AS330 Series Elevator-Used Inverter User Manual V1.01

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 128

AS330 Escalator Intrgrated Drive Controller

AS330 Escalator Integrated Drive Controller

Release Status: Standard


Version: V1.01

All Copyright© reserved by Shanghai STEP Electric


Corporation

All rights reserved


The information in this document is subject to change without prior
notice. No part of this document may in any form or by any means
(electronic, mechanical, micro-coping, photocopying, recording or
otherwise) be reproduced, stored in a retrial system or transmitted
without prior written permission from Shanghai STEP Electric
Corporation.

I
Shanghai STEP Electric Corporation

Forward
AS330 escalator integrated drive controller is enhanced state-of-art escalator control and drive unit
as developed and manufactured by Shanghai Sigriner STEP Electric Corporation which, by taking
full consideration of the rule of Safety and Reliability First, inherent characteristics of escalator
operation and the specific characteristics of potential energy load of escalator, by introducing
advanced variable frequency speed control technology and intelligent escalator control technology
and additionally by perfectly integrating the control and drive of escalator, makes the product has
further-optimized service performances, easy-to-use property and cost efficiency.

Abstract

This manual describes the installation, operation, parameter setting, maintenance and fault handling
of AS330 escalator integrated drive controller in detail and in full. It may be used not only for
information in design of escalator control system, but also for reference in installation,
commissioning and maintenance of complete system.

Be sure to read and understand this manual thoroughly before operating in order to ensure correct
installation and operation of this escalator integrated drive controller.

Readers

Users of escalator
Control and design staff of escalator
Engineering service persons
Technical support persons to the user

This manual will have supplement or revision, please keep an eye on the revised
version in our website. The company website is: www.stepelectric.com

II
AS330 Escalator Intrgrated Drive Controller

Main Features
a) Perfect integration of control and drive, compact design, smaller overall size, decreased
wiring amount, enhanced reliability and easy-to-use property and cost efficiency.

b) Double 32-bit built-in micro processor fulfils the escalator’s operating functions and motor’s
drive control together.

c) Redundant safety design. The control processor and the drive processor provide the double
safety protections, finalizing the most reliable safety.

d) Strong anti-interference property: beyond the highest grade required by industry

e) CAN Bus communition provides the effective monitoring for the switches of every
channel,which makes the complete system with simple wiring and easier way to find the faults
on site.

f) Smart running speed control according to passenger flow change,which realizes the most

energy saving operation.

g) Sufficient and advanced escalator operation fuctions, satisfying different requirements of the

customers.

h) Frequency conversion and working frequency redundant control with many patterns like full

frequency conversion, bypass frequency conversion control, and Y-△ control,which satisfy the

requirements of different customers to the most degree,reducing the possibility of faulty stop.

i) Bypass frequency conversion technology, which uses frequency conversion control at the

time of escalator standby or acceleration and deceleration and used working frequency at the

time of stable operation. It realizes downshift energy-saving for the escalator frequency

conversion.

j) New PWM dead-time compensation method allowing effectively reducing noise and wearing

of motor.

k) Dynamic PWM carrier wave modulation technology reducing noise of the motor.

l) Sixth generation new hardware module, up to 175℃ temperature resistant, low wearing for

switch and dredge, longer life span

Safety-related Signs

III
Shanghai STEP Electric Corporation

The following safety-related signs are used in the manual. Be sure to observe the instructions with
these signs.

Danger

“Danger” indicates an imminently hazardous situation which, if not avoided, will cause death or
serious injury.

Caution

“Caution” indicates a potential hazardous situation, which, if no suitable precautions are taken, may
result in minor injury and/or property damage.

Important

This symbol indicates important contents which instructions should be observed.

IV
AS330 Escalator Intrgrated Drive Controller

TABLE OF CONTENTS

CHAPTER 1 USER MANUAL OF INTEGRATED DRIVE CONTROLLER..................................... 1

1.1 APPLICATION SCOPE ............................................................................................................................ 1


1.2 OPEN UP CASE AND CHECK .................................................................................................................. 1
1.3 MODEL DESCRIPTION .......................................................................................................................... 1
1.4 NAMEPLATE DISCRIPTION ................................................................................................................... 2
1.5 SAFETY NOTICE................................................................................................................................... 2
1.6 PRECAUTIONS IN APPLICATION ............................................................................................................ 3
1.6.1 Selection of Optional Brake Resistor .......................................................................................... 3
1.6.2 Absorption Devices are not allowed at output side ..................................................................... 4
1.6.3 Working Voltage .......................................................................................................................... 4
1.6.4 Two-phase Input Inappropriate.................................................................................................... 4
1.6.5 Altitude and Derated Application ................................................................................................ 4
1.6.6 Ambient Temperature&Derated Application ............................................................................... 5
1.7 WASTE PRECAUTION ........................................................................................................................... 5
1.7.1 Disposal of Capacitors ................................................................................................................ 5
1.7.2 Disposal of Plastic Components .................................................................................................. 5

CHAPTER 2 MODEL&SPECIFICATIONS ........................................................................................... 1

2.1 MODEL ................................................................................................................................................ 1


2.2 TECHNOLOGY STANDARDS AND SPECIFICATION OF INTEGRATED DRIVE CONTROLLER ...................... 1
2.3 MOUNTING DIMENSION & MASS ....................................................................................................... 56
2.4 MOUNTING INSTRUCTION .................................................................................................................... 7
2.4.1 Mounting Place ........................................................................................................................... 7
2.4.2 Mounting Orientation and Clearance Requirements .................................................................. 8

CHAPTER III PRODUCT FUNCTIONS ................................................................................................ 9

3.1 FUCTION LIST ...................................................................................................................................... 9


TABLE 3.1 PRODUCT DESCRIPTION ......................................................................................................... 9
3.2 A BRIEF ON FUNCTION AND SETTING................................................................................................... 1
3.2.1 Description Of Standard Functions ............................................................................................. 1
4.1INTEGRATED DRIVE CONTROLLER CONNECTED TO THE PERPHERIAL EQUIPMENTS ............................ 2
4.2 TERMINAL WIRING OF MAIN CURCUIT ............................................................................................... 4
4.4.2 Labeling of Main Circuit Terminals and Functional Description ................................................ 4
4.4.3 Conductor Specification in Main Circuit Connection ................................................................. 4
4.4.4 Structure of Main Circuit .......................................................................................................... 67
4.4.5 Detailed Wiring Description of Main Circuit Terminals ............................................................. 7
4.5 ANTI-INTERFERENCE MEASURES ................................................................................................... 1112
4.5.1 Connecting Specific Noise Filter at Output Side................................................................... 1112
4.5.2Layout of Main Circuit Wiring ............................................................................................... 1112
4.5.4Relationship between Wiring Length and Carrier Frequency ................................................ 1213
4.6WIRING OF CONTROL CIRCUIT TERMINALS .................................................................................... 1214
4.6.1Layout of Control Circuit Terminals ...................................................................................... 1214
4.6.2 Functional Description of Control Circuit Terminals ............................................................ 1314

V
Shanghai STEP Electric Corporation

4.6.3Description of Dip Switch Settings ........................................................................................ 1617


4.6.4Wire Specification in Control Circuit Connection ................................................................. 1618
4.6.5 Cautions on Wiring of Control Circuit Terminals ................................................................. 1718
4.7 WIRING OF PHASE POSITION COLLECTOR ....................................................................................... 1718

CHAPTERⅤ OPERATOR ...................................................................................................................... 1

5.1SEVEN-SEGMENT DISPLAY OPERATOR ................................................................................................. 1


5.1.1 LED Indicator Light .................................................................................................................... 1
5.1.2 Function Keys ............................................................................................................................. 1
5.1.3 Operations for the Operator......................................................................................................... 2
5.1.3.3. LED display digit and alphabet list ......................................................................................... 8
5.2 LCD HANDSET OPERATOR .................................................................................................................. 9
5.2.1 General Description..................................................................................................................... 9
5.2.2 Connection Of Handset Operator .............................................................................................. 10
5.2.3 Handset Operator Functions. ................................................................................................. 1011
5.2.4 INTRODUCTION TO DISPLAY WINDOWS........................................................................................ 1213
5.2.4.1 Classification of windows .................................................................................................. 1213
5.2.4.3 Function Switchover .......................................................................................................... 1415
5.2.4.5 How to set parameter.......................................................................................................... 1617

CHAPTER 6 INTRODUCTION TO THE SUPPORTING PRODUCTS ............................................. 1

6.1DETAILS FOR SAFETY CHAIN COLLECTION BOARD ES.02/B ............................................................... 2


6.1.1 MOUNTING DIMENSION FOR SAFETY CHAIN COLLECTION BOARD ES.02/B .................................. 2

CHAPTER 7 FUNCTION PARAMETERS ............................................................................................. 1

7.1 FUNCTION PARAMETER ........................................................................................................................ 1


7.2 FUNCTION PARAMETER DETAILS ......................................................................................................... 4

CHAPTER 8 ESCALATOR COMMISIONING GUIDE ....................................................................... 1

8.1 SIMPLE COMMISSIONING DIAGRAM...................................................................................................... 2


8.1.1PREPARATION PRIOR TO COMMISSIONING .......................................................................................... 2
8.2 OTHER FUNCTION COMMISSIONING. .................................................................................................... 3

CHAPTER 9 FAULTS AND SOLUTIONS .............................................................................................. 1

9.1 CONTROL SYSTEM FAULT AND ANALYSIS ........................................................................................... 1


9.2 DRIVE SYSTEM FAULT AND ANALYSIS ................................................................................................ 3

CHAPTER 10 MAINTENANCE .............................................................................................................. 1

10.1 Warranty....................................................................................................................................... 1
10.2 Product Checkup ........................................................................................................................ 12
10.3 ROUTINE INSPECTION ........................................................................................................................ 2
10.4 Periodic Inspection ....................................................................................................................... 2

APPENDIX A EMC INSTALLATION GUIDE................................................................................... 1

A1NOISE CONTROL................................................................................................................................... 1
A1.1 Noise Type .................................................................................................................................. 1

VI
AS330 Escalator Intrgrated Drive Controller

A1.2 Transmission Path ...................................................................................................................... 1


A1.3 Basic Measures for Noise Suppression ....................................................................................... 2
A2 REQUIREMENTS ON CABLE LAYING ..................................................................................................... 3
A2.1 Requirement on Cable Laying ..................................................................................................... 3
A2.2 Requirements on Cable Size........................................................................................................ 3
A2.3 Requirements on Shielded Cable............................................................................................... 34
A2.4 Requirements on Installation of shielded cable ........................................................................... 4
A3 GROUNDING REQUIREMENTS .............................................................................................................. 4
A3.1 Grounding Method ...................................................................................................................... 4
A3.2 Precautions for Grounding Connection ..................................................................................... 45
A4 INSTALL SURGE ABSORPTION DEVICE ................................................................................................. 5
A5 LEAKAGE CURRENT AND COUNTERMEASURES .................................................................................. 56
A5.1 Ground Leakage Current ............................................................................................................. 6
A5.2 Line-to-Line Leakage Current ................................................................................................... 67
A6 SUPPRESSION OF RADIATED EMISSION .............................................................................................. 67
A7 GUIDE FOR USE OF POWER LINE FILTER ............................................................................................. 78
A7.1 Functions of Power line filter .................................................................................................... 78
A7.2 Precautions for Installation of Power Line Filter ...................................................................... 78
A8 EMC INSTALLATION ZONING .............................................................................................................. 8
A9 PRECAUTIONS FOR ELECTRIC INSTALLATION ....................................................................................... 9
A10 EMC CONFORMITY ..................................................................................................................... 1011

APPENDIX B FUNCTION PARAMETER, FAULT LIST SUMMARY............................................... 1

B.1 FUNCTION PARAMETER LIST ............................................................................................................... 1

NOTICE TO CUSTOMERS...................................................................................................................... 1

VII
AS330 Escalator Intrgrated Drive Controller

Chapter 1 User Manual Of Integrated Drive Controller

This chapter is the general information for A330 integrated drive controller including the
controller voltage rating and adaptive motor capacity, and how to open up the case and check.
Besides, it describes details in the process of installation, wiring, usage, maintainence and waste,
helpful for the safe use and prolong the life span.Please carefully study! 第

1.1 Application Scope

AS330 escalator integrated drive controller is rated at voltage 400V and is adaptable to both
synchronous motor and asynchronous motor with capacity form 5.5kW to 37kW. If the value goes
beyond the limit, please contact our engineering center.

1.2 Open up case and check 体

Caution



◎ Do not install the damaged or shortly-assembled inverter 制
Otherwise it may cause the risk of fire and injury.

使

Open up the case and check carefully whether it is damaged during transportation.The nameplate

and specifications are required to be consistent with the order list. If not or something missing,

please contact the factory or the supplier for solution.
1.3 Model Description
See Figure 1.1 for model definition of AS330 escalator integrated drive controller.

AS330 4 T 0022

System Name
Code Motor Power
05P5 5.5kW

4 400V 07P5 7.5kW


0011 11kW
0015 15kW
T 3 Phase
18P5 18.5kW
0022 22kW
0030 30kW
0037 37kW

Figure 1.1 Model Definition of Escalator Integrated Drive Controller

1-1
Shanghai STEP Electric Corporation

1.4 Nameplate Discription


See schematic Figure 1-2 for example nameplate, which shows model number, specification
and lot number of a AS330 series escalator integrated drive controller.

Model Name(MODEL) :AS330 4T0022


第 Matching Motor Power (POWER) :22kW
Input Ratings(INPUT) :AC380V 50/60Hz

Output Ratings(OUTPUT)
: AC380V 0-120Hz 48A 34kVA

Machine No.(No.) :
Manufacturing No.(SER.No.)

Shanghai STEP Electric Corporation

一 Figure 1.2 Nameplate Discription of Escalator Integrated Drive Controller



化 1.5 Safety Notice

动 Danger

制 ◎ Always install on metal structures or other noninflammable objects;
器 Or it may cause fire risk.
◎ Never install in explosive environments
使 Or it may cause explosion risk
用 ◎ Never place combustibles near the product
Or it may cause fire risk.

Caution

◎ Always support the body bottom during handling


Or the possible falling of the main body of escalator integrated drive
controller may cause risk of injury and/or property damage.
◎ The platform on which the product will be installed shall have
sufficient load bearing capacity
Or the contingent falling of the main body of escalator integrated drive
controller may case risk of injury and/or property damage.
◎ Don’t install it in the vicinity of sewage pipe or the points with
splatters
Or it may cause the risk of property damage.
◎ Prevent screws, washers and metal rods falling into the inside of
escalator integrated drive controller
Or it may cause the risk of fire or property damage.

Danger

1-2
AS330 Escalator Intrgrated Drive Controller

◎ Make sure it is disconnected from the mains prior to wiring


Or it may cause risk of electric shock.
◎ The wiring can only be performed by trained and qualified electricians
Or it may cause risk of electric shock.
◎ Always keep the AS330 integrated drive controller properly grounded
at its grounding terminal E
Or it may cause risk of electric shock.
◎ Avoid confusing main circuit input terminals and output terminals of
escalator integrated drive controller
Or it may cause risk of property damage and/or explosion.
◎ Never make terminal ○ +1/○
+2 and ○- be shorted. 第
or it may case risk of fire and explosion
◎ Make sure the cover is placed in position prior to switching on 一
Or it may cause risk of electric shock and/or explosion. 章
◎ Don’t use soggy hands operating escalator integrated drive controller
Or it may cause risk of electric shock
◎ At completion of wiring the emergency stop safety circuit, carefully check
and make sure all the wirings are correct
Or it may case risk of hazard. 一



Danger


◎ When switching on a escalator integrated drive controller which has
been stored for more than 2 years, a voltage regulator is needed to 制
supply it by increasing the voltage gradually 器
Or it may cause risk of electric shock and explosion。 使
◎ Avoid faulty operation when escalator integrated drive controller is 用
running 须
Or it may cause risk of high-voltage electric shock.
◎ After it is switched off, the inside of escalator integrated drive controller 知
may remain dangerous high voltage for a certain period, don’t open the
cover or touch connection terminals
Or it may cause risk of high-voltage electric shock.
◎ Only trained, qualified and authorized person may be allowed to work
on escalator integrated drive controller
Or it may cause risk of electric shock or property damage.
◎ Always remove watches, rings or other metal articles prior to working
and always wear suitable clothes and use appropriate tools when
working on escalator integrated drive controller
Or it may cause risk of electric shock and explosion.

1.6 Precautions in Application


The flowing precautions must be taken in the application of AS330 escalator integrated drive
controller.
1.6.1 Selection of Optional Brake Resistor
Escalator is potential load in four-quadrant running mode, which may cause occurrence of negative
torque. Therefore, escalator integrated drive controller should be provided with optional brake
assembly to avoid overcurrent or overvoltage and the resultant tripper. All As330 series escalator
integrated drive controllers are provided with integrated brake units. You are only required to
connect an external brake resistor. See Table 1.1 for external brake resistors matching various power
classes:
Table 1.1 External brake resistors specifications of AS330 integrated drive controller

1-3
Shanghai STEP Electric Corporation

Matching Total power of the


Model Min Max Recommended
Motor recommended
AS330- (Ω) (Ω) (Ω)
(kW) resistors(W)

4T05P5 5.5 56 100 70 1600

4T07P5 7.5 56 72 64 2000



一 4T0011 11 34 48 40 3200
章 4T0015 15 34 41 36 4000

4T18P5 18.5 17 31 24 5000

4T0022 22 17 27 20 6400

体 4T0030 30 11 20 15 8000

4T0037 37 8 16 12 10000

动 1.6.2 Absorption Devices are not allowed at output side
控 Care should be taken in design, Escalator integrated drive controller provides pulsed output, so it
制 may cause failure of escalator integrated drive controller failure, tripping or element damage when
capacitors or lightning protection piezoresistor for improving power factor of the line is installed.
器 Care must be taken in its design. When retrofit an old escalator, the existing capacitors and
使 piezoresistors at the output side must be removed. See Figure 1.3


知 U
V
W
M

Figure 1.3 No capacitors are allowed at the output side of escalator integrated drive controller
1.6.3 Working Voltage
AS330 escalator integrated drive controller only applies to within rated voltage. Where the supply
voltage is inconsistent with the rated voltage, a voltage regulator must be used.
1.6.4 Two-phase Input Inappropriate
It is not agreeable to change 3-phase input to 2-phase input to avoid failures
1.6.5 Altitude and Derated Application
Where the altitude is above 1000m, the thin air may impair the cooling effect of escalator integrated
drive controller; therefore it is necessary to use it by derating. See Figure 1.4 for the relation between
derated output current and altitude:

1-4
AS330 Escalator Intrgrated Drive Controller



Figure 1.4 Relation between rated output current of escalator integrated drive controller and 章
altitude
1.6.6 Ambient Temperature&Derated Application
Integrated drive controller normally works in the temperature range of -10~+45℃. If it goes 一
over 45℃, each 5℃ up require 10% derated application. 体

1.6.7 Low Voltage directive complies

That our products comply with EN61800-5-1:2007 standards, which comply with the Low 动
Voltage Directive (Low Voltage Directive 2006/95/EC).If the inverter as a component integration in 控
the entire electrical system, make sure theentire system meets the requirements of EC 制
Directives.Note:

① Machine make sure the ground, and make sure the ground terminal is a separateground. 使

② Inverter prohibited for use in of ᇞ ground and IT power systems.

③ If you are loading the cabinet, make sure that the cabinet ground. 知

④ Use CE certified circuit breaker, electromagnetic contactor, and other accessories.Leakage


circuit breakers, please use the B-type leakage circuit breakers.

⑤ Inverter in the overvoltage catalog III, Pollution Degree II, under the conditions of use. The
level of protection of the inverter protection class Ⅰ

1.7 Waste Precaution


The wasted escalator integrated drive controller shall be treated as industrial refuse
1.7.1 Disposal of Capacitors
Burning the electrolytic capacitors on main board or other PC boards may cause risk of explosion.
So, it is forbidden to burn any capacitor.
1.7.2 Disposal of Plastic Components
There are several plastic components on escalator integrated drive controller. It is forbidden to burn
them due to burned plastics will produce toxic gases.

1-5
AS330 Escalator Intrgrated Drive Controller

Chapter 2 Model&Specifications

This Chapter focuses on AS330 seies integrated drive controller’s model, specifications and
mounting dimension.
2.1 Model
AS330 Model see table 2.1
Table 2.1 AS330 Series Integrated Drive Controller Model List 第

Model Rated Capacity Rated Output Current Matching Motor

AS330- (kVA) (A) (kW)

4T05P5 8.5 13 5.5



4T07P5 14 18 7.5

4T0011 18 27 11 与

4T0015 24 34 15 格
4T18P5 29 41 18.5

4T0022 34 48 22

4T0030 50 65 30

4T0037 61 80 37

2.2 Technology Standards and Specification Of Integrated Drive Controller


AS330 Technology Standards and Specificationas following table 2.2
Table 2.2 Technology Standards and Specification Of AS330 Integrated Drive Controller

4T05P5 4T07P5 4T0011 4T0015 4T0018 4T0022 4T0030 4T0037

Max. Matching motor 5.5 7.5 11 15 18.5 22 30 37

Capacity, kW
Capacity 8.5 14 18 24 29 34 50 61

Rating, kVA
Output Ratings

Current Rating, 13 18 27 34 41 48 65 80

A
Max Output 400V:3-Phase 380/400/415/440/460V(corresponds to input voltage
Voltage, V )

Phase number,
Power
Input

voltage, 400V:3-Phase 380/400/415/440/460V、50/60Hz

frequency

2-1
Shanghai STEP Electric Corporation

Allowable
voltage -15%~+10%

fluctuations
Allowable
Frequency -5%~+5%
Deviation
Acceptable 400V:keep running at AC300V or above; activate under-voltage protection
instantaneous after 15 ms from the moment when it drops from rated voltage to below
第 voltage drop AC300V.

Control Mode Escalator special control mode

Starting torque 180%/0.5Hz

Speed control
1:100
型 range
号 Speed control
±0.5%
与 accuracy
规 Torque Limited Yes (Parameter Setting)
格 Torque
±5%
Accuracy
Frequency
0~120Hz
control range
Drive Characteristics

Frequency
Accuracy
±0.1%
(Temperature
fluctuation)
Frequency
setting ±0.06Hz/120Hz

resolution
Output
frequency
resolution 0.01Hz
(computer
resolution)
Overload
zero speed is 150% , < 3Hz is 160%, > 3Hz is 200%
capacity
Brake torque 150%(external braking resistor),integrated braking unit
Acceleration/D
0.01~600s
eceleration time

2-2
AS330 Escalator Intrgrated Drive Controller

Carrier
2~11kHz
frequency
Optoelectronic
input control Isolated 24V DC
supply
Relay output
Isolated 24V DC
control supply
Low-voltage
20-channnel switching capacity. Optoelectronic control signal is isolated 24V 第
optoelectronic 二
Control input/output signal

DC input signal.
isolated input 章
high-voltage
optoelectronic 1-channel switching capacity

isolated input 型

8-channel; Normal open contact; SPST; contact capacity: resistive load, 3A
relay output-1 与
250VAC or 3A 30VDC 规
4-channel; Normal close contact, SPDT; contact capacity: resistive load, 6A 格
relay output-2
250VAC
CAN
communicati 1 channel (safety switch monitoring)

on interface
Analog Input 1 channel,,single or differential input, input voltage range -10V~+10V,accuracy 0.1%

Motor overload
Parameter setting motor protection curve
protection

Inverter Overlaod < 3Hz: 160%,5 seconds, > 3Hz:185%,10 seconds

Short circuit provide protection to escalator integrated drive controller when overcurrent
Protection Function

protection occurs to any two phases at output side

Input open
In case of open phase of input during operating, it cuts off output to protect
phase
escalator integrated drive controller.
protection
Output open In case of open phase of output during operating, it cuts off output to protect
phase
protection escalator integrated drive controller.

Overvoltage
810V(400V Series)
threshold

2-3
Shanghai STEP Electric Corporation

Undervoltage
380V(400V Series)
threshold

Instantaneous

power failure Protection for over 15ms

compensation
Overheat of
Protected by thermistor
第 heat sink
二 Braking unit Automatically detects abnormal conditions of braking unit and activate

protection protection.

Module Protection Overcurrent, Short circuit and overheat protection

型 Current Sensor
号 Self checking after energized
Protection

规 Speed Reverse
格 Check up through encoder
Protection

I²tprotection check up trough 3 phase current

Input overvoltage
400V: more than725V, stop and check
protection

Output grounding Any phase get grounding short connected during operation,switch off the output to protect

protection the inverter

Output unbalance
3 phase current checked to be unbalanced,switch off the output, protect the inverter.
protection

Brake Resistor

Short Curcuit Check up at time of brake

Protection

Anti-reversion
check out the escalator reversion running and activate protection
protection

Overspeed
Activate protection when overspeed to 115% of rated speed.
protection
Underspeed Activate protection in case that real traveling speed of escalator is 80% lower
protection than the rated speed due to some reasons including failures.

2-4
AS330 Escalator Intrgrated Drive Controller

Handrail speed
Check out the handrail speed inconsistency, activate the protection
ckecking protection

Stair Loss
Check out the stair loss during operation,and activate protection
protection

EEPROM fault self checking after energized

LCD in
Display

Chinese and Menus at each level


English 第
Ambient 二
-10~+45℃
temperature 章
Humidity Below 95% RH (no dew)
Environment

Storage
-20~+60℃(temperature allowable during short-term transport) 型
temperature

Application
Indoor (no corrosive gas, dust and so on) 与
place 规
Altitude Below 1000m 格
Protection
IP20
Configuration

class
Cooling
Forced air cooling
mode
Installation mode In-cabinet installation

2.3 Mounting Dimension & Mass

See Fig 2.1 and table 2.3 for integrated drive controller mounting dimension and mass

2-5
Shanghai STEP Electric Corporation








Fig 2.1 Mounting Dimension
Table 2.3 Mass Specification For Escalator Integrated Drive Controller

Mounting Mounting Fastenin


Model A B H W D Hole Bolt Nut g Mass
AS330- (mm) (mm) (mm) (mm) (mm) diameteΦ( Gaske Torque( (kg)
mm) t Nm)

4T05P5 100 253 265 151 166 5.0 4M4 4M4 4Φ4 2 4.5

4T07P5
165.5 357 379 222 192 8.2
4T0011

4T0015 7.0 4M6 4M6 4Φ6 3

4T18P5 165.5 392 414 232 192 10.3

4T0022

4T0030 6
200 512 530 330 290 9.0 4M8 4M8 4Φ8 30
4T0037 9

2-6
AS330 Escalator Intrgrated Drive Controller

2.4 Mounting Instruction

Danger

◎ Always install on metal structures or other


noninflammable objects;
Or it may cause fire risk.
◎ Never place combustibles near the product
Or it may cause fire risk. 第
◎ Never install in explosive environments 二
Or it may cause explosion risk 章
◎ The cabinet in which the product will be installed
shall meet the requirements of EN50178.



Caution


◎ The platform on which the product will be installed
shall have sufficient load bearing capacity
Or the contingent falling of the main body of escalator
integrated drive controller may case risk of injury
and/or property damage
◎ Don’t install it in the vicinity of sewage pipe or the
points with splatters
Or it may cause risk of property damage.
◎ Prevent screws, washers and metal rods falling into
the inside of escalator integrated drive controller
Or it may cause the risk of fire or property damage.
◎ Never start a escalator integrated drive controller
which is damaged or components are not completed
mounted
Or it may cause risk of property damage.
◎ Don’t install under direct sunlight
Or it may cause risk of overheat or resulting accidents;
2.4.1 Mounting Place

The place where the escalator integrated drive controller will be mounted shall meet such conditions
as:
a) Clean, without oil mist, dust or suspended matters which may fly into the fully enclosed
cabinet;
b) No possibility of metal powder, oil or water entering into the inside of escalator integrated drive
controller;
c) No wood and other combustibles are stored;

2-7
Shanghai STEP Electric Corporation

d) No radioactive substances are placed;


e) No hazardous gases or liquids are stored;
f) Vibration is as low as possible;
g) Not a salty atmosphere;
h) Not under direct sunlight;
i) Temperature rise is as low as possible;

when install the product in a enclosed cabinet, suitable cooling fans or air conditioners should be
provided to keep the ambient temperature under 40℃。

2.4.2 Mounting Orientation and Clearance Requirements

章 To avoid impair the cooling effect of escalator integrated drive controller; this product shall be
installed at a well-ventilated place. In general, it is vertically installed with suitable clearances as
shown by Figure 2.2.




Figure 2.2 Requirements on Mounting Clearance

2-8
AS330 Escalator Intrgrated Drive Controller

Chapter III Product Functions

This chapter focuses on the function list and function detailed description for AS330 series escalator
integrated drive controller

3.1 Fuction List

Table 3.1 Product Description

Code Description Notes Code Description Notes


(Standard) (Optional)

1 Up-down Operation 1 Running Monitering

2 Inspection Running 2 Bypass Conversion Running


3 Automatic Oil Filling 3 Fire Escalator Function
Up-Down Machine Room Theftproof
4 Running Situation Display 4
Check
5 Historical Fault Log 5 Water Level Check
Energy Saving
6 Operation(Frequency Conversion 6 Lubrication Oil Level Check
Mode)
7 Stair Loss Check 7 Overheated Motor Check
8 Stair Speed Measurement 8 Brake Wearing Check
9 Handrail Speed Measurement 9 Additional Brake Function
10 Anti Reverse Protection 10 Alarm Light
11 Fault Protection 11 Fault Information Display
12 Escalator Smart Stop 12 Safety Switch Monitering
13 Alarm Bell 13 Fault Memory
14 Running Direction Indicator 14
15 Contact Anti-Adhesive Check 15
16 Brake Switch Check 16

9
AS330 Escalator Intrgrated Drive Controller

3.2 A Brief on Function and Setting

3.2.1 Description Of Standard Functions

1、Up-Down Operation
In the automatical situation, up/down command is input to the integrated drive controller
through outdide key, which activates the up/down operation. The outside switch is of automatical
reset.
2、Inspection Running
If the main board of integrated drive controller is in inspection, the auto input point is of no
signals, the system is in inspection mode. Outside, through up/down button of inspection handle, the
escalator is activated by inching. The escalator inspection running speed can be modified through the
main board parameter adjustment .The interlock against up-down handle simultaneous operation 第
should be set outside. 三
3、Automatical Oil Filling 章
The parameter setting can specify the interval between the oil fillings and the filling
time. If the escalator continuous running time reaches the set value, a continuous relay
signal will be sent to start the oil pump for filling. After a set period of time, the relay

signal stops. The filling can only be done during escalator running. For temporary it can

not match the pulse oil filling equipment.

4、Running Situation Display

Different running situations can be displayed through the handset or on-borad operator, like
inspection/auto, up/ down, safety loop, running mode (normal/energy saving), fault, fire and so on.
The escalator running direction can be output through the relay and displayed by the outside
light indicator
5、Historical Fault Log
Fault code, time and troubleshooting time, first running time and direction can be recorded.
The fault historical logs can be read through handset or on board operator, including fault
code,fault time,fault code definition, fault time escalator running situation(up/down/stop),
troubleshooting time.
6、Energy Saving Operation
Support casual low speed operation or casual pause mode. Not support bi-directional
auto operation mode. When the escalator photoelectricity has no person passing during
the set period of time, the system turns to casual low speed mode. And after a set period
of time, the system truns to the casual stop mode. For the Y-ᇞ operation, the casual
mode is directly to stop.
7、Stair Loss Check
When main processor pulse value between X12 and X13 is bigger than set value, or the
interval between two pulses is bigger than set value, the system takes it as stair loss, and
the escalator will be emergently stopped. Meanwhile.X12,X13 take self checking. If
during running, the signals continuously input with high or low electricity level, then it
will judge the check switch has problem and activate problem.
8、Escalator Speed measurement
Measurement point is fixed on the main gear. The escalator pulse number is recorded
with 200ms refreshing frequency, and it is compared with the set benchmark value. If

3-1
Shanghai STEP Electric Corporation

the differential between the current value and the set value is more than 20 %, the
escalator will be emergently stopped for protection
9、Handrail Speed Measurement
Check the pulse number of the stair speed measurement between every two pulses and
compare it with the set benchmark value, if the differential between the current value
and the set value is more than 20 %, it means handrail speed is wrong
10、Anti-reverse protection: through two escalator speed measurement points, compare
Phase A and Phase B, and confirm the escalator direction by the differential between
phase A and B, and compare to the set direction.
12、 Escalator Smart Stop
Normal stop: Non emergent fault stop, press the stop button, the controller turns off all the
第 outputs.
三 Emergent Stop: At the time of emergent fault like overspeed, reversion, drive chain breakage,
章 the controller turns off all the outputs, meanwhile stop the additional brake output.
Soft Stop, use the key switch to make reverse-direction continous input over 3S (against the set
operation direction), the conreoller will stop in the condition of uniformly deceleration
产 13、 Alarm Bell
品 The bell will be on at the time of overhaul’s first startup and normal running startup. Bell time
功 is also set for the situation of direction or cover plate stolen.
能 14、 Running Direction Indicator
The controller will provide 2 ouput points for the auto-escalator running direction. The output
will be kept after the end of casual situation. It will be stopped only at the time of stop signal input.
15、 Contact Anti Adhesive Check;
The controller provides the check for the contact point. It is used when there is no outout, the
input point has no output ,then next time operation controller will not have output until the input
point recovers.
16 Brake Switch Check
When the operation starts, the controllers outputs the brake signals, check the input point of the
brake switch, if the output of the brake switch is not off, then means the switch fault. Turn off the
output and send the fault signal.

Optional Function
1、Running Monitering
Currently it can moniter the fault log, the current operation direction, casual situation, auto
maintainnence/fire (if more need for the monitoring board, please check the manual for the escalator
monitoring software)
2 Bypass Conversion Operation
When the parameter F0 is set to “1”,at that time the system goes into the mode of bypass
conversion operation., During the escalator running,the converter get started, it will uniformly
accerlerate to full speed, then the controller make the auto switchover to working frequency through
Y-ᇞ contact. The startup is finished
In the set period of time, the photoelectricity switch does not receive the signals; the controller
will automatically switch to conversion operation and meanwhile lower the frequency to the set

3-2
AS330 Escalator Intrgrated Drive Controller

value to adjust the escalator speed to satisfy the need of energy saving.
3、 Fire Function
For the normal escalator, all stops. For fire escalator,down operation stops,up-operation keeps
normal, at that time the system will shield casual function.
4、Up-Down Machine Room Theftproof Check
In the auto situation of up-down machine room theftproof check, the theftproof switch works
but the cover plate check switch is not active, fault alarm will be on and the escalator will stop.
5、Water level Check
The monitoring point of the monitoring water level has input, the controller will output the fault
information and turn off the output.
6、Lubrication Oil Level Check
When the oil level check point has outputs, the controller will give the fault signal, to indicate 第
the oil feeding. The escalater at that time still keeps running. 三
7、Overheated Motor Check 章
Overheated motor protection, when the motor overheat switch get the input signal, the
controller will output the fault signal and turn off the output.
8、Brake Wearing Check 产
Brake wearing protection, when the brake wearing switch gets the input signal, the controller 品
output fault signal and turn off the output 功
9、Additional Brake Function 能
This function has 2 logics(check situation,auto situation)
1) In the check situation, input the up-going signal, output the additional brake signal. After
additional brake is powered on, check its switch signal, if it goes normally, keep going,
if not, then the controller cuts off the output and records the fault. But it will return to
check situation, if continuous 3 checks turn out to be problem, then it is needed to cut
off the power and reset the fault.
Input the down going meanwhile check the switch signal, if it is abnormal,then stop
operation.
For non emergent stop for the escalator,the additional brake do not work.

2) In the auto situation input the up-going signal, output the additional brake signal. After
2S, check its switch signal, if it places normally, keep going, if not, then the controller
cuts off the output and records the fault. But it will return to check situation,if
continuous 3 checks turn out to be problem, then it is needed to cut off the power and
reset the fault.
Input the down-going signal, output the additional brake signal. After 2S, check its
switch signal, if it places normally, keep going, if not, then the controller cuts off the
output of the switch signal and brake signal.
For non emergent stop for the escalator, the additional brake cuts off the output after set
period of delay time.
3) For the normal operation, the conditions that the additional brake cut off the output are
overspeeding, reverse, drive chain breaking off.
10、Alarm Indicator
Rolling display for the fault information and event list.

3-3
Shanghai STEP Electric Corporation

11、Fault Information Display


The controller checks out the outside and inside faults, which can be displayed through fault
displayer or shown and checked through the handset operator.
12、Safety Switch Monitering
Safety loop switch monitoring can be made through ES.02/B safety chain fault collector. If the
safety switch gets off, the fault information can be sent through CAN Bus to the fault displayer or
handset operator.
13、Fault Memory
The controller checks out the outside and inside faults, automatically restore the time, code and
troubleshooting time. Check through the handset operator.






3-4
AS330 Escalator Intrgrated Drive Controller

Chapter 4 Wiring of Escalator Integrated Drive Controller


This chapter defines the wiring of escalator integrated drive controller terminals, including the
wiring of main circuit terminals, control circuit terminals and PG card terminals.

Danger

◎ Before wiring, please make sure that power supply is completely


disconnected.
Or it may cause risk of electric shock.
◎ Wiring must be performed by professional electrical personnel.

Or it may cause risk of electric shock.

◎ Earth terminal E shall be grounded reliably.

Or it may cause risk of electric shock.
◎ Please never touch the terminal with hands; never have the drive
controller output line contact the enclosure.
Or it may cause risk of electric shock. 电
◎ Please never connect the power supply to output terminals U, V and 梯
W. 一
Or it may cause damage. 体
◎ Please never short the terminal +1/
○ +2○ with-.
○ 化
Or it may cause risk of explosion.







Caution 线

◎ Please check the voltage of AC main circuit power supply is consistent


with the rated voltage of integrated driver controller.

Or it may cause risk of fire and physical injury.

◎ Please correctly connect the braking resistor as per the wiring


diagram.

Or it may cause risk of fire.

◎ Main circuit terminal must be firmly connected with the conductor or

4-1
Shanghai STEP Electric Corporation

wire crimping terminal.

Or it may cause risk of damage.

4.1Integrated Drive Controller Connected To The Perpherial Equipments

4.1.1 Escalator Integrated Drive Controller Typical Scheme Example
















线

4-2
AS330 Escalator Intrgrated Drive Controller















线

Fig 4.1 Escalator Integrated Drive Controller Typical Scheme Example

4-3
Shanghai STEP Electric Corporation

4.2 Terminal Wiring Of Main Curcuit

4.2.1 Layout of Main Circuit Terminals


+1 ○
+2 B ○
- R/L1 S/L2 T/L3 U/T1 V/T2 W/T3

第 4.4.2 Labeling of Main Circuit Terminals and Functional Description


四 Table 4.11 Function Description of Main Circuit Terminals

Terminal label Terminal function description


+1 External connection with DC reactor, factory situation

梯 ○
+2 is short connection
一 ○
+2
体 External braking resistor connection
化 B

驱 ○
- Negative output terminal of DC bus

R/L1

Main circuit AC power input, connecting 3-phase input
制 S/L2
器 power
T/L3

配 U/T1
线 Escalator integrated drive controller output, connecting
V/T2
3-phase synchronous/asynchronous motor
W/T3

4.4.3 Conductor Specification in Main Circuit Connection

The conductor is 600V plastic insulation conductor for power supply. See Table 4.2 for conductor
specification and fastening torque.

Table 4.2 Conductor Specification and Fastening Torque

4-4
AS330 Escalator Intrgrated Drive Controller

Spec. of connectible Spec. of recommended Fastening


Model AS330-
wire mm2 wire mm2 torque(N.m)

4T05P5 2~6 4 1.5

4T07P5 4~8 6 2.5

4T0011 4~8 6 2.5

4T0015 4~8 6 2.5

4T18P5 8~16 16 4.0

4T0022 8~16 16 4.0

4T0030 14~25 25 9 第
4T0037 35~100 35 9 四

Important
The wire specification is as per ambient temperature 50℃. The allowable temperature is 电
confirmed to be up to 75℃ 梯
Main circuit of integrated drive controller is of open wiring terminal. For this, round crimp 一
terminals should be used. The round crimp terminals can be optional against the below table 4.3. 体

Table 4.3 Specification Of Round Crimp Terminals

Wire Section(mm2) Terminal Bolt Speci. Round Crimp Terminal Speci. 动

M3.5 1.25/3.5

0.5
M4 1.25/4 器

M3.5 1.25/3.5 配
0.75
M4 1.25/4 线

M3.5 1.25/3.5
1.25
M4 1.25/4

M3.5 2/3.5

M4 2/4

2 M5 2/5

M6 2/6

M8 2/8

M4 5.5/4
3.5/5.5
M5 5.5/5

4-5
Shanghai STEP Electric Corporation

M6 5.5/6

M8 5.5/8

M5 8/5

8 M6 8/6

M8 8/8

M6 14/6
14
M8 14/8

M6 22/6
22
M8 22/8

四 30/38 M8 38/8

M8 60/8
50/60
M10 60/10

电 80 80/10
梯 M10
一 100 100/10





控 Important
制 The voltage drop should be paid enough attention while confirming the wire section area
器 General principle is to keep voltage within 2% of the rated value. If the voltage drops much,
的 the wire section should be enlarged. The formula is as follows:
配 Inter Wire Voltage Drop(V)= 3 * Wire Resistance(Ω)* Current(A)
线

4.4.4 Structure of Main Circuit

4-6
AS330 Escalator Intrgrated Drive Controller

+1 +2 B -

R U
V
S
T W

Plug
Emergency Power Switch Power Control loop 第

Fig 4.4 Structure of Main Circuit




4.4.5 Detailed Wiring Description of Main Circuit Terminals 一
4.4.5.1 Earth Terminal (E), i.e. (PE) 体

a) Preferably, earth terminal could be dedicated earth electrode and must be properly grounded, 驱
with earth resistance below 10Ω; 动

b) Never use an earth wire together with a welder or other power equipment; 制
c) Please use the earth wire with the specification required in electrical equipment technical 器

standard and it should be as short as possible. If the wire is too far from the grounding point, 配
leakage current of the drive controller will destabilize the potential of earth terminal; 线

d) Earth wire should be multistrand cooper conductor of at least 3.5mm2; it is recommended to

use the dedicated yellow-green wire;

e) In the case of grounding several drive controllers, it is recommended not to form a loop.

Grounding several drive controllers see Fig 4.5

4-7
Shanghai STEP Electric Corporation

Fig 4.5 Grounding several drive controllers


4.4.5.3 Main Circuit Power Input Terminals(R/L1,S/L2,T/L3)

a) 3-phase AC power is connected with main circuit terminals R/L1, S/L2 and T/L3 via the circuit

breaker. Phase sequence of input power is not related to the sequence of terminals R/L1, S/L2 and

T/L3, any terminal could be connected.

章 b) To reduce the conduction and radiation interference of the drive controller over input power, the

noise filter may be provided at the power side. This filter can reduce the noise ingress into the

drive controller from power cable and also reduce the noise outflow from the drive controller to

梯 power cable.

体 Caution

Special Note: Please use the specific noise filter for the escalator integrated drive controller.

动 See Fig. 4.7 for correct setting of power-side noise filter.





线
Fig. 4.7 Correct Setting of Power-side Noise Filter

See Fig. 4.8 and 4.9 for incorrect setting examples of power-side noise filter.

Fig. 4.8 Incorrect Setting Example 1 of Power-side Noise Filter

In Fig. 4.8, setting a noise filter at power-side does not necessarily achieve the expected results and
should be avoided.

4-8
AS330 Escalator Intrgrated Drive Controller

Fig. 4.9 Incorrect Setting Example 2 of Power-side Noise Filter

In Fig. 4.9, setting a noise filter at reception-side does not necessarily achieve the expected results
and should be avoided.

4.4.5.4 External DC Reactor Terminals (+1,


○ +2)

a) To improve the power coefficient of the escalator integrated drive controller, DC reactor may be

○ 1 and +
connected. Before delivery, a short-circuit block is mounted between terminals + ○ 2. To 四

connect DC reactor, please remove short-circuit block before connection;

b) If the DC reactor is not used, do not remove short-circuit block, otherwise abnormal operation

will occur; 电
See Fig. 4.10 for connection of short-circuit block. 梯
Short-circuit block


Short-circuit 化
短路块
block 驱

+1 +2 B -

R/L1
+
U/T1 制
S/L2 V/T2
T/L3 W/T3 器
E


Fig. 4.10 Short-circuit Block Connection Diagram 线
See Fig. 4.11 for connection of external DC reactor.

External
外接直流电抗器 DC reactor

+1 +2 B -

R/L1 U/T1
S/L2 + V/T2
T/L3 W/T3

Fig. 4.11 Connection Diagram of External DC Reactor

4.4.5.5)External Braking Resistor Terminals (+2,


○ B)

a) All AS330 escalator integrated drive controllers are provided with built-in braking units. To

4-9
Shanghai STEP Electric Corporation

release the energy feedback in motor braking, the braking resistor must be connected. See the

Braking Resistor Configuration Table 1.6.1 in Chapter 1 for specifications of braking resistors.

b) ○ 2 and B;
The braking resistor is mounted between terminals +

c) To keep the resistor work normally, be sure to thoroughly consider the condition of its heat

dispersion and ensure sound ventilation;

d) The connection of braking resistor shall be less than 5m.


See Fig. 4.12 for connection of external braking resistor.

External braking resistor


外接制动电阻

第 +1 +2 B -

R/L1 U/T1
章 S/L2 + V/T2
T/L3 W/T3

电 Fig. 4.12 Connection of External Braking Resistor



一 4.4.5.6 Output Terminals of Escalator Integrated Drive Controller(U/T1,V/T2,W/T3)

a) Output terminals U/T1, V/T2, W/T3 of AS330 escalator integrated drive controller connect with

驱 motor terminals U, V and W. If the direction of motor rotation is wrong, please exchange any two

connections of output terminal or motor terminal.

制 b) Never connect the power supply with output terminals U/T1,V/T2,W/T3 of the drive controller.

c) Never ground or short the output terminals.

配 d) Never connect the capacitor and/or surge filter at output side. Since the escalator integrated
线
drive controller outputs higher harmonic wave, capacitor and/or surge filter connection at output

side may result in overheat and damage.

See Fig. 4.13 for schematic of never connecting the capacitor at output side of the escalator
integrated drive controller.

4-10
AS330 Escalator Intrgrated Drive Controller

U/T1
V/T2
W/T3
M

Fig. 4.13 Schematic of Never Connecting the Capacitor at Output Side

4.5 Anti-interference Measures


4.5.1 Connecting Specific Noise Filter at Output Side

To depress the noise produced at output side, a specific noise filter may be connected at the output
side of AS303 escalator integrated drive controller. See Fig. 4.14 for connection of output-side noise
filter.

Escalator




Fig. 4.14 Connection of Output-side Noise Filter

4.5.2Layout of Main Circuit Wiring 化
To depress the radiation interference produced at output side and increase the interference immunity,

the wiring of main circuit and control circuit should be separated. Main circuit wiring inserts through

metal earth tube, at least 10cm away from signal cable. See Fig. 4.15 for main circuit wiring layout

schematic.




线
Escalator

Fig. 4.15 Main Circuit Wiring Layout Schematic

4.5.3 Preferred Anti-interference Measures

4-11
Shanghai STEP Electric Corporation

The preferred anti-interference action is to set the noise filter at input and output sides, and have the
drive controller unit shielded in an iron box. See Fig. 4.16 for details.

Fig. 4.16 Preferred Anti-interference Measures

4.5.4Relationship between Wiring Length and Carrier Frequency



四 If the wiring between the escalator integrated drive controller and the motor room is too long, higher
章 harmonic leakage current will be increased due to the influence of wire distributed capacitors, which
might enable over-current protection for the drive controller output and produce adverse impact on
surrounding equipment and the motor. Hence, preferably, the wiring between the escalator integrated
电 drive controller and the motor room shall not be more than 100m in length.
梯 If the length is over 100M, please adjust the carrier frequency by referring to the Table below and
一 select the appropriate output-side filter and reactor.

化 Wiring distance between the
驱 escalator integrated drive Below 50m Below 100m Above 100m
动 controller and the motor room

Carrier frequency Below 11kHz Below 8kHz Below 5kHz

器 4.6Wiring of Control Circuit Terminals

4.6.1Layout of Control Circuit Terminals

线 Layout of control circuit terminals is as shown in Fig. 4.17.

High voltage Relay output


opto-coupler
input

4-12
AS330 Escalator Intrgrated Drive Controller

图 4.17 控制回路端子

CAN Communication
Cotactor For
Extened Board

Isolated Power Input

High voltage
Analog Input
opto-coupler

input

Fig. 4.17 Control Circuit Terminals



4.6.2 Functional Description of Control Circuit Terminals 梯
See Table 3.4 for functional description of control circuit terminals. 一

Table 4.4 Functional Description of Control Circuit Terminals 化

Code Terminal Name Definitions Usage Notes

JP1.1 Y0 Brake Contact Output Output

Frequency Conversion Operation Contact 制
JP1.2 Y1 Output
Output/Kmc(Pure Frequency Conversion) 器


Working Frequency Operation Contact
JP1 JP1.3 Y2 Output 线
Output/Stand By(Pure Frequency Conversion)

JP1.4 Y3 Auxilary Brake Contact Output Output

JP1.5 COM1 Common terminal Y0-Y3 of output relay

Up-Going Contact Contact Output/Stand By(Pure


JP2 JP2.1 Y4 Output
Frequency Conversion)

4-13
Shanghai STEP Electric Corporation

Y5
Down-Going Contact Contact Output/Stand
JP2.2 Output
By(Pure Frequency Conversion)

Y6 Y-Contactor Output/Kmy(Pure Frequency


JP2.3 Output
Conversion)

ᇞ-Contactor Output(At double mode conversion


JP2.4 Y7 situation,output to be connected with Output
motor)/Standby(Pure Frequency Conversion)

JP2.5 COM2 Common terminal Y4-Y7 of output relay




JP3.1 Y8 Up direction instruction output Output

JP3.2 Y9 Down direction instruction output Output
JP3 JP3.3 Y10 Buzzer Signal Output Output
电 JP3.4 Y11 Oil Feeding Signal Output Output

一 JP3.5 COM3 Common terminal Y8-Y11 of output relay

JP4.1 24V 24V DC

JP4.2 0V 0V DC

动 Serial communication signal terminal
JP4 JP4.3 CAN0H
(TXA0+)

制 Serial communication signal terminal
JP4.4 CANOL
器 (TXA0-)

配 JP5.1 XCOM X20 common terminal of input OV

线
Safety loop check positive voltage terminal,
JP5 JP5.2 X20 line-in 110V /220V Input

JP5.3 XCOM X20 common terminal of input OV

JP7.1 G5VIO Isolated Power 0V


To consider the power
supply while working
JP7.2 +5VIO Isolated Power +5V
with single board
JP7
JP7.3 Blank
optocoupler isolation power 0V
JP7.4 G24VIO

4-14
AS330 Escalator Intrgrated Drive Controller

optocoupler isolation power +24V


JP7.5 +24VIO

JP8.1 X0 Inspection Signal,off is for “inspection” Input o

JP8.2 X1 Up-Going Signal Input


JP8.3 X2 Down-Going Signal Input

Contact Adhesion Test/Xmy (Pure Frequency


JP8.4 X3 Input
Conversion)

JP8
JP8.5 X4 Up side photoelectricity check Input
JP8.6 X5 Down side photoelectricity check Input
JP8.7 X6 Safety loop check Input

JP8.8 X7 Drive Chain Breakup Check Input

JP8.9 X8 Brake Switch Check Input

JP8.10 X9 Auxilary Brake Switch Check Input

2K High Speed
JP9.1 X10 Motor Speed Check 1 Input 电
Input
2K High Speed 梯
JP9.2 X11
Motor Speed Check 2/Anti-Reversion Switch
Input Input 一
Check(Parameter Option) 体

2KHigh Speed
JP9.3 X12 Up Stair Loss Detector Input 驱
Input

2KHigh Speed 控
JP9.4 X13 Down Stair Loss Detector Input
Input 制
2KHigh Speed 器
JP9.5 X14 Left rail speed check Input
Input 的
2KHigh Speed 配
JP9 JP9.6 X15 Right rail speed check Input
Input 线

JP9.7 X16 Auxilary Brake Contact Check Input

Converter Contact Check/Xmc(Pure Frequency


JP9.8 X17 Input
Conversion)

Working Frequency Contact Check/Brake


JP9.9 X18 Input
Contact(Pure Frequency Conversion)

Y-ᇞ switchover input/fire/motor


JP9.10 X19 temperature(Parameter Setting) Input

4-15
Shanghai STEP Electric Corporation

Input Isolated Power +24V,inside connected with


JP10.1 +24VIO JP7.5

Outside connected with JP10.1,then input low


electrical level, at that time JP10.3 is the common
JP10 JP10.2 VSIO terminal for input; Outside connected with
JP10.3,then input high electrical level, at that time
JP10.1 is the common terminal for input;


四 Input Isolated Power 0V, inside connected with
JP10.3 G24VIO
章 JP7.4

JP11.1 0V Anolog Input 0V


AIN- Differential Analog Input-
JP11.2
电 JP11
AIN+ Differential Analog Input+
梯 JP11.3


化 4.6.3Description of Dip Switch Settings

动 Valid Monitering CAN terminal
ON
控 resistor
制 SW1 set to ON at maker’s factory

Invalid Monitering CAN terminal
的 OFF
resistor

线

ON program burn recording


at maker’s factory
SW2
(try to keep OFF during the use)
OFF normal working

4.6.4Wire Specification in Control Circuit Connection

The wire is 600V plastic insulation wire for control curcuit. See Table 4.5 for wire specification and
fastening torque.

Table 4.5 Wire Specification and Fastening Torque

4-16
AS330 Escalator Intrgrated Drive Controller

Spec. of
Spec. of connectible Fastening
Model recommended wire
wire mm2 torque(N.m)
mm2

AS330 FULL SERIES 0.75~1 0.75 1.5

The wire specification is as per ambient temperature 50℃.the allowable temperature is


confirmed to be up to 75℃
4.6.5 Cautions on Wiring of Control Circuit Terminals

The wiring of control terminals should be away from that of main circuit as far as possible,
otherwise false action may be resulted in due to the interference.

4.7 Wiring of phase position collector



1、 Description For Phase Position Collector 四
PHC-100 Phase position collector is to collect the three power phase postion while bypass 章
conversion switchover



H1
H2
H3
H




W2 D
W1
W



相位采集器外形图1

相位采集器型号 外形图 外形尺寸mm 器
W H D H1 W1 H2 W2 H3
AS.L15-A 1 的
59 108 33 96.5 49 74 41 50.5

Outline Figure 1 of Phase Position Collector (Dimension)
线

4-17
AS330 Escalator Intrgrated Drive Controller

ChapterⅤ Operator

AS330 Integrated Drive Controller carries LED Indicator light and Seven-Segment Displayer. Its
programmable LED indicator light is to show the input and output situations and some other basic
situations of the escalator. Integrated drive controller’s parameter and fault codes can be checked out
through seven segment displayer. Besides, AS330 integrated drive controller also supports LCD
liquid crystal handset operator, which realizes the advanced commissioning for the escalator.
5.1Seven-Segment Display Operator
See below fig 5.1 for the appearance and definition of Seven Segment Displayer including the
detailed description for the operator key functions.

LED Indicator 第
Light 五

Seven Segment
Operator
Digital Tubes 操
Contact

Function Key

Fig 5.1 Part definition for seven Segment Operator


5.1.1 LED Indicator Light

Seven segment displayer has 27 LED Indicator light,the mid 18 channels L1-L18 is of X0-X17
input situation. Light on means input, Light off means no input, other lights are all invalid.
5.1.2 Function Keys

9 keys on the operator, see table 5.1 for key function

Table 5.1 Key Function Description


Key Discription Function
1.Move up by one item in function selection
UP 2. Increase 1 of the present data in data input

1. Move down by one item in function selection


DOWN
2. Decrease 1 of the present data in data input

1.Move left by one item in function selection


LEFT
2.Move cursor left for data input

5-1
Shanghai STEP Electric Corporation

1.Move right by one item in function selection


RIGHT
2.Move cursor right for data input

ESC Esc 1.Cancel data input

1.Modify the parameter when viewing parameter


ENTER Enter
2.Save data input

MENU MENU Temperary For No Function

F1 F1 Display the Fault Code

F2 F2 Input situation of safety chain fault collection board




章 5.1.3 Operations for the Operator

5.1.3.1 Menu Structure


Main Menu Structure is as below fig 2. Due to the limit of seven segment and button structure,

the interface utilizes one level menu. Press “left” amd “right” to switchover among the menus. Press

“Menu” to switchover between LED function options and door close/open control

Drive parameter Faultcode Drive program Control program Escalator running
version Escalator speed
reset reset version situation

Control
parameter reset Faultcode

First level main menu


Input type Use “<””>”to switchover among the menus System date

Safetychain fault
ParameterF
Password login collectorboard System time System year
setting
input situation

Fig 5.1 Menu Structure

5.1.3.2 “Left”and “right”keys swichover to each menu operation details


Press “left” or “right” under the first level menu to switch for every menu. Every time energized,
the escalator running situation is on display. Each menu detail is as follows:
1. Escalator Running Situation(energized to display)

5-2
AS330 Escalator Intrgrated Drive Controller

Speed
Model
Running Situation
This menu is to show the basic situations of the escalator inclusive of running, floor, and door.
Running Situation:

escalator going up, escalator going down, escalator stop



Escalator running mode:

pure working frequency , pure frequency conversion , working 操


frequency/converted frequency 作
Escalator running speed: 器

no speed, casual jogging

Inspection, Normal

2. Fault Code

Fault Code
Fault Code Series Number
Integrated drive controller is able to save 20 fault codes. The closest fault code series number is 00.
Up/down button operation to browse these fault codes. Press “Enter” to show the fault

5-3
Shanghai STEP Electric Corporation

date,Press”left” and “right” to check the fault time and fault floor. Press”ESC” to quit.

3. System Year

The fig above is the year 2010. “Y” is the short for “Year”. When modification needed, press
“Enter”, the lowest number starts to blink. Use the “left’ and “right” button to modify the number
need to be changed. The chosen number will blink, then modify through “up’ and ‘down”
button,then Press”Enter” for confirmation.
4. System Date




The above fig is for 8/12. “d” is for Day. When the modification is needed, press “Enter” the
lowest number starts to blink, Use the “left’ and “right” button to modify the number need to be
操 changed. The chosen number will blink, then modify through “up’ and ‘down” button,then
作 Press”Enter” for confirmation.

5. System Time

The above fig is 15:36. “T” is short for Time, Please be noted, due to the limit of seven
segment,the “T” is all as above for integrated drive controller. When the modification is needed,
press “Enter” the lowest number starts to blink, Use the “left’ and “right” button to modify the
number need to be changed. The chosen number will blink, then modify through “up’ and ‘down”
button,then Press”Enter” for confirmation.

6. Input situation of safety chain fault collection board

X series number
X input situation

5-4
AS330 Escalator Intrgrated Drive Controller

The above fig is : X0 has no input. Press”up” and “down” to choose X series number, the series
number from 0~15, the highest position means this input port has no valid input, (0 means no valid
input. 1 means valid input available
7. password Login

Press “Enter” into the below menu display,



Input password, as shown the password is 149

In the login menu, you can see “login”. Press “Enter” ,the lowest position of LED starts to blink.
Use the “left’ and “right” button to locate the position needed for digit input,the chosen location will
blink, it means in the digit input situation.Then choose the digit needed through “up’ and ‘down”
button. Complete the digit input and Press “Enter”, login finished. If the password is 操
correct.press”Enter” to display “login” if not, press “Enter” to still remains in the password input 作
situation. Press “ESC” to quit 器
Notes: Under the situation of non-login, the escalator situatuin and parameters are only for
browse. Only after login , the modification is allowed.

8. F Parameter Setting

Considering very many F parameters, the parameter code is of 3 digit display, and the
parameter requires multi digit display. So the special treatment is taken in designing, using alternate
display to show F parameters. The specific operation is as follows: use “up” and “down” button to
choose the browsed parameters. For istance, F5, the screen display the above fig “F-005”,one second
later, the screen will show the parameter of F5 ,as above fig,after you see “300”, “F-005” and
“300” will be alternately on display, each is for one second. Press”Enter” lowest position of LED
start to blink, choose the digit for this position via “up” and “down” button. Choose the position via

5-5
Shanghai STEP Electric Corporation

“left’ and “right” button, the chosen position will blink, it means for the digit input situation, reuse
the “Up” and “down” to chooest the digit. And “Enter” to finish the parameter modification,the
chosen position stop blink.
F parameter modification must be done with login authority, if without login, press “Enter” to
jump to “Login”

9. Input Type

Input Type Parameter


X input position



Input Type Parameter


操 GX input position

Input Type Parameter


HX input position
Through “up’ and “down”button,to choose the X/GX/HX input positions for modification.
Press “Enter”, the parameter sart to blink, then through “up’ and “down”button to set the
parameter.”Enter” to confirm. “1” means constantly-closed input, “0” means constantly-open input.
Please be careful, the ‘X’ “G’ “H” display for the integrated drive controller is as above, “X” is very
similar to ‘H”, Do not make mistake!
Input type modification must be done with login authority, if without login, press “Enter” to jump to
“Login”

10. Control Parameter Reset

This menu is to finalize F0~F199 control parameter Reset. Please take note, the control

5-6
AS330 Escalator Intrgrated Drive Controller

parameter Reset will be effective on condition that the login grade must be ≥2, if the login grade is
not enough, “Enter” press will not have any effect. If the login grade is enough, press “Enter” into
the authentication code input menu (the authentication code is for misoperation, the code is fixed as
5678) If the authentication code is correct, press’Enter” control parameter get reset.

11. Drive parameter Reset

This menu is to finalize F200~F255 drive parameter Reset. Please take note, the drive parameter
Reset will be effective on condition that the login grade must be ≥2, if the login grade is not enough,
“Enter” press will not have any effect. If the login grade is enough, press “Enter” into the
authentication code input menu (the authentication code is for misoperation, the code is fixed as

5678) If the authentication code is correct, press’Enter” drive parameter get Reset.


12. Fault Code Reset




This menu is to finalize fault code Reset. Please take note, the fault code Reset will be effective
on condition that the login grade must be ≥2, if the login grade is not enough, “Enter” press will not
have any effect. If the login grade is enough, press “Enter” into the authentication code input
menu(the authentication code is for misoperation, the code is fixed as 5678) If the authentication
code is correct, press’Enter”fault code get Reset.

13. Drive Program Version

This menu is to display the version No. of the drive section program, one second later, the
screen will show the Version No.30.03 of drive section program as above fig. Then “VER1” and “30.03”

5-7
Shanghai STEP Electric Corporation

display alternately, each is for 1 second.

14. Control Program Version

This menu is to display the version No. of the control section program, one second later, the
screen will show the Version No.30.03 of control section program as above fig. Then “VER2” and “E20”

display alternately, each is for 1 second.

章 5.1.3.3. LED display digit and alphabet list

Due to the LED structure limit, the display digit sand alphabets are partly difficult to read. So
the below display list is offered

作 Display Meaning Display Meaning Display Meaning Display Meaning

1 2 3 4

5 6 7 8

9 0 A B

C D E F

G H I J

K L M N

O P Q R

5-8
AS330 Escalator Intrgrated Drive Controller

S T U V

W X Y Z

5.2 LCD HandSet Operator


5.2.1 General Description
Handset is designed specially for the commissioning and maintenance. It consists of a LCD display
and a film button. And the main functions are described below:

One,Main monitor interface


The following escalator status can be monitored via LCD display:
a) Situation like Inspection, Normal, etc; 第
b) Running times of escalator; 五

c) Running direction of escalator;
Two.Monitor status

a) Drive Situation: Check the escalator set speed, feedback speed, bus voltage,output 操
current,output torque,pre-torque,ect 作
b) Input/Output:Escalator Input and Output situation and the description for each port 器
c) Fault Log: Escalator Running Record and Fault Code, and fault code floor and time.
d) Speed Check:Check the escalator speed information
e) Running time:Check the escalator running time
f) Maintenance time: Check the escalator maintenance time
g) Program Version: Progam Version Information of the operator and the main borad.
Three,Parameter Classifications
Function option menu, the escalator parameters can be read and checked via handset operator.
a) Converter Parameter: Under this menu, the common F parameters of commissioning can be
read and set.
b) Escalator Specifiaction:This menu is about the classified menu about the escalator
specifications, to check or set the related parameters of the escalator specifications.
c) Parameter Summary: this menu is to check and set all the F parameter.
d) Control parameter Service:Reset for F0~F199 escalator control parameter. To avoid the
misoperation and its loss, authentication code should be input before Reset action.
e) Drive Parameter Reset:Reset for F200~F255 escalator drive parameter. To avoid the
misoperation and its loss, authentication code should be input before Reset action.
f) Parameter copy: Download and save set parameters of main borad into the operator or
upload the saved parameters in the operator to escalator main board.
Notes: The authentication code should be input before any downloading and uploading to avoid
the misoperation and its loss during parameter up/download.
Four, Command Reset

5-9
Shanghai STEP Electric Corporation

All the escalator parameters can be reset including fault code and escalator running
times via handset operator. To avoid the misoperation and its loss, authentication code
should be input before Reset action.
Five, Added Functions

Set the mainboard time or fire mode function via the handset operator.

Six,Re-login:

Input the login password on the handset operator and re-login the mainboard.

Seven, Password Modification:

The mainborad login password of the operator can be modified, the current grade password can

modify the lower-grade or current grade password.


5.2.2 Connection Of Handset Operator
第 The connection of hand held operator and main board is the standard one of RS232, and USB plug is
五 used on operator side, D type 9-pin plug is used for connection between the integrated drive
章 controller and seven segment operator with the connection wire of SM-08/USB.

Below picture is the example for connection between the controller and handset operator.



Picture 5.2 connection drawing of controller and handset


Note
1. This operator’s connection (plug in and out) supports hot plug when the main controller is
energized.
2. Avoid shock, falling or use of operator in bad environment.
5.2.3 Handset Operator Functions.

5-10
AS330 Escalator Intrgrated Drive Controller

The handset appearance is as below picture 5.3. The table 5.3 make the detailed description for the

operator functions.



Picture 5.3 Handset Apperance

Table.5.2 Operator Functions 操


Key Function 作

1. Return to escalator status window when it is not in status
window
2. Enter failure inquiry window from escalator status window
1. Return to escalator status window from failure inquiry window
2. Enter from escalator situation sisplay window
Shortcut 3. Enter input & output inquiry window from call window.

1.Enter detailed information interface,checking main motor

pulse,,stoo brake,escalator stair,handrail ect.


1.Move up by one item in function selection
2.Increase 1 of the present data in data input
3.Move up by 16 items
4.Set ON or OFF status when position setting.
1.Move down by one item in function selection
2.Decrease 1 of the present data in data input
Direction 3.Move down by 16 items for selecting position parameter
4.Set ON or OFF status
1.Move up by 10 items in function selection
2.Move cursor left for data input
3.Move left by 1 item for position setting
1. Move down by 10 items for function
selection

5-11
Shanghai STEP Electric Corporation

2.Move right for data input


3.Move right by one item for position setting
1.Return to previous menu
2.Cancel data input

Function
1.Enter function selection
2. Enter edit status when viewing data
2.Save data input

5.2.4 Introduction to display windows


5.2.4.1 Classification of windows
Refer to the following table for the main windows displayed on operator




Table 5.3 Window Classification & Main Content

WINDOW Main Content

操 Mode Option: The first status after energized and connected, to choose the mode of

Model Option
the operator. For the integrated drive controller,please press “ENTER”

Press”enter”autoenter to enter
Perss”ESC”manuallyenter

Version Window After power and connection. Press “ENTER”to enter,to display the

Versions
program version number. The third line is version no. for escalator

30.01 drive program and the fourth line is version no. for escalator control
NSPG03
program.
Enter escalator status window after the input of correct password in this
Login Window
window.

Login Note: Wrong password input will lead to main monitoring

0 window,monitoring window or re-login window.

Press F1 to return to this window if not in error record window after


Escalator Status
login. It includes the following contents in this window:
Display Escalator in Inspection/Normal ect
Running direction of escalator
Running speed of escalator
Running situation of escalator
Note: the operation instructed below take this window as the first

5-12
AS330 Escalator Intrgrated Drive Controller

normal goingup
window if there is no special notice.
=== 00000000 ===
0101 00:00:00

Function Selection This window contains the following functions: monitor, parameters

Mode Option
classification, reset command, added functions, re-login,set password,

surveillance state etc, and there are sub-function in some function.


para. classification

Detailed function Press Enter key to enter the detailed function status, and they can be

viewed and modified, please refer to the next content for details.

5.2.4.2 Operations from power on to escalator status window



Please refer to the following steps to view the escalator status after the correct connection:



Picture 5.4 operations from power on to escalator status window


Take the operation of login as an example: (initial password is 1234; you’d better change the initial
password)

Table 5.4 Password Login

Step Key Display Notes

0 Power On To see Pic.5.4

1 Login Enter login window

5-13
Shanghai STEP Electric Corporation

Press 4 times

Press 3 times



章 6

Press 2
times

作 7

8 Password Input Finished

9 normal goingup
Log in to enter escalator status
=== 00000000 ===
0101 00:00:00 window

5.2.4.3 Function Switchover


Press F1 key to return escalator status window if is not in error record window. Users can
select function following the below picture 5.5:

ENTER

Elevaltor State Display


Drive State
F1 ESC
ENTER

ENTER
Output/Input

Surveillance State
Regulator Parametric ESC Failure Logging

5-14 Escalator Standard


Parametric Classification
ESC
Speed Check

Motor Standard Reset Order


Run Time
AS330 Escalator Intrgrated Drive Controller




Fig 5.5 Function Status Switchover
Through the above methods, select one function, enter Enter into the related function window.
Below is the explaination for the main function window operation of the first level menu. 操
5.2.4.4 Check Monitering Status 作

Take view failure history 1 as an example:

Table 5.5 Check Fault Record

Step Key Operator Status Notes

0 —— normal goingup
Escalator Status Display
=== 00000000 ===
0101 00:00:00

1 Function Option
Function Option Status

Surveillace status
Para. classification

2 Monitering status
Into Second Level Menu

Input/output
Fault record

3 Monitering status and to select


Fault record
Speed check up/down items

5-15
Shanghai STEP Electric Corporation

4 No. 0 Check Fault Record


Fault Code 35

Time 1007251330

5 No. 1
and to change
Fault Code 11
page
Time 1007261530

6 Check Fault Record


Fault information

Drive chain broken


10-07-26 15:30

。Note: Time format in fault information is shown in yy/mm/dd/hh/mm, each occupys 2 digits


五 For other functions under the situation of monitoring, refer to above table. Use and to
章 page for view.

5.2.4.5 How to set parameter


Take the setting of F11=12 as an example:

作 Table 5.6 Modify F Parameter
器 Step Key Operator Status Notes

0 —— normal going up
Escalator Status Display
=== 00000000 ===
0101 00:00:00

1 Function Option
Enter Function Option Status

Monitering status
Para. classification

2 Function Opiton
Press to make function option
Para.
classification
Commissioning
opertion
Press 1 time

3 Paramter Into Second level menu


classification
Concertor
Escalator
parameter
operation

5-16
AS330 Escalator Intrgrated Drive Controller

4 Parameter
classification
Parameter
summary
Control parameter
reset
Press 1

time

5 Parameter summary
Check the value of F parameter

F0 = 0
Drive mode

6 Parameter summary
Check the next-down parameter

F1 = 2
Casual mode
Ckeck previous-up
parameter 第
6 Check the following 10 五
Parameter summary

F11 = 0.300m/s parameters
Inspection speed

Check the following 10




parameters 器

7 Parameter summary
In the parameter check

F11 = 0. 3 00 status ,press “Enter”into edit


Inspection speed
status, edit the parameters

8 Parameter summary
Down to decrease by 1

F11 = 0. 2 00 Up to increase by1


Inspection speed

9 Parameter summary
Move left to the highest position

F11 = 0.200 Move right to the lowest


Inspection speed
position

10 Parameter summary
Up to increase by 1

F11 = 1 .200
Inspection speed

5-17
Shanghai STEP Electric Corporation

11 Parameter summary
F11 Edit Successful ,if not, to

F11 = 1.200 display the unchanged one


Inspection speed

Please refer to the above steps to modify the other parameters basically the same way as F. but
please take note that some parameters like input setting and contain only two status with ON and
OFF, and press and key can move by 16.

Now take setting of X9 from NO to NC as an example:


Table 5.7 Setting Input

Step Key Operator Status Notes

0 —— Normal goingup
Escalator Status Display
=== 00000000 ===
0101 00:00:00


章 1 Function option
Enter Function Option

Monitering status
Parameter classification

操 2 Press to finalize the


Function option

器 Parameter classification function option
Reset command
Press 1 time

3 Parameter classification
Into second level menu

Convertor parameter
Escalator specification

4 Parameter classification
Press to finalize the

Input type function option.


Press 3
Parameter summary
times

5 Input type IntoParameter Setting


F26 = 512
Input type X0-15 Window

6 Input type
Into Parameter Setting
----------*------
F26 = 512
Inspection(X10) NO

5-18
AS330 Escalator Intrgrated Drive Controller

7 Input type
-*-------*------
-
F26 = 512
inpection(X10) NO
按1次

8 Input type
Setting Parameter
---------*------
*
F26 = 514 Option
inspection(X9) NO

9 Input type
Confirmed Parameter

F26 = 514 Modification


Input type X0-15

Take Notes: Under the menu of Input Type, NC is for normal close, NO is for normal open.
5.2.4.7 Other Function 第

There are functions of motor learning, reset, time setup, change password, re-login in the first menu,

these function is easy to be operated by pressing .
Now take resetting parameter F as an example:

Table 5.8 F Parameter Reset Operation




Step Key Operator Status Notes 器
0 —— normal goingup
Escalator Status Display
=== 00000000 ===
0101 00:00:00

1 Function option
Enter Function Option

Monitering classification
Parameter classification

2 Function option

Reset command
Press 2
Other function
times

3 Reset command

Fparameter classification

4 Fparameter classification Input Authentication


Enter password:5678 5678, to avoide the
5678
misoperation, as the

5-19
Shanghai STEP Electric Corporation

password input

5 Fparameter classification Correct Authentication


Enter password:5678 Code Input 5678
5678

6 Fparameter lassification
Press ENTER for reset,

Fparameter classification if it successes, “Reset


Success!
successful” will be

shown; if “Reset

unsuccessful”, please

check whether this


第 operation is needed in

章 the inspection condition.

The time setting is a little different from F parameter setting, now take time set of year 2009, month
10, date10, hour 15, minute 20 for example:

Table 5.9 Time Setting

器 Step key Operator Status Notes

0 —— normal goingup
Escalator Status Display
=== 00000000 ===
0101 00:00:00

1 Function Option
Enter Function Option

Surveillace status
Para. classification

2 Function option

Other function
Press 3 times
relogin

3 Other function

Time setting
Fire frighting

4 Time setting
09/10/01
09:20:30

5-20
AS330 Escalator Intrgrated Drive Controller

5 Time setting
909/10/01
09:20:30

6 Time setting
09/10/01 1
09:20:30
Press 2 times

7 Time setting
09/10/10 0
09:20:30
Press 9 times

8 Time setting
09/10/10 第
9
09:20:30 五

9 Time setting
09/10/10
5
15:20:30
Press 6 times 操

10 Time setting 器
09/10/10
15:20:30

Operation of password modification is very similar with the operation of parameter F


modification.Modify time and password according to the way of F Parameters in the operation
window. The re-login window is like the login window, so we won’t introduce again.

5-21
AS330 Escalator Intrgrated Drive Controller

Chapter 6 Introduction To The Supporting Products

In the following Table 6.1, AS330 escalator integrated drive controller and other supporting products
are listed for users to make choices in accordance with the specific configuration of their escalators

Table 6.1 Supporting Products For Integrated Drive Controller

Items Description Notes

Safety chain fault collection


Safety chain fault collection
board(one for up machine room, one Optional Accessory
board ES.02/B
for down machine room)

Fault Display Board


Fault Display Board Optional Accessory
SM.04/HGB

For bypass channel and


Phase Collector PHC-100 Phase Collector 第
bypass converter






6-1
Shanghai STEP Electric Corporation

6.1Details For Safety Chain Collection Board ES.02/B

6.1.1 Mounting Dimension For Safety Chain Collection Board ES.02/B

Pic 6.1 Appearance of Safety Chain Collection Board








Pic 6.2 Mounting Dimension For Safety Chain Fault Collection Board

6-2
AS330 Escalator Intrgrated Drive Controller

6.1.2 Definitions of Plug-ins and Ports on Safety Chain Fault Collection Board ES.02/B
Table 6.1 ES.02/B Plug-ins Spescification

JP1 ANYTEK Terminal ;3.81;4;OQ/180D


JP2 ANYTEK Terminal ;3.81;8;OQ/180D
JP3,JP4,JP5,JP6 ANYTEK Terminal ;3.81;6;OQ/180D
S1,S2 2.54*3 Single row straight pins

Table 6.2 ES.02/B Input/Output Port Definition


Up Machine Room Fault Collection Board Port Definition
Port Port Code Input Signal Noted
Location
No.
JP1.1 TXV+ Power +24VDC
Twisted Pair
JP1.2 TXV- Power 0V
JP1
JP1.3 TXA+ CANH
Twisted Pair
JP1.4 TXA- CANL

JP2.1 COM Common Terminal

JP2.2 COM Common Terminal

JP2.3 X0 Up Control Cabinet Emergent Stop
Button
JP2.4 X1 Middle Slope Part Emergent Stop
JP2 Button 配
JP2.5 X2 Up Left Comb Tooth Plate Switch


JP2.6 X3 Up Right Comb Tooth Plate Switch

JP2.7 X4 Up Left Apron Plate Safety Switch

JP2.8 X5 Up Right Apron Plate Safety

Switch
JP3.1 X6 Middle Slope Left Apron Plate
Safety Switch
JP3.2 X7 Middle Slope Right Apron Plate
Safety Switch
JP3.3 X8 Up left handrail inlet safety switch
JP3
JP3.4 X9 Up right handrail inlet safety switch
JP3.5 X10 Motor Overcurrent/overload
protection switch
JP3.6 X11 power wrong phase/off phase
protection switch
JP4.1 X12 Grounding Leakage Protection
Switch
JP4.2 X13 Main Drive Chain Breakage
JP4
JP4.3 X14 Left Handrail Drive Chain
Breakage
JP4.4 X15 Right Handrail Drive Chain

6-3
Shanghai STEP Electric Corporation

Breakage
JP4.5 X16 Handrail Drive Chain Breakage
JP4.6 X17 Up Stair Collapse
JP5.1 X18 Up Apron Plate Emergency Switch
JP5.2 X19 Manual Turning Gear Stop Switch
JP5.3 X20 Up Left Stair Anti-Rebound Switch
JP5.4 X21 Up Maintenance Control Box Stop
JP5
Button
JP5.5 X22 Control Cabinet Emergency Stop
JP5.6 X23 Main Board Y7 Relay Normal Non faulty time to show
Open Contact(JP8.4) “↑UP”

Down Machine Room Fault Collection Board Port Definition








6-4
AS330 Escalator Intrgrated Drive Controller

Port Port Code Input Signal Notes


Location
No.
JP1.1 TXV+ Power+24VDC
Twisted Pair
JP1.2 TXV- Power 0V
JP1
JP1.3 TXA+ CANH
Twisted Pair
JP1.4 TXA- CANL
JP2.1 COM Common Terminal
JP2.2 COM Common Terminal
JP2.3 X0 Down Control Cabinet Emergent
Stop Button
JP2.4 X1 Down Left Comb Tooth Plate
Switch
JP2.5 X2 Down Right Comb Tooth Plate
JP2
Switch
JP2.6 X3 Down Left Apron Plate Safety

Switch

JP2.7 X4 Down Right Apron Plate Safety

Switch
JP2.8 X5 Down Left Handrail Inlet Protection
Switch
JP3.1 X6 Down Right Handrail Inlet 配
Protection Switch 套
JP3.2 X7 Left Stair Chain Breakage 产
JP3 JP3.3 X8 Right Stair Chain Breakage 品
JP3.4 X9 Left Handrail Breakage 介
JP3.5 X10 Right Handrail Breakage 绍
JP3.6 X11 Down Stair Collapse
JP4.1 X12 Escalator Down End Stop Open
JP4.2 X13 Down Right Stair Anti Rebound
Switch
JP4.3 X14 Down Maintenance Control Box
Stop Button(Now not available)
JP4
JP4.4 X15 Down Mid-Right Apron Plate
Safety Switch
JP4.5 X16 Down Mid-Left Apron Plate Safety
Switch
JP4.6 X17 Vacant
JP5.1 X18 Down Apron plate Emergency
Switch
JP5.2 X19 Vacant
JP5.3 X20 Vacant
JP5
JP5.4 X21 Vacant
JP5.5 X22
JP5.6 X23 Main Board Y8 Relay Normal Open Non faulty time to 6-5
Contact(JP8.6) show “↓DOWN”
AS330 Escalator Intrgrated Drive Controller

Chapter 7 Function Parameters

7.1 Function parameter


Table 7.1 F Parameter List

Para-number Parameter
Default Range Unit Reference
Description
F0 Drive Mode 1 0~2 0 Frequency Conversion
1 Double Mode 2 Y-ᇞ
F1 Casual Mode 0 0~2 0 non-casual 1 only
casual half speed 2
Casual half speed/casual
pause
F2 X19 Input Style 0 0~2 0 Mode Option 1 Fire
Input 2 Motor
Overheated
F3 Fire Escalator 0 0~1 1yes 0 no

F4 Reversed Entry Alarm 20 10~1000 0.1s

TIme

F5 Same Direction Running 300 50~60000 0.1s
Casual Time
F6 Reverse Direction Running 100 50~6000 0.1s
Casual TIme


F7 Half Speed Running Stop 50 0~6000 0.1s

Time

F8 General Additional Brake 50 0~1000 0.1s
Release Time
F9 Emergent Additional Brake 5 0~1000 0.1s
Release Time
F10 Rated Speed 700 100~3000 0.001m/s
F11 Inspection Speed 300 10~3000 0.001m/s
F12 Casual Speed 150 10~3000 0.001m/s
F13 Motor Speed Measurement 50 1~1000 0.1s
Delay
F14 Standby 30 1~1000 0.1s
F15 Motor Speed Measurement 100 1~10000
Frequency Conversion
Standard(Double Mode)
F16 Motor Speed Measurement 100 1~10000
ᇞ Standard

7-1
Shanghai STEP Electric Corporation

F17 Stair Speed Measurement 100 1~10000


Standard
F18 Left Handrail Speed 100 1~10000
Measurement Standard
F19 Right Handrail Speed 100 1~10000
Measurement Standard
F20 Oil Filling Time Gap 8 0~1000 Hour
F21 Single Oil Filling Time 10 0~1000 S
F22 Standby 0 0~0
F23 Fault Ring Time 40 0~1000 0.1S
F24 Function Activation 0 0~65535
F25 Casual Motor Torque Limit 900 800~2000 0.1%
F26 Input Type X0 -15 0 0~65535
F27 Input Type X16-31 0 0~65535
F28 Input Type X32-47 0 0~65535
F29 Input Type X48-63 0 0~65535
F30 Monitering Address 255 0~255
F31 Inlet Photoelectrical Fault 0 Soft Stop 1 Cancel
第 0 0~1
Handling Casual
七 F32 0 Speed Measurement
章 Mode A Motor Installed
Motor Speed Measurement On
0 0~1
and Installation 1Speed Measurement

Mode B Stairs Installed

On

F33 Standby 0 0~65535

F34 Standby 0 0~65535
F35 Standby 0 0~65535
F36 Standby 0 0~65535
F37 Initial Password 149 0~65535
F38 Commissioning Password 1234 0~65535
F39 Super Password 19163 0~65535
F200 Converter Software Version 30.01 0~65535 -
F201 Control Mode 0 0~4 -
F202 Motor Type 0 0~1 -
F203 Motor Rated Power - 0~65535 0.01kW
F204 Motor Rated Current - 0~65535 0.1A
F205 Motor Rated Frequency 50.00 0~65535 0.01Hz
F206 Motor Rated Rotation 1460 0~65535 rpm
Speed
F207 Motor Rated Voltage 380 0~65535 V

7-2
AS330 Escalator Intrgrated Drive Controller

F208 Motor Polarity 4 0~65535 P


F209 Motor Rated Slip 1.40 0~65535 0.01Hz
Frequency
F210 Tracking Delay Time 1000 0~9000 ms
F211 Tracking Zero Voltage 100 0~9000 ms
TIme
F212 Tacking Voltage Kp 0.20 0~65535 0.01
F213 Tracking Voltage Ki 0.30 0~65535 0.01
F214 Tracking Quit Delay 1000 1000~10000 ms
F215 Tracking Max Current 100.0 0~65536 0.1%
F216 Tracking Frequency 30.0 100~2000 0.1%
Change Gain
F217 Tracking Initial Frequency 50.00 0~65535 0.01Hz
F218 Tracking Max Voltage 0 0~65535 V
F219 Tracking Max Current 0.00 0~65535 0.1A
F220 Acceleration Time Ta0 5.00 0~65535 0.01s
F221 Deceleration Time Td0 5.00 0~65535 0.01s
F222 Acceleration Round Angle 1.30 0~65535 0.01s
Ts0 第
F223 Acceleration Round Angle 1.30 0~65535 0.01s 七
Ts1 章
F224 Decerleration Round Angle 1.30 0~65535 0.01s
Ts2
F225 Deceleration Round Angle 1.30 0~65535 0.01s 功
Ts3 能
F226 Max Frequency 55.00 0~65535 0.01Hz 参
F227 Brake Action Time 0.20 0~65535 0.01s 数
F228 Current Slow Down Time 0.00 0~65535 0.01s
F229 Compensated Torque 0 0~65535
Direction
F230 Acceleration Time Ta1 5.00 75~65535 0.01s
F231 Deceleration Time Td1 5.00 75~65535 0.01s
F232 Encoder Filter TIme 0 0~65535 ms
F233 Encoder 1 0~65535 -
Direction1:Positive
Sequence
F234 Motor phase Sequence 0/1 1 0~65535 -
F235 Motor Empty Load Current 32.00 0~65535 0.01%
Coefficient
F236 PWM Carrier Frequency 6.000 1100~13000 0.001kHz
F237 Random PWM Width 0.000 0~1000 0.001kHz
F238 Adjustor Mode 1 0~3 -
F239 Output Torque Limit 150 0~200 %

7-3
Shanghai STEP Electric Corporation

F240 Converter Rated Voltage 380 0~65535 V


F241 Converter Rated Power - 0~65535 0.01kW
F242 Angle Synchronical 130.0 0~3600 0.1
Adjustment I2G Degree
F243 I2G Switch Frequency 49.50 0~5300 0.01Hz
F244 Synchronical Overtime 10.0 0~160 0.1s

7.2 Function Parameter Details


F0———Drive Mode: This mode is to set escalator running mode. 0 is for full frequency conversion running, 1 is
for double mode running(bypass frequency conversion mode), 2 is for Y-ᇞ running, when faulty, set the Y-ᇞ running.
F1———Casual Mode: This parameter is to set casual running mode. 0 is for non-casual running , 1 is for half
speed casual running, 2 is for half speed casual running and escalator stops after continous no receiving the
optoelectrical signal
F2 ———Input X19 is of user-defined: 0 is double mode option switch, 1 is fire option switch, 2 is motor overheat
input
F3 ———Fire Escalator: This parameter is to set whether the escalator to be fire escalator, 0 is No, 1 is Yes
F4 ———Reversed Entry Alarm Time: This parameter is to set the alarm time for reversed entry.

第 F5 ———Same direction running casual time: This parameter is to set the delay of the casual speed sent by the

七 controller when no signal input from same direction optpelectrical switch.

章 F6 ———Reversed Running Casual Time: This parameter is to set the delay of the casual speed sent by the
controller after reversed entry in the casual mode.
F7 ———Half speed stop time: This parameter is to set the delay of “cut off the input and stop the escalator” when
功 no more optoelectrical signal coming after casual speed input
能 F8 ———General additional brake release time: This parameter is to set the delay of cutting off additional brake
参 output at the the time of normal escalator stop or non emergent fault stop under the auto mode
数 F9 ———Emergent additional brake release time :This parameter is to set the delay of cutting off additional brake
output at the time of emergent fault like overspeed,reversed running,drive chain breakage
F10 ———Rated Speed: This parameter is to set the escalator rated speed. For istance 0.5m/s is set to 0.500
F11 ———Inspection Speed: This parameterer is to set the escalator rated speed, for istance 0.25m/s is set to 0.250.
F12 ———Casual Speed: This parameter is to set the escalator casual period,for istance 0.25 is set to 0.250
Notes: The parameter setting of Inspection and casual speed is related to F10 rated speed, Inside the controller
F11 and F12 speed control is according to some ratio of F10
F13 ———Motor Speed Measurement Delay: This parameter is set the effective delay of motor speed measurement
after the high speed set output
F14 ———Handrail Speed Measurement Fault Allowed Time:This parameter is to set how much time to send the
fault after handrail speed measurement pulse become continuously over or under the standard value
F15 ———Motor Speed Measurement Frequency Conersion Standard, this parameter is to set the time gap between
two pulse. It can be checked via the handset operator.
F16 ———Motor Speed Measurement ᇞ Standard: This parameter is to set the time gap between two pulse. It can
be checked via the handset operator.
F17 ———Stair Speed Measurement Standard: The standard value please check F32
F18 ———Left handrail speed measurement standard, the standard value please check F32

7-4
AS330 Escalator Intrgrated Drive Controller

F19 ———Right handrail sped measurement standard, the standard value please check F32
F20 ———Oil filling time gap: This parameter is to set the time gap between oil fillings. The unit is hour
F21 ———Single Oil filling time: This parameter is to set the time for the relay continuous output in the main
board at the time of oil filling.
F22 ———Standby
F23 ———Fault Ring Time: This parameter is to set the output time of the buzzer relay when the safety loop fault
takes place
F24 ———Function Activation: This parameter is of the digit parameter,which can set the function on /off. This
parameter has 5 effective digits; from left to right is 0-5. Setting method is: Entry Parameter is displayed as
──────,at this time functions are off. When needed to activate the functions, place the curser to the related digit,

press , now should be ─*────, that means this function on

0-5 defines as follows:


0: Additional brake function
1: Motor Speed Measurement (Overspeed, Underspeed)
2: Anti reversed running inspection
3: Reverse Inspection Method( ON is for proximity switch speed measurement, OFF is for contact switch, No. 2
digit function decide this parameter effect

4: Stair Loss Inspection

5: Handrail Speed Measurement

6: Contact Adhesive Protection Auto Reset
F25 ———Casual Motor Torque Limit: This parameter is to set the load running due to the invalidation of the
optoelectrical switch under the casual mode. Suggest: 80%-90%
F26 ———Input Type X0-X15: This parameter is to set Input Normal Open and Normal Closed for X0-X15. 功
Please refer to F24 for setting. 能
F27 ———Input Type X16-X31: This parameter is to set Input Normal Open and Normal Closed for X16-X31. 参
Please refer to F24 for setting. 数
F28 ———Input Type X32-X47: This parameter is to set Input Normal Open and Normal Closed for X32-X47.
Please refer to F24 for setting.
F29 ——— Input Type X48-X63: This parameter is to set Input Normal Open and Normal Closed for X48-X63.
Please refer to F24 for setting.
F30 ———Monitering Address: When this parameter setting uses tele-monitering, this escalator address and this
parameter is reserved. Need to contact the factoty for activation.
F31 ———Inlet optoelectrical fault handling mode: This parameter is the controller handling mode when the
converter is faulty. 0 is faulty stop 1 is cancel casual, that is no casual jogging or casual pause
F32 ———Motor Speed Measurement Installation method:This parameter is to set the pulse mode of the speed
measurement for the motor escalator stair, and handrail.
0 is for the site high pulse, speed measurement standard value of the handrail and stair is the pulse
number of the motor between two pulses. Check via the operator.
1 is for the site low pulse, speed measurement standard value of the handrail and stair is time between
two pulses,meanwhile for the sake of accuracy, set 1 tohave the controller skip the speed measurement of the stair
and handrail.
F33 ———Standby

7-5
Shanghai STEP Electric Corporation

F34 ———Standby
F35 ———Standby
F36 ———Standby
F37 ———Initial Password: This password is only to moniter status, set the time, not to modify parameters.
F38 ———Commisioning Password:This password can not be reset to operate the time and can not modify the
password, other operations are available
F39 ———Super Password:This password is to modify any parameter.
F200——Converter Software Version No. This is an only read data set before factory release
F201——Converter Control Mode: 0: non speed sensorV/f control mode, 1: non speed sensor vector
control mode, 2: speed sensor torque control mode, 3: speed sensor vector control mode,
default is 3 .Generally, speed sensor vector control mode is used, so basically this
parameter default to 3. But some commissioning sites require the parameter to 0 for
temporary to move the car position before encoder installation to make the converter run in
open loop V/f control mode. Be careful, before the hoistway self learning, the encoder
must be installed and wired, and recover F201 to 3.
F202——Motor Type Option 0: Asynchronous 1:Synchronous
F203——Motor Rated Power Unit:kW Set according to nameplate
F204——Motor Rated Current。Unit: A Set according to nameplate
F205——Motor Rated Frequency Unit:Hz。Set according to nameplate

F206——Motor Rated Speed Unit: rpm Set according to nameplate

F207——Motor Rated Voltage Unit: V Set according to nameplate

F208——Motor Polarity. Set according to nameplate.If there is no motor polarity parameter, then
calculate as below formula
功 Polarity =(120×f)÷n n is rated rotary speed ,f is rated frequency
能 The even whole number from the value calculated is “Polarity”
参 F209——Motor Rated Slip Frequency: Unit: Hz Only for asynchronous motor and set according to
数 nameplate. If no slip frequency value on the nameplate, then F209 value is as below
calculation
Suppose rated frequency is f(F205), rated speed is n(F206), motor polarity is p (F208) then
Slip Frequency=f-((n×p)÷120)
For example, rated frequency is 50Hz, rated speed is 1430rpm, motor polarity is 4 then
F209 set value is =50-( (1430×4)÷120)=2.33Hz
F210——Tracking Delay Time: After this period of delay time , speed tracking start
F211——Tracking Zero Voltage Time: Zero voltage duration
F212——Tracking Voltage Kp: Kp during switchover
F213—— Tracking Voltage Ki : Ki during switchover
F214——Tracking Quit Delay: process end delay from working frequency switchover to conversion
frequency
F215——Tracking Maximum Current: Switch current limit from working frequency to conversion
frequency
F216——Tracking Frequency Change Gain: Frequency change speed from working frequency to
conversion frequency
F217——Tracking Initial Frequency:The initial frequency in the process from working frequency to

7-6
AS330 Escalator Intrgrated Drive Controller

conversion frequency
F218——Tracking Maximum Voltage.: Maximum voltage of the bus during monitoring and tracking
F219——Tracking Maximum Current:Monitering and tracking maximum effective current value in
the process
F220——Acceleration time Ta0: This parameter is to decide the acceleration slope (the value of
constant acceleration), it is the time needed from 0 speed to the highest speed with
constant acceleration. It is not average acceleration, the average accerleration includes 2
acceleration round angles besides this parameter.
F221——Deceleration Time Td0. This parameter is to decide the deceleration slope (the value of
constant deceleration), it is the time needed from highest speed to the 0 speed with
constant deceleration. It is not average deceleration, the average decerleration includes 2
deceleration round angles besides this parameter.

F222—— Acceleration Ts0: Set the time for acceleration round angle of S curve start part. More this
time more round angle
F223——Acceleration round angle TS1: Set the time for the acceleration round angle of S curve
constant speed part. More this time, more round angle
F224——Deceleration angle round Ts2: Set deceleration round angle for the S curve deceleration
start part. More this time more round angle.

F225—— Deceleration angle round Ts3: Set deceleration round angle for the S curve deceleration

end part. More this time more round angle.

F226——Maximum Frequency: the maximum frequency allowed by the converter
F227——Brake Action Time: It is the adjustment parameter for brake mechanical open time. Set
this parameter according to actual brake release mechanical action time 功
F228——Current slow-down time parameter: Parameter F228 is to set the time of current slow 能
down, from converter receiving command for output stop to actual current output zero. 参
Generally this parameter default is 0. For some special occasions when convertrer current 数
rapidly goes off, bringing about the big noise from the motor at the time of eascalator stop,
this parameter can be increased suitably. However this parameter can not be too big,
should not be more than the delay time of main contact release. Otherwise it turns out to
be contact arc discharge at the time of contact electric release, reducing the contact life
span. In addition, the converter can not have current due to the loop off after contact
release.
F229——Compensation Torque Direction Adjustment Parameter: This parameter is used when to
start pre-load compensation function. Generally, the factory default is set to 0 . But if
other reasons make the reverse system torque compensation direction, then modify
parameter F229 from 0 to 1 to solve this problem.
F230—— Acceleration Time Ta1: the time needed from zero speed accelerated to the rated speed 1
F231——Deceleration Time Td1: the time needed from rated speed decelerated to 0 speed.
F232——Encoder Feedback Signal Filter Time Parameter: default is 0 ,only for theseriously
disturbance occasion, suitably increase the filter time to increase the system
anti-disturbance ability.
F233——Encoder Feedback Direction: 0: negative sequence 1: positive sequence the default is 1.

7-7
Shanghai STEP Electric Corporation

Generally do not need to change it but if it happens that encoder get wrong wiring causing
feedback direction discordant with the actual direction. It can be adjusted through F233
parameter modification.
F234——Motor Phase Sequence: generally, F234 is set to 1, but if motor running direction is
reverse to the required direction, change from 1 to 0 through F234 to turn the motor
direction
F235—— Motor Empty Load Current Coefficient: Set the proportion of tractor empty load current
and rated current. The default is 32%. Generally do not need to modify this parameter.
F236—— PWM Carrier Frequency: More carrier frequency, less motor noise, but more wearing
down. Normally user does not need to set it, just use the default(6kHz). If the situation
really requires reducing the motor noise and increase the carrier frequency, it will cause
more wearing down due to more carrier frequency. Thus when the carrier frequency is
over the default value, every 1KHz up, the converter need to be 5% derated in use
F237——PWM Carrier Frequency Width: Normally user does not need to set it, just use the default
to operate. Its function is to make carrier frequency automatically change within this
scope of width. In some occasions, it has effect of reducing motor noise. For example,
F236 is set to 6KHz, F237 is set to 0.4KHz, then theactual converter carrier frequency will
automatically change within the scope of 5.8~6.2KHz
F238——Adjustor Mode: Normally default is 1, standard adjustor mode

F239—— Output Torque Limit: It is to set the limit value of output torque. It is the percentage data

against the rated torque. Default is 175%

F240——Converter Rated Voltage: Set Converter input voltage
F241——Angle synchronous adjustment 12G: The modification angle from frequenct conversion to
功 working frequency.
能 F242——12G Switchover Frequency: The switch frequency in the process from frequenct
参 conversion to working frequency.
数 F243——Synchronous Over Time: The maximum time for the phase position synchronous waiting
from frequency conversion to working frequency. If the synchronous signal is not detected
when over this time , the escalator will automatically switch to working frequency .
F245——F246~F255 Parameter functyion Options: To modify this parameter will change the
definitions of F246~F255, scope 0~6,default is 0
When F245=0
F246—— Heatsink Overheat Protection: Integrated drive controller will activate the protection after
a set period of continuous heatsink overheating.
F247——Over Speed Protection Coefficient: Integrated drive controller activates the protection if
the motor running speed goes over the protection coefficient set by this parameter for a set
period of overspeed protection time .
F248——Overspeed Protection Time: To set motor continuous overspeed protection time.
F249——Input Open Phase Voltage Threshold Value: Bus voltage fluctuate beyond this value , and
continuous 150 working frequency power cycle, then it is judged to be input open phase.
F250——Brake Resistor Short Curcuit Confirmation Times: Activate protection after certain times
of the instant brake resistor short circuit times going over this set value
F251——Sincos Encoder Breaking Off Confirmation Times: Activate protection after certain times

7-8
AS330 Escalator Intrgrated Drive Controller

of Sincos encoder breaking off times going over this set value
F252——Output Open Phase Confirmation Time: Acitvate protection when output open phase goes
over the parameter set time
F253——Charging Relay Fault Confirmation Voltage: Activate protection when running three phase
input voltage goes down by the parameter set value, report it to be No. 144 fault.
In that at the initial time of site commissioning, 114 fault was reported when temporary
power capacity was not enough and no improving condition on site. When power on or
off, the turn-on and off voice of relay inside the converter is available, that means the
charging relay of the converter is not damaged. Modify converter parameter to satisfy the
escalator running of this temporary power. The way of realization is as follows:
Turn the default of F253 from 45 to 90; therefore the escalator is able to run under the low
power capacity supply. Recover the parameter to 45 when the normal power supply is on
after the end of the site installation.
F254——Speed Curve Option 0: acceleration/deceleration time o , 1: acceleration/deceleration
time 1 2: port choose acceleration/deceleration time 3: communication choose
acceleration/deceleration time
F255——ABZ Encoder Breaking Off Protection Threshold Value: Default is 20%. When
synchronous motor uses ABZ encoder , if the feedback speed deviation exceeds this
threshold value, then judging encoder breaking off. Converter reports it to be No. 12 fault

When F245=2

F246---- Special Function parameter: 8: slip compensation is decided by the motor parameter 32,

Under voltage fault is also recorded at the time of no running.
F247——PWM Commissioning Mode: 0: 5 segment 1: 7 segment 2: <40%rpm 7 segment,> 5
segment, when low speed ,the integrated drive controller have more disturbance for the
external, for example when CAN communication signal is not good , modify to 0(5 功
segment), it will have obvious effect, meanwhile reducing the converter heating, however 能
it will cause low speed converter more noise 参
F248----Automatical Torque Up 数
1: Automatical Torque Up 2: suppress fluctuation 14: slip compensation 8: stator
resistance compensation 16: dead time compensation 32: bus voltage compensation 64:
suppress fluctustion 2
F249---- Dead Time Compensation Mode, Standby parameter
F250—— Three phase current balance coefficient: this parameter is ony read which will
automatically change after three phase current balance coefficient get calibrated. If it is
synchronous motor, triggering asynchronous self learning command will turn on output
contact, calibrate the three phase balance coefficient, this function is to reduce motor
fluctuatuion and increase the comfort.
Three phase current balance coefficient self learning is as follows: First enter motor self
learning mode of commissioning menu via handset operator, press “Confirm” the
integrated drive controller output KMY turn on command to turn on thr output contact,
then three phase current sensor calibration self learning, the operator will show “learning”,
about 30 senconds later learning get successful and it will show”learning done” At that
time set F245 to 2, observe F250 which will be one value between 800-1200(can not be
1000). F 250 is defaulted to be 1000, after learning this valur will not be 1000, otherwise

7-9
Shanghai STEP Electric Corporation

relearn until the value gets accurate.


F251---- Deat Time Compensation Capacity: Dead time compensation coefficient
F252---- Reverse running prohibited 1: Reverse running not allowed
F253---- Interval Time of positive and negative running: o speed remaining time after the running
direction changed
F254——Converter Acceleration Overcurrent Threshold Value: During acceleration, if the current
exceeds this value, stop acceleration, keep the current speed, and continue acceleration
after the current goes down
F255——Converter Deceleration Overvoltage Threshold Value: During deceleration, if the bus
voltage exceeds this value, stop deceleration, keep the current speed, and continue
deceleration after the voltage goes down
When F245=3,
F246——Current Loop PID Adjustor Integral P. Normally no need to adjust
F247——Current Loop PID Adjustor Integral I. Normally no need to adjust
F248——Current Loop PID Adjustor Integral D. Normally no need to adjust
When F245=4
F246——Software Version Code, Only Read
F247——Integrated Drive Controller ID No. 0 Only Read
F248——Integrated Drive Controller ID No. 1 Only Read

F249——Integrated Drive Controller ID No. 2 Only Read

F250——Integrated Drive Controller ID No. 3 Only Read

F251——Integrated Drive Controller ID No. 4 Only Read
F252——Integrated Drive Controller ID No. 5 Only Read
功 F253——Integrated Drive Controller Rated Current Only Read
能 F254——Integrated Drive Controller Sensor Rated Current. Only Read
参 When F245=5
数 F246——Stator Resistance: Stator resistance of asynchronous motor.
F247——Rotor Resistance: Rotor resistance of asynchronous motor.
F248——Stator Electric Induction: Stator electric induction of asynchronous motor
F249——Rotor Electic Induction: Rotor electric induction of asynchronous motor
F250——Mutual Induction: Mutual induction of asynchronous motor
F251——Motor Low Speed Overcurrent Threshold Value: Motor speed goes below 20% of the rated
speed, the current go beyond this value and the lasting time get over F252 set time, then
report it to be motor low speed overcurrent, stop running.
F252——Low Speed Overcurrent Time: Motor low speed overcurrent lasting time
F253——Motor High Speed Overcurrent Threshold Value: Motor speed goes over 20% of the rated
speed, the current go beyond this value and the lasting time get over F254 set time , then
report it to be motor high speed overcurrent, stop running.
F254——High Speed OverCurrent Time: Motor high speed overcurrent lasting time

7-10
AS330 Escalator Intrgrated Drive Controller

Chapter 8 Escalator Commisioning Guide

This chapter provides the guide for operation of escalator. By the operation procedures described in
this chapter, the design, installation, wiring, parameter setting and commissioning of escalator may
be completed quickly.

Important Notice:

9 Any users of our products are required to carefully read and understand this manual and the
related equipment manuals to system prior to starting system commissioning or putting it into
operation in order to avoid accident losses.

9 Be sure to read and understand the instructions for System Parameter Setting in this manual
prior to starting system commissioning or putting it into operation in order to avoid accident losses.

9 Site commissioning can not be started until all mechanical equipment, (how the machine room
equipment is required depends on the preparation of machine room).

9 Any equipment and devices required to be installed and commissioned before system
commissioning shall be surely completed in a reliable manner.

9 Before commissioners starting its works, all the works must be confirmed by the related 第
installation persons and commissioning director of mechanical system and other system or by the 八
other persons designated to taking the related responsibilities.

9 Prior to system commissioning, the commissioner shall carefully check all the equipment and
other devices related to the commissioning of electric system are all completely installed and
commissioned appropriately.

9 Prior to system commissioning, the commissioner must carefully check there is not any 梯
existences of unsafe factors to human body and property (including potential and possible unsafe

factors).

9 The commissioner must be of trained and qualified to execute commissioning of escalator 指
control system. 南
9 In case that this manual can not satisfy your requirements, please contact us timely to get
supporting in time.

9 Commissioner shall, before starting its work, check all the site conditions are ready to carry out
system commissioning.

Danger

◎ Energized, don’t remove the shell


Or it may cause risk of electric shock.
◎ Do not reset alarm signals until operating signals are surely cut off

8-1
Shanghai STEP Electric Corporation

Or it may cause risk of injury.

Caution

◎ Heat sink and brake resistor is at elevated temperature, do not touch


it
Or it may cause risk of burn.
Prior to put them into operation, make sure all motors and machines are
to be used in their scope of application.
Or it may cause risk of injury.

8.1 Simple commissioning diagram


8.1.1Preparation prior to commissioning
1、 Use AS330 escalator control cabinet
2、 Make correct and reliable wiring according to the schematic drawing
3、 Tools needed(multimeter, AS330 special handset operator
8.1.2 Commissioning Flow Chart








8-2
AS330 Escalator Intrgrated Drive Controller








8.2 Other Function Commissioning.


According to the requirements, activate or debug other functions. You may refer to chapter 3.1
--escalator operation function descriptions and setting method. Set and activate the required
function, and test the activated function correct or not according to function description.

8-3
AS330 Escalator Intrgrated Drive Controller

Chapter 9 Faults and Solutions

This chapter describes the fault codes, situations, causes and solutions, and additionally, provides
analysis of faults occurred in operating and commissioning for information.

Danger

◎ Start operation 10minutes after it is disconnected to main in order to


ensure at that time charge indicator lamp goes out or DC bus voltage is under
24V.
Or it may cause risk of electric shock.
◎ In no case may the escalator integrated drive controller be remodeled
without authorization.
Or it may cause risk of electric shock and/or injury.
◎ Only professional electricians may be allowed for maintenance. Never
leave foreign wire ends or metal substances inside.
Or it may cause fire risk.

Caution

When power is on, do not change wiring and remove terminals 九

Or it may cause risk of electric shock.

9.1 Control System Fault And Analysis 故


See table 9.1 for control system fault and analysis of AS330 escalator integrated drive controller 障
Table 9.1Control System Fault Code And Analysis 对

Code Faults Possible Causes and Analysis

Contact Adhensive(not
when brake ,ᇞ contact,angle contact,up going contact,down going contact all
01 pure frequency
have no output,adhesive check still have signal
conversion)

Frequency Conversion
02 Contact Fault(Not pure Frequency conversion contact input and output discordance
frequency conversion)

9-1
Shanghai STEP Electric Corporation

Working Frequency
03 Contact Fault(Not pure Working frequency contact input and output discordance
frequency conversion)

04 Brake Switch Fault Brake switch output and check discordance

05 Safety Loop Relay Fault Safety loop/high voltage and safety loop relay discordance

Additional brake switch can not open


Additional Brake Switch
06 When startup, continually 3 times not open means the fault
Fault
When in operation, one time means fault

Additional Brake Relay


07 Additional brake relay output and input discordance
Fault

08 Temperature Fault Temperature Alarm Input

Converter No communication with converter,check board installation loose or not and


10
Communication Fault power voltage stable or not

11 Drive Chain Breakage Chain breakage action

Oil Level Inspection


12 Out of oil( temperary no this fault)
Fault
Inlet Optoelectricity Inlet Optoelectricity Damaged
13
Damaged Escalator load is normal but check out no action of the inlet optoelcticity
第 Contact Brake Fault(Pure
14 Brake contact input and output discordance
九 Frequency Conversion)
章 Out-wired Contact 1
15 Fault(Pure Frequency Out-wired Contact 1 input and output discordance
Conversion)

Out-wired Contact 2

16 Fault(Pure Frequency Out-wired Contact 2 input and output discordance

Conversion)

Mode Abnormal
17 During operation, inspection automatically makes switchover
Switchover

Reversed escalator
50 Reverse
Speed measurement switch fault

Escalator Overspeed
51 Overspeed
Speed measurement switch fault

Escalator underspeed
52 Underspeed
Speed measurement switch fault

53 Handrail Overspeed Handrail Overspeed

9-2
AS330 Escalator Intrgrated Drive Controller

Speed measurement switch fault

Handrail Underspeed
54 Handrail Underspeed
Speed measurement switch fault

Stair Loss
55 Stair Loss
Stair Inspection Switch Fault

Brake Distance Over


56 After brake closed,escalator brake distance too long
Limit

69 parameter not initialized please reset the control parameter

9.2 Drive System Fault And Analysis


See table 9.2 for drive system fault and analysis of AS330 escalator integrated drive controller
Table 9.2 Drive System Fault Code And Analysis

Fault Fault
Possible Cause Solutions
Code Display
DC terminal over high Check the meshwork power, to see whether fast stop
voltage with high inertia load,no energy consumption brake

Check the motor or the out wires are short curciuted, or
Short curciuted around 九
the grounding short curcuited

Output open phase Check the motor and the outputted wires are loose or not

Encoder Fault Check encoder is damaged or correctly wired.

Mode Hardware not well



71 Overcurrent contacted or damaged
Refer to the specialist for maintenance 障
Protection 对
Plug-ins loose inside
Refer to the specialist for maintenance 策
converter
Induction Adjust the induction motor slip
motor slip setting unrea
sonable
No-load Adjust the no-load current coefficient
current coefficient set
unreasonable
Current Sensor Damage Replace the current sensor
72 ADCFault
Current Sampling Loop
Replace the control board
Problem
Heatsink Overhigh Surrounding
73 Cool down the temperature, enhance the ventilation
Overheated Temperature

9-3
Shanghai STEP Electric Corporation

Fault Fault
Possible Cause Solutions
Code Display

Clear off dust,cotton and some other rubbish in the wind


Wind Tunnel Blocked
tunnel

Check the fa power line whether well wired or replace


Fan Abnormal
same type fan
Temperature Check Circiut
Refer to the specialist for maintenance
Fault

Brake Unit Damage Replace related drive mode


Brake Unit
74
Fault External Brake Resistor
Check the brake resistor connection
Circuit Shorted
Overcurrrent leads to fuse
75 Fuse Fault Check fuse loop off or not ,or contact loose
broken
Undervoltage of the input
Check the input power
power
Motor Block Up/Serious Prevent it from motor block up and reduce the sudden
Output Over
76 Sudden Load Change load change
Torque
Encoder Fault Check whether encoder is damaged or correctly wired

output open phase Check motor and the outputted wires whether loose or not
第 Acceleration Time Too
九 Short
Extend the acceleration time
章 Acceleration
77 Too Much Load Reduce load
Deviation
Raise up the current limit value within the range of
Current Limit Too low
故 permit
障 Bus Input Power Voltage
对 Check the input power
Overvoltage Abnormal
策 Protection(in Motor Quick Restart when
Motor stop and restart up
acceleration) high speed running
Load Running Inertia Too
Bus Use suitable energy consumption brake parts
Big
Overvoltage
Deceleration Too Short
78 Protection(in Entend deceleration time
Time
decceleratio
Brake Resistor Value Too
n) Connect the suitable brake resistor
Big/ No connected

Bus Input Power Abnormal Check Input Power


Overvoltage
Load Running Inertia Too
Protection(in Use suitable energy consumption brake parts
Big

9-4
AS330 Escalator Intrgrated Drive Controller

Fault Fault
Possible Cause Solutions
Code Display
constant Brake Resistor Value Too
Connect the suitable brake resistor
speed) Big/ No connected
Power voltage under
Check Input Power
minimum working voltage

Instant Power Off


Check Input Power , ready-input voltage ,reset and restart
Input power voltage change up
Bus too much

79 Undervoltag Power Wired Terminal


Check input wiring
e Loose
Inside Switch Power
Refer to specialist for maintenance
Abnormal
Load of high startup
Change power system to make it accord with the standard
current in the same power
value
system
Converter output side
abnormal wiring, bobble or
Check converter output side wiring situation, prevent
break off
bobbling and breaking off
Output Terminal Loose

Output Open Motor Power Too Small, 第


80
Phase under 1/20 of converter max Adjust converter capacity and motor capacity 九
power 章
Check motor well wired ot not
Output 3 phase unbalance
Off power,check converter output side and DC side
terminals of the same character or not 故
Power Networks Low 障
Motor Low Check input power 对
Voltage
Speed 策
Motor Parameter Setting
Overcurrent( Correctly set motor parameters
Abnormal
in
Direct startup during motor
acceleration) Motor running stop and startup
running
Power networks low
81 Check input power
voltage
Motor Low
Load Running Inertia
Speed Use suitable energy consumption brake parts
Bigger
Overcurrent(
Motor Parameter Setting
in Correctly setting motor parameter
Abnomal
deceleration)
Deceleration Tinme Too
Extend deceleration time
Short

9-5
Shanghai STEP Electric Corporation

Fault Fault
Possible Cause Solutions
Code Display
Motor Low Load Sudden Change
Decrease load sudden change frequency and its range
Speed during Running
Overcurrent(
Motor parameter setting
in constant correctly set motor parameter
abnormal
speed)

Encoder not well contacted Change encoder wiring

Check Encoder in good condition or not and its power


Encoder No Signal Output
Encoder supply
82
Fault Encoder Connection Wire
Repair the broken part
Breaking off
Function Code Setting
make sure converter encoder function codes correct
Abnormal

Motor stop does not Motor Slippage


Find Current
83 effectively cut off the
When Stop
current Refer to specialist for maintenance

Speed Reversed During


Check outside load has sudden change or not
Speed Running
Reversed Encoder and Motor are of
84 Change motor or encoder phase sequence
During different phase sequence

Running Motor Reverse Running
九 Current limit too low , not matching the motor
When Startup

Brake loose , escalator
Check Brake
Find Current slippage
85
When Stop


Wrong
对 Motor wire reverse
86 Motor Turn over and adjust the parameter
策 connection
Sequence
Motor Magnetism loss leads
Check Motor
to free wheel
Codirectiona
l Overspeed
87
(max speed
range)
Positive direction overload
Check load sudden change external reasons
or load sundden change
Motor Magnetism loss
Reverse Check motor
situation leads to free wheel
88 Overspeed
(Within max

9-6
AS330 Escalator Intrgrated Drive Controller

Fault Fault
Possible Cause Solutions
Code Display
Speed
Allowed
Negative direction overload
Check load udden change external reasons
or load sudden change
UVW
Encoder Encoder wiring has problem
89 Wrong or parameter setting Check wiring connection or change the parameter
Phase problem
Sequence
Encoder
90 Communicat Encoder Fault Check the encoder and reset the encoder self learning
ion Fault
motor single phase get short
Abc Check motor and its outputted wire loop
circuited to grounding
overcurrent
91 (3 phase
instant
Drive Board Inspection
value) Replace drive board
Loop Problem

outputed replay no action Check relay control circuit


Brake
92 Inspection Relay action/brake not open Check brake power line loose or not 第
Fault Feedback component 九
Adjust feedback component
checked to be no signal 章
Input High Voltage Too
check input voltage whether matching the converter
Input High High
93
Voltage Switch Power Voltage 故
Refer to the specialist for maintenance.
Inspection Loop Problem 障
UVW 对
Encoder Encoder Wiring Loop Wiring terminal loose or damage and breakage in the 策
94
Wiring Problem wiring
Break Off
Encoder Not
96 Self
Learning
Too much time on overload stop running for a while, if it takes place again after
situation, more load less restart ,check the overload whether beyond the permit
Output time value
Overcurent
97 Motor Rnning Block Up Checck motor or brake
(validated
value) Motor coil Short circuited Check the motor

Output Short Circuited Check Wiring /Motor

9-7
Shanghai STEP Electric Corporation

Fault Fault
Possible Cause Solutions
Code Display
Sincos
Encoder Damaged or wiring
98 Encoder Check encoder and its wiring
problem
Fault
Input Side Voltage
Abnormal Check Networks Voltage
Input Open
99 Input Voltage Open Phase
Phase
Input side wiring terminal
Check input terminal wiring
loose
Overspeed Encoder parameter setting
check encoder loop
Protection(O fault or get disturbance
ver max Load sudden change check load sudden change external reasons
100
speed
Overspeed Protection
protection Check Parameter
Parameter Setting Problem
limit)
Power Networks Check input power
Motor High Load sudden change Reduce the load sudden change frequency and scope
101 Speed motor parameter setting Correctly set motor parameter
Overcurrent Encoder Parameter Setting
Check encoder Loop
fault or get disturbance

第 Wiring Fault Correct the wrong wiring according to user manual

九 Motor Abnormal replace the motor ,first make grounding insulation test
Grounding
章 102 Converter output side over
protection
current leakage to refer to the specialist for maintenance
grounding

Capacitor
障 103 Converter capacitor aging Refer to the specialist for maintenance
Aging

External
策 104 Externally input fault signal Check external fault reasons
Fault
converter output side wiring
Check converter output side wiring situations, prevent
abnormal, bobble or break
Output bobbling and breaking off
105 off
Unbalance
motor three phase
check the motor
unbalance
Parameter
106 Parameter Setting Incorrect Modify coverter parameter
Setting Fault
Current Drive Board Hardware
107 Refer to the specialist for maintenance
Sensor Fault Fault
Brake External brake resistor
108 Check brake resistor circuit
Resistor circuit shorted

9-8
AS330 Escalator Intrgrated Drive Controller

Fault Fault
Possible Cause Solutions
Code Display
Short
Curcuited
three phase instant
Current
current value get over and
109 Instant Refer to the specialist for maintenance
alarm when Ia,Ib,Ic no
Value Over
operation

Charging Relay Damage Refer to the specialist for maintenance


Charging
114 Three phase input power
Relay Fault
voltage instant drop by over check the reason for voltage drop
30v
Safety Loop
Breaking
Off (safety
6000 switch
checked to
be no
problem)
Safety Loop
6000+
First Switch
i
Off 第




9-9
AS330 Escalator Intrgrated Drive Controller

Chapter 10 Maintenance

This chapter describes general information for maintenance of this product.

◎ Start operation 10minutes after it is


disconnected to main in order to ensure at
that time charge indicator lamp goes out or
DC bus voltage is under 24V
Or it may cause risk of electric shock.
◎ In no case may the escalator integrated
drive controller be remodeled without
authorization
Or it may cause risk of electric shock and injury.
◎ Only professional electricians may be
allowed for maintenance. Never leave foreign
wire ends or metal substances inside.
Or it may cause fire risk.


◎ When power is on, don’t change the 十
wiring or remove terminals. 章
Or it may cause risk of electric shock
10.1 Warranty
Our company guarantees the escalator integrated drive controller (main body) in the following cases: 保

In the warranty period calculated form the delivery date, the manufacture will be liable for failures
or damages occurred in normal operating conditions; when warranty period is expired, the service

will be reasonably paid. 维

The services for dealing with the flowing troubles will also be paid even if it is still in warranty
period:
1) Failures and/or troubles caused due to use it not in accordance with instruction manuals or
modify or remodel it without authorization.
2) Not used for its intended use.
3) Damages during transport or due to falling after purchase.
4) Damages due to earthquake, fire, flood, lightning, abnormal voltage or other force majeure.
10.2 Product Checkup

10-1
Shanghai STEP Electric Corporation

In case damages, troubles or other problems are found on product, please contact the agencies or out
technical departments and provides the following information:
1) Product Type
2) Serial number
3) Purchase date
The following information must be informed of: damage condition, unclear problems and troubles.

10.3 Routine Inspection


Never remove the casing of escalator integrated drive controller when power is on or operating. You
are only needed to carry out visual examination from outside. The routine inspection aims to check:
a) Ambient environment is in compliance with standard specification;
b) Operating performance is compliance with the standard specification;
c) No noise, vibration and other abnormal conditions;
d) The cooling fan of escalator integrated drive controller is running normally;
e) There is no overheating.
10.4 Periodic Inspection
Prior to inspection, stop escalator. After it is disconnected from the main, remove the casing of this
product. At this time, the reservoir capacitors of main circuit may still remain charging voltage
which may be discharged out after certain dwell time. Please wait until the charging indicator lamp
goes out and be additionally proofed by using multimeter, the as measured DC bus voltage is lower
than safety voltage (DC 24V). Touch terminals immediately after switching off may cause the risk of
electric shock. See table 10.1 for detailed periodic inspection items.
Table 10.1 Periodic Inspection Items

十 Objects Inspection Items Methods Criteria
章 1) Visual 1) the ambient temperature
1) Ambient temperature, humidity, inspection, must be lower than 40℃. RH
vibration, dust, corrosive gas, oil mist, thermometer, must be in compliance with
Operating environment
water drop. hygrometer environmental requirements.
保 2) Hazardous materials around 2) Visual 2) no existence of
inspection hazardous materials around.

3) LCD displays clearly with uniform
与 back light. 1) Uniform backlight
LCD display Visual inspection
维 4) If some characters can not be 2) Display in good condition
displayed by LCD

Plug-in terminal 1) check for loose bolts 1)screw down 1) no abnormal conditions
Bolt 2) check for loose plugs 2)visual inspection 2) installed securely

1) Check for broken or faded cover layer


Main circuit

Conductor Visual inspection No abnormal


2) Deformation of copper strip

1) check for vibrating noise during 1) No vibration noise


Electromagnetic acoustic inspection
operation 2) Hear the picking-up
contactor, relay Visual Inspection
2) if contacts pick up or not sound

10-2
AS330 Escalator Intrgrated Drive Controller

1) check for liquid leakage, fade,


reservoir
fissure, expansion of casing
electrolytic Visual inspection No abnormality
2) if safety valve works normally and if
capacitor
expansion occurs to valve body
1) Check for dust
Heat sink 2) Check for blocking or foreign Visual inspection No abnormality
materials in air tunnel
1) Acoustic/visual
inspection. Turn the
fan blade after
1) Check for abnormal noise,
powering off
2) Check for abnormal vibration; 1) Rotate smoothly
Cooling fan 2) Visual
3) Check for fade and deformation due 2),3)no abnormality
inspection
to overheat
3) Visual
inspection, olfactory
inspection
Check for dust and absorbed foreign
materials on double-bank plug-in
Control circuit

Wiring Plugs Visual inspection No abnormality


assembly between control board and main
circuit
1) Check for fade and off odor of control 1) Visual/
circuit board olfactory inspection
Control panel No abnormality
2) Check for fissure, breakage and 2) Visual
deformation of circuit board inspection







10-3
AS330 Escalator Intrgrated Drive Controller

Appendix A EMC Installation Guide

From such aspects as noise control, wiring requirement, grounding, peripheral equipment surge
absorption, leakage current, EMC Zoning, installation precaution, use of supply filter and disposal of
radiated noise, this appendix describes the escalator integrated drive controller EMC design and
installation guide for reference by escalator integrated drive controller users.
A1Noise Control

As determined by operating principle, the escalator integrated drive controller produces certain
noises. The effect of noise on peripheral equipment is relevant to the noise type, transmission path as
well as the design, installation, wiring and grounding of drive system
A1.1 Noise Type
Noise types are shown by Attached figure A1.1.


A1.2 Transmission Path 录
See attached figure A1.2 for transmission path of noise. A

E
M
C



A-1
Shanghai STEP Electric Corporation

A1.3 Basic Measures for Noise Suppression


See attached Table A1.1 for basic noise suppression measures.
Attached Table A1.1 Basic Noise Suppression Measures.

No. Causes Measures


1. avoid arranging signal line and power line in
duplex and in bundle.
Due to electromagnetic induction and 2. keep susceptible peripherals far away from
① electrostatic induction where signal lines are escalator integrated drive controller;
⑦ arranged in duplex with power lines or arranged 3. keep susceptible signal line far away from the
⑧ in bundle, noises occurs and transmits in signal input/output cable of escalator integrated drive
line and additionally results in malfunction of controller;
peripherals 4. use shielded lines as signal line and power line.
It is better to put them in metal hoses (hose-to-hose
spacing shall not be less than 20cm )
Where closed loop circuit is formed among
peripherals and escalator integrated drive
If that time the peripherals are not grounded, the
② controller, the grounding leakage current of
malfunction due to leakage current may be avoided.
integrated drive controller may cause malfunction
of peripherals.
When peripherals sharing a power supply system
with escalator integrated drive controller, the Connect a noise filter at the input side of escalator
③ noise of escalator integrated drive controller may integrated drive controller; or isolate the peripheral
transit along the supply line and resultantly cause from noise by isolating transformer/supply filter.
malfunction of the related peripherals.

A-2
AS330 Escalator Intrgrated Drive Controller

1. Susceptible peripherals and their signal lines must


be arranged far away from escalator integrated drive
controller. Furthermore, the signal line shall be of type
shielded line which shielding layer is properly
grounded. Signal line shall be threaded into metal hose
and arranged far away from the input/output cable of
escalator integrated drive controller. These two kinds
When such weak voltage equipment as control of cable shall be perpendicular to each other.
computers, measuring gauges, radio sets and 2. radio noise filter and linear noise filter (ferrite
④ sensor and their signal lines are installed in a common mode choke) as installed at both input side
⑤ same control cabinet with escalator integrated and output side of escalator integrated drive controller
⑥ drive controller and are wired very close to each will be effective for suppress its noise radiation;
other, the radiated interference may cause 3. the cables of escalator integrated drive controller
malfunction of peripheral. shall be arranged in thicker shielding layer such as
ducts with thickness 2mm or be embedded in cement
tray. In addition, the cables must be threaded in
grounded metal hose. (Four-core cable may be
appreciable for motor cable. One end of a core
conductor shall be grounded to the escalator integrated
drive controller side and another end shall be
connected to motor casing.
A2 Requirements on Cable Laying
A2.1 Requirement on Cable Laying
As shown by figure A2.1(a): To prevent mutual coupling of interferences, control signal cable must
be laid separately with supply cable and motor cable and be spaced as far as practicable. as shown by
figure A2.1(b): where the control signal cable has to cross over supply cable or motor cable, they
must be perpendicular with each.



A

E
M
C



A2.2 Requirements on Cable Size 南
Greater cable size causes greater ground capacitance and greater ground leakage current. Therefore,
motor cable with excessive cross-sectional area shall be used by derating so as to reduce output
current (each increment of cross sectional area makes current decreasing by 5%).
A2.3 Requirements on Shielded Cable
High frequency low-impedance shielded and armored (such as weaved copper wire mesh or,
aluminum wire mesh) cable shall be used.

A-3
Shanghai STEP Electric Corporation

A2.4 Requirements on Installation of shielded cable


Control cables are mostly shielded cables which shielding-purpose metal wire mesh must be
connected to metal casing by 360° girth jointing method with cable clip at both ends, as shown by
figure A2.2. In addition, the figure A2.3 shows an incorrect shield grounding method.

Figure A2.2 Correct Shield Grounding Method

Figure A2.3 Incorrect Shield Grounding Method

A3 Grounding Requirements
A3.1 Grounding Method
See figure A3.1 for grounding method of Ground pole

Figure A3.1 Dedicated Ground Pole


Among the above-shown four figures, (a) shows the optimal grounding method. Users are advised to
use this method as practicably as possible.
A3.2 Precautions for Grounding Connection

A-4
AS330 Escalator Intrgrated Drive Controller

(1) Use grounding cable of standard cross section as far as possible in order to minimize the
grounding impedance; due to flat cable has smaller high-frequency impedance than round-section
cable, therefore, flat cable with identical cross-sectional area will be more preferable.
(2) The ground cable should be as short as possible and the grounding point should be close to the
escalator integrated drive controller as practicably as possible.
(3) If four-core cable is used for motor line, one of the four core conductors must be grounded in
such a way that one end of it is grounded by the side of escalator integrated drive controller and
another end is connected to the ground terminal of motor. The optimal grounding effect may be
achieved if each of both motor and the escalator integrated drive controller has individual dedicated
ground pole.
(4) Where all ground terminals of system components are combined together, the noise source
caused by ground leakage current will affect the other peripherals of escalator integrated drive
controller. Therefore, in a same control system, the grounding for escalator integrated drive
controller shall be separated from those for weak voltage equipment such as computer, sensor or
audio devices.
(5) To get smaller high-frequency impedance, the anchor bolts of equipment may be used as
high-frequency terminal connecting rear panel of cabinet. Note to remove insulation coating around
the securing point in installation.
(6) The grounding cable must be laid far away from the I/O wirings of noise sensitive equipment.
In addition, the grounding cable must be as short as possible.

A4 Install Surge Absorption Device


Even if they are installed outside or escalator integrated drive controller, such heavy noise
production devices as relay, contactor and electromagnetic brake must be additionally provided with
surge suppressor. As shown in Figure 4.1.



A

E
M
C



Figure 4.1 Use Requirements of Relay, Contactor and Electromagnetic Brake 南
A5 Leakage Current and Countermeasures
Figure A5.1 shows the wiring capacitance, motor capacitance, ground leakage current and
line-to-line leakage current by the input/output side of escalator integrated drive controller. The
intensity of leakage current depends upon the carrier frequency and capacitance.

A-5
Shanghai STEP Electric Corporation

Figure A5.1 Paths of Leakage Current


A5.1 Ground Leakage Current
Ground leakage current not only flows by escalator integrated drive controller but also flows by
other equipment via the ground wire. As a result, it may cause malfunction of leakage protection
circuit breaker, relay or other equipment. The leakage current increases with the increment of carrier
frequency of escalator integrated drive controller and the extension of motor cable.
Suppression measures: reduce carrier frequency; shorten motor cable as practicably as possible; use
leakage protection circuit breaker specially designed for leakage current due to higher
harmonic/surge.
A5.2 Line-to-Line Leakage Current
As for leakage current flowing by the distributed capacitance between I/O side cables of escalator
integrated drive controller, its higher/sub harmonics may cause malfunction of external thermorelay.
Especially when small capacity escalator integrated drive controller under 7.5Kw is used, and at the
same time, long wiring (more than 50m) is provided, the increased leakage current is liable to make
malfunction of external thermorelay.
Suppression Measures: reduce carrier frequency; install AC output reactor at the output side;
monitor the motor temperature directly with the temperature sensor; or use electronic thermorelay,
the motor overload protection integrated to escalator integrated drive controller instead of external
thermorelay,

A6 Suppression of Radiated Emission


Escalator integrated drive controller is usually installed in metal control cabinet, the external
instruments and equipments are lightly affected by radiated emission of escalator integrated drive
controller. Therefore, the external connecting cables are deemed as the main source of radiated
emission. Due to the supply cable, motor cable as well as the control cable and keyboard cable are
all necessary to be led outside of the shielding cabinet; the cable outlet must be so treated specially
to avoid impairing the shielding effects.
In Figure A6.1: the cables in the shielded cabinet acts as an antenna, which absorbs the radiated
noises in cabinet, transmits outside via cables and emits them to the space; in Figure A6.2: ground
the cable’s shielding layer at the outlet of the shielded cabinet, thus the noise radiation absorbed by
the cable will flow to earth directly via the shielding cabinet so as to eliminate its effect on external
environment.

A-6
AS330 Escalator Intrgrated Drive Controller

When using the shielding layer grounding method as shown in figure A6.2, the shielding layer must
be grounded as close to the cabinet as possible, otherwise the sectional cable from grounding point
to the outlet of cabinet will still act as an antenna coupling. The noise grounding point shall not be
more than 15cm from cable outlet of cabinet, and smaller clearance will always be more preferable.

A7 Guide for Use of Power line filter 附


Power line filter may be used by heavy-noise protection devices and noise susceptible devices. 录
A7.1 Functions of Power line filter A
(1) The power line filter is two-way low pass filter which only permits flowing of DC current or
50HZ operating frequency AC current but stops flowing of higher frequency electromagnetic
interference current. Therefore, it can not only inhibit the equipment’s electromagnetic interferences E
flowing into power line but also inhibit the noises in power line flowing into equipment. M
(2) The power line filter may be able to make equipment meeting EMC requirements on conducted C
emission and transmission sensitivity. In addition, it may also suppress the radiated interference of 安
equipment. 装
A7.2 Precautions for Installation of Power Line Filter 指
(1) In the cabinet, the filter shall be located close to the power line inlet as practicably as possible. 南
Additionally, the filter supply line section left in the control cabinet must be as short as possible.
(2) Where the input line and output line of filter is too closely laid, the high-frequency interference
may bypass the filter, couple directly with output line and input line and as a result make the power
filter failing to function.
(3) Usually there is a dedicated ground terminal on the casing of filter. However, if this ground
terminal is connected by a conductor to the cabinet body, the filters will not functions due to the long
conductor with great high-frequency resistance can not plays the role of a bypass. Correct

A-7
Shanghai STEP Electric Corporation

installation method shall be such: closely laid the filter casing on the conductive plane of metal
cabinet so as to maximize their contact area. Note to remove the insulation coating during
installation in order to ensure good electric contact.
A8 EMC Installation Zoning
n the drive system constituted by escalator integrated drive controller and motor, the escalator
integrated drive controller and peripherals such as control devices and sensors are usually installed in
a same control cabinet. The interferences of control cabinet on external environment may be
inhibited by taking suitable measures at the main contacts, therefore, the supply line radio noise filter
and supply line AC reactor shall be installed. In order to meet the EMC directive, the interiors of
control cabinet shall also be arranged in accordance with EMC requirements.
In the drive system constituted by escalator integrated drive controller and motor, the escalator
integrated drive controller, brake units and contactors are all heavy noise source which may affect
the normal operation of such noise sensitive peripherals as automated assembly, encoder and sensor.
On the basis of electric characteristics of peripherals, they will be installed at different EMC zones in
order to spatially isolate the noise sources and noise receivers. This is an effective measure for
eliminating interferences.
See Figure A8.1 for EMC installation zoning for escalator integrated drive controller.

Figure A8.1 EMC Zone for installation of escalator integrated drive controller
Description of above shown EMC zoning for installation:
I zone: Control supply transformer, control device and sensor
II zone: Control signal cable interface requiring certain anti-interference capacity
III zone: Main noise sources including input reactor, escalator integrated drive controller, brake
unit, contactor and the like
IV zone: Output noise filter and its wiring
V zone: Power supply (includes wiring of radio noise filter)
VI zone: Motor and its cable

A-8
AS330 Escalator Intrgrated Drive Controller

These zones shall be separated by minimum 20cm in order to realize electromagnetic decoupling; for
better decoupling effect, ground separator is preferred among the zones. The cables shall be laid and
arranged by zone; if necessary, filters shall be installed at interfacing point between zones; all the
bus cables led out from cabinet (e.g. RS485) and signal cable must be shielded.
A9 Precautions for Electric Installation
See Figure A9.1 for electric installation of escalator integrated drive controller.



A

Figure A9.1 Electric Installation of escalator integrated drive controller In order to meet the EMC
directive, the following notices must be taken: E
(1) Escalator integrated drive controller shall be installed in a cabinet where the base plates of M
escalator integrated drive controller and such peripherals as input filter will be secured on the rear C
panel in order to ensure good electric contact; the escalator integrated drive controller and filters 安
must be arranged as close as possible within 15cm in order to minimize the high-frequency 装
impedance of their grounding line and reduces high-frequency noises.

(2) Install a wide ground terminal bank at the inlet (5cm or less from outlet) of control cabinet and 南
than secure all the shielding layers of cabinet in/out cables onto the terminal bank by 360° girth
jointing method in order to ensure good electric contact.
(3) Motor cable shall be of type shielded cable and it is more preferable to use shielded cables with
such two shielding layers as spiral metal belt and metal mesh. By the escalator integrated drive
controller side, the shielding layer of motor cable shall be connected, by 360° girth jointing method
and with cable clip, to the rear panel of cabinet at two points: one point shall be close to escalator
integrated drive controller as far as possible within 15cm, another point is located on ground
terminal bank. 360° girth jointing method shall also be used when the motor cable’s shielding layer

A-9
Shanghai STEP Electric Corporation

threads through motor terminal box and grounds at motor metal casing; if it is impractical, firstly
strand both shielding layers as braid, then flatten it to width of more than 1/5 braid length in for
connecting to motor terminal. The core conductor of motor cable and its PE soft braid lead shall be
as short as possible within 5cm.
(4) Terminal control cable must be of type shielded cable, which shielding layer should be
connected to terminal bank at the cable inlet of cabinet by 360° girth jointing method; the shielding
layer end connecting escalator integrated drive controller may be secured to the metal casing of
escalator integrated drive controller. If impractical, firstly strand both shielding layers as short and
wide braid, and then flatten it to facilitate connecting to the PE terminal of escalator integrated drive
controller. The uncovered section of cable core conductor and the PE soft braid lead shall be as short
as possible within 15cm.
⑸ Keyboard cable shall not be threaded out from the shielding cabinet.
The slot holes on shielding cabinet shall be as small as possible within 15cm in length.

A10 EMC Conformity


The AS330 series escalator integrated drive controller conforms to the EMC directive as shown by
attached Table A10.1 provided that suitable input/output filters and AC reactors (see “Optional
Parts” for the type of optional filters and reactors) and installed and the above-said precautions are
carefully taken.
Table A10.1 General EMC Performance of AS330 Escalator Integrated Drive Controller

Item Applicable standard Criteria Level

Conducted noise emission EN12015.1998 0.15≤ƒ <0.50MHz, 100db (μν/m) quasipeak


immunity 0.50≤ƒ <5.0MHz, 86db (μν/m) quasipeak
5.0≤ƒ <30MHz, 90:70db (μν/m) quasipeak
Radiated noise emission EN12015.1998 30≤ƒ <230MHz, 40db (μν/m) quasipeak
immunity 230≤ƒ <1000MHz, 47db (μν/m) quasipeak
Electrostatic discharge noise EN12016.2004 Criterion B(contact discharge 4000V, air discharge
immunity 8000V)
Radiated electromagnetic EN12016.2004 Level 3, criterion A(3V/m)
field noise immunity
EFTB immunity EN12016.2004 Level 4, Criterion B(heavy voltage end ±2KV/2.5kHz)

Surge Immunity EN12016.2004 Criterion B(±1KV)


Conducted noise immunity EN12016.2004 Criterion A (3V,0.15~80MHz)

A-10
AS330 Escalator Intrgrated Drive Controller

Appendix B Function Parameter, Fault List Summary

This appendix summarize the function parameter, running situation and fault list, in order to make
it convenient for the user to check and use.
B.1 Function Parameter List

Para-number Parameter
Default Range Unit Reference
Description
F0 Drive Mode 1 0~2 0 Frequency Conversion
1 Double Mode 2 Y-ᇞ
F1 Casual Mode 0 0~2 0 non-casual 1 only
casual half speed 2
Casual half speed/casual
pause
F2 X19 Input Style 0 0~2 0 Mode Option 1 Fire
Input 2 Motor
Overheated
F3 Fire Escalator 0 0~1 1yes 0 no
F4 Reversed Entry Alarm 20 10~1000 0.1s
TIme
F5 Same Direction Running 300 50~60000 0.1s
Casual Time
F6 Reverse Direction Running 100 50~6000 0.1s
Casual TIme
F7 Half Speed Running Stop 50 0~6000 0.1s
Time
F8 General Additional Brake 50 0~1000 0.1s
Release Time
F9 Emergent Additional Brake 5 0~1000 0.1s
Release Time
F10 Rated Speed 700 100~3000 0.001m/s

F11 Inspection Speed 300 10~3000 0.001m/s

F12 Casual Speed 150 10~3000 0.001m/s

F13 Motor Speed Measurement 50 1~1000 0.1s

Delay

F14 Standby 30 1~1000 0.1s 故
F15 Motor Speed Measurement 100 1~10000 障
Frequency Conversion 表
Standard(Double Mode) 汇
F16 Motor Speed Measurement 100 1~10000 总
ᇞ Standard

B-1
Shanghai STEP Electric Corporation

F17 Stair Speed Measurement 100 1~10000


Standard
F18 Left Handrail Speed 100 1~10000
Measurement Standard
F19 Right Handrail Speed 100 1~10000
Measurement Standard
F20 Oil Filling Time Gap 8 0~1000 Hour
F21 Single Oil Filling Time 10 0~1000 S
F22 Standby 0 0~0
F23 Fault Ring Time 40 0~1000 0.1S
F24 Function Activation 0 0~65535
F25 Casual Motor Torque Limit 900 800~2000 0.1%
F26 Input Type X0 -15 0 0~65535
F27 Input Type X16-31 0 0~65535
F28 Input Type X32-47 0 0~65535
F29 Input Type X48-63 0 0~65535
F30 Monitering Address 255 0~255
F31 Inlet Photoelectrical Fault 0 Soft Stop 1 Cancel
0 0~1
Handling Casual
F32 0 Speed Measurement
Mode A Motor Installed
Motor Speed Measurement On
0 0~1
and Installation 1Speed Measurement
Mode B Stairs Installed
On
F33 Standby 0 0~65535
F34 Standby 0 0~65535
F35 Standby 0 0~65535
F36 Standby 0 0~65535
F37 Initial Password 149 0~65535
F38 Commissioning Password 1234 0~65535
F39 Super Password 19163 0~65535

F200 Converter Software Version 30.01 0~65535 -

参 F201 Control Mode 0 0~4 -

数 F202 Motor Type 0 0~1 -

、 F203 Motor Rated Power - 0~65535 0.01kW

故 F204 Motor Rated Current - 0~65535 0.1A

障 F205 Motor Rated Frequency 50.00 0~65535 0.01Hz


表 F206 Motor Rated Rotation 1460 0~65535 rpm
汇 Speed
总 F207 Motor Rated Voltage 380 0~65535 V

B-2
AS330 Escalator Intrgrated Drive Controller

F208 Motor Polarity 4 0~65535 P


F209 Motor Rated Slip 1.40 0~65535 0.01Hz
Frequency
F210 Tracking Delay Time 1000 0~9000 ms
F211 Tracking Zero Voltage 100 0~9000 ms
TIme
F212 Tacking Voltage Kp 0.20 0~65535 0.01
F213 Tracking Voltage Ki 0.30 0~65535 0.01
F214 Tracking Quit Delay 1000 1000~10000 ms
F215 Tracking Max Current 100.0 0~65536 0.1%
F216 Tracking Frequency 30.0 100~2000 0.1%
Change Gain
F217 Tracking Initial Frequency 50.00 0~65535 0.01Hz
F218 Tracking Max Voltage 0 0~65535 V
F219 Tracking Max Current 0.00 0~65535 0.1A
F220 Acceleration Time Ta0 5.00 0~65535 0.01s
F221 Deceleration Time Td0 5.00 0~65535 0.01s
F222 Acceleration Round Angle 1.30 0~65535 0.01s
Ts0
F223 Acceleration Round Angle 1.30 0~65535 0.01s
Ts1
F224 Decerleration Round Angle 1.30 0~65535 0.01s
Ts2
F225 Deceleration Round Angle 1.30 0~65535 0.01s
Ts3
F226 Max Frequency 55.00 0~65535 0.01Hz
F227 Brake Action Time 0.20 0~65535 0.01s
F228 Current Slow Down Time 0.00 0~65535 0.01s
F229 Compensated Torque 0 0~65535
Direction
F230 Acceleration Time Ta1 5.00 75~65535 0.01s
F231 Deceleration Time Td1 5.00 75~65535 0.01s
F232 Encoder Filter TIme 0 0~65535 ms


F233 Encoder 1 0~65535 -

Direction1:Positive

Sequence

F234 Motor phase Sequence 0/1 1 0~65535 -

F235 Motor Empty Load Current 32.00 0~65535 0.01%

Coefficient

F236 PWM Carrier Frequency 6.000 1100~13000 0.001kHz

F237 Random PWM Width 0.000 0~1000 0.001kHz

F238 Adjustor Mode 1 0~3 -
F239 Output Torque Limit 150 0~200 %

B-3
Shanghai STEP Electric Corporation

F240 Converter Rated Voltage 380 0~65535 V


F241 Converter Rated Power - 0~65535 0.01kW
F242 Angle Synchronical 130.0 0~3600 0.1
Adjustment I2G Degree
F243 I2G Switch Frequency 49.50 0~5300 0.01Hz
F244 Synchronical Overtime 10.0 0~160 0.1s

B.2 Fault Code And Analysis


Control System Fault Code And Analysis

Code Faults Possible Causes and Analysis

Contact Adhensive(not
when brake ,ᇞ contact,angle contact,up going contact,down going contact all
01 pure frequency
have no output,adhesive check still have signal
conversion)

Frequency Conversion
02 Contact Fault(Not pure Frequency conversion contact input and output discordance
frequency conversion)

Working Frequency
03 Contact Fault(Not pure Working frequency contact input and output discordance
frequency conversion)

04 Brake Switch Fault Brake switch output and check discordance

05 Safety Loop Relay Fault Safety loop/high voltage and safety loop relay discordance

Additional brake switch can not open


Additional Brake Switch
06 When startup, continually 3 times not open means the fault
Fault
When in operation, one time means fault

Additional Brake Relay


功 07 Additional brake relay output and input discordance
Fault

参 08 Temperature Fault Temperature Alarm Input

数 Converter No communication with converter,check board installation loose or not and


10
、 Communication Fault power voltage stable or not
故 11 Drive Chain Breakage Chain breakage action

Oil Level Inspection
表 12 Out of oil( temperary no this fault)
Fault

Inlet Optoelectricity Inlet Optoelectricity Damaged
总 13
Damaged Escalator load is normal but check out no action of the inlet optoelcticity

B-4
AS330 Escalator Intrgrated Drive Controller

Contact Brake Fault(Pure


14 Brake contact input and output discordance
Frequency Conversion)

Out-wired Contact 1
15 Fault(Pure Frequency Out-wired Contact 1 input and output discordance
Conversion)
Out-wired Contact 2
16 Fault(Pure Frequency Out-wired Contact 2 input and output discordance
Conversion)
Mode Abnormal
17 During operation, inspection automatically makes switchover
Switchover

Reversed escalator
50 Reverse
Speed measurement switch fault

Escalator Overspeed
51 Overspeed
Speed measurement switch fault

Escalator underspeed
52 Underspeed
Speed measurement switch fault

Handrail Overspeed
53 Handrail Overspeed
Speed measurement switch fault

Handrail Underspeed
54 Handrail Underspeed
Speed measurement switch fault

Stair Loss
55 Stair Loss
Stair Inspection Switch Fault

Brake Distance Over


56 After brake closed,escalator brake distance too long
Limit

69 parameter not initialized please reset the control parameter






Drive System Fault Code And Analysis 故
Fault Fault 障
Possible Cause Solutions
Code Display 表
Mode DC terminal over high Check the meshwork power, to see whether fast stop 汇
71
Overcurrent voltage with high inertia load,no energy consumption brake 总

B-5
Shanghai STEP Electric Corporation

Fault Fault
Possible Cause Solutions
Code Display
Protection Check the motor or the out wires are short curciuted, or
Short curciuted around
the grounding short curcuited

Output open phase Check the motor and the outputted wires are loose or not

Encoder Fault Check encoder is damaged or correctly wired.

Hardware not well


Refer to the specialist for maintenance
contacted or damaged
Plug-ins loose inside
Refer to the specialist for maintenance
converter
Induction Adjust the induction motor slip
motor slip setting unrea
sonable
No-load Adjust the no-load current coefficient
current coefficient set
unreasonable
Current Sensor Damage Replace the current sensor
72 ADCFault
Current Sampling Loop
Replace the control board
Problem
Overhigh Surrounding
Cool down the temperature, enhance the ventilation
Temperature

Clear off dust,cotton and some other rubbish in the wind


Wind Tunnel Blocked
Heatsink tunnel
73
Overheated
Check the fa power line whether well wired or replace
Fan Abnormal
same type fan
Temperature Check Circiut
Refer to the specialist for maintenance
Fault

Brake Unit Damage Replace related drive mode


Brake Unit
功 74
Fault External Brake Resistor
Check the brake resistor connection
能 Circuit Shorted
参 Overcurrrent leads to fuse
75 Fuse Fault Check fuse loop off or not ,or contact loose
数 broken
、 Undervoltage of the input
故 Check the input power
power
障 Output Over Motor Block Up/Serious Prevent it from motor block up and reduce the sudden
76
表 Torque Sudden Load Change load change

Encoder Fault Check whether encoder is damaged or correctly wired

B-6
AS330 Escalator Intrgrated Drive Controller

Fault Fault
Possible Cause Solutions
Code Display

output open phase Check motor and the outputted wires whether loose or not

Acceleration Time Too


Extend the acceleration time
Short
Acceleration
77 Too Much Load Reduce load
Deviation
Raise up the current limit value within the range of
Current Limit Too low
permit
Bus Input Power Voltage
Check the input power
Overvoltage Abnormal
Protection(in Motor Quick Restart when
Motor stop and restart up
acceleration) high speed running
Load Running Inertia Too
Bus Use suitable energy consumption brake parts
Big
Overvoltage
Deceleration Too Short
Protection(in Entend deceleration time
Time
78 decceleratio
Brake Resistor Value Too
n) Connect the suitable brake resistor
Big/ No connected

Bus Input Power Abnormal Check Input Power


Overvoltage
Load Running Inertia Too
Protection(in Use suitable energy consumption brake parts
Big
constant
Brake Resistor Value Too
speed) Connect the suitable brake resistor
Big/ No connected
Power voltage under
Check Input Power
minimum working voltage

Instant Power Off


Check Input Power , ready-input voltage ,reset and restart
Input power voltage change up
Bus too much

79 Undervoltag Power Wired Terminal


Check input wiring
e Loose 功
Inside Switch Power 能
Refer to specialist for maintenance
Abnormal 参
Load of high startup 数
Change power system to make it accord with the standard
current in the same power 、
value
system 故
Converter output side 障
abnormal wiring, bobble or 表
Output Open Check converter output side wiring situation, prevent
80 break off 汇
Phase bobbling and breaking off

Output Terminal Loose

B-7
Shanghai STEP Electric Corporation

Fault Fault
Possible Cause Solutions
Code Display
Motor Power Too Small,
under 1/20 of converter max Adjust converter capacity and motor capacity
power

Check motor well wired ot not


Output 3 phase unbalance
Off power,check converter output side and DC side
terminals of the same character or not
Power Networks Low
Motor Low Check input power
Voltage
Speed
Motor Parameter Setting
Overcurrent( Correctly set motor parameters
Abnormal
in
Direct startup during motor
acceleration) Motor running stop and startup
running
Power networks low
Check input power
voltage
Motor Low
Load Running Inertia
Speed Use suitable energy consumption brake parts
81 Bigger
Overcurrent(
Motor Parameter Setting
in Correctly setting motor parameter
Abnomal
deceleration)
Deceleration Tinme Too
Extend deceleration time
Short
Motor Low Load Sudden Change
Decrease load sudden change frequency and its range
Speed during Running
Overcurrent(
Motor parameter setting
in constant correctly set motor parameter
abnormal
speed)

Encoder not well contacted Change encoder wiring

Check Encoder in good condition or not and its power


Encoder No Signal Output
Encoder supply
功 82
Fault Encoder Connection Wire
Repair the broken part
能 Breaking off
参 Function Code Setting
make sure converter encoder function codes correct
数 Abnormal
、 Motor stop does not Motor Slippage
故 Find Current
83 effectively cut off the
障 When Stop
current Refer to specialist for maintenance

Speed Speed Reversed During
汇 84 Check outside load has sudden change or not
Reversed Running

B-8
AS330 Escalator Intrgrated Drive Controller

Fault Fault
Possible Cause Solutions
Code Display
During Encoder and Motor are of
Change motor or encoder phase sequence
Running different phase sequence
Motor Reverse Running
Current limit too low , not matching the motor
When Startup
Brake loose , escalator
Check Brake
Find Current slippage
85
When Stop

Wrong
Motor wire reverse
86 Motor Turn over and adjust the parameter
connection
Sequence
Motor Magnetism loss leads
Check Motor
to free wheel
Codirectiona
l Overspeed
87
(max speed
range)
Positive direction overload
Check load sudden change external reasons
or load sundden change
Motor Magnetism loss
Check motor
Reverse situation leads to free wheel

Overspeed
88 (Within max
Speed
Allowed Negative direction overload
Check load udden change external reasons
or load sudden change
UVW
Encoder Encoder wiring has problem
89 Wrong or parameter setting Check wiring connection or change the parameter
Phase problem
Sequence

Encoder

90 Communicat Encoder Fault Check the encoder and reset the encoder self learning

ion Fault

motor single phase get short
Abc Check motor and its outputted wire loop 、
circuited to grounding
overcurrent 故
91 (3 phase 障
instant
Drive Board Inspection

value)
Loop Problem
Replace drive board 汇

92 Brake outputed replay no action Check relay control circuit

B-9
Shanghai STEP Electric Corporation

Fault Fault
Possible Cause Solutions
Code Display
Inspection
Relay action/brake not open Check brake power line loose or not
Fault
Feedback component
Adjust feedback component
checked to be no signal
Input High Voltage Too
check input voltage whether matching the converter
Input High High
93
Voltage Switch Power Voltage
Refer to the specialist for maintenance.
Inspection Loop Problem
UVW
Encoder Encoder Wiring Loop Wiring terminal loose or damage and breakage in the
94
Wiring Problem wiring
Break Off
Encoder Not
96 Self
Learning
Too much time on overload stop running for a while, if it takes place again after
situation, more load less restart ,check the overload whether beyond the permit
Output time value
Overcurent
97 Motor Rnning Block Up Checck motor or brake
(validated
value) Motor coil Short circuited Check the motor

Output Short Circuited Check Wiring /Motor

Sincos
Encoder Damaged or wiring
98 Encoder Check encoder and its wiring
problem
Fault
Input Side Voltage
Abnormal Check Networks Voltage
Input Open
99 Input Voltage Open Phase
Phase
Input side wiring terminal
Check input terminal wiring
功 loose
能 Overspeed Encoder parameter setting
check encoder loop
参 Protection(O fault or get disturbance
数 ver max Load sudden change check load sudden change external reasons
100
、 speed
Overspeed Protection
故 protection Check Parameter
Parameter Setting Problem
障 limit)
表 Motor High Power Networks Check input power
汇 101 Speed Load sudden change Reduce the load sudden change frequency and scope
总 Overcurrent motor parameter setting Correctly set motor parameter

B-10
AS330 Escalator Intrgrated Drive Controller

Fault Fault
Possible Cause Solutions
Code Display
Encoder Parameter Setting
Check encoder Loop
fault or get disturbance
Wiring Fault Correct the wrong wiring according to user manual

Motor Abnormal replace the motor ,first make grounding insulation test
Grounding
102 Converter output side over
protection
current leakage to refer to the specialist for maintenance
grounding
Capacitor
103 Converter capacitor aging Refer to the specialist for maintenance
Aging
External
104 Externally input fault signal Check external fault reasons
Fault
converter output side wiring
Check converter output side wiring situations, prevent
abnormal, bobble or break
Output bobbling and breaking off
105 off
Unbalance
motor three phase
check the motor
unbalance
Parameter
106 Parameter Setting Incorrect Modify coverter parameter
Setting Fault
Current Drive Board Hardware
107 Refer to the specialist for maintenance
Sensor Fault Fault
Brake
Resistor External brake resistor
108 Check brake resistor circuit
Short circuit shorted
Curcuited
three phase instant
Current
current value get over and
109 Instant Refer to the specialist for maintenance
alarm when Ia,Ib,Ic no
Value Over
operation

Charging Relay Damage Refer to the specialist for maintenance


Charging 功
114 Three phase input power
Relay Fault 能
voltage instant drop by over check the reason for voltage drop

30v

Safety Loop

Breaking

Off (safety

6000 switch

checked to

be no

problem)

B-11
Shanghai STEP Electric Corporation

Fault Fault
Possible Cause Solutions
Code Display
Safety Loop
6000+
First Switch
i
Off










B-12
AS330 Escalator Intrgrated Drive Controller

Appendix C Inverter Complies With The Standards

1. European Low Voltage directive


AS320 Series converter products complies with EN61800-5-1 :2007standards, which comply
with the Low Voltage Directive(Low Voltage Directive 2006/95/EC)。
The inverter also meet the following standards:
EN61800-5-1 : 2007:Adjustable speed electrical powerdrive systems –Part
5-1:Safetyrequirements –Electrical, thermal and energy

2. European EMC regulations


When you follow the recommendations in this manual for
installation, the AS320 seriesinverter product meets the following EMC standards:
EN12015.1998 Electromagnetic compatibility-Product family standard for lifts, escalators
and passenger conveyors-Emission.

EN12016.2004 Electromagnetic compatibility-Product family standard for lifts, escalators


and passenger conveyors-Immunity.

EN61800-3:2004: Power drive D of Part 3




3. ISO9001 Quality Management System C
Shanghai Sigriner STEP Electric Co., Ltd will manage its quality management
system in accordance with the ISO9001 standards.







C-1
AS330 Escalator Intrgrated Drive Controller

Notice to customers

Dear customers:

RoHS is the English abbreviation of the Restriction of the use of certain hazardous substances in
electrical and electronic equipment. EU implemented the RoHS on July 1, 2006, it regulates the
limited use of six kinds of harmful materials during the electrical and electronic equipment products
of recently putting on the market, such as lead, mercury, cadmium, sexavalence chromium, PBB, and
PBDE etc..

On Feb 28, 2006, the seven ministries and commissions of Ministry of Information Industry of
China, Development and Reform Commission, Department of Commerce, General Administration
of Customs, State Administration for Industry and Commerce, State General Administration for
Quality Supervision and Inspection and Quarantine, State Environmental Protection Administration
jointly issued the Measures for Administration of the Pollution Control of Electronic Information
Products which is the RoHS of Chinese version and make a compulsory implementation. On Feb 1,
2008, Measures for Administration of the Environmental Protection of Electronic Wastes Pollution
which was issued by China Environmental Protection Administration began to be implemented
which clearly regulated that the user of the electrical and electronic equipment product should offer
or relegate the electronic waste to units (including individual business households) who had the
corresponding scope of business listed in directory (including temporary directory) to demolish,
utilize or dispose them.

The products of our company comply with the requirements of Measures for Administration of the
Pollution Control of Electronic Information Products and RoHS on the part of electronic parts and
components, PCB board, harness material, selecting and purchasing of structural element etc., it
strictly controls the six kinds of harmful materials of lead, mercury, cadmium, sexavalence
chromium, PBB, and PBDE. Also, during the production, PCB parts and components are welded in
lead free product line using the lead free welding process.

The possible poisonous elements contained in the following components:

Components type Electronic Electronic printed Sheet metal Radiator Working of Wire
component circuit board(PCB) parts plastics

Possible
Six kinds of harmful materials of lead, mercury, cadmium, sexavalence chromium, PBB,
poisonous
and PBDE
elements
1 Environmental impact analysis

During the usage, our company products will produce some heat to result in some harmful materials
volatilizing very a little, however, it can not seriously affect the environment. While the electronic
products are out of use at the end of the lifecycle and are discarded, the heavy metal and chemical
poisonous material will seriously pollute the soil and water source.

2 Lifecycle of electronic products and equipments

Any electronic products and equipments have its service life and can be abandoned, even though it
can be used, it also will be washed out by upgraded products. The lifecycle of our company

C-1
Shanghai STEP Electric Corporation

electronic products and equipments are generally below 20 years.

3 Abandoned disposal methods of electronic products

When the various electronic products are abandoned, if disposed improperly, they will pollute the
environment. Our company requires the customer to establish the recycle system according to the
national corresponding provisions, it can not be disposed as general domestic garbage or general
industrial solid waste, and it shall be stored and utilized by environmental harmless method or
unified recovered and disposed by authorized units strictly according to Measures for Administration
of the Environmental Protection of Electronic Wastes Pollution issued by China Environmental
Protection Administration. For any individual and unit without rights, to demolish, utilize or dispose
electronic wastes is forbidden.

Please don’t discard the electronic wastes with common domestic garbage. Any proposal about
disposal of electronic wastes, please contact local waste product disposal organization or
environmental protection bureau.