Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

MSSP Report

1. Project Informa on
Date 2023-9-6
Project name
Project address
Country Venezuela
State
City CARACAS
Client name
Client address
Designed by
Reference
Revision
Al tude(m) 48
Indoor DB temperature in cooling(℃) 26
Indoor WB temperature in cooling(℃) 19
Outdoor DB temperature in cooling(℃) 32
Outdoor WB temperature in cooling(℃) 27.4
Indoor DB temperature in hea ng(℃) 21
Indoor WB temperature in hea ng(℃) 14
Outdoor DB temperature in hea ng(℃) 21.5
Outdoor WB temperature in hea ng(℃) 18.6

2. Overall Material List


2.1 Equipment List
Model Quan ty Descrip on
MVC-670WV2WN1 1 VC Pro Series VRF (220V)
MVC-335WV2WN1 1 VC Pro Series VRF (220V)
MVC-224WV2WN1 2 VC Pro Series VRF (220V)
MI2-140T2DHN1 4 Medium Sta c Pressure Duct
MI2-112T2DHN1 4 Medium Sta c Pressure Duct
MI2-90T2DHN1 2 Medium Sta c Pressure Duct
MI2-45T2DHN1 5 Medium Sta c Pressure Duct
MI2-36T2DHN1 1 Medium Sta c Pressure Duct
MI2-22GDHN1 2 Wall_mounted
FQZHN-01D 6 Branch joint
FQZHN-03D 3 Branch joint
FQZHN-02D 5 Branch joint
Φ1<->Φ1-1/8 2 Reducer
RM12F 2 2nd genera on remote controller
WDC-86E/KD 16 2nd genera on wired controller

2.2 Field Providing List


2.2.1 Refrigerant Piping Materials
Model Quan ty Unit Descrip on
Φ1/4 24 m Copper pipe
Φ3/8 60 m Copper pipe
Φ1/2 33 m Copper pipe
Φ5/8 48 m Copper pipe
Φ3/4 3 m Copper pipe
Φ7/8 12 m Copper pipe
Φ1-1/8 9 m Copper pipe
Φ1-1/4 3 m Copper pipe
Insula on casing for piping All refrigerant piping and branch joints should be completely insulated.

Recommended insula on casing thickness:


Piping size Thickness
Humidity<80%RH Humidity≥80%RH
Φ6.35~Φ38.1mm ≥15mm ≥20mm
Φ41.3~Φ38.1mm ≥20mm ≥25mm

1
2.2.2 Refrigerant charge
System name Model Quan ty Unit Descrip on
C1 R410A 0.54 kg Extra Refrigerant Added
C2 R410A 3.11 kg Extra Refrigerant Added
C3 R410A 1.39 kg Extra Refrigerant Added
C4 R410A 1.26 kg Extra Refrigerant Added
Total(R410A) R410A 6.3 kg Extra Refrigerant Added

2.2.3 Electrical cables


Type Size Length
Power supply cable Select based on MCA of each unit According to the actual system design
Communica on cable 0.75mm2 3-core shielded According to the actual system design

3. Overall Electrical Characteris cs


Model Quan ty Power supply MCA(A) MFA(A)
MVC-670WV2WN1 1 220V-3ph-60Hz 91.00 100
MVC-335WV2WN1 1 220V-3ph-60Hz 43.00 50
MVC-224WV2WN1 2 220V-3ph-60Hz 42.50 50
MI2-140T2DHN1 4 220-240V-50/60Hz 2.60 15
MI2-112T2DHN1 4 220-240V-50/60Hz 1.50 15
MI2-90T2DHN1 2 220-240V-50/60Hz 1.30 15
MI2-45T2DHN1 5 220-240V-50/60Hz 1.00 15
MI2-36T2DHN1 1 220-240V-50/60Hz 0.77 15
MI2-22GDHN1 2 220-240V-50/60Hz 0.32 15

Notes:

1. MCA: Minimum Circuit Amps. MCA is used to select wire size.The value in above table is for one unit.

2. MFA: Maximum Fuse Amps. MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.The value in above
table is for one unit.

4. C1
4.1 BOM List (C1)
Model Quan ty Unit Descrip on
MVC-224WV2WN1 1 VC Pro Series VRF (220V)
MI2-140T2DHN1 1 Medium Sta c Pressure Duct
MI2-112T2DHN1 1 Medium Sta c Pressure Duct
FQZHN-02D 1 Branch joint
WDC-86E/KD 2 2nd genera on wired controller
R410A 0.54 kg Extra Refrigerant Added
Φ3/8 9 m Copper pipe
Φ5/8 6 m Copper pipe
Φ7/8 3 m Copper pipe

4.2 Indoor Unit Details (C1)


4.2.1 Indoor Unit Details Table
IDU Name Model Weight(kg) Dimension(WxHxD)(mm) Power supply MCA(A) MFA(A)
UE 4 MI2-112T2DHN1 37 1230*270*775 220-240V-50/60Hz 1.5 15
UE 5 MI2-140T2DHN1 46.5 1290*300*865 220-240V-50/60Hz 2.6 15

IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
UE 4 MI2-112T2DHN1 26.0/19.0 35,602 28,609 200 21 41,333 200
UE 5 MI2-140T2DHN1 26.0/19.0 44,503 35,920 250 21 52,906 250

IDU Name Model Airflow(CFM) Sound-Pr dB(A) ESP(Pa)


UE 4 MI2-112T2DHN1 881.12[SSH] 39[SSH] 20(10~100)

2
UE 5 MI2-140T2DHN1 1151.34[SSH] 41[SSH] 40(30~150)

IDU Name Model Piping Length to 1st Y Joint(m)


UE 4 MI2-112T2DHN1 3.00
UE 5 MI2-140T2DHN1 3.00

4.2.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in hea ng (Dry bulb temp.)
RHC Required hea ng capacity
AHC Available hea ng capacity
Tdis-H Indoor unit discharge air temperature in hea ng
Airflow Indoor unit airflow (High/Medium/Low)
ESP External sta c pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in hea ng
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

4.3 Outdoor Unit Details (C1)


4.3.1 Outdoor Unit Details Table
Model MVC-224WV2WN1
Module MVC-224WV2WN1
Tmp-C ℃ 32
RTC Btu/h
ATC Btu/h 80,105
PI-C kW 5.02
EER 4.68
Tmp-H ℃/℃ 21.5/18.6
RHC Btu/h
AHC Btu/h 0
PI-H kW -0.00
COP
CR 112.5
Airflow CFM 6109.13
Sound-Pr 57
Sound-Po
Bas-Refr kg 8.00
Ex-Refr kg 0.54
TCO2 eq. 17.83
MCA A 42.5
MFA A 50
Power supply V/ph/Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 960*1615*765
Weight kg 193

4.3.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Outdoor condi ons in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity
PI-C Power input in cooling
EER EER
Tmp-H Indoor condi ons in hea ng (Dry bulb temp. / Wet bulb temp. / RH)

3
RHC Required hea ng capacity
AHC Available hea ng capacity
PI-H Power input in hea ng
COP COP
CR Combina on ra o
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight

4.4 Piping Limita ons (C1)


4.4.1 Piping Limita ons
Item Capability Actual Value
Total piping length 1000.00(m) 9.50(m)
Longest actual length 175.00(m) 6.00(m)
Longest equivalent length 200.00(m) 6.50(m)
Longest equivalent length a er first branch 90.00(m) 3.00(m)
Indoor unit to nearest branch length 40.00(m) 3.00(m)
Length difference between longest and shortest distance to indoor units 40.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU up) 90.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU down) 110.00(m) 0.00(m)
Height difference between indoor units 30.00(m) 0.00(m)
Combina on ra o 50-130% 112.50%
IDU quan ty 13 2

4.4.2 Correc on Factors


Item Correc on factor
Al tude (indoor unit) 0.999
Al tude (outdoor unit) 1.000
Piping (cooling) 1.000
Piping (hea ng) 1.000
Defrost (hea ng) 1.000

4.4.3 Piping Details Table


No. Length(m) Piping diameter
(1) 3.00 Φ7/8/Φ3/8
(2) 3.00 Φ5/8/Φ3/8
(3) 3.00 Φ5/8/Φ3/8

4.4.4 Branch Joints Details Table


No. Load(Btu/h) Model
(1) 85,986 FQZHN-02D

4.4.5 Reducer Details Table

4.5 Piping Diagrams (C1)

4
4.6 Wiring Diagrams (C1)

5. C2
5.1 BOM List (C2)
Model Quan ty Unit Descrip on
MVC-670WV2WN1 1 VC Pro Series VRF (220V)
MI2-140T2DHN1 3 Medium Sta c Pressure Duct
MI2-112T2DHN1 1 Medium Sta c Pressure Duct
MI2-90T2DHN1 2 Medium Sta c Pressure Duct
FQZHN-02D 2 Branch joint
FQZHN-03D 3 Branch joint
WDC-86E/KD 6 2nd genera on wired controller
Φ1<->Φ1-1/8 1 Reducer
R410A 3.11 kg Extra Refrigerant Added
Φ3/8 24 m Copper pipe
Φ1/2 6 m Copper pipe
Φ5/8 18 m Copper pipe
Φ3/4 3 m Copper pipe
Φ7/8 6 m Copper pipe
Φ1-1/8 6 m Copper pipe
Φ1-1/4 3 m Copper pipe

5.2 Indoor Unit Details (C2)


5
5.2.1 Indoor Unit Details Table
IDU Name Model Weight(kg) Dimension(WxHxD)(mm) Power supply MCA(A) MFA(A)
IDU1 MI2-140T2DHN1 46.5 1290*300*865 220-240V-50/60Hz 2.6 15
IDU1 MI2-90T2DHN1 37 1230*270*775 220-240V-50/60Hz 1.3 15
IDU1 MI2-140T2DHN1 46.5 1290*300*865 220-240V-50/60Hz 2.6 15
IDU1 MI2-112T2DHN1 37 1230*270*775 220-240V-50/60Hz 1.5 15
IDU1 MI2-140T2DHN1 46.5 1290*300*865 220-240V-50/60Hz 2.6 15
IDU1 MI2-90T2DHN1 37 1230*270*775 220-240V-50/60Hz 1.3 15

IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
IDU1 MI2-140T2DHN1 26.0/19.0 46,102 37,211 250 21 52,906 250
IDU1 MI2-90T2DHN1 26.0/19.0 29,637 24,039 120 21 33,066 120
IDU1 MI2-140T2DHN1 26.0/19.0 46,102 37,211 250 21 52,906 250
IDU1 MI2-112T2DHN1 26.0/19.0 36,881 29,637 200 21 41,333 200
IDU1 MI2-140T2DHN1 26.0/19.0 46,102 37,211 250 21 52,906 250
IDU1 MI2-90T2DHN1 26.0/19.0 29,637 24,039 120 21 33,066 120

IDU Name Model Airflow(CFM) Sound-Pr dB(A) ESP(Pa)


IDU1 MI2-140T2DHN1 1151.34[SSH] 41[SSH] 40(30~150)
IDU1 MI2-90T2DHN1 740.14[SSH] 37[SSH] 20(10~100)
IDU1 MI2-140T2DHN1 1151.34[SSH] 41[SSH] 40(30~150)
IDU1 MI2-112T2DHN1 881.12[SSH] 39[SSH] 20(10~100)
IDU1 MI2-140T2DHN1 1151.34[SSH] 41[SSH] 40(30~150)
IDU1 MI2-90T2DHN1 740.14[SSH] 37[SSH] 20(10~100)

IDU Name Model Piping Length to 1st Y Joint(m)


IDU1 MI2-140T2DHN1 6.50
IDU1 MI2-90T2DHN1 10.00
IDU1 MI2-140T2DHN1 10.00
IDU1 MI2-112T2DHN1 10.00
IDU1 MI2-140T2DHN1 10.00
IDU1 MI2-90T2DHN1 6.50

5.2.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in hea ng (Dry bulb temp.)
RHC Required hea ng capacity
AHC Available hea ng capacity
Tdis-H Indoor unit discharge air temperature in hea ng
Airflow Indoor unit airflow (High/Medium/Low)
ESP External sta c pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in hea ng
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

5.3 Outdoor Unit Details (C2)


5.3.1 Outdoor Unit Details Table
Model MVC-670WV2WN1
Module MVC-670WV2WN1
Tmp-C ℃ 32
RTC Btu/h

6
ATC Btu/h 234,461
PI-C kW 18.82
EER 3.65
Tmp-H ℃/℃ 21.5/18.6
RHC Btu/h
AHC Btu/h 0
PI-H kW -0.00
COP
CR 106.3
Airflow CFM 11513.37
Sound-Pr 64
Sound-Po
Bas-Refr kg 19.00
Ex-Refr kg 3.11
TCO2 eq. 46.16
MCA A 91
MFA A 100
Power supply V/ph/Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 1585*1615*765
Weight kg 352

5.3.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Outdoor condi ons in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity
PI-C Power input in cooling
EER EER
Tmp-H Indoor condi ons in hea ng (Dry bulb temp. / Wet bulb temp. / RH)
RHC Required hea ng capacity
AHC Available hea ng capacity
PI-H Power input in hea ng
COP COP
CR Combina on ra o
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight

5.4 Piping Limita ons (C2)


5.4.1 Piping Limita ons
Item Capability Actual Value
Total piping length 1000.00(m) 35.50(m)
Longest actual length 175.00(m) 12.00(m)
Longest equivalent length 200.00(m) 13.50(m)
Longest equivalent length a er first branch 90.00(m) 10.00(m)
Indoor unit to nearest branch length 40.00(m) 3.00(m)
Length difference between longest and shortest distance to indoor units 40.00(m) 3.50(m)
Height difference between indoor and outdoor unit(ODU up) 90.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU down) 110.00(m) 0.00(m)
Height difference between indoor units 30.00(m) 0.00(m)
Combina on ra o 50-130% 106.27%
IDU quan ty 39 6

5.4.2 Correc on Factors


Item Correc on factor
Al tude (indoor unit) 0.999
Al tude (outdoor unit) 1.000
Piping (cooling) 1.000
Piping (hea ng) 1.000

7
Defrost (hea ng) 1.000

5.4.3 Piping Details Table


No. Length(m) Piping diameter
(1) 3.00 Φ1-1/4/Φ3/4
(2) 3.00 Φ1-1/8/Φ1/2
(3) 3.00 Φ1-1/8/Φ1/2
(4) 3.00 Φ5/8/Φ3/8
(5) 3.00 Φ7/8/Φ3/8
(6) 3.00 Φ7/8/Φ3/8
(7) 3.00 Φ5/8/Φ3/8
(8) 3.00 Φ5/8/Φ3/8
(9) 3.00 Φ5/8/Φ3/8
(10) 3.00 Φ5/8/Φ3/8
(11) 3.00 Φ5/8/Φ3/8

5.4.4 Branch Joints Details Table


No. Load(Btu/h) Model
(1) 242,944 FQZHN-03D
(2) 126,249 FQZHN-03D
(3) 116,695 FQZHN-03D
(4) 78,479 FQZHN-02D
(5) 85,986 FQZHN-02D

5.4.5 Reducer Details Table


Reducer Name Descrip on
J1-G1 Φ1<->Φ1-1/8

5.5 Piping Diagrams (C2)

5.6 Wiring Diagrams (C2)

8
6. C3
6.1 BOM List (C3)
Model Quan ty Unit Descrip on
MVC-224WV2WN1 1 VC Pro Series VRF (220V)
MI2-45T2DHN1 4 Medium Sta c Pressure Duct
MI2-22GDHN1 2 Wall_mounted
FQZHN-01D 4 Branch joint
FQZHN-02D 1 Branch joint
RM12F 2 2nd genera on remote controller
WDC-86E/KD 4 2nd genera on wired controller
R410A 1.39 kg Extra Refrigerant Added
Φ1/4 18 m Copper pipe
Φ3/8 15 m Copper pipe
Φ1/2 18 m Copper pipe
Φ5/8 12 m Copper pipe
Φ7/8 3 m Copper pipe

6.2 Indoor Unit Details (C3)


6.2.1 Indoor Unit Details Table
IDU Name Model Weight(kg) Dimension(WxHxD)(mm) Power supply MCA(A) MFA(A)
IDU1 MI2-45T2DHN1 21.5 1000*210*500 220-240V-50/60Hz 1 15
IDU1 MI2-45T2DHN1 21.5 1000*210*500 220-240V-50/60Hz 1 15
IDU1 MI2-45T2DHN1 21.5 1000*210*500 220-240V-50/60Hz 1 15
IDU1 MI2-45T2DHN1 21.5 1000*210*500 220-240V-50/60Hz 1 15
IDU2 MI2-22GDHN1 8.4 835*280*203 220-240V-50/60Hz 0.32 15
IDU2 MI2-22GDHN1 8.4 835*280*203 220-240V-50/60Hz 0.32 15

IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
IDU1 MI2-45T2DHN1 26.0/19.0 15,335 12,609 92 21 16,448 92
IDU1 MI2-45T2DHN1 26.0/19.0 15,335 12,609 92 21 16,448 92
IDU1 MI2-45T2DHN1 26.0/19.0 15,335 12,609 92 21 16,448 92
IDU1 MI2-45T2DHN1 26.0/19.0 15,335 12,609 92 21 16,448 92
IDU2 MI2-22GDHN1 26.0/19.0 7,497 6,475 28 21 7,936 28
IDU2 MI2-22GDHN1 26.0/19.0 7,497 6,475 28 21 7,936 28

9
IDU Name Model Airflow(CFM) Sound-Pr dB(A) ESP(Pa)
IDU1 MI2-45T2DHN1 469.93[SSH] 36[SSH] 10(0~70)
IDU1 MI2-45T2DHN1 469.93[SSH] 36[SSH] 10(0~70)
IDU1 MI2-45T2DHN1 469.93[SSH] 36[SSH] 10(0~70)
IDU1 MI2-45T2DHN1 469.93[SSH] 36[SSH] 10(0~70)
IDU2 MI2-22GDHN1 247.89[SSH] 31[SSH] 0
IDU2 MI2-22GDHN1 247.89[SSH] 31[SSH] 0

IDU Name Model Piping Length to 1st Y Joint(m)


IDU1 MI2-45T2DHN1 10.00
IDU1 MI2-45T2DHN1 10.00
IDU1 MI2-45T2DHN1 6.50
IDU1 MI2-45T2DHN1 10.00
IDU2 MI2-22GDHN1 10.00
IDU2 MI2-22GDHN1 6.50

6.2.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in hea ng (Dry bulb temp.)
RHC Required hea ng capacity
AHC Available hea ng capacity
Tdis-H Indoor unit discharge air temperature in hea ng
Airflow Indoor unit airflow (High/Medium/Low)
ESP External sta c pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in hea ng
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

6.3 Outdoor Unit Details (C3)


6.3.1 Outdoor Unit Details Table
Model MVC-224WV2WN1
Module MVC-224WV2WN1
Tmp-C ℃ 32
RTC Btu/h
ATC Btu/h 76,335
PI-C kW 4.77
EER 4.69
Tmp-H ℃/℃ 21.5/18.6
RHC Btu/h
AHC Btu/h 0
PI-H kW -0.00
COP
CR 100.0
Airflow CFM 6109.13
Sound-Pr 57
Sound-Po
Bas-Refr kg 8.00
Ex-Refr kg 1.39
TCO2 eq. 19.61
MCA A 42.5
MFA A 50
Power supply V/ph/Hz 220V-3ph-60Hz

10
Dimension (WxHxD) mm 960*1615*765
Weight kg 193

6.3.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Outdoor condi ons in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity
PI-C Power input in cooling
EER EER
Tmp-H Indoor condi ons in hea ng (Dry bulb temp. / Wet bulb temp. / RH)
RHC Required hea ng capacity
AHC Available hea ng capacity
PI-H Power input in hea ng
COP COP
CR Combina on ra o
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight

6.4 Piping Limita ons (C3)


6.4.1 Piping Limita ons
Item Capability Actual Value
Total piping length 1000.00(m) 35.50(m)
Longest actual length 175.00(m) 12.00(m)
Longest equivalent length 200.00(m) 13.50(m)
Longest equivalent length a er first branch 90.00(m) 10.00(m)
Indoor unit to nearest branch length 40.00(m) 3.00(m)
Length difference between longest and shortest distance to indoor units 40.00(m) 3.50(m)
Height difference between indoor and outdoor unit(ODU up) 90.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU down) 110.00(m) 0.00(m)
Height difference between indoor units 30.00(m) 0.00(m)
Combina on ra o 50-130% 100.00%
IDU quan ty 13 6

6.4.2 Correc on Factors


Item Correc on factor
Al tude (indoor unit) 0.999
Al tude (outdoor unit) 1.000
Piping (cooling) 1.000
Piping (hea ng) 1.000
Defrost (hea ng) 1.000

6.4.3 Piping Details Table


No. Length(m) Piping diameter
(1) 3.00 Φ7/8/Φ3/8
(2) 3.00 Φ5/8/Φ3/8
(3) 3.00 Φ5/8/Φ3/8
(4) 3.00 Φ5/8/Φ3/8
(5) 3.00 Φ1/2/Φ1/4
(6) 3.00 Φ1/2/Φ1/4
(7) 3.00 Φ1/2/Φ1/4
(8) 3.00 Φ5/8/Φ3/8
(9) 3.00 Φ1/2/Φ1/4
(10) 3.00 Φ1/2/Φ1/4
(11) 3.00 Φ1/2/Φ1/4

6.4.4 Branch Joints Details Table


No. Load(Btu/h) Model

11
(1) 76,432 FQZHN-02D
(2) 46,064 FQZHN-01D
(3) 30,709 FQZHN-01D
(4) 30,368 FQZHN-01D
(5) 22,861 FQZHN-01D

6.4.5 Reducer Details Table

6.5 Piping Diagrams (C3)

6.6 Wiring Diagrams (C3)

12
7. C4
7.1 BOM List (C4)
Model Quan ty Unit Descrip on
MVC-335WV2WN1 1 VC Pro Series VRF (220V)
MI2-112T2DHN1 2 Medium Sta c Pressure Duct
MI2-45T2DHN1 1 Medium Sta c Pressure Duct
MI2-36T2DHN1 1 Medium Sta c Pressure Duct
FQZHN-01D 2 Branch joint
FQZHN-02D 1 Branch joint
WDC-86E/KD 4 2nd genera on wired controller
Φ1<->Φ1-1/8 1 Reducer
R410A 1.26 kg Extra Refrigerant Added
Φ1/4 6 m Copper pipe
Φ3/8 12 m Copper pipe
Φ1/2 9 m Copper pipe
Φ5/8 12 m Copper pipe
Φ1-1/8 3 m Copper pipe

7.2 Indoor Unit Details (C4)


7.2.1 Indoor Unit Details Table
IDU Name Model Weight(kg) Dimension(WxHxD)(mm) Power supply MCA(A) MFA(A)
IDU1 MI2-112T2DHN1 37 1230*270*775 220-240V-50/60Hz 1.5 15
IDU1 MI2-45T2DHN1 21.5 1000*210*500 220-240V-50/60Hz 1 15
IDU1 MI2-36T2DHN1 18 780*210*500 220-240V-50/60Hz 0.77 15
IDU1 MI2-112T2DHN1 37 1230*270*775 220-240V-50/60Hz 1.5 15

IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
IDU1 MI2-112T2DHN1 26.0/19.0 38,179 30,680 200 21 41,333 200
IDU1 MI2-45T2DHN1 26.0/19.0 15,340 12,613 92 21 16,448 92
IDU1 MI2-36T2DHN1 26.0/19.0 12,272 10,227 45 21 13,090 45
IDU1 MI2-112T2DHN1 26.0/19.0 38,179 30,680 200 21 41,333 200

IDU Name Model Airflow(CFM) Sound-Pr dB(A) ESP(Pa)


IDU1 MI2-112T2DHN1 881.12[SSH] 39[SSH] 20(10~100)
IDU1 MI2-45T2DHN1 469.93[SSH] 36[SSH] 10(0~70)
IDU1 MI2-36T2DHN1 340.70[SSH] 33[SSH] 10(0~70)
IDU1 MI2-112T2DHN1 881.12[SSH] 39[SSH] 20(10~100)

IDU Name Model Piping Length to 1st Y Joint(m)


IDU1 MI2-112T2DHN1 6.50
IDU1 MI2-45T2DHN1 6.50
IDU1 MI2-36T2DHN1 6.50
IDU1 MI2-112T2DHN1 6.50

7.2.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in hea ng (Dry bulb temp.)
RHC Required hea ng capacity
AHC Available hea ng capacity
Tdis-H Indoor unit discharge air temperature in hea ng
Airflow Indoor unit airflow (High/Medium/Low)
ESP External sta c pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps

13
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in hea ng
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

7.3 Outdoor Unit Details (C4)


7.3.1 Outdoor Unit Details Table
Model MVC-335WV2WN1
Module MVC-335WV2WN1
Tmp-C ℃ 32
RTC Btu/h
ATC Btu/h 103,970
PI-C kW 6.40
EER 4.76
Tmp-H ℃/℃ 21.5/18.6
RHC Btu/h
AHC Btu/h 0
PI-H kW -0.00
COP
CR 91.0
Airflow CFM 6344.10
Sound-Pr 60
Sound-Po
Bas-Refr kg 8.00
Ex-Refr kg 1.26
TCO2 eq. 19.33
MCA A 43
MFA A 50
Power supply V/ph/Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 960*1615*765
Weight kg 193

7.3.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Outdoor condi ons in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity
PI-C Power input in cooling
EER EER
Tmp-H Indoor condi ons in hea ng (Dry bulb temp. / Wet bulb temp. / RH)
RHC Required hea ng capacity
AHC Available hea ng capacity
PI-H Power input in hea ng
COP COP
CR Combina on ra o
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight

7.4 Piping Limita ons (C4)


7.4.1 Piping Limita ons
Item Capability Actual Value
Total piping length 1000.00(m) 22.50(m)
Longest actual length 175.00(m) 9.00(m)
Longest equivalent length 200.00(m) 10.00(m)

14
Longest equivalent length a er first branch 90.00(m) 6.50(m)
Indoor unit to nearest branch length 40.00(m) 3.00(m)
Length difference between longest and shortest distance to indoor units 40.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU up) 90.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU down) 110.00(m) 0.00(m)
Height difference between indoor units 30.00(m) 0.00(m)
Combina on ra o 50-130% 91.04%
IDU quan ty 20 4

7.4.2 Correc on Factors


Item Correc on factor
Al tude (indoor unit) 0.999
Al tude (outdoor unit) 1.000
Piping (cooling) 1.000
Piping (hea ng) 1.000
Defrost (hea ng) 1.000

7.4.3 Piping Details Table


No. Length(m) Piping diameter
(1) 3.00 Φ1-1/8/Φ1/2
(2) 3.00 Φ5/8/Φ3/8
(3) 3.00 Φ5/8/Φ3/8
(4) 3.00 Φ5/8/Φ3/8
(5) 3.00 Φ1/2/Φ1/4
(6) 3.00 Φ1/2/Φ1/4
(7) 3.00 Φ5/8/Φ3/8

7.4.4 Branch Joints Details Table


No. Load(Btu/h) Model
(1) 104,070 FQZHN-02D
(2) 53,571 FQZHN-01D
(3) 50,500 FQZHN-01D

7.4.5 Reducer Details Table


Reducer Name Descrip on
J1-G1 Φ1<->Φ1-1/8

7.5 Piping Diagrams (C4)

7.6 Wiring Diagrams (C4)

15
8. Centralized Control Solu on
8.1 Centralized Controller List
The centralized control system of this project is full output regardless of whether the system is selected.

16

You might also like