Review Module 42 - RCD 2-May 2022-Online
Review Module 42 - RCD 2-May 2022-Online
Review
ULTIMATE Module-Reinforced
STRENGTH Concrete Design-Ultimate Strength Design (Beams)
DESIGN: BEAMS
SINGLY REINFORCED BEAMS
Load Factors:
NSCP 2001: 1.4D+1.7L 𝜌𝑚𝑖𝑛 ≤ 𝜌𝑎𝑐𝑡 ≤ 𝜌𝑚𝑎𝑥
NSCP 2010/2015: 1.2D+1.6L
𝑨𝒔
MODES OF DESIGN 𝜌𝑎𝑐𝑡 =
𝒃𝒅
𝑎 = 𝛽𝑐
1. Balanced Design 𝑎 = 𝑑𝑒𝑝𝑡ℎ 𝑜𝑓 𝑐𝑜𝑚𝑝𝑟𝑒𝑠𝑠𝑖𝑜𝑛 𝑏𝑙𝑜𝑐𝑘
𝑐 = 𝑑𝑖𝑠𝑡𝑎𝑛𝑐𝑒 𝑓𝑟𝑜𝑚 𝑛𝑒𝑢𝑡𝑟𝑎𝑙 𝑎𝑥𝑖𝑠 𝑡𝑜 𝑡ℎ𝑒 𝑜𝑢𝑡𝑒𝑟𝑚𝑜𝑠𝑡
𝑐𝑜𝑚𝑝𝑟𝑒𝑠𝑠𝑖𝑜𝑛 𝑓𝑖𝑏𝑒𝑟
NSCP 2001
𝛽 = 0.85 𝑖𝑓 𝑓𝑐′ ≤ 30𝑀𝑝𝑎
0.05 ′
𝛽 = 0.85 − [𝑓𝑐 − 30] ≥ 0.65
7
NSCP 2010/2015
𝛽 = 0.85 𝑖𝑓 𝑓𝑐′ ≤ 28𝑀𝑝𝑎
𝜀𝑐 = 0.003; 𝜀𝑡 = 𝜀𝑦 0.05 ′
𝑓 = 𝜀 𝐸𝑠 = 𝑓𝑦 𝜀 = 𝑓𝑦/𝐸𝑠 𝛽 = 0.85 − [𝑓𝑐 − 28] ≥ 0.65
𝑠 𝑡 𝑦 7
𝑓𝑠 = 𝑓𝑦 (𝑎𝑐𝑡𝑢𝑎𝑙 𝑠𝑡𝑟𝑒𝑠𝑠 𝑜𝑛 𝑡𝑒𝑛𝑠𝑖𝑙𝑒 𝑠𝑡𝑒𝑒𝑙)
“STEEL YIELDS” General Formula for steel ratio 𝜌
0.85𝑓𝑐′𝛽 𝑐
2. Under-Reinforced Design 𝜌= ( )
𝑓𝑦 𝑑
Beams reinforced for tension only
0.85𝑓𝑐′𝛽 600
𝜌𝑏𝑎𝑙 = ( )
𝑓𝑦 600 + 𝑓𝑦
𝜀𝑐 = 0.003; 𝜀𝑡 < 𝜀𝑦
𝑓𝑠 = 𝜀𝑡𝐸𝑠 < 𝑓𝑦
𝑓𝑠 = 𝑓𝑠 = 𝜀𝑡𝐸 (𝑎𝑐𝑡𝑢𝑎𝑙 𝑠𝑡𝑟𝑒𝑠𝑠 𝑜𝑛 𝑡𝑒𝑛𝑠𝑖𝑙𝑒 𝑠𝑡𝑒𝑒𝑙)
“STEEL DOES NOT YIELD”
600(𝑑 − 𝑐)
𝑓𝑆 = 𝜀𝑡𝐸𝑠 =
𝑐
MANILA: Room 206, JPD Building, CM Recto Avenue, Manila
CEBU: 4/F J. Martinez Bldg., Osmeña Blvd., Cebu City
Telephone Number: (02) 516 7559 (Manila) E-Mail: buksmarquez1 @yahoo.com
(032) 254-9967 (Cebu)
Problem 2 Problem 3
A 12m simply supported beam is provided by an Determine the amount of reinforcement required to
additional support at midspan. The beam has a width resist a Factored Moment of 800 kN-m, if b=350 mm,
of b= 300mm and a total depthh = 450mm. It is h=600mm, effective cover of 70mm, fc’=28MPa,
reinforced with 4 – 25mm dia. at the tension side and fy=415 MPa. Use ρmax=0.75ρb, and strength
2 – 25mm dia. at the compression side with 70mm reduction factor for flexure of 0.90.
cover to centroid of reinforcements. fc’ = 30 MPa,
fy = 415 MPa. Use NSCP 2015 PROVISIONS
Problem 3
Beam section is b = 300mm, h = 450 mm. Effective
depth is 380 mm. Compressive strength of
concrete fc’ = 30 MPa, steel strength fy = 415 MPa.
The beam is simply supported on a span of 5m and
carries the following loads:
Superimposed dead load = 16 KN/m, live load = 14
KN/m.