IECEx INE 10.0008X 001

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

IECEx Certificate

of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

Certificate No.: IECEx INE 10.0008X Page 1 of 5 Certificate history:


Issue 0 (2011-01-17)
Status: Current Issue No: 1

Date of Issue: 2011-06-08

Applicant: WEG
WEGeuro Indústria Eléctrica S.A
Rua Eng Frederico Ulrich
P-4476-908 MAIA
Portugal

Equipment: Asynchronous Motor type W22X C 315...

Optional accessory:

Type of Protection: d, e and tD

Marking: Ex d IIC T4 or Ex d e IIC T4


and Ex tD A21 IP 6X T125 °C or T135 °C

Approved for issue on behalf of the IECEx Thierry HOUEIX


Certification Body:

Position: Ex Certification Officer

Signature:
(for printed version)

Date:

1. This certificate and schedule may only be reproduced in full.


2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting www.iecex.com or use of this QR Code.

Certificate issued by:


INERIS
Institut National de l'Environnement Industriel
et des Risques
BP n2
Parc Technologique ALATA
F-60550 Verneuil-En-Halatte
France
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 10.0008X Page 2 of 5

Date of issue: 2011-06-08 Issue No: 1

Manufacturer: WEGeuro Indústria Eléctrica S.A


Rua Eng Frederico Ulrich
P-4476-908 MAIA
Portugal

Additional
manufacturing
locations:

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended

STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards

IEC 60079-0:2004 Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
Edition:4.0

IEC 60079-1:2003 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:5

IEC 60079-7:2001 Electrical apparatus for explosive gas atmospheres - Part 7: Increased safety 'e'
Edition:3

IEC 61241-0:2004 Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
Edition:1

IEC 61241-1:2004 Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
Edition:1

This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.

TEST & ASSESSMENT REPORTS:


A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in:

Test Reports:
FR/INE/ExTR10.0013/00 FR/INE/ExTR10.0013/01

Quality Assessment Report:


GB/BAS/QAR07.0032/01
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 10.0008X Page 3 of 5

Date of issue: 2011-06-08 Issue No: 1

EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:

Three-phase asynchronous motor with frame and endshieds in cast iron or steel.
A primary junction box protected by flameproof enclosure or by increased safety, in cast iron or steel is mounted on the
housing. As a variation, one or more auxiliary boxes protected by flameproof enclosure or by increased safety, can be
mounted on the motor. These boxes don’t communicate with the motor. As a variation, the connection can be made of a
unterminated cable.
The motor may be designed with one up to four speeds.
Mounting position of motor can be either horizontal or vertical.Cooling types can be IC 411, IC 416 or IC 418 (motor in an air
flow), according to IEC 60034-6.Terminal boxes can be mounted on top or left/right side.Temperature sensors may be
incorporated in the stator windings and/or in the bearings.
The motor may be supplied through a frequency inverter. In this case, it is fitted with temperature sensors.
These sensors should be connected to a device that shuts off power to the motor so that the maximum indicated surface
temperature is never reached.Heating resistances may be located in the winding.
A drain and breathing device can be mounted.
The degree of protection of enclosures and junction boxes is IP55 or IP56 or IP65 or IP66 according to IEC 60 034 - Part 5
and IEC 60 529.The motor and/or terminal boxes can be fitted with differents components. All components are stipulated on
the descriptive documents.

SPECIFIC CONDITIONS OF USE: YES as shown below:


The yield stress of the fastener elements of the flameproof casing must be equal to class 12.9 or stainless steel A2-70 or
A4-80.
The gap and diametrical clearances are less than the values specified in the table 2 of the standard IEC 60079-1.
The other special conditions are stipulated on the instructions.
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 10.0008X Page 4 of 5

Date of issue: 2011-06-08 Issue No: 1

DETAILS OF CERTIFICATE CHANGES (for issues 1 and above)


Issue 1:

Introduce of adapters between the motor and the terminal boxes protected by flameproof enclosure "d" or increased safety "e".
Update of the manufacturer's documents
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 10.0008X Page 5 of 5

Date of issue: 2011-06-08 Issue No: 1

Additional information:
PARAMETERS RELATING TO THE SAFETY
Maximum supply voltages:
1100/50Hz (Low voltage) or 6600/50Hz (Medium voltage).
1100V/60Hz (Low voltage) or 6600V/60Hz (Medium voltage).
Maximum frequencies:
Without frequency inverter : 50 Hz or 60 Hz.
With frequency inverter : from 1Hz to 300 Hz.
Maximum powers:
Standard version, service S1 :
from 75kW to 250kW under Low voltage.
from 90kW to 132kW under Medium voltage.
For special versions the different parameters can be adapted.
Maximum operating thresholds of the temperature sensors :
For the winding : 155°C ± 5°C
For the bearing : 120°C ± 5°C

Annex:

IECEx INE 10.0008X_01_Annex.pdf


IECEx Certificate
of Conformity
Certificate No.: IECEx INE 10.0008X
Date of Issue: 2011-06-08 Issue No.: 1

Annexe: IECEx INE 10.0008X_01_Annex.pdf Page 1 of 2

MARKING
Marking has to be readable and indelible; it has to include the following indications:
• WEGeuro Indústria Eléctrica S.A
• Rua Eng Frederico Ulrich
• P– 4476-908 MAIA (Portugal)
• W22XC 315.... (*)
• IECEx INE 10.0008X
• (Serial number)
• (Year of construction)
• Ex d IIC T4 or Ex d e IIC T4
• Ex tD A21 IP 6X T125°C or T135°C
• Tamb : (**)
• T.cable : (***)
• WARNINGS:
• DO NOT OPEN THE COVER WHEN ENERGIZED
• DO NOT OPEN WHEN ENERGIZED IF AN EXPLOSIVE ATMOSPHERE MAY BE
PRESENT.
When the terminal is protected by increased safety :
On the terminal box : the symbol “e” (rated voltage and rated current and/or rated power)
(*) The points are replaced by letter and/or number according to the manufacturing variations.
The different types are indicated on the descriptive documents.
(**) Obligatory mention when the range of the ambient temperatures differs from –20°C to 40°C : -
55ºC/+40ºC or -55ºC/+50ºC or -55ºC/+60ºC or -30ºC/+40ºC or -30ºC/+50ºC or
-30ºC/+60ºC or -20ºC/+50ºC or -20ºC/+60ºC.
(***) See table below:
Ambient
Cable temperature
temperature
40°C NC
50°C 90°C
60°C 100°C
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 10.0008X
Date of Issue: 2011-06-08 Issue No.: 1

Annexe: IECEx INE 10.0008X_01_Annex.pdf Page 2 of 2

ROUTINE EXAMINATIONS AND TESTS


In accordance with clause 16.1 of IEC 60079-1 standard, each sample of the equipment defined
above must have successfully passed before delivery, an overpressure test, of a period comprised
between 10 and 60 secondes, carried out on each flameproof compartment under a pressure of :

Overpressure values
Type of enclosure
Up to -20°C Up to -30°C Up to -40°C Up to -55°C

Motor enclosure 18.8 bar 25.7 bar 27.2 bar 29.6 bar

Junction boxes type CEFGH 220 17.1 bar 18 bar 18 bar 18 bar

Junction boxes type CEFGH 340 14.4 bar 19.7 bar 20.9 bar 22.8 bar

Junction boxes type CEFGH 500 12.2 bar 16.6 bar 17.6 bar 19.2 bar

Junction boxes type CG 47 16.5 bar 22.6 bar 23.9 bar 26.1 bar

Spherical adapter “Ex d” 14.7 bar 19.2 bar 19.2 bar 19.2 bar

In accordance with clause 7.2 of the IEC 60079-7 standard, each sample of the terminal boxes
protected by increased safety defined above must have successfully passed before delivery a test
of dielectric strength on each of the different circuits of the connection units, performed according to
the relevant standards .