MSSP Report

1. Project Informa on
Date 2023-9-4
Project name Pales na Mall
Project address
Country Venezuela
State
City CARACAS
Client name
Client address
Designed by
Reference New Project
Revision
Al tude(m) 48
Indoor DB temperature in cooling(℃) 26
Indoor WB temperature in cooling(℃) 19
Outdoor DB temperature in cooling(℃) 32
Outdoor WB temperature in cooling(℃) 27.4
Indoor DB temperature in hea ng(℃) 21
Indoor WB temperature in hea ng(℃) 14
Outdoor DB temperature in hea ng(℃) 21.5
Outdoor WB temperature in hea ng(℃) 18.6

2. Overall Material List


2.1 Equipment List
Model Quan ty Descrip on
MVC-850WV2WN1 3 VC Pro Series VRF (220V)
MVC-730WV2WN1 9 VC Pro Series VRF (220V)
MVC-560WV2WN1 2 VC Pro Series VRF (220V)
MI2-560T1DHN1 18 High Sta c Pressure Duct
MI2-450T1DHN1 1 High Sta c Pressure Duct
FQZHW-02N1E 1 Branch joint
FQZHW-03N1E 4 Branch joint
FQZHN-04D 6 Branch joint
FQZHN-05D 7 Branch joint
FQZHN-07D 1 Branch joint
Φ1-1/2<->Φ1-5/8 6 Reducer
Φ1-1/4<->Φ1-3/8 7 Reducer
Φ1-1/8<->Φ1-1/4 7 Reducer
WDC-86E/KD 19 2nd genera on wired controller

2.2 Field Providing List


2.2.1 Refrigerant Piping Materials
Model Quan ty Unit Descrip on
Φ5/8 63 m Copper pipe
Φ3/4 63 m Copper pipe
Φ7/8 24 m Copper pipe
Φ1-1/8 60 m Copper pipe
Φ1-1/4 6 m Copper pipe
Φ1-3/8 36 m Copper pipe
Φ1-5/8 39 m Copper pipe
Φ1-3/4 12 m Copper pipe
Φ2-1/8 3 m Copper pipe
Insula on casing for piping All refrigerant piping and branch joints should be completely insulated.

Recommended insula on casing thickness:


Piping size Thickness
Humidity<80%RH Humidity≥80%RH
Φ6.35~Φ38.1mm ≥15mm ≥20mm
Φ41.3~Φ38.1mm ≥20mm ≥25mm

1
2.2.2 Refrigerant charge
System name Model Quan ty Unit Descrip on
PB-UC 1 R410A 11.95 kg Extra Refrigerant Added
PB-UC 2 R410A 8.9 kg Extra Refrigerant Added
SOT UC 1 R410A 8.9 kg Extra Refrigerant Added
SOT UC 2 R410A 8.9 kg Extra Refrigerant Added
SOT UC 3 R410A 3.08 kg Extra Refrigerant Added
Total(R410A) R410A 41.73 kg Extra Refrigerant Added

2.2.3 Electrical cables


Type Size Length
Power supply cable Select based on MCA of each unit According to the actual system design
Communica on cable 0.75mm2 3-core shielded According to the actual system design

3. Overall Electrical Characteris cs


Model Quan ty Power supply MCA(A) MFA(A)
MVC-850WV2WN1 3 220V-3ph-60Hz 92,50 100
MVC-730WV2WN1 9 220V-3ph-60Hz 91,50 100
MVC-560WV2WN1 2 220V-3ph-60Hz 86,00 100
MI2-560T1DHN1 18 220-240V-50/60Hz 15,40 30
MI2-450T1DHN1 1 220-240V-50/60Hz 12,50 30

Notes:

1. MCA: Minimum Circuit Amps. MCA is used to select wire size.The value in above table is for one unit.

2. MFA: Maximum Fuse Amps. MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.The value in above
table is for one unit.

4. PB-UC 1
4.1 BOM List (PB-UC 1)
Model Quan ty Unit Descrip on
MVC-850WV2WN1 3 VC Pro Series VRF (220V)
MI2-560T1DHN1 4 High Sta c Pressure Duct
MI2-450T1DHN1 1 High Sta c Pressure Duct
FQZHW-03N1E 1 Branch joint
FQZHN-04D 2 Branch joint
FQZHN-05D 1 Branch joint
FQZHN-07D 1 Branch joint
WDC-86E/KD 5 2nd genera on wired controller
Φ1-1/2<->Φ1-5/8 2 Reducer
Φ1-1/4<->Φ1-3/8 1 Reducer
Φ1-1/8<->Φ1-1/4 1 Reducer
R410A 11.95 kg Extra Refrigerant Added
Φ5/8 15 m Copper pipe
Φ3/4 15 m Copper pipe
Φ7/8 6 m Copper pipe
Φ1-1/8 18 m Copper pipe
Φ1-3/8 9 m Copper pipe
Φ1-5/8 9 m Copper pipe
Φ1-3/4 3 m Copper pipe
Φ2-1/8 3 m Copper pipe

4.2 Indoor Unit Details (PB-UC 1)


4.2.1 Indoor Unit Details Table
IDU Name Model Weight(kg) Dimension(WxHxD)(mm) Power supply MCA(A) MFA(A)
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30

2
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU2 MI2-450T1DHN1 220 2010*680*905 220-240V-50/60Hz 12,5 30

IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
IDU1 MI2-560T1DHN1 26,0/19,0 184,961 149,290 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 184,961 149,290 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 184,961 149,290 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 184,961 149,290 2272 21 208,316 2272
IDU2 MI2-450T1DHN1 26,0/19,0 148,629 120,225 1800 21 165,330 1800

IDU Name Model Airflow(CFM) Sound-Pr dB(A) ESP(Pa)


IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU2 MI2-450T1DHN1 3826[1] 60[SSH] 300(100-400)

IDU Name Model Piping Length to 1st Y Joint(m)


IDU1 MI2-560T1DHN1 10,00
IDU1 MI2-560T1DHN1 10,00
IDU1 MI2-560T1DHN1 10,00
IDU1 MI2-560T1DHN1 10,00
IDU2 MI2-450T1DHN1 3,00

4.2.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in hea ng (Dry bulb temp.)
RHC Required hea ng capacity
AHC Available hea ng capacity
Tdis-H Indoor unit discharge air temperature in hea ng
Airflow Indoor unit airflow (High/Medium/Low)
ESP External sta c pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in hea ng
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

4.3 Outdoor Unit Details (PB-UC 1)


4.3.1 Outdoor Unit Details Table
Model MVC-2550WV2WN1
Module MVC-850WV2WN1 MVC-850WV2WN1 MVC-850WV2WN1
Tmp-C ℃ 32
RTC Btu/h
ATC Btu/h 888,473
PI-C kW 76,97
EER 3,38
Tmp-H ℃/℃ 21,5/18,6
RHC Btu/h
AHC Btu/h 0
PI-H kW -0,00
COP
CR 105,5

3
Airflow CFM 12100,78 12100,78 12100,78
Sound-Pr 64 64 64
Sound-Po
Bas-Refr kg 57,00
Ex-Refr kg 11,95
TCO2 eq. 143,97
MCA A 92,5 92,5 92,5
MFA A 100 100 100
Power supply V/ph/Hz 220V-3ph-60Hz 220V-3ph-60Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 1585*1615*765 1585*1615*765 1585*1615*765
Weight kg 352 352 352

4.3.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Outdoor condi ons in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity
PI-C Power input in cooling
EER EER
Tmp-H Indoor condi ons in hea ng (Dry bulb temp. / Wet bulb temp. / RH)
RHC Required hea ng capacity
AHC Available hea ng capacity
PI-H Power input in hea ng
COP COP
CR Combina on ra o
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight

4.4 Piping Limita ons (PB-UC 1)


4.4.1 Piping Limita ons
Item Capability Actual Value
Total piping length 1000,00(m) 29,00(m)
Longest actual length 175,00(m) 12,00(m)
Longest equivalent length 200,00(m) 13,50(m)
Longest equivalent length a er first branch 90,00(m) 10,00(m)
Indoor unit to nearest branch length 40,00(m) 3,00(m)
Length difference between longest and shortest distance to indoor units 40,00(m) 7,00(m)
Height difference between indoor and outdoor unit(ODU up) 90,00(m) 0,00(m)
Height difference between indoor and outdoor unit(ODU down) 110,00(m) 0,00(m)
Height difference between indoor units 30,00(m) 0,00(m)
Combina on ra o 50-130% 105,49%
IDU quan ty 64 5

4.4.2 Correc on Factors


Item Correc on factor
Al tude (indoor unit) 0,999
Al tude (outdoor unit) 1,000
Piping (cooling) 1,000
Piping (hea ng) 1,000
Defrost (hea ng) 1,000

4.4.3 Piping Details Table


No. Length(m) Piping diameter
(1) 3,00 Φ2-1/8/Φ1-1/8
(2) 3,00 Φ1-3/4/Φ7/8
(3) 3,00 Φ1-1/8/Φ5/8
(4) 3,00 Φ1-5/8/Φ3/4
(5) 3,00 Φ1-5/8/Φ3/4

4
(6) 3,00 Φ1-1/8/Φ5/8
(7) 3,00 Φ1-1/8/Φ5/8
(8) 3,00 Φ1-1/8/Φ5/8
(9) 3,00 Φ1-1/8/Φ5/8

4.4.4 Branch Joints Details Table


No. Load(Btu/h) Model
(1) 917,866 FQZHN-07D
(2) 764,319 FQZHN-05D
(3) 382,160 FQZHN-04D
(4) 382,160 FQZHN-04D

4.4.5 Reducer Details Table


Reducer Name Descrip on
J1-G1 Φ1-1/8<->Φ1-1/4+Φ1-1/4<->Φ1-3/8
J3-G1 Φ1-1/2<->Φ1-5/8
J4-G1 Φ1-1/2<->Φ1-5/8

4.4.6 Combined Outdoor Units Details Informa on

Outdoor branch joint model


Outdoor branch Model name
L+M FQZHW-03N1E

Outdoor unit-Branch/Branch-Branch
Piping Piping diameter(mm) Piping length(m)
L1 Φ1-3/8,Φ3/4 3
L2 Φ1-3/8,Φ3/4 3
L3 Φ1-3/8,Φ3/4 3
L4 Φ1-5/8,Φ7/8 3

4.5 Piping Diagrams (PB-UC 1)

5
4.6 Wiring Diagrams (PB-UC 1)

5. PB-UC 2
5.1 BOM List (PB-UC 2)
Model Quan ty Unit Descrip on
MVC-730WV2WN1 3 VC Pro Series VRF (220V)
MI2-560T1DHN1 4 High Sta c Pressure Duct
FQZHW-03N1E 1 Branch joint
FQZHN-04D 1 Branch joint
FQZHN-05D 2 Branch joint
WDC-86E/KD 4 2nd genera on wired controller
Φ1-1/2<->Φ1-5/8 1 Reducer
Φ1-1/4<->Φ1-3/8 2 Reducer
Φ1-1/8<->Φ1-1/4 2 Reducer
R410A 8.9 kg Extra Refrigerant Added
Φ5/8 12 m Copper pipe
Φ3/4 15 m Copper pipe
Φ7/8 6 m Copper pipe
Φ1-1/8 12 m Copper pipe
Φ1-3/8 9 m Copper pipe
Φ1-5/8 9 m Copper pipe
Φ1-3/4 3 m Copper pipe

6
5.2 Indoor Unit Details (PB-UC 2)
5.2.1 Indoor Unit Details Table
IDU Name Model Weight(kg) Dimension(WxHxD)(mm) Power supply MCA(A) MFA(A)
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30

IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272

IDU Name Model Airflow(CFM) Sound-Pr dB(A) ESP(Pa)


IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)

IDU Name Model Piping Length to 1st Y Joint(m)


IDU1 MI2-560T1DHN1 10,00
IDU1 MI2-560T1DHN1 10,00
IDU1 MI2-560T1DHN1 6,50
IDU1 MI2-560T1DHN1 3,00

5.2.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in hea ng (Dry bulb temp.)
RHC Required hea ng capacity
AHC Available hea ng capacity
Tdis-H Indoor unit discharge air temperature in hea ng
Airflow Indoor unit airflow (High/Medium/Low)
ESP External sta c pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in hea ng
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

5.3 Outdoor Unit Details (PB-UC 2)


5.3.1 Outdoor Unit Details Table
Model MVC-2190WV2WN1
Module MVC-730WV2WN1 MVC-730WV2WN1 MVC-730WV2WN1
Tmp-C ℃ 32
RTC Btu/h
ATC Btu/h 691,675
PI-C kW 55,36
EER 3,66
Tmp-H ℃/℃ 21,5/18,6
RHC Btu/h

7
AHC Btu/h 0
PI-H kW -0,00
COP
CR 102,3
Airflow CFM 11513,37 11513,37 11513,37
Sound-Pr 64 64 64
Sound-Po
Bas-Refr kg 57,00
Ex-Refr kg 8,90
TCO2 eq. 137,60
MCA A 91,5 91,5 91,5
MFA A 100 100 100
Power supply V/ph/Hz 220V-3ph-60Hz 220V-3ph-60Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 1585*1615*765 1585*1615*765 1585*1615*765
Weight kg 352 352 352

5.3.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Outdoor condi ons in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity
PI-C Power input in cooling
EER EER
Tmp-H Indoor condi ons in hea ng (Dry bulb temp. / Wet bulb temp. / RH)
RHC Required hea ng capacity
AHC Available hea ng capacity
PI-H Power input in hea ng
COP COP
CR Combina on ra o
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight

5.4 Piping Limita ons (PB-UC 2)


5.4.1 Piping Limita ons
Item Capability Actual Value
Total piping length 1000,00(m) 22,50(m)
Longest actual length 175,00(m) 12,00(m)
Longest equivalent length 200,00(m) 13,50(m)
Longest equivalent length a er first branch 90,00(m) 10,00(m)
Indoor unit to nearest branch length 40,00(m) 3,00(m)
Length difference between longest and shortest distance to indoor units 40,00(m) 7,00(m)
Height difference between indoor and outdoor unit(ODU up) 90,00(m) 0,00(m)
Height difference between indoor and outdoor unit(ODU down) 110,00(m) 0,00(m)
Height difference between indoor units 30,00(m) 0,00(m)
Combina on ra o 50-130% 102,28%
IDU quan ty 64 4

5.4.2 Correc on Factors


Item Correc on factor
Al tude (indoor unit) 0,999
Al tude (outdoor unit) 1,000
Piping (cooling) 1,000
Piping (hea ng) 1,000
Defrost (hea ng) 1,000

5.4.3 Piping Details Table


No. Length(m) Piping diameter
(1) 3,00 Φ1-3/4/Φ7/8

8
(2) 3,00 Φ1-5/8/Φ3/4
(3) 3,00 Φ1-1/8/Φ5/8
(4) 3,00 Φ1-5/8/Φ3/4
(5) 3,00 Φ1-1/8/Φ5/8
(6) 3,00 Φ1-1/8/Φ5/8
(7) 3,00 Φ1-1/8/Φ5/8

5.4.4 Branch Joints Details Table


No. Load(Btu/h) Model
(1) 764,319 FQZHN-05D
(2) 573,240 FQZHN-05D
(3) 382,160 FQZHN-04D

5.4.5 Reducer Details Table


Reducer Name Descrip on
J1-G1 Φ1-1/8<->Φ1-1/4+Φ1-1/4<->Φ1-3/8
J2-G1 Φ1-1/8<->Φ1-1/4+Φ1-1/4<->Φ1-3/8
J3-G1 Φ1-1/2<->Φ1-5/8

5.4.6 Combined Outdoor Units Details Informa on

Outdoor branch joint model


Outdoor branch Model name
L+M FQZHW-03N1E

Outdoor unit-Branch/Branch-Branch
Piping Piping diameter(mm) Piping length(m)
L1 Φ1-3/8,Φ3/4 3
L2 Φ1-3/8,Φ3/4 3
L3 Φ1-3/8,Φ3/4 3
L4 Φ1-5/8,Φ7/8 3

5.5 Piping Diagrams (PB-UC 2)

9
5.6 Wiring Diagrams (PB-UC 2)

6. SOT UC 1
6.1 BOM List (SOT UC 1)
Model Quan ty Unit Descrip on
MVC-730WV2WN1 3 VC Pro Series VRF (220V)
MI2-560T1DHN1 4 High Sta c Pressure Duct
FQZHW-03N1E 1 Branch joint
FQZHN-04D 1 Branch joint
FQZHN-05D 2 Branch joint
WDC-86E/KD 4 2nd genera on wired controller
Φ1-1/2<->Φ1-5/8 1 Reducer
Φ1-1/4<->Φ1-3/8 2 Reducer
Φ1-1/8<->Φ1-1/4 2 Reducer
R410A 8.9 kg Extra Refrigerant Added
Φ5/8 12 m Copper pipe
Φ3/4 15 m Copper pipe
Φ7/8 6 m Copper pipe
Φ1-1/8 12 m Copper pipe
Φ1-3/8 9 m Copper pipe
Φ1-5/8 9 m Copper pipe
Φ1-3/4 3 m Copper pipe

6.2 Indoor Unit Details (SOT UC 1)


6.2.1 Indoor Unit Details Table
IDU Name Model Weight(kg) Dimension(WxHxD)(mm) Power supply MCA(A) MFA(A)

10
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30

IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272

IDU Name Model Airflow(CFM) Sound-Pr dB(A) ESP(Pa)


IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)

IDU Name Model Piping Length to 1st Y Joint(m)


IDU1 MI2-560T1DHN1 10,00
IDU1 MI2-560T1DHN1 10,00
IDU1 MI2-560T1DHN1 6,50
IDU1 MI2-560T1DHN1 3,00

6.2.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in hea ng (Dry bulb temp.)
RHC Required hea ng capacity
AHC Available hea ng capacity
Tdis-H Indoor unit discharge air temperature in hea ng
Airflow Indoor unit airflow (High/Medium/Low)
ESP External sta c pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in hea ng
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

6.3 Outdoor Unit Details (SOT UC 1)


6.3.1 Outdoor Unit Details Table
Model MVC-2190WV2WN1
Module MVC-730WV2WN1 MVC-730WV2WN1 MVC-730WV2WN1
Tmp-C ℃ 32
RTC Btu/h
ATC Btu/h 691,675
PI-C kW 55,36
EER 3,66
Tmp-H ℃/℃ 21,5/18,6
RHC Btu/h
AHC Btu/h 0
PI-H kW -0,00
COP
CR 102,3
Airflow CFM 11513,37 11513,37 11513,37

11
Sound-Pr 64 64 64
Sound-Po
Bas-Refr kg 57,00
Ex-Refr kg 8,90
TCO2 eq. 137,60
MCA A 91,5 91,5 91,5
MFA A 100 100 100
Power supply V/ph/Hz 220V-3ph-60Hz 220V-3ph-60Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 1585*1615*765 1585*1615*765 1585*1615*765
Weight kg 352 352 352

6.3.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Outdoor condi ons in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity
PI-C Power input in cooling
EER EER
Tmp-H Indoor condi ons in hea ng (Dry bulb temp. / Wet bulb temp. / RH)
RHC Required hea ng capacity
AHC Available hea ng capacity
PI-H Power input in hea ng
COP COP
CR Combina on ra o
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight

6.4 Piping Limita ons (SOT UC 1)


6.4.1 Piping Limita ons
Item Capability Actual Value
Total piping length 1000,00(m) 22,50(m)
Longest actual length 175,00(m) 12,00(m)
Longest equivalent length 200,00(m) 13,50(m)
Longest equivalent length a er first branch 90,00(m) 10,00(m)
Indoor unit to nearest branch length 40,00(m) 3,00(m)
Length difference between longest and shortest distance to indoor units 40,00(m) 7,00(m)
Height difference between indoor and outdoor unit(ODU up) 90,00(m) 0,00(m)
Height difference between indoor and outdoor unit(ODU down) 110,00(m) 0,00(m)
Height difference between indoor units 30,00(m) 0,00(m)
Combina on ra o 50-130% 102,28%
IDU quan ty 64 4

6.4.2 Correc on Factors


Item Correc on factor
Al tude (indoor unit) 0,999
Al tude (outdoor unit) 1,000
Piping (cooling) 1,000
Piping (hea ng) 1,000
Defrost (hea ng) 1,000

6.4.3 Piping Details Table


No. Length(m) Piping diameter
(1) 3,00 Φ1-3/4/Φ7/8
(2) 3,00 Φ1-5/8/Φ3/4
(3) 3,00 Φ1-1/8/Φ5/8
(4) 3,00 Φ1-5/8/Φ3/4
(5) 3,00 Φ1-1/8/Φ5/8
(6) 3,00 Φ1-1/8/Φ5/8

12
(7) 3,00 Φ1-1/8/Φ5/8

6.4.4 Branch Joints Details Table


No. Load(Btu/h) Model
(1) 764,319 FQZHN-05D
(2) 573,240 FQZHN-05D
(3) 382,160 FQZHN-04D

6.4.5 Reducer Details Table


Reducer Name Descrip on
J1-G1 Φ1-1/8<->Φ1-1/4+Φ1-1/4<->Φ1-3/8
J2-G1 Φ1-1/8<->Φ1-1/4+Φ1-1/4<->Φ1-3/8
J3-G1 Φ1-1/2<->Φ1-5/8

6.4.6 Combined Outdoor Units Details Informa on

Outdoor branch joint model


Outdoor branch Model name
L+M FQZHW-03N1E

Outdoor unit-Branch/Branch-Branch
Piping Piping diameter(mm) Piping length(m)
L1 Φ1-3/8,Φ3/4 3
L2 Φ1-3/8,Φ3/4 3
L3 Φ1-3/8,Φ3/4 3
L4 Φ1-5/8,Φ7/8 3

6.5 Piping Diagrams (SOT UC 1)

13
6.6 Wiring Diagrams (SOT UC 1)

7. SOT UC 2
7.1 BOM List (SOT UC 2)
Model Quan ty Unit Descrip on
MVC-730WV2WN1 3 VC Pro Series VRF (220V)
MI2-560T1DHN1 4 High Sta c Pressure Duct
FQZHW-03N1E 1 Branch joint
FQZHN-04D 1 Branch joint
FQZHN-05D 2 Branch joint
WDC-86E/KD 4 2nd genera on wired controller
Φ1-1/2<->Φ1-5/8 1 Reducer
Φ1-1/4<->Φ1-3/8 2 Reducer
Φ1-1/8<->Φ1-1/4 2 Reducer
R410A 8.9 kg Extra Refrigerant Added
Φ5/8 12 m Copper pipe
Φ3/4 15 m Copper pipe
Φ7/8 6 m Copper pipe
Φ1-1/8 12 m Copper pipe
Φ1-3/8 9 m Copper pipe
Φ1-5/8 9 m Copper pipe
Φ1-3/4 3 m Copper pipe

7.2 Indoor Unit Details (SOT UC 2)


7.2.1 Indoor Unit Details Table
IDU Name Model Weight(kg) Dimension(WxHxD)(mm) Power supply MCA(A) MFA(A)
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30

IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 172,919 139,570 2272 21 208,316 2272

IDU Name Model Airflow(CFM) Sound-Pr dB(A) ESP(Pa)


IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)

14
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)

IDU Name Model Piping Length to 1st Y Joint(m)


IDU1 MI2-560T1DHN1 10,00
IDU1 MI2-560T1DHN1 10,00
IDU1 MI2-560T1DHN1 6,50
IDU1 MI2-560T1DHN1 3,00

7.2.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in hea ng (Dry bulb temp.)
RHC Required hea ng capacity
AHC Available hea ng capacity
Tdis-H Indoor unit discharge air temperature in hea ng
Airflow Indoor unit airflow (High/Medium/Low)
ESP External sta c pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in hea ng
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

7.3 Outdoor Unit Details (SOT UC 2)


7.3.1 Outdoor Unit Details Table
Model MVC-2190WV2WN1
Module MVC-730WV2WN1 MVC-730WV2WN1 MVC-730WV2WN1
Tmp-C ℃ 32
RTC Btu/h
ATC Btu/h 691,675
PI-C kW 55,36
EER 3,66
Tmp-H ℃/℃ 21,5/18,6
RHC Btu/h
AHC Btu/h 0
PI-H kW -0,00
COP
CR 102,3
Airflow CFM 11513,37 11513,37 11513,37
Sound-Pr 64 64 64
Sound-Po
Bas-Refr kg 57,00
Ex-Refr kg 8,90
TCO2 eq. 137,60
MCA A 91,5 91,5 91,5
MFA A 100 100 100
Power supply V/ph/Hz 220V-3ph-60Hz 220V-3ph-60Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 1585*1615*765 1585*1615*765 1585*1615*765
Weight kg 352 352 352

7.3.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Outdoor condi ons in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity

15
PI-C Power input in cooling
EER EER
Tmp-H Indoor condi ons in hea ng (Dry bulb temp. / Wet bulb temp. / RH)
RHC Required hea ng capacity
AHC Available hea ng capacity
PI-H Power input in hea ng
COP COP
CR Combina on ra o
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight

7.4 Piping Limita ons (SOT UC 2)


7.4.1 Piping Limita ons
Item Capability Actual Value
Total piping length 1000,00(m) 22,50(m)
Longest actual length 175,00(m) 12,00(m)
Longest equivalent length 200,00(m) 13,50(m)
Longest equivalent length a er first branch 90,00(m) 10,00(m)
Indoor unit to nearest branch length 40,00(m) 3,00(m)
Length difference between longest and shortest distance to indoor units 40,00(m) 7,00(m)
Height difference between indoor and outdoor unit(ODU up) 90,00(m) 0,00(m)
Height difference between indoor and outdoor unit(ODU down) 110,00(m) 0,00(m)
Height difference between indoor units 30,00(m) 0,00(m)
Combina on ra o 50-130% 102,28%
IDU quan ty 64 4

7.4.2 Correc on Factors


Item Correc on factor
Al tude (indoor unit) 0,999
Al tude (outdoor unit) 1,000
Piping (cooling) 1,000
Piping (hea ng) 1,000
Defrost (hea ng) 1,000

7.4.3 Piping Details Table


No. Length(m) Piping diameter
(1) 3,00 Φ1-3/4/Φ7/8
(2) 3,00 Φ1-5/8/Φ3/4
(3) 3,00 Φ1-1/8/Φ5/8
(4) 3,00 Φ1-5/8/Φ3/4
(5) 3,00 Φ1-1/8/Φ5/8
(6) 3,00 Φ1-1/8/Φ5/8
(7) 3,00 Φ1-1/8/Φ5/8

7.4.4 Branch Joints Details Table


No. Load(Btu/h) Model
(1) 764,319 FQZHN-05D
(2) 573,240 FQZHN-05D
(3) 382,160 FQZHN-04D

7.4.5 Reducer Details Table


Reducer Name Descrip on
J1-G1 Φ1-1/8<->Φ1-1/4+Φ1-1/4<->Φ1-3/8
J2-G1 Φ1-1/8<->Φ1-1/4+Φ1-1/4<->Φ1-3/8
J3-G1 Φ1-1/2<->Φ1-5/8

7.4.6 Combined Outdoor Units Details Informa on

16
Outdoor branch joint model
Outdoor branch Model name
L+M FQZHW-03N1E

Outdoor unit-Branch/Branch-Branch
Piping Piping diameter(mm) Piping length(m)
L1 Φ1-3/8,Φ3/4 3
L2 Φ1-3/8,Φ3/4 3
L3 Φ1-3/8,Φ3/4 3
L4 Φ1-5/8,Φ7/8 3

7.5 Piping Diagrams (SOT UC 2)

7.6 Wiring Diagrams (SOT UC 2)

17
8. SOT UC 3
8.1 BOM List (SOT UC 3)
Model Quan ty Unit Descrip on
MVC-560WV2WN1 2 VC Pro Series VRF (220V)
MI2-560T1DHN1 2 High Sta c Pressure Duct
FQZHW-02N1E 1 Branch joint
FQZHN-04D 1 Branch joint
WDC-86E/KD 2 2nd genera on wired controller
Φ1-1/2<->Φ1-5/8 1 Reducer
R410A 3.08 kg Extra Refrigerant Added
Φ5/8 12 m Copper pipe
Φ3/4 3 m Copper pipe
Φ1-1/8 6 m Copper pipe
Φ1-1/4 6 m Copper pipe
Φ1-5/8 3 m Copper pipe

8.2 Indoor Unit Details (SOT UC 3)


8.2.1 Indoor Unit Details Table
IDU Name Model Weight(kg) Dimension(WxHxD)(mm) Power supply MCA(A) MFA(A)
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30
IDU1 MI2-560T1DHN1 218 2010*680*905 220-240V-50/60Hz 15,4 30

IDU Name Model Tmp-C(℃) RTC(Btu/h) ATC(Btu/h) RSC(Btu/h) ASC(Btu/h) PI-C(W) Tmp-H(℃) RHC(Btu/h) AHC(Btu/h) PI-H(W)
IDU1 MI2-560T1DHN1 26,0/19,0 190,896 154,081 2272 21 208,316 2272
IDU1 MI2-560T1DHN1 26,0/19,0 190,896 154,081 2272 21 208,316 2272

IDU Name Model Airflow(CFM) Sound-Pr dB(A) ESP(Pa)


IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)
IDU1 MI2-560T1DHN1 4356[1] 59[SSH] 300(100-400)

IDU Name Model Piping Length to 1st Y Joint(m)


IDU1 MI2-560T1DHN1 3,00
IDU1 MI2-560T1DHN1 3,00

8.2.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity

18
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in hea ng (Dry bulb temp.)
RHC Required hea ng capacity
AHC Available hea ng capacity
Tdis-H Indoor unit discharge air temperature in hea ng
Airflow Indoor unit airflow (High/Medium/Low)
ESP External sta c pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in hea ng
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

8.3 Outdoor Unit Details (SOT UC 3)


8.3.1 Outdoor Unit Details Table
Model MVC-1120WV2WN1
Module MVC-560WV2WN1 MVC-560WV2WN1
Tmp-C ℃ 32
RTC Btu/h
ATC Btu/h 381,791
PI-C kW 29,96
EER 3,73
Tmp-H ℃/℃ 21,5/18,6
RHC Btu/h
AHC Btu/h 0
PI-H kW -0,00
COP
CR 100,0
Airflow CFM 7166,48 7166,48
Sound-Pr 63 63
Sound-Po
Bas-Refr kg 26,00
Ex-Refr kg 3,08
TCO2 eq. 60,72
MCA A 86 86
MFA A 100 100
Power supply V/ph/Hz 220V-3ph-60Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 1250*1615*765 1250*1615*765
Weight kg 296 296

8.3.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Outdoor condi ons in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity
PI-C Power input in cooling
EER EER
Tmp-H Indoor condi ons in hea ng (Dry bulb temp. / Wet bulb temp. / RH)
RHC Required hea ng capacity
AHC Available hea ng capacity
PI-H Power input in hea ng
COP COP
CR Combina on ra o
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm

19
Weight Weight

8.4 Piping Limita ons (SOT UC 3)


8.4.1 Piping Limita ons
Item Capability Actual Value
Total piping length 1000,00(m) 9,50(m)
Longest actual length 175,00(m) 6,00(m)
Longest equivalent length 200,00(m) 6,50(m)
Longest equivalent length a er first branch 90,00(m) 3,00(m)
Indoor unit to nearest branch length 40,00(m) 3,00(m)
Length difference between longest and shortest distance to indoor units 40,00(m) 0,00(m)
Height difference between indoor and outdoor unit(ODU up) 90,00(m) 0,00(m)
Height difference between indoor and outdoor unit(ODU down) 110,00(m) 0,00(m)
Height difference between indoor units 30,00(m) 0,00(m)
Combina on ra o 50-130% 100,00%
IDU quan ty 64 2

8.4.2 Correc on Factors


Item Correc on factor
Al tude (indoor unit) 0,999
Al tude (outdoor unit) 1,000
Piping (cooling) 1,000
Piping (hea ng) 1,000
Defrost (hea ng) 1,000

8.4.3 Piping Details Table


No. Length(m) Piping diameter
(1) 3,00 Φ1-5/8/Φ3/4
(2) 3,00 Φ1-1/8/Φ5/8
(3) 3,00 Φ1-1/8/Φ5/8

8.4.4 Branch Joints Details Table


No. Load(Btu/h) Model
(1) 382,160 FQZHN-04D

8.4.5 Reducer Details Table


Reducer Name Descrip on
J1-G1 Φ1-1/2<->Φ1-5/8

8.4.6 Combined Outdoor Units Details Informa on

Outdoor branch joint model


Outdoor branch Model name
L+M FQZHW-02N1E

Outdoor unit-Branch/Branch-Branch
Piping Piping diameter(mm) Piping length(m)
L1 Φ1-1/4,Φ5/8 3

20
L2 Φ1-1/4,Φ5/8 3

8.5 Piping Diagrams (SOT UC 3)

8.6 Wiring Diagrams (SOT UC 3)

9. Centralized Control Solu on


9.1 Centralized Controller List
The centralized control system of this project is full output regardless of whether the system is selected.