Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 5

Technical Particular and Guarantee

TPG OPTICAL GROUNDWIRES (OPGW) AND ACCESSORIES OPGW 60 mm2

NO. DESCRIPTION UNIT REQUIRED GUARANTEE

1. Properties of OPGW as Groundwire


Manufacturer To Be Mentioned
Standard :
- Optical Fibre IEC 60793, IEC 60794, ITU-T G.652D
- Aluminium clad steel (AS) wire IEC 61232
- Aluminium Alloy wire IEC 60104
No. of different coloured fiber Core 24
No. of buffer tube To Be Mentioned
Construction
- Al alloy wire. Nos To Be Mentioned
- Aluminum clad steel (AS) wire Nos To Be Mentioned
- Fiber Optic metalic tube Nos To Be Mentioned
aluminium tube or aluminium coated or
( metalic tube )
stainless-steel tube
Overall diameter (approximatelly) mm To Be Mentioned
Cross Section Area :
- AS Wire (approximatelly) mm² To Be Mentioned
- Hard drawn Aluminium or Alumunium
mm² To Be Mentioned
Alloy Wire
Nominal weight (max) kg/km To Be Mentioned
Modules of elasticity N/mm² To Be Mentioned
Coefficient of linear expansion x 10-6/°C To Be Mentioned
Rated tensile strength (min) kN 77.8
Ultimate tensile strength (min) kN To Be Mentioned
Maximum tension stress N/mm² To Be Mentioned

T/L 150 KV KOLONEDALE – TENTENA (SECTION 2) PT PLN (Persero) UIP SULAWESI


1
Technical Particular and Guarantee

TPG OPTICAL GROUNDWIRES (OPGW) AND ACCESSORIES OPGW 60 mm2

NO. DESCRIPTION UNIT REQUIRED GUARANTEE

Everyday stress N/mm² To Be Mentioned


Permanent tensile stress N/mm² To Be Mentioned
Max. allowable temperature :
- Continuous °C To Be Mentioned
- For one sec. °C To Be Mentioned
D.C. resistance at 20° C (max) Ohm/km To Be Mentioned
- Mean sub-span with spacer/dampers m To Be Mentioned
- Number of Vibration dampers per span :
* Span up to 400 metres pcs 2
* Span over to 400 metress pcs 4
Short circuit current capacity (min.) kA² - sec. 9.68
2. Component Wire
Appropriate standard IEC 61232
Manufacturer name To Be Mentioned
Material To Be Mentioned
Nominal diameter mm To Be Mentioned
Min. Breaking strength N/ mm² To Be Mentioned
Nominal Weight kg/ km To Be Mentioned
Max. D.C Resistance at 20°C ohm/ km To Be Mentioned
Calculated cross section area mm² To Be Mentioned
Permissible variations in
- Specified % To Be Mentioned
- Diameter mm To Be Mentioned
Minimum Tickness of Aluminium mm To Be Mentioned
Number of Twist ( min ) Nos To Be Mentioned
Stress at 1 % elongation N/ mm² To Be Mentioned

T/L 150 KV KOLONEDALE – TENTENA (SECTION 2) PT PLN (Persero) UIP SULAWESI


2
Technical Particular and Guarantee

TPG OPTICAL GROUNDWIRES (OPGW) AND ACCESSORIES OPGW 60 mm2

NO. DESCRIPTION UNIT REQUIRED GUARANTEE

3. Construction and Properties of SPLN S3.002-1 2013


Optical Fibre ITU-T G.652D
Mode Field Diameter at 1310 μm μm 9.3 ± 0.5
Cladding diameter μm 125 ±1,0
Mode field concentricity error μm 0.8
Cladding Non-circularity % 1.0
Cable cut off wavelength nm ≤ 1260
Attenuation at 1310 nm dB/ km 0.34
Attenuation at 1383 nm dB/ km 0.31
Attenuation at 1550 nm dB/ km 0.21
Attenuation at 1625 nm dB/ km 0.24
Chromatic dispersion at 1310 nm ps/(nm.km) 3.5
Chromatic dispersion at 1550 nm ps/(nm.km) Max 18
Chromatic dispersion at 1530 ~1565 nm ps/(nm.km) NA
Chromatic dispersion at 1565 ~1625 nm ps/(nm.km) 22
Primary coating UV Arcrylate
Nominal coating diameter mm 245 ± 5
Zero dispersion wavelengths nm 1302 -1322
Polarization Mode Dispersion (PMD) ps/ km½ 0.1
Zero Dispersion Slope ps/nm².km 0.090

T/L 150 KV KOLONEDALE – TENTENA (SECTION 2) PT PLN (Persero) UIP SULAWESI


3
Technical Particular and Guarantee

TPG OPTICAL GROUNDWIRES (OPGW) AND ACCESSORIES OPGW 60 mm2

NO. DESCRIPTION UNIT REQUIRED GUARANTEE

4. Joint Boxes, Gantry Boxes


4.1 Joint Box, 24 Core
Manufacturer - To Be Mentioned
Type - To Be Mentioned
Material - Aluminium/Polycarbonate
Index Protection Level - IP 65
Capacity
Number of cable unit To Be Mentioned
Hole Input for OPGW hole Min. 3
Cable diameter (max) mm To Be Mentioned
Number of Splice Tray unit To Be Mentioned
Number of Splice per Tray unit To Be Mentioned
Dimensional
- Height mm To Be Mentioned
- Widht mm To Be Mentioned
- Depth mm To Be Mentioned
- Total Weight kg To Be Mentioned
Permisible Temperature Range
- Transportation °C -40 to +70
- Storage °C -40 to +70
- Operation °C -40 to +70

Relative Humidity % 90

Relative Humidity % 90

T/L 150 KV KOLONEDALE – TENTENA (SECTION 2) PT PLN (Persero) UIP SULAWESI


4
Technical Particular and Guarantee

TPG OPTICAL GROUNDWIRES (OPGW) AND ACCESSORIES OPGW 60 mm2

NO. DESCRIPTION UNIT REQUIRED GUARANTEE

4. Joint Boxes, Gantry Boxes


4.2 Gantry Box, 24 Core
Manufacturer - To Be Mentioned
Type - To Be Mentioned
Material - Stainless Steel
Index Protection Level - IP 65
Capacity
Number of cable unit To Be Mentioned
Cable diameter (max) mm To Be Mentioned
Number of Splice Tray unit To Be Mentioned
Number of Splice per Tray unit To Be Mentioned
Dimensional
- Height mm To Be Mentioned
- Widht - mm To Be Mentioned
- Depth - mm To Be Mentioned
- Total Weight kg To Be Mentioned
Permisible Temperature Range
- Transportation °C -40 to +70
- Storage - °C -40 to +70
- Operation °C -40 to +70

Relative Humidity % 90

T/L 150 KV KOLONEDALE – TENTENA (SECTION 2) PT PLN (Persero) UIP SULAWESI


5