CODE REFERENCE:
PROJECT DESCRIPTION:
· HOUSTON AMENDED 2012 IRC
SCOPE OF WORK: · 2012 IFC
· 2020 NEC
SIGNATURE:_____________________________
Equisolar
Roof-mounted , transformerless
· 2015 IECC, OR ASHRAE 90.1-2013
photovoltaic system and new · Underwriters Laboratories (UL) Standards
electrical components, including · OSHA Guidelines
modules, mounting hardware, · All AHJ Requirements
inverter, load center, disconnects and
metering devices as required.
8.400
· All outdoor equipment shall be minimum NEMA 3R rated, including all roof mounted transition boxes and switches.
(21 ) SolarEdge: P400 OPTIMIZERS · All exterior conduit, fittings, and boxes shall be rain tight and approved for use in wet locations. ADDRESS Encino, CA 91436
ARRAY PLACEMENT: PHONE 818.784.2300
· All conductors exposed to weather shall be listed and identified for use in direct sunlight.
FLUSH MOUNTED
TDLR EC-33063
ROOF TYPES: · The module conductors must be type USE-2 or listed for Photovoltaic (PV) Wire (UL 4703 & 854 Listed).
COMP SHINGLE SHEET INDEX
· All conductors must be copper and 90° Rated.
FRAMING TYPE:
HOUSTON, TX 77064
MANJARREZ, ISALIA
· All equipment shall be properly grounded and bonded in accordance with NEC Article 250. T-01 TITLE SHEET
---
· All NEC required warning signs, markings, and labels shall be posted on equipment and disconnects.
PV ARRAY AREA: PV.03 SINGLE LINE DIAGRAM/ELECTRICAL
· All circuits connected to more than one source shall have over current devices located so as to provide over current protections from
453.92 ft². all sources.
PV.04 WARNING LABELS & SIGNAGE
PSF PRESSURE:
· The PV Power source circuit breaker shall be located at the opposite end of the main service disconnect. PV.05 RACKING AND ATTACHMENTS
2.53 lbs/ft²
INTERCONNECTION METHOD: · Flexible, fine-stranded cables shall be terminated only with terminals, lugs, devices, or connectors that are identified and listed for such PV.06 PV MODULE DATA SHEET
use.
Interconnect via Load Side . PV.07 INVERTER DATA SHEET
Paper Size
WIND SPEED: · Connectors shall be of latching or locking type. Connectors that are readily accessible and operating over 300 volts shall require a tool Scale
110 MPH
to open and shall me marked "Do Not Disconnect under load". PV.08 UL
Drawn by
· The roof mounted photovoltaic modules, panels, or solar photovoltaic roll roofing material shall have the same or better listed PV.09 GROUNDING
fire-resistance rating than the building roof-covering material. Title
Project Number
· Smoke alarms and carbon monoxide alarms are required to be retrofitted onto the existing dwelling as per the 2012 IRC. These
smoke alarms are required to be in all bedrooms, outside each bedroom, and a least one on each floor of the house.
Sheet
· Smoke alarms and carbon monoxide alarms are to be verified and inspected by the IHE inspector in the field.
ADDITIONAL NOTES: 2/2/2022
· SYSTEM INFORMATION
ROOF ARRAY MAGNETIC TRUE
ARRAY MOUNT
PITCH TILT ORIENTATION ORIENTATION
SIGNATURE:_____________________________
Equisolar
2 AR-02
3 AR-03
4 AR-04
5 AR-05
PROPERTY LINE
56'
PROPERTY LINE
PROPERTY LINE
8.400
160'
MAIN
RESIDENCE
32' 96'
HOUSTON, TX 77064
MANJARREZ, ISALIA
9819 FOX ROAD,
---
1
22'
PROPERTY LINE
Paper Size
180'
Scale
1" = 30'
Drawn by
Title
· PRIOR TO COMMENCING WORK, CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND SHALL NOTIFY ENGINEER OF ANY SCALE: NTS Ironridge
DISCREPANCIES, INCLUDING BUT NOT LIMITED TO DIMENSIONS, STRUCTURE, ELECTRICAL SERVICE, CONDUIT PATHS, UNDERGROUND UTILITIES,
OBSTRUCTIONS, ACCESSIBILITY ISSUES AND WORKING CLEARANCES. Flashfoot 2
· THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS BEFORE STARTING ANY OF THE WORK.
· ALL LOCATIONS ARE APPROXIMATE AND REQUIRE FIELD VERIFICATION.
818.784.2300
16530 Ventura Blvd Suite 104
Encino, CA 91436
LICENSE: EC-33063
SIGNATURE:_____________________________
Equisolar
· ALL EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
Ironridge Rail
· ALL OUTDOOR EQUIPMENT SHALL BE RAIN TIGHT WITH MINIMUM NEMA 3R RATING.
· ALL EXPOSED CONDUIT SHALL BE EMT AND SHALL BE MOUNTED AT MIN 3.5” OFF SURFACE OFF ROOF SURFACE.
· ALL FIELD INSTALLED JUNCTION, PULL AND OUTLET BOXES LOCATED BEHIND MODULES OR PANEL SHALL BE ACCESSIBLE DIRECTLY OR BY
DISPLACEMENT OF MODULE(S) OR PANEL(S) SECURED BY REMOVABLE FASTENERS. pv module
· LIVE PARTS IN PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150 VOLTS TO GROUND SHALL NOT BE ACCESSIBLE TO OTHER THAN QUALIFIED COMP SHINGLE
PERSONS WHILE ENERGIZED.
· IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE VERIFIABLE GROUNDING ELECTRODE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL roofing material
A SUPPLEMENTAL GROUNDING ELECTRODE.
· THE SOLAR PHOTOVOLTAIC INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. flashing
· PROVIDE MINIMUM 4" CLEARANCE BETWEEN SOLAR AND ANY VENT.
18.43°
2x FRAMING
@24" OC, TYP
5/16"x 4.75" SS Lag Bolt
3" Min Embedment
MODULE SPECS
MODEL: Jinko: JKM400M-72HL-V
STC: 400W
PTC: 359.1 W
3' 49.60LBS
WEIGHT:
LENGTH: 79.06"
WIDTH: 39.45"
ARRAY SPECS
8.400
(N) SolarEdge: SE7600H-US [240V] 22' NUMBER OF MODULES: 21
INVERTER 6' SYSTEM WEIGHT (LBS): 1146.60
(N) 60A AC DISCONNECT ARRAY AREA (SQ.FT.): 454.84
2P, 240V, FUSED NUMBER OF MOUNTS: 53
LOAD PER MOUNT (LBS): 21.63
(E) 200A MAIN SERVICE PANEL LOAD PER SQ.FT. (LBS): 2.52
HOUSTON, TX 77064
MANJARREZ, ISALIA
9819 FOX ROAD,
& UTILITY METER, 120/240VAC, 1ɸ 3'
---
BUILDING SPECS
3'
STORIES: 2
BUILDING HEIGHT: 25'
3' BUILDING FT²: 3158ft²
(E) 2X FRAMING FRAMING SIZE: 2X FRAMING Paper Size
3' FRAMING SPACING: 24" O.C. Scale
3' @24" OC, TYP SPAN: 22'-0" 1/8" = 1'-0"
Drawn by
SLOPE OF ROOF: 4/12
MIN LAG BOLT Title
EMBEDMENT: 3"
Project Number
1 ROOF PLAN ROOFING MATERIAL: COMP SHINGLE
PV-02 SCALE: 1/8" = 1'-0" STANDOFF SPACING: 4' MAX Sheet
RACKING CO: IRONRIDGE
2/2/2022
818.784.2300
LICENSE: EC-33063
16530 Ventura Blvd Suite 104
Encino, CA 91436
SIGNATURE:_____________________________
Equisolar
120/240 VAC
1
SINGLE PHASE SERVICE
(E) 200A MAIN PANEL 3/4" EMT: SOLAR
(E) 200A MAIN BREAKER (2) #8 AWG THWN-2 CONDUCTORS
(1) #8 AWG THWN-2 NEUTRAL
MODULE
STRING 1
(1) #8 AWG THWN-2 GROUND
(11) Jinko: JKM400M-72HL-V MODULES AND
CONNECT MODULE OUTPUT (11) SolarEdge: P400 SOLAREDGE DC POWER
CONDUCTORS EXPOSED TO FREE AIR: CONDUCTORS TO SOLAR EDGE OPTIMIZERS.
UTILITY (4) #10 AWG PV-WIRE CONDUCTORS INPUT LEADS
METER
(1) #6 AWG BARE COPPER GROUND OPTIMIZERS ARE WIRED IN SERIES
· 380V FIXED STRING VOLTAGE DURING OPERATION
(CONTROLLED BY INVERTER).
SolarEdge: SE7600H-US [240V] DC DC DC
2 · 480V DC MAXIMUM STRING VOLTAGE (LIMITED BY
200A,2P
SUPPLEMENTAL FACILITY GEC COMPLIANT WITH NEC ARTICLES 250 AND 690.
GROUND IF GROUND 6AWG BARE COPPER GROUND RUN OUTSIDE RACEWAY OR 8AWG THWN-2 IN CONDUIT
NECESSARY (690.47, 250.30, 250.33, 250.66, 250.64 & ANY OTHER APPLICABLE SECTIONS)
8.400
DC WIRE SIZING CALCULATIONS:
ASSUMPTIONS
AC WIRE SIZING CALCULATIONS:
OCPD CALCULATIONS PER INVERTER: ELECTRICAL NOTES:
C. INVERTER TO MAIN SERVICE PANEL
1. THE PROVISIONS OF ARTICLE 690 OF THE 2017 NATIONAL ELECTRIC CODE MUST BE ADHERED TO FOR THE CONSTRUCTION
HIGH TEMP AMBIENT = 39°C
HOUSTON, TX 77064
MAX AC OUTPUT CURRENT = (Inverter Output Circuit Current)[690.8(A)(3)] x (Safety)[690.9(B)] =
MANJARREZ, ISALIA
AND INSTALLATION OF ELECTRICAL WIRING AND EQUIPMENT ASSOCIATED WITH SOLAR PHOTOVOLTAIC SYSTEM.
HIGH TEMP ROOF = 56°C SolarEdge: SE7600H-US [240V]:
---
per 310.15(B)(2)(a): 50A x 0.91[CORRECTION] = 45.5A 125% DERATING FOR EXTREME IRRADIANCE CONDITIONS [NEC 690.8(A)(1)]
per 310.15(B)(3)(a): 45.5A x 100% [ADJUSTMENT] = 45.5A
125% DERATING, CONTINUOUS PHOTOVOLTAIC SOURCE CURRENT [NEC 690.8(B)(1)].
A. OPTIMIZER TO JUNCTION BOX (OPEN AIR)
40.00A ≤ 45.5A ===> OK
ID QTY ITEM 156% TOTAL DERATING (COMBINATION OF ABOVE)
15.79 AMPS TOTAL CAPACITY
SolarEdge: P400 POWER OPTIMIZER
(AMPS TOTAL CAPACITY = STRING SHORT CIRCUIT CURRENT MULTIPLIED BY TWO ABOVE DERATES, 1.25 X 1.25 X SHORT
per 690.8(A)(5): 15A (max output current)
per 690.8(B)(1): 15A x 1.25 = 18.75A
1 21 (N) Jinko: JKM400M-72HL-V MODULE CIRCUIT CURRENT)
6. INVERTER PROVIDES NECESSARY GROUND FAULT PROTECTION AS REQUIRED BY NEC 690.41(B)
WIRE CHOICE: #10 AWG PV-WIRE 7. PHOTOVOLTAIC SYSTEM IS UNGROUNDED/FUNCTIONALLY GROUNDED. NO CONDUCTORS ARE SOLIDLY GROUNDED IN THE
per 310.15(B)(16): #10 PV-WIRE = 40A @90°C 2 21 (N) SolarEdge: P400 POWER OPTIMIZER INVERTER. SYSTEM COMPLIES WITH 690.41
per 310.15(B)(3)(C): 39°C + 17°C[3.5" ABOVE ROOF] = 56°C 8. USE UL APPROVED BONDING FITTINGS AT ALL CONDUIT/BOX JUNCTIONS.
per 310.15(B)(2)(a): 40A x 0.71[CORRECTION] = 28.4A 9. MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
per 310.15(B)(3)(a): 28.4A x 100% [ADJUSTMENT] = 28.4A INVERTER 1 (N) SolarEdge: SE7600H-US [240V] INVERTER 10. INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741. Paper Size
11. INSTALLER TO IDENTIFY THE EXISTING GROUNDING ELECTRODE TYPE (I.E. DRIVEN ROD, UFER, WATER PIPE, OR COMBINATION
18.75A ≤ 28.4A ===> OK OF SOME OR ALL OF THE PREVIOUSLY MENTIONED). IN EXISTING ELECTRICAL SYSTEMS THAT USE ONLY A WATER PIPING
Scale
B. JUNCTION BOX TO INVERTER
3 TBD (N) NEMA 3R JUNCTION BOX GROUNDING ELECTRODE SYSTEM, AN ADDITIONAL GROUNDING ELECTRODE (I.E DRIVEN ROD) SHALL BE PROVIDED. (NEC 250.50)
12. PER NEC 250.53(A)(2), A SINGLE ROD, PIPE OR PLATE ELECTRODE SHALL BE SUPPLEMENTED BY AN ADDITIONAL ELECTRODE OF
SolarEdge: P400 POWER OPTIMIZER TYPE SPECIFIED IN 250.52(A)(2) THROUGH (A)(8) SPACED NO LESS THAN 6FT APART. EXCEPTION, IF A SINGLE ROD, PIPE OR PLATE Drawn by
per 690.8(A)(5): 15A (max output current)
4 1 (N) NEMA 3R 60A NON-FUSED AC DISCONNECT GROUNDING ELECTRODE HAS A RESISTANCE TO EARTH OF 25 OHMS OR LESS, THE SUPPLEMENTAL ELECTRODE SHALL NOT BE
per 690.8(B)(1): 15A x 1.25 = 18.75A REQUIRED. Title
WIRE CHOICE: #10 AWG THWN-2
240VAC, 10KAIC RATING, 13. #4 AWG CU TO UNDERGROUND METAL WATER PIPE THAT IS A MINIMUM 10 FOOT BURIAL IN PIPE LENGTH. CONNECT GROUNDING
per 310.15(B)(16): #10 THWN-2 = 35A @75°C ELECTRODE CONDUCTOR WITHIN FIVE FEET OF WHERE IT ENTERS BUILDING. NEC 250.52(A)(1), 250.68(C)(1).
14. ADDITIONAL #4 AWG CONNECTION TO UFER IF AVAILABLE SIZED PER NEC 250.66. IF UFER NOT AVAILABLE THEN TWO #6 AWG CU Project Number
per 310.15(B)(3)(C): 39°C + 17°C[3.5" ABOVE ROOF] = 56°C
CONNECTIONS TO GROUND RODS SEPARATED BY AT LEAST 6 FT IS INTALLED PER NEC 250.53.
per 310.15(B)(2)(a): 35A x 0.71[CORRECTION] = 24.85A
per 310.15(B)(3)(a): 24.85A x 80% [ADJUSTMENT] = 19.88A Sheet
18.75A ≤ 19.88A ===> OK
2/2/2022
GENERAL FIRE GUIDELINES & MARKING REQTS: REQUIRED WARNING LABELS
SEC. 5. MARKINGS, LABELS, AND WARNING SIGNS.
818.784.2300
LICENSE: EC-33063
16530 Ventura Blvd Suite 104
Encino, CA 91436
SIGNATURE:_____________________________
Equisolar
MAX CIRCUIT CURRENT: 9.49A
MAX RATED OUTPUT CURRENT OF 15A
WARNING: PHOTOVOLTAIC POWER SOURCE THE CHARGE CONTROLLER OR DC-TO-DC
CONVERTER (IF INSTALLED)
WARNING
“ ”
∕
8.400
THIS LABEL TO BE INSTALLED AT THE
CAUTION: MULTIPLE SOURCES OF POWER
MAIN ELECTRICAL SERVICE PANEL
CAUTION
POWER TO THIS BUILDING IS ALSO
SEC. 8. GROUND MOUNTED PHOTOVOLTAIC ARRAYS.
SUPPLIED FROM THE FOLLOWING
HOUSTON, TX 77064
MANJARREZ, ISALIA
SOURCES WITH DISCONNECTS
---
PV MODULES
SEC. 9. OVERHEAD ARRAYS ON ROOFTOPS (E.G. TRELLIS SYSTEMS).
POWER SOURCE OUTPUT
CONNECTIONDO NOT
RELOCATE THIS
OVERCURRENT DEVICE
Paper Size
Scale
INTERACTIVE PHOTOVOLTAIC POWER SOURCE
RATED AC OUTPUT CURRENT (A): 32.00A Drawn by
NOMINAL OPERATING AC VOLTAGE (V): 240V SOLAR D/C
DISCONNECT
MAIN ELECTRIC Title
SERVICE
PV SYSTEM DISCONNECT
DISCONNECT
FOR UTILITY OPERATION
Project Number
Equisolar
Scale
Sheet
MANJARREZ, ISALIA
Paper Size
Encino, CA 91436
9819 FOX ROAD, 818.784.2300
Project Number
---
SIGNATURE:_____________________________
Title
Equisolar
Scale
Sheet
MANJARREZ, ISALIA
Paper Size
Encino, CA 91436
9819 FOX ROAD, 818.784.2300
Project Number
---
SIGNATURE:_____________________________
Title
Equisolar
Scale
Sheet
MANJARREZ, ISALIA
Paper Size
Encino, CA 91436
9819 FOX ROAD, 818.784.2300
Project Number
---
SIGNATURE:_____________________________
Title
Equisolar
Scale
Sheet
MANJARREZ, ISALIA
Paper Size
Encino, CA 91436
9819 FOX ROAD, 818.784.2300
Project Number
---
SIGNATURE:_____________________________
Title
Equisolar
Scale
Sheet
MANJARREZ, ISALIA
Paper Size
Encino, CA 91436
9819 FOX ROAD, 818.784.2300
Project Number
---
SIGNATURE:_____________________________
Title
Equisolar
Scale
Sheet
MANJARREZ, ISALIA
Paper Size
Encino, CA 91436
9819 FOX ROAD, 818.784.2300
Project Number
---
SIGNATURE:_____________________________
Title
Equisolar
Scale
Sheet
MANJARREZ, ISALIA
Paper Size
Encino, CA 91436
9819 FOX ROAD, 818.784.2300
Project Number
---
SIGNATURE:_____________________________
Title
Equisolar
Scale
Sheet
MANJARREZ, ISALIA
Paper Size
Encino, CA 91436
9819 FOX ROAD, 818.784.2300
Project Number
---
SIGNATURE:_____________________________
Title
Equisolar
Scale
Sheet
MANJARREZ, ISALIA
Paper Size
Encino, CA 91436
9819 FOX ROAD, 818.784.2300
Project Number
---
SIGNATURE:_____________________________
Title
Equisolar
Scale
Sheet
MANJARREZ, ISALIA
Paper Size
Encino, CA 91436
9819 FOX ROAD, 818.784.2300
Project Number
---
SIGNATURE:_____________________________