Professional Documents
Culture Documents
Reporte
Reporte
1. Project Informa on
Date 2023-9-6
Project name
Project address
Country Venezuela
State
City CARACAS
Client name
Client address
Designed by
Reference
Revision
Al tude(m) 48
Indoor DB temperature in cooling(℃) 26
Indoor WB temperature in cooling(℃) 19
Outdoor DB temperature in cooling(℃) 32
Outdoor WB temperature in cooling(℃) 27.4
Indoor DB temperature in hea ng(℃) 21
Indoor WB temperature in hea ng(℃) 14
Outdoor DB temperature in hea ng(℃) 21.5
Outdoor WB temperature in hea ng(℃) 18.6
1
2.2.2 Refrigerant charge
System name Model Quan ty Unit Descrip on
C1 R410A 0.54 kg Extra Refrigerant Added
C2 R410A 3.11 kg Extra Refrigerant Added
C3 R410A 1.39 kg Extra Refrigerant Added
C4 R410A 1.26 kg Extra Refrigerant Added
Total(R410A) R410A 6.3 kg Extra Refrigerant Added
Notes:
1. MCA: Minimum Circuit Amps. MCA is used to select wire size.The value in above table is for one unit.
2. MFA: Maximum Fuse Amps. MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.The value in above
table is for one unit.
4. C1
4.1 BOM List (C1)
Model Quan ty Unit Descrip on
MVC-224WV2WN1 1 VC Pro Series VRF (220V)
MI2-140T2DHN1 1 Medium Sta c Pressure Duct
MI2-112T2DHN1 1 Medium Sta c Pressure Duct
FQZHN-02D 1 Branch joint
WDC-86E/KD 2 2nd genera on wired controller
R410A 0.54 kg Extra Refrigerant Added
Φ3/8 9 m Copper pipe
Φ5/8 6 m Copper pipe
Φ7/8 3 m Copper pipe
IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
UE 4 MI2-112T2DHN1 26.0/19.0 35,602 28,609 200 21 41,333 200
UE 5 MI2-140T2DHN1 26.0/19.0 44,503 35,920 250 21 52,906 250
2
UE 5 MI2-140T2DHN1 1151.34[SSH] 41[SSH] 40(30~150)
3
RHC Required hea ng capacity
AHC Available hea ng capacity
PI-H Power input in hea ng
COP COP
CR Combina on ra o
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight
4
4.6 Wiring Diagrams (C1)
5. C2
5.1 BOM List (C2)
Model Quan ty Unit Descrip on
MVC-670WV2WN1 1 VC Pro Series VRF (220V)
MI2-140T2DHN1 3 Medium Sta c Pressure Duct
MI2-112T2DHN1 1 Medium Sta c Pressure Duct
MI2-90T2DHN1 2 Medium Sta c Pressure Duct
FQZHN-02D 2 Branch joint
FQZHN-03D 3 Branch joint
WDC-86E/KD 6 2nd genera on wired controller
Φ1<->Φ1-1/8 1 Reducer
R410A 3.11 kg Extra Refrigerant Added
Φ3/8 24 m Copper pipe
Φ1/2 6 m Copper pipe
Φ5/8 18 m Copper pipe
Φ3/4 3 m Copper pipe
Φ7/8 6 m Copper pipe
Φ1-1/8 6 m Copper pipe
Φ1-1/4 3 m Copper pipe
IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
IDU1 MI2-140T2DHN1 26.0/19.0 46,102 37,211 250 21 52,906 250
IDU1 MI2-90T2DHN1 26.0/19.0 29,637 24,039 120 21 33,066 120
IDU1 MI2-140T2DHN1 26.0/19.0 46,102 37,211 250 21 52,906 250
IDU1 MI2-112T2DHN1 26.0/19.0 36,881 29,637 200 21 41,333 200
IDU1 MI2-140T2DHN1 26.0/19.0 46,102 37,211 250 21 52,906 250
IDU1 MI2-90T2DHN1 26.0/19.0 29,637 24,039 120 21 33,066 120
6
ATC Btu/h 234,461
PI-C kW 18.82
EER 3.65
Tmp-H ℃/℃ 21.5/18.6
RHC Btu/h
AHC Btu/h 0
PI-H kW -0.00
COP
CR 106.3
Airflow CFM 11513.37
Sound-Pr 64
Sound-Po
Bas-Refr kg 19.00
Ex-Refr kg 3.11
TCO2 eq. 46.16
MCA A 91
MFA A 100
Power supply V/ph/Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 1585*1615*765
Weight kg 352
7
Defrost (hea ng) 1.000
8
6. C3
6.1 BOM List (C3)
Model Quan ty Unit Descrip on
MVC-224WV2WN1 1 VC Pro Series VRF (220V)
MI2-45T2DHN1 4 Medium Sta c Pressure Duct
MI2-22GDHN1 2 Wall_mounted
FQZHN-01D 4 Branch joint
FQZHN-02D 1 Branch joint
RM12F 2 2nd genera on remote controller
WDC-86E/KD 4 2nd genera on wired controller
R410A 1.39 kg Extra Refrigerant Added
Φ1/4 18 m Copper pipe
Φ3/8 15 m Copper pipe
Φ1/2 18 m Copper pipe
Φ5/8 12 m Copper pipe
Φ7/8 3 m Copper pipe
IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
IDU1 MI2-45T2DHN1 26.0/19.0 15,335 12,609 92 21 16,448 92
IDU1 MI2-45T2DHN1 26.0/19.0 15,335 12,609 92 21 16,448 92
IDU1 MI2-45T2DHN1 26.0/19.0 15,335 12,609 92 21 16,448 92
IDU1 MI2-45T2DHN1 26.0/19.0 15,335 12,609 92 21 16,448 92
IDU2 MI2-22GDHN1 26.0/19.0 7,497 6,475 28 21 7,936 28
IDU2 MI2-22GDHN1 26.0/19.0 7,497 6,475 28 21 7,936 28
9
IDU Name Model Airflow(CFM) Sound-Pr dB(A) ESP(Pa)
IDU1 MI2-45T2DHN1 469.93[SSH] 36[SSH] 10(0~70)
IDU1 MI2-45T2DHN1 469.93[SSH] 36[SSH] 10(0~70)
IDU1 MI2-45T2DHN1 469.93[SSH] 36[SSH] 10(0~70)
IDU1 MI2-45T2DHN1 469.93[SSH] 36[SSH] 10(0~70)
IDU2 MI2-22GDHN1 247.89[SSH] 31[SSH] 0
IDU2 MI2-22GDHN1 247.89[SSH] 31[SSH] 0
10
Dimension (WxHxD) mm 960*1615*765
Weight kg 193
11
(1) 76,432 FQZHN-02D
(2) 46,064 FQZHN-01D
(3) 30,709 FQZHN-01D
(4) 30,368 FQZHN-01D
(5) 22,861 FQZHN-01D
12
7. C4
7.1 BOM List (C4)
Model Quan ty Unit Descrip on
MVC-335WV2WN1 1 VC Pro Series VRF (220V)
MI2-112T2DHN1 2 Medium Sta c Pressure Duct
MI2-45T2DHN1 1 Medium Sta c Pressure Duct
MI2-36T2DHN1 1 Medium Sta c Pressure Duct
FQZHN-01D 2 Branch joint
FQZHN-02D 1 Branch joint
WDC-86E/KD 4 2nd genera on wired controller
Φ1<->Φ1-1/8 1 Reducer
R410A 1.26 kg Extra Refrigerant Added
Φ1/4 6 m Copper pipe
Φ3/8 12 m Copper pipe
Φ1/2 9 m Copper pipe
Φ5/8 12 m Copper pipe
Φ1-1/8 3 m Copper pipe
IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
IDU1 MI2-112T2DHN1 26.0/19.0 38,179 30,680 200 21 41,333 200
IDU1 MI2-45T2DHN1 26.0/19.0 15,340 12,613 92 21 16,448 92
IDU1 MI2-36T2DHN1 26.0/19.0 12,272 10,227 45 21 13,090 45
IDU1 MI2-112T2DHN1 26.0/19.0 38,179 30,680 200 21 41,333 200
13
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in hea ng
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight
14
Longest equivalent length a er first branch 90.00(m) 6.50(m)
Indoor unit to nearest branch length 40.00(m) 3.00(m)
Length difference between longest and shortest distance to indoor units 40.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU up) 90.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU down) 110.00(m) 0.00(m)
Height difference between indoor units 30.00(m) 0.00(m)
Combina on ra o 50-130% 91.04%
IDU quan ty 20 4
15
8. Centralized Control Solu on
8.1 Centralized Controller List
The centralized control system of this project is full output regardless of whether the system is selected.
16