INTRODUCTION TO BOILER & BPR

CONTROL SYSTEM AND INSTRUMENT


SANMAX INDUSTRIES

WATER TUBE BOILER

• A high pressure water tube boiler is a type of boiler in which


water circulates in tubes heated externally by the fire.
• Fuel is burned inside the furnace, creating hot gas which boils
water in the steam-generating tubes.
2
SANMAX INDUSTRIES

1- BOILER CONTROL SYSTEM


Boiler control system consist of :-
1- Boiler Water Level Control
1.1- Water Level Control ( 3 Element / Single-element)

2- Boiler Combustion Control


2.1- Induced Draught Fan (ID fan)
2.2- Force Draught Fan (FD fan)
2.3- Fuel Feeding gate control by pneumatic
2.4- Auger control by inverter
2.5- Force Draught damper control
2.6- Induced Draught damper control

3
SANMAX INDUSTRIES

BOILER CONTROL PANEL

4
SANMAX INDUSTRIES

BOILER CONTROL PANEL


Water level
Indicator

Water Level Controller Inlet Draft gauge

Chart Recorder
Outlet Draft gauge

Furnace Draft gauge


Pressure, FD and ID
damper controller
5
SANMAX INDUSTRIES

WATER LEVEL CONTROL METHOD


• Single Element
o Instrument
i. Water Level
• Three Element
o Instrument
i. Water Level
ii. Water Flow
iii. Steam Flow Single-Element Controller

Three-Element Controller

6
SANMAX INDUSTRIES

WATER LEVEL CONTROL METHOD

• 3 element control Method


i. Water Level
ii. Water Flow
iii. Steam Flow
7
SANMAX INDUSTRIES

Water level control method

• Single Element Method


i. Water Level
8
SANMAX INDUSTRIES

WATER LEVEL PANEL INDICATOR


High Water Level • Indicates the boiler water
level from controller and
Mobrey
• Extra low level indicator
Normal Water triggered by Mobrey or
Level water level controller
( Depends boiler maker)
Low Water Level but we suggest triggered
by mobrey to avoid false
reading of instrument
Extra Low Water
Level (MOBREY)

9
SANMAX INDUSTRIES

BOILER PRESSURE FD,ID PANEL CONTROLLER


• Indicates boiler
Boiler Pressure pressure
• Control FD damper
FD opening percentage opening and closing
Proportional

FD Manual Regulator
Auto/Manual switch

Band

10
SANMAX INDUSTRIES

COMBUSTION FLOW
SANMAX INDUSTRIES

FORCED DRAFT DAMPER (FD)


• FD damper is used
to control the air
flow going inside
the boiler

12
SANMAX INDUSTRIES

BOILER PRESSURE PANEL LOADING

ID Opening • ID damper
percentage
(Auto) control
ID Opening
indicator
percentage
(Manual) • Auto Manual
switch
ID opening or • ID damper
closing
regulator
Pressure bias
ID bias
Opening

13
SANMAX INDUSTRIES

INDUCED DRAFT DAMPER (ID)


• ID damper is used to
control the air flow
going outside the
boiler

14
SANMAX INDUSTRIES

BOILER PRESSURE FEEDING GATE


CONTROL SWITCH
• Feeding gate control
signal is dependant
on FD percentage
Pressure opening
switch
Feeding • The pressure is
Gate 1
being set by the
pressure switch
located at the back
Pressure
switch
of panel
Feeding
Gate 2
15
SANMAX INDUSTRIES

BOILER INSTRUMENTS
1. Mobrey water level switch
2. Water Level transmitter
3. Boiler Pressure transmitter
4. Feed Water Control Valve
5. Water Flow transmitter
6. Steam Flow transmitter
7. Water Inlet Temperature transmitter
8. Steam Temperature transmitter
9. Flue Gas Temperature transmitter
10. Furnace Draft gauge
11. Inlet Draft gauge
12. Outlet Draft gauge
13. Paper/Paperless Chart Recorder
14. Smoke Density Meter
15. MC43 ( Pneumatic Panel Controller)

16
SANMAX INDUSTRIES

Basic Instrumentation signal


• Power supply (24VDC)
• Transmitter
i. 4-20mA output
Power supply
• Controller Transmitter
i. 4-20mA input
ii. 1-5V input
• Control valve
i. 4-20mA input
Controller
Control Valve
17
SANMAX INDUSTRIES

MOBREY FLOAT SWITCH

Type of Sensor : Contact Signal


Source Of input : 240VAC/24VDC

18
SANMAX INDUSTRIES

Type of Transmitter
• Differential Pressure Transmitter
i. Water level
ii. Water flow
iii. Steam flow

Unit : mmh20

19
SANMAX INDUSTRIES

Type of Transmitter
• Pressure Transmitter
• Unit : Barg/Psig

20
SANMAX INDUSTRIES

Control valve
• Feed Water Control
Valve
• Control the feed
water into the boiler

21
SANMAX INDUSTRIES

Type of Transmitter
• Temperature Transmitter
i. Water inlet Temperature
ii. Steam Temperature
iii. Flue gas Temperature
• Unit : Deg c

22
SANMAX INDUSTRIES

Basic Transmitter signal wiring


diagram
• Signal • Signal
o 4-20mA o 1-5V

4-20mA Output 4-20mA Output

4-20mA input 1-5V input

23
SANMAX INDUSTRIES

Basic Control Valve wiring diagram


• Signal 4-20mA Input

o 4-20mA
4-20mA Output

Control Valve

24
SANMAX INDUSTRIES

Instrument placement
• Water level
mmH20

Low High
25
SANMAX INDUSTRIES

INSTRUMENT PLACEMENT
• Water flow
• Steam flow

Orifice plate

High Low SANMAX ENGINEERING 26


SANMAX INDUSTRIES

MAKE UP VALVE
LIST OF INSTRUMENTS
1- BPR Pressure Transmitter
2- Boiler Pressure Transmitter

Operation :-
1- Make up valve will operated when BPR less then setpoint and boiler
more then setpoint

2- Followed by the FGV Mill current situation,Sterilizer process will


integrated with make up valve meaning,when sterilizer in a “drain “
mode make up valve doest work.

3-Normally we set the maximum opening for make up valve is ( 30 –


50%) to prevent high steam flow

27
SANMAX INDUSTRIES

BLOW OFF VALVE (BPR)



Description :-
• Blow off valve will
operated when BPR
more then setpoint
and operated in PID
mode.

28
SANMAX INDUSTRIES

SETTING OF BLOWOFF VALVE

29
SANMAX INDUSTRIES

• Q & A SECTION