‘Manual No. 165-56380
BAYLOR
INSTRUCTION OPERATION
AND SERVICE MANUAL
FOR MODEL. 56380
« BATTERY CHARGER AND
SWITCHOVER UNIT
EQUIPMENT FURNISHED
BY
BAYLOR COMPANY
500 INDUSTRIAL BLVD.
SUGAR LAND, TEXAS 77478-2898
PHONE (281) 240-6111
FAX (281) 274-0426
6/98 REVISEDBAYLOR
NOTICE
This document is and contains confidential and trade secret
information of the Baylor Company. This Document is loaned
for limited purposes only, and remains the property of the
Baylor Company. It is to be returned upon request and in all
events upon completion of the purpose of the loan. Neither it nor
the information it contains may be reproduced, used, or
disclosed to persons not having a need to know consistent with
the purpose of the loan, without written consent of Baylor
Company.
ADDRESS COMMENTS TO:
BAYLOR COMPANY
500 INDUSTRIAL BLVD.
SUGAR LAND, TEXAS 77478-2898
TELEPHONE: (281) 240-6111
FAX: (281) 274-0426
PRINTED INU.S.A.SECTION 1
INTRODUCTION AND DESCRIPTION
SCOPE OF MANUAL
GENERAL DESCRIPTION
SECTION 2
PRESCRIPTION OF OPERATION
MAJOR COMPONENTS
2.1.1 BATTERY SWITCHOVER PANEL - P/N 56406
2.1.2 BATTERY CHARGER PANEL (P/N 56032)
2.1.2.1 ALARM CIRCUITS
2.1.2.2 CHARGING PROCEDURE
2.1.2.3 BATTERY CHECKS
2.1.3 DRILL FLOOR EMERGENCY STOP STATION
(P/N 53564)
SECTION 3
SPECIFICATIONS
GENERAL
BATTERY CHARGER AND SWITCHOVER UNIT
DRILL FLOOR EMERGENCY STOP STATION
GENERAL
BATTERY CHARGER AND SWITCHOVER UNIT4.3
4.2.1 MAIN POWER FREQUENCY SELECTION
DRILL FLOOR EMERGENCY STOP STATION
SECTION 5.
OPERATING INSTRUCTIONS
OPERATING PROCEDURE
5.1.1 Reset Procedures
SECTION 6
MAINTENANCE
BATTERY SWITCHOVER PANEL
BATTERY CHARGER PANEL
6.2.1 | CURRENT LIMIT CHECK
6.2.2 FLOAT VOLTAGE CHECK
6.2.3 EQUALIZE VOLTAGE CHECK
6.2.4 ALARM CHECKS
6.2.4.1 FIRING BOARD POWER ALARM CHECK
6.2.4.2 HIGH, LOW AND RECTIFIER FAILURE
ALARM CHECK
6.2.4.3 GROUND DETECTION ALARM CHECK
SECTION 7
PARTS AND SERVICE
GENERAL
PARTS AND SERVICE
RECOMMENDED SPARE PARTS - BATTERY SWITCHOVER PANEL
RECOMMENDED SPARE PARTS - BATTERY CHARGER PANEL
RECOMMENDED SPARE PARTS - EMERGENCY STOP STATION
ii
6-2
6-2
6-2
6-3
6-4
6-4BAYLOR
1.2
SECTION 1.
INTRODUCTION AND DESCRIPTION
SCOPE OF MANUAL
This manual provides information regarding the
installation, operation, troubleshooting and maintenance of
the BAYLOR Model 56360 Battery Charger and Switchover Unit.
This manual is divided into sections giving a narrative
description of the theory of operation, function of
controls, operating instructions, maintenance and service,
a parts and supplies list, applicable schematics, flow
diagrams, and major assembly drawings.
Operators are requested to read and thoroughly familiarize
themselves with this manual before attempting to operate
the equipment.
GENERAL DESCRIPTION
The Baylor Battery Switchover Unit provides a simple and
safe method of interfacing a Brake Control System with a
bank of rechargeable batteries and a battery charger used
as a source of backup DC power to the Eddy Current Brake.
The 56032 Battery Charger is designed to charge the battery
bank used for emergency backup power supply to an Eddy
Current Brake. The charger consists of a main power
transformer, an SCR bridge, a firing board, alarm circuits,
and a display panel integrated together in a steel
enclosure manufactured to NEMA 12 standards.
The system is designed to operate on 50/60 Hz single phase
120/240 Volts AC. Two power ranges are available on the
transformer output. Low power range is for charging
battery banks of 240 Volts DC or less. The high power
1-1BAYLOR
1.2
GENERAL DESCRIPTION (Cont! d)
range is for charging battery banks of 240 to 325 Volts DC.
In all cases voltage output is controlled by the firing
board. In addition, the firing board also limits the
output current to 5 amps.
The alarm circuits installed in the Battery Charger detect
high voltage output, low voltage output, SCR failure,
firing board loss of power, and DC power output grounded.
The Battery Charger contains a second transformer which
provides control voltage to the firing board, alarm
circuits, and indicator lights on the display panel. An
indicator light is provided on the display panel for each
of the above mentioned alarm conditions. In addition, the
display panel contains voltage = output'_— control
potentiometers for float and equalizing operations, as well
as panel meters for displaying the voltage and current
output of the Battery Charger. A circuit breaker is also
mounted in the display panel to provide short circuit
protection to the AC input circuits of the Battery Charger.
It also functions as the on/off switch.
The battery disconnect switch is a heavy duty, two pole,
circuit breaker used to manually disconnect the battery
bank from the battery transfer unit. The fuse in the
battery circuit is sized to protect the battery cables and
limit available battery fault current.
The disconnect switch is rated for 250 volts DC at 125
amperes.
An auxiliary switch is installed to be connected to the
battery transfer logic circuitry.
1-2BAYLOR
GENERAL DESCRIPTION (Cont! d)
If the switchover panel (DWG 56406) is revision “C” or
higher, the following applies. A shunt trip is installed in
the battery disconnect, which can be remotely shunt tripped
using a contact closure that is rated for 120 vac. It is
only used for emergency total shutdown condition. Also
included is a timed shunt trip, which senses the battery
supply monitor relay (CR1)and the de-energization of C1. When
CR1 is energized and C1 is de-energized, the timer (TDR2)
starts timing out. The timer has a range that can be adjusted
up to 10 minutes. Once timed at the timer’s set point, it
shunt trips the battery disconnect. This will prevent the
batteries from draining down to a nonrecoverable recharging
condition. The recommended set point on the timer is 5
minutes, which should provide adequate time to bring the
drawworks load to a stop and set the drill pipe into the
slips. As soon as conditions permit, the system can be
reset using the reset procedure in Section 5.1.1.BAYLOR
SECTION 2
DESCRIPTION OF OPERATION
MAJOR COMPONENTS AND THEIR THEORY OF OPERATION
BATTERY SWITCHOVER PANEL
The 56406 Battery Switchover Panel has been designed to
give a maximum of trouble-free operation in the rugged
drilling rig environment with a minimum of maintenance
required.
A magnetic DC contactor is used to connect a bank of
rechargeable batteries to the Eddy Current Brake when
either one of the following occu:
1. Loss of AC power to the primary Brake Control unit.
2. Upon energizing the Drill Floor Emergency Stop
Button, by the Driller.
Input AC power to the primary Brake Control unit is
monitored by providing an input at fuses F3, F4 and FS from
the Brake Control unit 186/240 volt AC power input. Loss
of power is sensed by relays MR1, MR2 and MR3. Upon loss
of power MR1, MR2 or MR3 is de-energized which allows its
contacts 1 and 7 to open, in turn de-energizing normally
closed contactor Cl. When contactor Cl closes full battery
voltage is applied to the brake and the "BACK UP IN USE"
lamps are illuminated on the Unit’s front door and on the
Drill Floor Emergency Stop Station. Depressing the
Emergency Stop Pushbutton at the Driller's position on the
rig floor accomplishes the same function by breaking the
path of coil voltage to the contactor C1.BAYLOR
2.1.2
BATTERY SWITCHOVER PANEL (Cont'd)
The reader will note, upon examination of the logic and
wiring diagrams, that the positive output of the primary
SCR unit and the positive terminal of the battery bank are
always connected to the positive brake terminal thru
steering diodes which isolate the primary Brake Control
unit from the battery bank. Upon closure of the DC
contactor Cl, the battery bank is effectively in parallel
with the primary Brake Control. Therefore regardless of
the output voltage level of the primary Brake Control unit
the highest voltage present at the point of connection of
the steering diode cathode terminals will be present at the
brake after the DC contactor closes.
After an operation of the transfer unit the system is reset
by opening the battery disconnect switch. Disconnecting
battery voltage from the unit is sensed by Battery Supply
Monitor Relay CR-1, When battery voltage is removed, CR-1
is de-energized which starts the time delay relay TDRI
cycle. TDR1 should be set to provide a time delay while
the brake field is collapsed thru the free wheeling diode
and contactor Cl which is still in the closed position.
Upon completion of the time delay, contactor ci is
energized (opened) and the "CLOSE DISCONNECT" lamp will be
illuminated. Upon closure of the battery disconnect
switch, Ri-1 will be energized, which in turn extinguishes
the "CLOSE DISCONNECT" lamp and illuminates the "SYSTEM
READY" lamp. The system is now ready for use.
An isolation transformer is provided in the battery
transfer unit to accept a the customer furnished, stable,
source of 120/240 VAC power to operate system logic. Be
sure and select the correct voltage during installation as
an improper voltage setting may damage components.
2-2BAYLOR
2.1.2
BATTERY CHARGER PANEL - P/N 56032
The 56032 Battery Charger provides a means for charging the
battery bank used as emergency backup power for a Baylor Eddy
Current Brake. The voltage output of the Battery Charger is
adjustable to match the voltage requirements for charging the
battery bank. The voltage level is adjusted by moving the
float or equalizing voltage controls on the display panel.
Float voltage is defined as the voltage level required to
maintain the charge of the battery bank. Equalizing voltage
is defined as the voltage level necessary to recharge all of
the cells in a battery bank to the same volts per cell. A
battery bank that has been discharged to a level of 60% to 708
of the rated voltage per cell can be recharged in the equalize
mode for 6 hours maximum. This will insure the full charging
of all cells in the battery bank. The Battery Bank must be
maintained on float charge and should be fully recharged
within 24 hours after any discharge. output current is
limited to 5 Amps. in either the float or equalize operation.
Do not attempt to recharge a battery with an
open circuit voltage less than 1.0 volt per
cell. Hydration shorts may be present, causing
the battery to be non-recoverable.
2.1.2.1 ALARM CIRCUITS
Alarm circuits are integrated into the Battery Charger. These
alarm circuits detect high voltage output, low voltage output,
SCR failure, firing board power failure, and DC output
grounded. Alarm conditions are indicated by lights on the
display panel. In addition, a dry set of contacts are
available for interfacing the general alarm into a customer
supplied alarm annunciation system or brake monitor.
2-3BAYLOR
2.1.2.2
CHARGING PROCEDURE
If the battery bank has been engaged to power the Eddy Current
Brake, or a new battery bank is being charged for the first
time, the following charging procedure should be followed:
1)
2)
3)
Carry out the reset procedure for the battery switchover
system. Make sure that the battery bank is disconnected
from the Eddy Current Brake.
With the float/equalize timer switch in the float
position read the current and voltage as displayed on the
ammeter and voltmeter mounted on the display panel.
If the Battery Charger voltage is near the float voltage
setting ( Reference SECTION 6 "MAINTENANCE") and the
current is less than 2 Amp., leave the Float/Equalize
timer switch on the "Float" position.
If the ammeter on the display panel indicates that the
current is greater than 2 Amp., turn the Float/Equalize
timer knob for 6 hour equalize charge. The voltage level
indicated by the voltmeter on the display panel should
rise and the current, as indicated on the ammeter mounted
on the display panel, should increase. If the battery
charger is current limited there will not be any increase
in voltage or current. After the 6 hour charge time the
battery charger voltage will switch back to the "Float"
WARNING !
The “Equalize” setting of the Battery Charger
is not intended for long term use. If the
Battery Charger is left in the “Equalize”
setting for a period of time greater than 6
hours, damage to the cells of the battery
bank could result.
_——————
2-4
condition.BAYLOR
2.1.2.2 CHARGING PROCEDURE (Cont’d)
4)
If the battery bank is not quite fully charged, the
Battery Charger will continue to trickle charge the
battery bank on the "Float" setting.
2.1.2.3 BATTERY CHECKS
Periodic checks of the ammeter and voltmeter on the
display panel of the Battery Charger should be performed
to insure that the unit is functioning properly. Most
battery manufacturers recommend periodic checks of the
"Float" voltage of a battery bank on a volts per cell
basis. If one battery in the battery bank exhibits
“Bloat" voltage readings that are low, it may be
necessary to charge the bank at “Equalize" voltage for a
period of time to insure that all cells are fully charge.
When performing this operation, be sure and follow the
battery manufacturers recommendations. (See SECTION 9.)
DRILL FLOOR EMERGENCY STOP STATION P/N 53564
The Drill Floor Emergency Stop Station provides the Driller
with a means of manually activating the Model 56380 Battery
Switchover Unit in emergency situations or for test
purposes.
The Drill Floor Emergency Stop Station consists of a
mushroom head pushbutton and a red lamp installed in an
enclosure certified for use in a Class 1, Division 1, Group
c & D hazardous area.
2-5DRILL FLOOR EMERGENCY STOP STATION (Cont/d)
When the Driller firmly depresses the large mushroom
operator on the pushbutton, the battery switchover unit is
activated connecting full battery potential to the Eddy
Current Brake Magnet Coils.
The red "BACKUP IN USE" is illuminated when the battery
switchover unit is activated.GENERAL
The Model 56380 is designed and manufactured to meet the
special requirements of land and offshore drilling rig
service.
BATTERY CHARGER AND SHITCHOVER UNIT
Battery Bank Voltage (Max.). . . .
Battery Rating . 2...
sos ss +. 288 volt De
see es 40 amp, at 20 min.
to 1.75 V.P.c.
Brake Control Voltage Sense . ... . . 186/240 volt AC,
3 phase,
50/60 Hz
Customer Furnished Supply Feeder . . . 120/240 volt ac,
(Battery Charge Panel 20A/10A) 1 phase,
(Battery Switchover Panel 10A/5A) 50/60 Hz
DC Contactor Rating»... ..... 2... 110 amp DC
DC Contactor Coil Volts .......... . 120 volt AC
Max. Charger Current ...............5 amp
Battery Charger Float Voltage .... . . . 270-272.4 vde
Battery Charger Equalize Voltage . . . . . 280-282.4 vde
Enclosure Type... 2... 2. ....... . NEMA12
Cable Entry... ......... 2... Top or Bottom
DRILL FLOOR EMERGENCY STOP STATION
Emergency Stop Pushbutton . . .. 1N.0., 1 N.C. Contact
rated at 6 amp, 120
volt AC
"BACKUP IN USE" Lamp... . ... . . 120 volt AC, RED
Enclosure... 2... 2... Cast aluminum
3-1SECTION 4
INSTALLATION
GENERAL
The Battery Charger and Switchover system has two
components that require installation:
* Battery Charger and Switchover unit
* Drill Floor Emergency Stop Station
Baylor Drawings 56409, and 56008 detail SCHEMATICS for the
system. Also, see SECTION 8 for customer cable detail
connections.
BATTERY CHARGER AND SWITCHOVER UNIT
The Battery Charger and Switchover Unit should be installed
in an upright position against a wall or bulkhead using the
two mounting channels provided. There should not be any
restriction to air flow at the top or bottom and the
cabinet should be mounted as far away as possible from any
heat producing sources. The cabinet should be installed in
@ clean, dry, non-hazardous atmosphere such as the air
conditioned SCR house or switchboard room.
THE BATTERY CHARGER AND SWITCHOVER UNIT
SHOULD NOT BE INSTALLED IN A HAZARDOUS
AREA SUCH AS THE DRILL FLOOR
Provisions are made for top or bottom cable entry into the
enclosure.
4-1BAYLOR
4.2.1
MAIN POWER FREQUENCY SELECTION
If the AC power to the Battery Charger is 50 Hz, insure
that the jumper at JU8 is in the 50 Hz position on the
firing board. This is accomplished by installing a jumper
between points 1 and 2 of JU8. For 60 Hz power the jumper
at JU8 should be in the 60 Hz position of the firing board.
This is accomplished by installing a jumper between points
2 and 3 of gus.
DRILL FLOOR EMERGENCY STOP STATION
The Drill Floor Hmergency Stop Station should be installed
on the Drill Floor within easy sight and reach of the
Driller. Two mounting ears for 1/4 inch bolts are provided
at the rear of the enclosure. Mount the enclosure to allow
cable entry from the bottom. Always use cable glands or
fittings appropriate for hazardous area.
4-2W ka FP
SECTION 5
OPERATING INSTRUCTIONS
OPERATING PROCEDURE
The Baylor Model 56380 Battery Charger and Switchover Unit
provides a means of interfacing a bank of rechargeable
batteries, that are used to backup the primary Brake
Control System, in the event of an AC power loss or in an
emergency.
In normal operations the Eddy Current Auxiliary Drawworks
Brake is powered by the primary Brake Control unit. The
"SYSTEM READY" lamp on the Battery Charger and Switchover
Unit front door should be illuminated and the Battery
Disconnect Switch should be closed. The battery bank
should be charged and ready for use.
In the event of a loss of power to the primary Brake
Control unit, contactor Cl in the Battery Charger and
Switchover Unit will close automatically, connecting the
Battery Bank voltage to the Eddy Current Brake magnet
coils. At this time the "BACKUP IN USE" lamps, located on
the Battery Charger and Switchover Unit front door and on
the Emergency Stop Station, will be illuminated.
On BRAKE MONITOR SYSTEMS only (Models 1025, 1040, 2025, or
2040) there is a throttle mismatch relay (R3 or K3) if an
error is detected, it will open a set of contacts on R3
that breaks the circuit to the coil of Contactor (C1).
Contactor (Cl), on the battery switchover panel will de-
energized. This connects the battery bank potential to the
Eddy Current Brake. Also, at this time the “BACKUP IN USE”
lamps, located on the Battery Charger/Switchover Unit and
Emergency Stop Station, will be illuminated.