Hilti PROFIS Engineering 3.0.

88

www.hilti.com.tr
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 8, 2021 (1) Date: 11.09.2023
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 200 + Rebar 12mm
Item number: not available (element) / 2045030 HIT-HY 200-A
(adhesive)
Effective embedment depth: hef,opti = 70.0 mm (hef,limit = 218.0 mm)
Material: B500B
Evaluation Service Report: ESR-3187
Issued I Valid: 1.05.2021 | 1.03.2022
Proof: Design Method ACI 318-11 / Chem
Stand-off installation: eb = 0.0 mm (no stand-off); t = 8.0 mm

Anchor plate :
R lx x ly x t = 250.0 mm x 250.0 mm x 8.0 mm; (Recommended plate thickness: not calculated)

Profile: IPE, IPE 100; (L x W x T x FT) = 100.0 mm x 55.0 mm x 4.1 mm x 5.7 mm


Base material: cracked concrete, C25/30, fc' = 3,626 psi; h = 250.0 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.88

www.hilti.com.tr
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 8, 2021 (1) Date: 11.09.2023
Fastening point:

1.1 Design results


Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
1 Combination 1 N = 10.000; Vx = 5.000; Vy = 0.000; no 29
Mx = 0.000; My = 0.000; Mz = 0.000;
Nsus = 2.000; Mx,sus = 0.000; My,sus = 0.000;

2 Load case/Resulting anchor forces y

3 4

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 2.500 1.250 1.250 0.000
2 2.500 1.250 1.250 0.000 x
3 2.500 1.250 1.250 0.000 Tension
4 2.500 1.250 1.250 0.000

max. concrete compressive strain: - [‰]


max. concrete compressive stress: - [N/mm ]
2
1 2
resulting tension force in (x/y)=(0.0/0.0): 10.000 [kN]
resulting compression force in (x/y)=(0.0/0.0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 2.500 40.300 7 OK
Bond Strength** 10.000 35.029 29 OK
Sustained Tension Load Bond Strength* 0.500 7.344 7 OK
Concrete Breakout Failure** 10.000 46.703 22 OK

* highest loaded anchor **anchor group (anchors in tension)

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.88

www.hilti.com.tr
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 8, 2021 (1) Date: 11.09.2023
Fastening point:

3.1 Steel Strength

Nsa = ESR value refer to ICC-ES ESR-3187


f Nsa ³ Nua ACI 318-11 Table D.4.1.1

Variables
2 2
Ase,N [mm ] futa [N/mm ]
113 550.00

Calculations
Nsa [kN]
62.000

Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
62.000 0.650 40.300 2.500

3.2 Bond Strength

Nag = (AA ) y
Na

Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ACI 318-11 Eq. (D-19)
f Nag ³ Nua ACI 318-11 Table D.4.1.1
ANa see ACI 318-11, Part D.5.5.1, Fig. RD.5.5.1(b)
2
ANa0 = (2 cNa) ACI 318-11 Eq. (D-20)
t uncr
cNa = 10 da √ 1100
ACI 318-11 Eq. (D-21)

( )
1
'
y ec,Na = eN £ 1.0 ACI 318-11 Eq. (D-23)
1+
cNa

y ed,Na = 0.7 + 0.3 (cc ) £ 1.0 a,min

Na
ACI 318-11 Eq. (D-25)

= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-11 Eq. (D-27)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)

Variables
t k,c,uncr [N/mm ]
2
da [mm] hef [mm] ca,min [mm] aoverhead 2
t k,c [N/mm ]
11.21 12.0 70.0 910.0 1.000 7.78

ec1,N [mm] ec2,N [mm] cac [mm] la


0.0 0.0 111.9 1.000

Calculations
cNa [mm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na
145.2 221,326 84,363 1.000

y ec1,Na y ec2,Na y cp,Na Nba [kN]


1.000 1.000 1.000 20.542

Results
Nag [kN] f bond f Nag [kN] Nua [kN]
53.891 0.650 35.029 10.000

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.88

www.hilti.com.tr
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 8, 2021 (1) Date: 11.09.2023
Fastening point:

3.3 Sustained Tension Load Bond Strength

0.55 f Nba ³ Nua,s ACI 318-11 Eq. (D-1)


Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)

Variables
la aoverhead t k,c [N/mm ]
2
da [mm] hef [mm]
1.000 1.000 7.78 12.0 70.0

Calculations
Nba [kN]
20.542

Results
Nba [kN] f bond 0.55 f Nba [kN] Nua,s [kN]
20.542 0.650 7.344 0.500

3.4 Concrete Breakout Failure

Ncbg = (AA ) y
Nc

Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-11 Eq. (D-4)
f Ncbg ³ Nua ACI 318-11 Table D.4.1.1
2
ANc0 = 9 hef ACI 318-11 Eq. (D-5)

( )
1
'
y ec,N = 2 eN £ 1.0 ACI 318-11 Eq. (D-8)
1+
3 hef

y ed,N = 0.7 + 0.3 (1.5h


c
) £ 1.0 a,min

ef
ACI 318-11 Eq. (D-10)

= MAX(
c ) £
c 1.5h a,min ef
y cp,N , 1.0 ACI 318-11 Eq. (D-12)
c ac ac
1.5
Nb = kc l a √ '
fc hef ACI 318-11 Eq. (D-6)

Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
70.0 0.0 0.0 910.0 1.000

'
cac [mm] kc la fc [psi]
111.9 17 1.000 3,626

Calculations
ANc [mm ]
2
ANc0 [mm ]
2
y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
152,100 44,100 1.000 1.000 1.000 1.000 20.833

Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
71.851 0.650 46.703 10.000

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.88

www.hilti.com.tr
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 8, 2021 (1) Date: 11.09.2023
Fastening point:

4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 1.250 22.500 6 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength 5.000 75.448 7 OK
controls)**
Concrete edge failure in direction x+** 5.000 95.345 6 OK

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength

Vsa = ESR value refer to ICC-ES ESR-3187


f Vsteel ³ Vua ACI 318-11 Table D.4.1.1

Variables
2 2
Ase,V [mm ] futa [N/mm ]
113 550.00

Calculations
Vsa [kN]
37.500

Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
37.500 0.600 22.500 1.250

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.88

www.hilti.com.tr
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 8, 2021 (1) Date: 11.09.2023
Fastening point:

4.2 Pryout Strength (Bond Strength controls)

Vcpg =kcp [(AA ) y


Na

Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ] ACI 318-11 Eq. (D-41)
f Vcpg ³ Vua ACI 318-11 Table (D.4.1.1)
ANa see ACI 318-11, Part D.5.5.1, Fig. RD.5.5.1(b)
2
ANa0 = (2 cNa) ACI 318-11 Eq. (D-20)
t uncr
cNa = 10 da √ 1100
ACI 318-11 Eq. (D-21)

( )
1
'
y ec,Na = eN £ 1.0 ACI 318-11 Eq. (D-23)
1+
cNa

y ed,Na = 0.7 + 0.3 (cc ) £ 1.0 a,min

na
ACI 318-11 Eq. (D-25)

= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-11 Eq. (D-27)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)

Variables
kcp aoverhead t k,c,uncr [N/mm ]
2
da [mm] hef [mm] ca,min [mm]
2
t k,c [N/mm ]
2 1.000 11.21 12.0 70.0 910.0 7.78

ec1,N [mm] ec2,N [mm] cac [mm] la


0.0 0.0 111.9 1.000

Calculations
cNa [mm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na
145.2 221,326 84,363 1.000

y ec1,Na y ec2,Na y cp,Na Nba [kN]


1.000 1.000 1.000 20.542

Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
107.783 0.700 75.448 5.000

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.88

www.hilti.com.tr
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 8, 2021 (1) Date: 11.09.2023
Fastening point:

4.3 Concrete edge failure in direction x+

Vcbg = (AA ) y
Vc

Vc0
ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-11 Eq. (D-31)
f Vcbg ³ Vua ACI 318-11 Table D.4.1.1
AVc see ACI 318-11, Part D.6.2.1, Fig. RD.6.2.1(b)
2
AVc0 = 4.5 ca1 ACI 318-11 Eq. (D-32)

( )
1
'
y ec,V = 2ev £ 1.0 ACI 318-11 Eq. (D-36)
1+
3ca1

y ed,V = 0.7 + 0.3 (1.5c


c
) £ 1.0
a2

a1
ACI 318-11 Eq. (D-38)

y h,V = √1.5ch ³ 1.0 a


a1
ACI 318-11 Eq. (D-39)

= (7 ( ) √ d ) l
0.2
l
Vb e
a a √f'c c1.5
a1 ACI 318-11 Eq. (D-33)
d a

Variables
ca1 [mm] ca2 [mm] ecV [mm] y c,V ha [mm]
910.0 910.0 0.0 1.000 250.0

'
le [mm] la da [mm] fc [psi] y parallel,V
70.0 1.000 12.0 3,626 1.000

Calculations
AVc [mm ]
2
AVc0 [mm ]
2
y ec,V y ed,V y h,V Vb [kN]
613,750 3,726,450 1.000 0.900 2.337 393.245

Results
Vcbg [kN] f concrete f Vcbg [kN] Vua [kN]
136.207 0.700 95.345 5.000

5 Combined tension and shear loads


bN bV z Utilization bN,V [%] Status
0.285 0.066 5/3 14 OK

z z
bNV = bN + bV <= 1

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.88

www.hilti.com.tr
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 8, 2021 (1) Date: 11.09.2023
Fastening point:

6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the
potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or
where pullout or pryout strength governs.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to
https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-11,
Part D.9.1

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.88

www.hilti.com.tr
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 8, 2021 (1) Date: 11.09.2023
Fastening point:

7 Installation data
Anchor type and diameter: HIT-HY 200 + Rebar 12mm
Profile: IPE, IPE 100; (L x W x T x FT) = 100.0 mm x 55.0 mm x 4.1 mm x 5.7 Item number: not available (element) / 2045030 HIT-HY
mm 200-A (adhesive)
Hole diameter in the fixture: df = 12.0 mm Maximum installation torque: -
Plate thickness (input): 8.0 mm Hole diameter in the base material: 16.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 70.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 102.0 mm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required

Rebar with HIT-HY 200 injection mortar with 70 mm embedment h_ef, 12mm, Hammer drilled installation per ESR-3187

7.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required • Dispenser including cassette and mixer
• Properly sized drill bit accessories to blow from the bottom of • For deep installations, a piston plug is
the hole necessary
• Proper diameter wire brush • Torque wrench

y
125.0 125.0
35.0

3 4
125.0
180.0

x
125.0

1 2
35.0

35.0 180.0 35.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -90.0 -90.0 9,910.0 1,090.0 910.0 10,090.0
2 90.0 -90.0 10,090.0 910.0 910.0 10,090.0
3 -90.0 90.0 9,910.0 1,090.0 1,090.0 9,910.0
4 90.0 90.0 10,090.0 910.0 1,090.0 9,910.0

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.0.88

www.hilti.com.tr
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 8, 2021 (1) Date: 11.09.2023
Fastening point:

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with
regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to
interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability
for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10

You might also like