95
73
55
40
θ1 = 45.4 °C
θ2 = 33.0 °C
LMTD 𝜃1 − 𝜃2
θm =
𝜃1
ln 𝜃2
(45 − 33)
θm = 45
ln
33
Фm = 38.87 °C
LMTD = 39 °C log mean temperature difference (4)
for correction factor required dimension parameters are,
𝑇𝑐𝑒 − 𝑇𝑐𝑖
𝑇𝑐𝑒 − 𝑇𝑐𝑖
P=
𝑇ℎ𝑖 − 𝑇𝑐𝑖
P= 32 − 30
98 − 30
P= 0.17 (5)
𝑇ℎ𝑖 − 𝑇ℎ𝑒
R=
𝑇𝑐𝑒 − 𝑇𝑐𝑖
R= 98 − 87.7
32 − 30
R= 2.3 (6)
Tube area of heat trasfer after considering correction factor is given as,
𝑞
A= 𝑈 𝑥 𝐹 𝑥 θ𝑚(𝑐𝑜𝑢𝑛𝑡𝑒𝑟𝑓𝑙𝑜𝑤)
A= 607952
350 𝑥 1 𝑥 39
A= 44.68 m² (8)
HEAT REJECTION CHECK
JACKET REQUIRED
ENGINE PYROBAN RADIATOR HEAT
ENGINE PERCENT EFFICIENCY WATER HEAT
NO. POWER HEAT CAPACITY REJECTION
RPM LOAD % VALUES HEAT REJECTION
(kW) REJECTION (kW) BALANCE
REJECTION (kW)