Sr.

No Description Gauranteed Particulars


1 Make
2 Reference IS 1180, Level-2
3 Service Outdoor
4 Type Copper Wound, Oil Immersed
5 Rating 2000 KVA
6 Rated Voltage
H.V. Winding 11 KV
L.V. Winding 0.433 KV
7 Rated Current
H.V. Winding 104.9 A
L.V. Winding 2666.8 A
8 Frequency 50 Hz
9 No. of Phases 3
Vector Group Dyn11
H.V. Winding Delta
L.V. Winding Star
10 Resistance of Windings at 20 °C
(With 5% Tolerance)
A. HV Winding (Ohms)
AS PER IS-1180
B. LV Winding ( Ohms)
11 System Data
a) System Voltage
H.V. Highest 12KV
L.V. Highest 1.1KV
12 Type Of Cooling ONAN
13 Tapping
Range +5% to -10%
Tapping Provided on
Off Circuit Tap Switch
No. of Steps
Capacity
14 Tap Changer Insulation Level
HV Impulse Voltage Withstand 75
HV Power Frequency Withstand 28
15 Losses
Total losses at 50 % loading at 75
deg.C. As per loss class Level 2 of IS-1180
Total losses at 75 % loading at 75
deg.C. As per loss class Level 2 of IS-1180
Total losses at 100 % loading at 75
deg.C. As per loss class Level 2 of IS-1180
16 Impedance Voltage
a) At Principal Tapping 5.00%
b) At Max. Tapp
c) At Min. Tapping
17 Temp. Rise Above 50 °C Temp.
a) Top Oil In oil thermometer
b) In winding by resistance
18 Efficiency at 75 °C UPF & 0.8 PF UPF 0.8PF
a) At Full Load
b) At 75% Load
c) At 50% Load
19 Load at which max. effici. Occurs
20 Max. Efficiency
21 Regulation at Full Load at 75°C
a) At Full Load
b) At 75% Load
c) At 50% Load
22 No Load Current referred to H.V.
a) At 90% Rated Voltage
b) At 100% Rated Voltage
c) At 110% Rated Voltage
23 Max. Current Density at Rated
Power
a) H.V. Winding
b) L.V. Winding
Material and Size of the Conductor
24
used
a) HV
b) LV
Strip Size
Nos. Of Conductors in parallel
Total area of cross section (Sq.mm.)
25 Max. Flux Density in Iron at Rated
(Curve to be furnished by
Manufacturer in support of this)
Approx. maximum flux
26 density(Web/ Sq. M)
At 90% rated voltage
At 100% Rated Voltage
At
Max.110% Rateddensity
current Voltage Amps / Sq.
cm
27 (HV/LV
VoltageWinding)
Ratio & Rated Frequency
a) At 100% Rated Voltage
b) At 110% Rated Voltage
28 Insulation Level
a) Impulse Voltage Withstand
H.V. Side 75
L.V. Winding NA
b) Power Frequency
H.V. Side 28
L.V. Winding 3
29 Withstand Time Without Injury for
teminal with rated voltage
a) Single phaseonshort
maintained the circuit at
other side
b) terminal with rated voltage
c) maintained
125% of ratedonvoltage
other side
d) 140% of rated voltage
30 Details Of Core
Core Laminations Materials CRGO
No. of Limbs (Core Type)
Specific Loss of W/kg Core Steel at
1.5 Tesla
31 Details of Tank
a) Material
b) Max. Internal Pressure the As per CBIP
Tank is capable of withstanding As per CBIP
Provision for lifting by crane.
32 Details Of Conservator
a) Main Tank
Volume of Conservator
Volume of Oil between the Highest
and Lowest Level
33 Details of Radiator
No. of Radiator Banks
Thickness of the Radiator Plate
Weight of each Radiator Tank
Extra Radiator Bank
34 Details of Bushings

Make
Type
Voltage
Creepage Distance
Current Rating
Insulation Level
Impulse
Power Freq.
35 Tank Pressure Test
Pressure
As per CBIP
Duration
36 Tank Vacuum Test
Vacuum
As per CBIP
Duration
37 Insulating Oil
10% excess oil furnished ?
Oil conforms to IS:335-2018
38 Marshaling Box
Weatherproof, suitable for outdoor YES
Degree of protection IP:55
39 Terminal Connection
H.V. Cable box
L.V. Bus duct
HV Cable Box shall be suitable for
LV Cable Box shall be suitable for
40 Max. Noise Level as per NEMA
Approx. Overall Dimension
41 Including Radiators & Conservator
42 Coolers and all Fittings
Height
Breadth
Length
43 Weight
Core and Winding
Tank and Fittings
Oil
Total Weight Including Oil
Cooling Motors, Tap Changer,
Fittings & Oil
44 Clearances (mm)
(a) Core and LV As per CBIP
(b) LV & HV As per CBIP
(c) HV Phase to Phase As per CBIP
(d) End Insulation clearances to
Earth As per CBIP
(e) Any point of Winding to Tank As per CBIP
45 Short Circuit Rating
HV As per IS
LV As per IS
Color Grade
46 Fittings & Accessories
Oil conservator with filler cap. drain
plug
Silicaand plain oil level
gel breather withgauge.
connecting
pipe & oil seal.
Air release
Pressure plugs.device Explosion
release
vent should be Double diaphragm
type.
Oil level gauge
indicator with maximum reading
pointer and
indicator with
electrically max. reading
separate pointer
contacts for
and electrically separate sets of
Thermometer pockets
release cock, shut-off valve on one
side and separate
Sampling sets
valve/Filter of contacts
valve with
threaded adopter (top and bottom).
Drain valve with threaded adopter
Jacking pads, handling and lifting
lugs
Cover lifting eyes
Bi-directional rollers and skids
Radiators
Two-grounding pads
housing control equipment and
terminal connections
Rating and terminal marking plates
Neutral bushing
HT cable end boxes
LT Side
Neutral CT
Routine Test To be Carried Out
1. Measurement of Winding
Resistance
2. Measurement of Voltage Ratio
3.
andMeasurement of displacement.
check of Phase Short Circuit
Impedance (principal tapping,
4. Measurement
when Applicable)of No load loss and
Current.
5. Measurement of Insulation
Resistance
6. Induced Over Voltage withstand
test
7. Separate Source voltage
withstand test.
8. Oil Leakage Test.

List of Accessories

Mandatory Spares
Gauranteed Particulars
IS 1180, Level-2
Outdoor
Copper Wound, Oil Immersed
2000 KVA

11 KV
0.433 KV

104.9 A
2666.8 A
50 Hz
3
Dyn11
Delta
Star

ohms (approx)
ohms (approx)

12KV
1.1KV
ONAN

+5% to -10%

75
28

As per loss class Level 2 of IS-1180


As per loss class Level 2 of IS-1180
As per loss class Level 2 of IS-1180

5.00%
UPF 0.8PF

75
NA

28
3
CRGO

As per CBIP
As per CBIP

As per CBIP

As per CBIP

IS:335-2018

YES
IP:55

Cable box
Bus duct

as per NEMA
As per CBIP
As per CBIP
As per CBIP
As per CBIP
As per CBIP

As per IS
As per IS