Professional Documents
Culture Documents
Automatic Voltage Control Research Book RETRAY
Automatic Voltage Control Research Book RETRAY
Master of Engineering
Submitted by
2022
Reactive Power and Voltage Control of Power
System Using Different Control Techniques
A Thesis
Submitted in partial fulfilment of the requirement for the degree
Master of Engineering
Department of Electrical Engineering
Assiut University, Egypt 2022
Submitted by
2022
Acknowledgement
Acknowledgement
i
Abstract
Abstract
It is well known that the electrical generated power can be controlled by the
mechanical power of prime mover. Opening or closing the steam or water valve
can control the mechanical power or hydraulic turbines. The power system has
two essential control systems, namely, reactive-voltage control loop, and power-
frequency control loop.
The present research has concentrated on the problems of establishing a
normal operating state and optimum scheduling of generation for a power
system and deals with the control of reactive powers in order to keep the system
in the steady-state condition. The objective of the voltage control system is to
generate power in an interconnected system as economically and reliably as
possible, while maintaining the voltage within permissible limits.
An increase in the reactive power load of the generator is accompanied by a
drop in the terminal voltage magnitude. The voltage magnitude is sensed
through a potential transformer on one phase. This voltage is rectified and
compared to a dc set point signal. The amplified error signal controls the exciter
field and increases the exciter terminal voltage. Thus, the generator field current
is increased, which results in an increase in the generated emf. The reactive
power generation is increased to a new equilibrium, raising the terminal voltage
to the desired value. The role of automatic generation control (AGC) in power
system operation, with reference to tie-line power control under normal
operating conditions, is first analyzed. Finally, the requirement of reactive
power and voltage regulation and the influence on stability of both speed and
excitation controls, with use of suitable feedback signals, are examined.
The above description and modeling have been performed for single voltage
control system. The conventional Proportional, Integral, and Derivative (PID)
controller is designed for establishing feedback load frequency control system.
The parameters of the PID controller are determined inside stability range of
power system.
ii
List of Content
List of Contents
Subject Page
Chapter 1: Introduction 1
1.1 Introduction 1
1.2 Reactive Power Sources and Their Control Devices 2
1.3 Methods of Voltage Controls 2
1.4 Overview on Different Voltage and Reactive Power Control 2
1.5 Automatic Voltage Regulator (AVR) 4
1.6 Working Principle of Voltage Regulator 4
1.7 Application of the Automatic Voltage Regulator 4
1.8 Objectives of Power System Operation and Control 5
1.9 Thesis Organization 5
Chapter 2: Description and Modeling of Voltage Control Systems 6
2.1 Introduction 6
2.2 Basic Generator Control Loops 6
2.3 Objective of Power System Control 7
2.4 Means of Power System Control 8
2.5 Role of Control in Power System 8
2.6 Controllers and System Transfer Functions 8
2.6.1 RC Controllers 9
2.6.2 Electronic Controllers 11
2.7 Reactive Power and Voltage Control Modeling 14
2.7.1 Amplifier Model 15
2.7.2 Exciter Model 15
2.7.3 Generator Model 16
2.7.4 Sensor Model 16
2.8 Voltage Control System without Controller 17
2.8.1 Transfer Function of Voltage Control System without Controller 17
2.8.2 State Space Model of Voltage Control System without Controller 17
Chapter 3: Voltage Control of Power System using PID Controller 18
3.1 Introduction 18
iii
List of Content
iv
List of Content
v
List of Tables
List of Tables
Table
Title page
No.
3.1 Characteristics of proportional, integral and derivative controllers 22
System poles and specifications due to a variation in the gain KA
3.2 44
between KA = 5 and 15 (without controller).
System poles and specifications due to a variation in the time constant
3.3 45
TA between TA = 0.02 and 0.50 sec (without controller).
System poles and specifications due to a variation in the gain K E
3.4 46
between KE = 0.5 and 1.5 (without controller).
System poles and specifications due to a variation in the gain K R
3.5 47
between KR = 0.5 and 2.0 (without controller).
System poles and specifications due to a variation in the parameter K P
3.6 48
between KP = 0.05 and 0.4 (with PI controller).
System poles and specifications due to a variation in the parameter K I
3.7 49
between KI = 0.1 and 0.5 (with PI controller).
System poles and specifications due to a variation in the parameter K P
3.8 50
between KP = 0.5 and 2.0 (with PD controller).
System poles and specifications due to a variation in the Parameter K D
3.9 51
between KD = 0.02 and 1.0 (with PD controller).
System poles and specifications due to a variation in the parameter K P
3.10 52
between KP = 0.1 and 4.5 (with PID controller).
System poles and specifications due to a variation in the parameter K I
3.11 53
between KI = 0.5 and 10.0 (with PID controller).
System poles and specifications due to a variation in the parameter K D
3.12 54
between KD = 0.1 and 1.5 (with PID controller).
System poles and specifications due to a variation in the stabilizer gain
3.13 60
KF between KF = 0.1 and 7.0 (with stabilizer).
System poles and specifications due to a variation in the amplifier gain
3.14 61
KA between KA = 5 and 100 (with stabilizer).
System poles and specifications due to a variation in the exciter gain K E
3.15 62
between KE = 0.2 and 100 (with stabilizer).
System poles and specifications due to a variation in the generator gain
3.16 63
KG between KG = 0.5 and 10.0 (with stabilizer).
System poles and specifications due to a variation in the sensor gain K R
3.17 64
between KR = 0.5 and 2.0 (with stabilizer).
System poles and specifications due to a variation in the amplifier gain
3.18 67
KA between KA = 5 and 15 (with pole placement controller).
System poles and specifications due to a variation in the amplifier time
3.19 constant TA between TA = 0.02 and 0.5 sec (with pole placement 68
controller).
System poles and specifications due to a variation in the exciter gain K E
3.20 69
between KE = .5 and 1.5 (with pole placement controller).
System poles and specifications due to a variation in the sensor gain K R
3.21 70
between KR = .5 and 2 (with pole placement controller).
vi
List of Figures
List of Figures
vii
List of Figures
3.23 State space model terminal voltage step response with PID control 41
3.24 Block diagram of terminal voltage step response with PID controller in
41
the Simulink window
3.25 Terminal voltage step response with PID control by using MATLAB 44
viii
List of Figures
stabilizer).
3.43 System time response due to a variation in the stabilizer gain KG (with
64
stabilizer).
3.44 System time response due to a variation in the stabilizer gain KR (with
65
stabilizer).
3.45 System time response based on nominal values of the system
67
parameters (without and with stabilizer).
3.46 System time response due to a variation in the amplifier gain KA (with
68
pole placement controller).
3.47 System time response due to a variation in the amplifier time constant
69
TA (with pole placement controller).
3.48 System time response due to a variation in the exciter gain KE (with
70
pole placement controller).
3.49 System time response due to a variation in the sensor gain KR (with
71
pole placement controller).
3.50 System time response based on nominal values of the system and
71
controller parameters (without and with pole placement controller
ix
List of Abbreviations
List of Abbreviations
Abbreviation Description
AVR Automatic Voltage Regulator
AGC Automatic Generation Control
PID Proportional-Integral-Derivative
PI Proportional-Integral
PD Proportional- Derivative
PSS Power System Stabilizer
LFC Load Frequency Control
ANN Artificial Neural Network
FLC Fuzzy Logic Control
NFLC Neuro-Fuzzy Logic Control
FACTS Flexible AC Transmission Systems
PLC Programmable Logic Control
EMF Electromotive Force
FSF Full State Feedback
SISO Single Input Single Output
PPC Pole Placement Controller
RPC Reactive Power Controller
SVC Static VAR Compensator
SCR Solid-State Rectifiers
OLTC On Load Tap Changers
x
List of Symbols
Symbol Description
KA Amplifier gain
TA Amplifier time constant
KE Exciter gain
TE Exciter time constant
KG Generator gain
TG Generator time constant
KR Sensor gain
AC Closed – loop system matrix
TR Sensor time constant
Vt Output System
Vref Input System
KI Integral gain
KP proportional controller
D Damping coefficient
KD Derivative controller
KF Stabilizer gain
TF Stabilizer time constant
rotor angle
List of Symbols
xi
Chapter 1
:
Introduction
Chapter 1 Introduction
Chapter 1
Introduction
1.1 Introduction
For an electric power system, to keep constant the nominal voltage level and
to control reactive power supply to or received from power system is an
important factor of power quality, grid security and grid reliability.
Actually, the transmission line losses depend upon the amount of active and
reactive powers. Also, a reactive power interested in widely on output voltages
of the synchronous generators connected to a power system. For this reason, to
reduce the real transmission losses needs to keep reactive power equilibrium
required to control a voltage value of a power system [1].
At present, an AVR system is basically applied to synchronous generators
included by a power system so as to resolve the problem [2]. Various control
techniques like linear or nonlinear can be used to provide AVR control [3]. An
increase in a reactive power load of generator is accompanied by a drop in
terminal voltage magnitude.
1|Page
Chapter 1 Introduction
within acceptable limit and reduce the transmission losses. In the last 20 years,
this problem has attracted the interest from both academia and industry and this
has produced many special devices and algorithms. Some countries have
adopted some of these in their real power networks and achieved reasonably
successful results [2].
2|Page
Chapter 1 Introduction
distribution system within the acceptable range and to minimize power losses.
Different voltage and reactive power control methods have been proposed.
Properly locating and sizing shunt capacitors will decrease power losses. As an
improvement to the capacitor planning based on the load size, methods to
include customer load profiles and characteristics in the capacitor planning are
proposed in [5]-[6].
Proper capacitor planning will also improve the voltage profile in the
distribution system. The capacitor locating and sizing is studied and executed in
the planning stage of the distribution system. In order to enhance the
distribution system further, the capacitor should also be switched properly in the
operation stage of the distribution system [7], using different types of available
capacitor control. Most recently, many researchers have addressed the problem
of voltage and reactive power control in distribution systems by focusing on
automated distribution systems, such as in [8]-[9].
At the moment, the voltage and reactive power control based on automated
distribution systems can be divided into two categories: off-line setting control
and real time control [10]. The off-line setting control, for instance, aims to find
a dispatch schedule for the capacitor switching and the OLTC movement based
on a one day ahead load forecast. Meanwhile, the real time control, [11] for
instance, aims to control the capacitor and OLTC based on real time
measurements and experiences.
3|Page
Chapter 1 Introduction
4|Page
Chapter 1 Introduction
3. The automatic voltage regulators reduce the over voltages which occur
because of the sudden loss of load on the system.
4. It increases the excitation of the system under fault conditions so that the
maximum synchronizing power exists at the time of clearance of the fault.
5|Page
Chapter 2
:
Description and Modeling
of Voltage Control System
Chapter 2 Description and Modeling of Voltage Control System
Chapter 2
Description and Modeling of Voltage Control
System
2
2.1 Introduction
This chapter has concentrated on the problems of establishing a normal
operating state and optimum scheduling of generation for a power system and
thesis deals with the control of active and reactive powers in order to keep the
system in the steady-state condition. In addition, simple models of the essential
components used in the control systems are presented. The objective of the
control strategy is to generate and deliver power in an interconnected system as
economically and reliably as possible, while maintaining the voltage and
frequency within permissible limits [1].
Changes in real power affect mainly the system frequency, while reactive
power is less sensitive to changes in frequency and is mainly dependent on
changes in voltage magnitude. Thus, real and reactive powers are controlled
separately. The load frequency control (LFC) loop controls the real power and
frequency and the automatic voltage regulator (AVR) loop regulates the reactive
power and voltage magnitude. LFC has gained in importance with the growth of
interconnected systems and has made the operation of interconnected systems
possible. Today, it is still the basis of many advanced concepts for the control of
large systems [2].
6|Page
Chapter 2 Description and Modeling of Voltage Control System
and take care of small changes in load demand to maintain the frequency and
voltage magnitude within the specified limits. Small changes in real power are
mainly dependent on changes in rotor angle and, thus, the frequency [4].
Fig. (2.1): Generation power plant control system for voltage and frequency.
7|Page
Chapter 2 Description and Modeling of Voltage Control System
1. The generation system: consists of: fuel injectors, steam valve, steam
turbines, gas turbines, generators excitation systems, and power system
stabilizers.
2. The transmission system: consists of the stepping up transformers,
overhead and cable transmission lines, bus-bars, the circuit breakers, the
shunt reactors, shunt capacitors, series capacitors, thyristor-controlled
series capacitors, lighting arrestors, earthling conductors …. etc.
3. The utilization system: contains the distribution transformers,
distribution network, loads (lighting, heating, rotating, electrolysis,
arcing, welding ... etc.), bus bars, protection systems, control systems,
communication systems, measurement devices, …. etc .
8|Page
Chapter 2 Description and Modeling of Voltage Control System
The transfer function of a linear system is defined as the ratio of the Laplace
transform of the output variable to the Laplace transform of the input variable,
with all initial conditions assumed to be zero. The transfer function of a system
or of an element represents the relationship describing the dynamics of the
system under consideration.
2.6.1 RC Controllers
RC networks controllers may be electrical or mechanical or hydraulic or
combination of them together with some amplifiers [9].
2.6.1.1 Resistive proportional controller
A proportional transfer function of certain output/input gain is usually
represented in Laplace transform as:
v 2 (s) R 2 R2
G (s)
v1 (s) R R 1 R 2 (2.1)
A potentiometer or a sliding resistor can give such transfer function. Fig.(2.2)
shows such controller element.
9|Page
Chapter 2 Description and Modeling of Voltage Control System
to the instant of the input had entered to the system. A circuit which represents
this transfer function is shown in Fig.(2.3). This transfer function appears in
many block diagrams of controllers and systems [10]. The gain/time delay
transfer functions is represented in Laplace transform by:
K
G c (s)
1 sT (2.2)
where K represents the amplifier gain and T reprersents the output circuit time
constant.
10 | P a g e
Chapter 2 Description and Modeling of Voltage Control System
11 | P a g e
Chapter 2 Description and Modeling of Voltage Control System
1 K
G c (s) K P (1 ) KP P
TIs TI s (2.7)
where KP and TI are functions of the circuit resistances and capacitance. The
PI controller possesses a zero at s = -I /TI and a pole at s = 0. This improves the
steady state characteristics. However, inclusion of the PI control action in the
system increases the type number of the compensated system by one, and this
causes the compensated system to be more [10]. The values of Kp and TI must
be chosen carefully to give a proper transient response. By properly designing
the PI controller, it is possible to make the transient response to a step input
exhibit relatively small or no overshoot. The speed of response, however,
becomes much slower [11]. The P1 controller can be realized by two stages of
operational amplifiers as those given in Fig.(2.8). The controller transfer
function of such PI controller is derived as:
R 4 R 2 ( R 2 C 2s 1)
G c (s)
R 3R 1R 2 C 2s (2.8)
12 | P a g e
Chapter 2 Description and Modeling of Voltage Control System
G c (s) K P (1 Td s) K P K Ds (2.9)
R 4R 2
G c (s) (R C s 1)
R 3R1 1 1 (2.10)
Note that the P1 control action and PD control action occur in different
frequency regions [12]. The P1 control action occurs at the low - frequency
region and PD control action occur at the the high-frequency region.
13 | P a g e
Chapter 2 Description and Modeling of Voltage Control System
The PID control may be used when the system requires improvements in
both transient and steady-state performances. The PID controller can be realized
by two stages of operational amplifiers with shunt and series RC elements
cotmected as in Fig.(1.10). Such electronic PID controller transfer function can
be derived as follows:
E o (s) Z
2
E i (s) Z1 (2.11)
where
R1 R C s 1
Z1 , Z2 2 2
R 1C1s 1 C 2s
As we have seen, a change in the real power demand affects essentially the
frequency, whereas a change in the reactive power affects mainly the voltage
magnitude. The interaction between voltage and frequency controllers is
generally weak enough to justify their analysis separately [13].
The sources of reactive power are generators, capacitors, and reactor. The
generator reactive powers are controlled by field excitation. Other
supplementary methods of improving the voltage profile on electric
transmission systems are transformer load-tap changes, switched capacitors,
14 | P a g e
Chapter 2 Description and Modeling of Voltage Control System
step-voltage regulators, and static var control equipment. The primary means of
generator reactive power control is the generator excitation control using (AVR)
which is discussed in this chapter. The role of an (AVR) is to hold the terminal
voltage magnitude of a synchronous generator at a specified level [14].
V R (s) KA
= (2.12)
V e ( s) 1+s T A
Typical values of K A are in the range of 1 to 400. The amplifier time constant is
small, in the range of 0.01 to 0.1 second [15].
15 | P a g e
Chapter 2 Description and Modeling of Voltage Control System
V F (s ) KE
= (2.13)
V R (s) 1+ s T E
The time constants of modern exciters are in the range of 0.1 to 1.0 second [9].
V t (s) KG
= (2.14)
V F (s ) 1+ s T G
These constants are load dependent, K G may vary between 0.7 to 1, and T G
varies between 1.0 and 2.0 seconds from full-load to no-load [16].
2.7.4 Sensor Model
The voltage is sensed through a potential transformer and, it is rectified
through a bridge rectifier. The sensor is modeled by a simple first order transfer
function, given by:
V S (s) KR
=
V t ( s) 1+ s T R
(2.15)
T R is very small, and we may assume a range of 0.01 to 0.06 second [17].
Utilizing the above models results in the AVR block diagram shown in Fig.
(2.12).
16 | P a g e
Chapter 2 Description and Modeling of Voltage Control System
V t (s)
From Fig. (2.12), the transfer function V (s ) is given as follows:
ref
V t (s) K A K E K g K R (1+T R s)
= (2.16)
V ref (s ) (1+ s T A )(1+ s T E )(1+s T g)(1+ s T R )+ K A K E K g K R
x 1=
( KG
)
x
1+T G s 2
−1 KG
⇒ ẋ 1= x 1+ x (2.18)
TG TG 2
x 2=
( KE
)
x
1+T E s 3
−1 KE
⇒ ẋ 2= x 2+ x (2.20)
TE TE 3
x 3=
( KA
1+T A s )
(V ref −x 4 )
−1 KA KA
⇒ ẋ 3= x 3− x 4+ V (2.22)
TA TA T A ref
x4 =
( KR
)
x
1+T R s 1
KR 1
⇒ ẋ 4 = x 1− x 4 (2.24)
TR TR
17 | P a g e
Chapter 2 Description and Modeling of Voltage Control System
From equations (2.18) to (2.24), the state – space model of the system
without controller can be expressed by vector – matrix as follows:
[ ] [ ][ ] [ ]
1 KG
¿− 00
¿ ẋ 1 T G TG ¿ x1
¿ ¿0
−1 K E ¿
¿0
¿ ẋ 2 ¿0 0 ¿ x2
= T E TE + K V
¿ ¿ ¿ A ref (2.25)
¿ ẋ 3 1 K ¿ x3 TA
¿ 0 0− − A
¿ TA TA ¿ ¿0
¿ ẋ 4 K 1 ¿ x4
¿ R 0 0−
TR TR
18 | P a g e
Chapter 3
:
Voltage Control of Power
System Using PID
Chapter 3 Voltage Control of Power System using PID
Chapter 3
Voltage Control of Power System Using PID
3.1 Introduction
The primary purpose of using feedback with automatic controller in control
is to reduce the sensitivity of the system to parameter variation and unwanted
disturbances. An automatic controller compares the actual value of the plant
output with the desired value, determines of the deviation and produces control
signal which will reduce the deviation to zero or to small value. So that, it is
decided in this chapter to study the effect of PID and pole placement controllers
on voltage control system. Hence, studying the stability of the system and
calculating the range of the parameters of the different types of controllers for
the system to be stable [1].
The term PID stands for proportional integral derivative and it is one kind of
device used to control different process variables like pressure, flow,
temperature, and speed in industrial applications. In this controller, a control
loop feedback device is used to regulate all the process variables [2].
This type of control is used to drive a system in the direction of an objective
location otherwise level. It is almost everywhere for temperature control and
used in scientific processes, automation & myriad chemical. In this controller,
Closed-loop feedback is used to maintain the real output from a method like
close to the objective otherwise output at the fixe point if possible. In this
article, the PID controller design with control modes used in them like P, I & D
are discussed [3].
19 | P a g e
Chapter 3 Voltage Control of Power System using PID
and rate of change to keep the ship on course. Controllers with electrical
systems were developed after World War II [4].
20 | P a g e
Chapter 3 Voltage Control of Power System using PID
One of the advantages of PID is that for many processes there are
straightforward correlations between the process responses and the use and
tuning of the three terms (P, I, and D) by the controller. Designing a PID system
involves two steps. First, the engineer must choose the structure of the PID
controller, for example P only, P and I, or all three terms P, I, and D. Second, to
tune the controller, the engineer must choose numerical values for the PID
parameters [8].
These three parameters for the PID algorithm are the proportional, integral,
and derivative constants. The proportional constant determines the reaction
based on the current error; the integral constant determines the reaction
according to the total of recent errors; and the derivative constant determines the
reaction using the rate at which the errors have been changing. These three
actions are then used to adjust the process through control elements such as the
position of a valve. In simple terms, P depends on the current error, I depend on
the sum of past errors, and D predicts future errors based on the current rate of
change of errors [9].
PID controller maintains the output such that there is zero error between the
process variable and set point/ desired output by closed-loop operations. PID
uses three basic control behaviors that are explained below.
3
3.1
3.2
3.3
3.4
3.4.1 P-Controller
Proportional or P- controller gives an output that is proportional to current
error e(t). It compares the desired or set point with the actual value or feedback
process value. The resulting error is multiplied with a proportional constant to
get the output. If the error value is zero, then this controller output is zero [10].
3.4.2 I-Controller
Due to the limitation of p-controller where there always exists an offset
between the process variable and setpoint, I-controller is needed, which
provides necessary action to eliminate the steady-state error. It integrates the
21 | P a g e
Chapter 3 Voltage Control of Power System using PID
error over a period of time until the error value reaches zero. It holds the value
to the final control device at which error becomes zero.
Integral control decreases its output when a negative error takes place. It
limits the speed of response and affects the stability of the system. The speed of
the response is increased by decreasing integral gain, Ki [11].
In the above figure, as the gain of the I-controller decreases, the steady-state
error also goes on decreasing. For most of the cases, the PI controller is used
particularly where the high-speed response is not required. While using the PI
controller, I-controller output is limited to somewhat range to overcome the
integral wind-up conditions where the integral output goes on increasing even at
zero error state, due to nonlinearities in the plant [12].
3.4.3 D-Controller
I-controller doesn’t have the capability to predict the future behavior of
error. So, it reacts normally once the setpoint is changed. D-controller
overcomes this problem by anticipating the future behavior of the error. Its
output depends on the rate of change of error with respect to time, multiplied by
derivative constant. It gives the kick start for the output thereby increasing
system response [12].
22 | P a g e
Chapter 3 Voltage Control of Power System using PID
A proportional controller (KP) will have the effect of reducing the rise time
and will reduce but never eliminate the steady-state error. An integral control
(KI) will have the effect of eliminating the steady-state error, but it may make
the transient response worse. A derivative control (KD) will have the effect of,
reducing the overshoot, and improving the transient response [8].
Effects of each of controllers KP, KI, and KD on a closed-loop system are
summarized in the Table (3.1).
Table (3.1): Characteristics of Proportional, Integral and Derivative controllers
Closed-loop Settling
Rise Time Overshoot Steady-state Error
Response Time
Small
KP Decrease Increase Decrease
change
Small
KD Decrease Decrease Small change
change
t
uc (t)=K P e (t)+ K I ∫ e( t) dt (3.1)
0
U c (s ) KI K p s + KI
=K P + = (3.2)
E(s) s s
23 | P a g e
Chapter 3 Voltage Control of Power System using PID
where: KP is the proportional gain and KI is the integral gain. Then, the block
diagram of PI controller can be represented as shown in Fig. (3.2).
Adding the block of the PI controller into the block diagram of AVR, the
resultant block diagram of the system is shown in Fig. (3.3)
3.5
3.6
3.6.1 Transfer Function of Voltage Control System with PI Controller
The transfer function between the output Vt (s) and the input Vref (s) of the
voltage control system with PI controller is obtained from Fig. (3.3) as:
V t (s) K A K E K G (K p s + K I )
= (3.3)
V ref (s ) s(1+ s T A )(1+ s T E)(1+ s T G )(1+s T R)+ K A K E K G K R (K p s + K I )
24 | P a g e
Chapter 3 Voltage Control of Power System using PID
KG
x 1= x
1+ s T G 2
−1 K
⇒ ẋ 1= x 1+ G x2 (3.4)
TG TG
KE
x 2=
1+ s T E x ¿
3
¿
−1 K KA
⇒ ẋ 2= x 2+ E x 3 (3.5) x 3= x
TE TE 1+ s T A 5
−1 K
⇒ ẋ 3= x3 + A x5 (3.6)
TA TA
KR
x4 = x
1+ S T R 1
KR 1
⇒ ẋ 4 = x 1− x 4 (3.7)
TR TR
KI
x 5=( K P + )(V ref −⥂ x 4)
s
−K P K R KP
⇒ ẋ 5= x 1 +( −K I )x 4+ K I V ref (3.8)
TR TR
From equations (3.4) to (3.8), the system state space model can be expressed
in vector – matrix as follows:
[ ][ [] ] [ ]
−1 KG
0 0 0
. TG TG
x ¿1 ¿0
ẋ ¿1 −1 KE
¿ 0 0 0
¿
¿
TE TE ¿ x2 ¿0
ẋ ¿2
¿ ¿
¿
−1 KA
ẋ ¿3 = 0 0 0 ¿ x3 ⥂ + ¿ 0 V ref (3.9)
¿ TA TA ¿ ¿
¿ ẋ ¿ 4 KR −1 ¿ x4 ¿0
¿ 0 0 0 ¿ ¿
¿ ẋ ¿5 TR TR
¿ x5 KI
¿
−K P K R KP
0 0 −K I 0
TR TR
25 | P a g e
Chapter 3 Voltage Control of Power System using PID
where:
KP is the proportional gain and KD is the integral gain.
Then, the block diagram of PD controller is represented as in Fig. (3.4).
Adding the block diagram of the PD controller into the block diagram of
AVR, the resultant block diagram of the system is shown in Fig. (3.5).
26 | P a g e
Chapter 3 Voltage Control of Power System using PID
V t (s) K A K E K G (K p + K D s)
= (3.12)
V ref (s ) (1+ s T A )(1+ s T E )(1+s T G )(1+ s T R )+ K A K E K G K R ( K p + K D s )
KG
x 1= x
1+ s T G 2
−1 KG
⇒ ẋ 1= x 1+ x (3.13)
TG TG 2
KE
x 2= x
1+ s T E 3
−1 K
⇒ ẋ 2= x 2+ E x 3 (3.14)
TE TE
KA
x 3= V
1+ s T A ref
−1 K
∴ ẋ3 = x 3 + A V ref (3.15)
TA TA
⇒ ẋ 3=
[ −K A K R K D
T ATR
x 1−
1
TA
x3 +
K A KD
(
T A TR
−K P ) x 4 +
KP KA
TA
V ref
]
KR
x4 = x
1+ s T R 1
KR 1
ẋ 4 = x− x
T R 1 TR 4
(3.16)
27 | P a g e
Chapter 3 Voltage Control of Power System using PID
[ ][ ][ ] [ ]
−1 KG
0 0 ¿0
¿ ẋ1 TG TG ¿ x1 ¿
¿ −1 KE ¿ ¿ 0
¿ ẋ2 0 0 ¿ x2
TE TE ¿
¿ = ¿ + K P K A V ref (3.17)
−K A K D K R −1 KA KD
¿ ẋ3 0 ( −K P) ¿ x 3 ¿ T
¿ T ATR TA TA TR ¿ A
ẋ 4 KR x4 ¿
−1 0
0 0
TR TR
t
de(t )
uc (t)=K PI e (t)+ K D + K I ∫ e(t )dt (3.18)
dt 0
U c (S ) K
=K PI + K D s+ I (3.19)
E(S) s
Adding the block of the PID controller into the block diagram of AVR, the
resultant block diagram of system is shown in Fig. (3.7).
28 | P a g e
Chapter 3 Voltage Control of Power System using PID
3.7
3.7.1 Transfer Function of Voltage Control System with PID Controller
The transfer function between the outputV t (s) and the inputV ref ( s) of the
voltage control system with PID controller is obtained from Fig. (3.15) as:
2
V t (s) K A K E K G (K D s + K I s+ K I )(1+s T R )
= (3.20)
V ref 2
s (1+s T A )(1+ s T E )(1+s T G )(1+ s T R )+ K A K E K G K R (K D s + K P s+ K I )
3.7.2 State Space Model of Voltage Control System with PID Controller
29 | P a g e
Chapter 3 Voltage Control of Power System using PID
From the block diagram of Fig. (3.7), the state space model can be obtained as
follows:
x 1=
( KG
)
x
1+T G s 2
(3.21)
−1 KG KE
⇒ ẋ 1= x 1+ x (3.22) x 2= x
TG TG 2 1+ s T E 3
−1 KE KA
⇒ ẋ 2= x 2+ x (3.23) x 3= x
TE TE 3 1+ s T A 5
−1 KA
⇒ ẋ 3= x3+ x (3.24)
TA TA 5
KR
x4 = x
1+ s T R 1
KR 1
ẋ 4 = x 1− x 4 (3.25)
TR TR
(
x 5= K P +
KI
s )
+ K D s (V ref −x 4 )
⇒˙ x 5=¿ (3.26)
From equations (3.21) to (3.26), the state space model of the system can be
obtained as follows:
30 | P a g e
Chapter 3 Voltage Control of Power System using PID
The pole placement technique is based upon an idea that closed loop
automatic flight control systems' pre- defined dynamic performances can be
ensured by appropriate selection of the closed loop poles, in other words, by
selection of the state feedback gain matrix, say, K.
Pole placement approach of controller design is capable of providing system
stability, setpoint tracking and disturbance rejection. The proposed work
focuses on design of a digital controller using pole placement method for
magnetic suspension ball system which is an open loop unstable system.
Closed-loop pole locations have a direct impact on time response characteristics
such as rise time, settling time, and transient oscillations. Root locus uses
compensator gains to move closed-loop poles to achieve design specifications
for SISO systems [17].
(3.27)
Now, consider the block diagram of the system shown in Fig. (2.1), with the
31 | P a g e
Chapter 3 Voltage Control of Power System using PID
Substituting from equation (3.28) into equation (3.27), the compensated system
state –variable representation becomes:
Where
A c A B K = closed-loop matrix.
The compensated system characteristic equation is:
|sI – AC | = 0 (3.30)
The function [K, Ac] = place (A, B, P) is developed for the pole placement
design, where A, B are system matrices and P is a row vector containing the
desired closed – loop poles. This function returns the gain vector K and the
closed – loop system matrix AC.
The block diagram of voltage control power system with pole placement
controller is constructed as shown in Fig. (3.8).
Fig. (3.8): Voltage control power system with pole placement controller.
32 | P a g e
Chapter 3 Voltage Control of Power System using PID
3.9
3.9.1 Stability Issues and the PSS
Traditionally the excitation system regulates the generated voltage and there
by helps control the system voltage .The automatic voltage regulators (AVR)
are found extremely suitable winding for the regulation of generated voltage
through excitation control .But extensive use of AVR has detrimental effect on
the dynamic stability or steady state stability of the power system as oscillations
of low frequencies (typically in the range of 0.2 to 3 Hz) persist in the power
system for a long period and sometimes affect the power transfer capabilities of
the system [20] .
The power system stabilizers (PSS) were developed to aid in damping these
oscillations by modulation of excitation system and by this supplement stability
to the system.
The basic operation of PSS is to apply a signal to the excitation system that
creates damping torque which is in phase with the rotor oscillations.
The generator voltage is controlled by excitation systems or automatic voltage
regulators (AVR) with input reference voltage signal [21].
Generator field voltage (and current) value controls the generator terminal
voltage and consequently the network and load voltages. It may be supplied by
exciters. Exciters consist of either dc generator driven by a motor or by the shaft
of the turbine-generator or by rectifiers or thyristor units. The complete voltage
control system, including an error detector and various feedback loops, is
33 | P a g e
Chapter 3 Voltage Control of Power System using PID
The closed – loop transfer function of the system between the output
terminal voltage Vt (s) and the input reference voltage Vref (s) is obtained from
Fig. (3.9) as:
K A K E K G K R (1 sTF )
G (s) H(s)
(1 sTR )(1 sTG ) [(1 sTA )(1 sTE )(1 sTF ) s K A K E K F ]
(3.31)
x 1=
( KG
)x
1+T G s 2
1 K
x 1 x1 G x 2
TG TG (3.32)
34 | P a g e
Chapter 3 Voltage Control of Power System using PID
KE
x2 x
1 sTE 3
1 K
x 2 x 2 E x3
TE TE
KA
x3 V x 4 x 5
1 sTA ref (3.33)
1 K K K
x 3 x 3 A x 4 A x 5 A Vref (3.34)
TA TA TA TA
KR
x4 x
1 sTR 1
KR 1 (3.35)
x 4 x1 x
TR TR 4
s KF
x5 x
1 sTF 2
KF K K 1 (3.36)
x 5 x2 E F x3 x5
TE TF TE TF TF
From equations (3.33) to (3.37), the state space model of the voltage control
system with stabilizer can be obtained in vector – matrix form as follows:
1 KG
x 1 x1
.
0 0 0 0
TG TG
1 KE
x 2 0 0 0 x 2 0
TE TE
1 KA K K
x 3 0 0 A x3 A V
TA TA TA T ref
A
KR 0 0
1
0 x 4 0
x 4
T TR
R
0 KF KEKF
0
1 0
x
5
x TE TF TE TF TF 5
35 | P a g e
Chapter 3 Voltage Control of Power System using PID
3.10
3.10.1 Simulation Results without Controller
3.10.1.1 Transfer function of voltage control without controller
From the Fig (3.10), we see that for an amplifier gain of KA = 10, the response
is highly oscillatory, with a very large overshoot/undershoot and a long settling
time.
36 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.11): Terminal voltage step response without control by state space
model.
Fig. (3.12): Block diagram of terminal voltage step response without control in
the Simulink window.
37 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.13): Terminal voltage step response without control by using MATLAB.
38 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.15): State space model of terminal voltage step response with PI control.
Fig. (3.16): Block diagram of terminal voltage Step response with PI control in
the Simulink window.
39 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.17): Terminal voltage step response with PI control by using MATLAB.
40 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.19): State Space Model of Terminal Voltage Step Response with PD
Control.
3.10.3.3 Simulation model of the system with PD control
Fig. (3.20): Block diagram of terminal voltage Step response with PI control in
the Simulink window.
41 | P a g e
Chapter 3 Voltage Control of Power System using PID
42 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.23): State Space Model of Terminal Voltage Step Response with PID
Control.
3.10.4.3 Simulation model of the system with PID control
43 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig.(3.24): Block diagram of terminal voltage step response with PID control in
the Simulink window.
Fig. (3.25): Terminal voltage step response with PID control by using
MATLAB.
44 | P a g e
Chapter 3 Voltage Control of Power System using PID
45 | P a g e
Chapter 3 Voltage Control of Power System using PID
It can be seen from these figures that the system with PI and PID controller has
better time response in terms of less settling time and large overshoot/
undershoot compared with the case without controller. On the other hand, the
PD controller has fast time response, but with relatively smaller overshoot/
undershoot and less settling time than the PI and PID controllers.
46 | P a g e
Chapter 3 Voltage Control of Power System using PID
Table (3.2): System poles and specifications due to a variation in the gain KA
between KA = 5 and 15 (without controller).
47 | P a g e
Chapter 3 Voltage Control of Power System using PID
48 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.27) :System time response due to a variation in the time constant TA
(without controller).
Table (3.4): System poles and specifications due to a variation in the gain KE
between KE = 0.5 and 1.5 (without controller).
49 | P a g e
Chapter 3 Voltage Control of Power System using PID
50 | P a g e
Chapter 3 Voltage Control of Power System using PID
(without controller).
Table (3.6): System poles and specifications due to a variation in the parameter
KP between KP = 0.05 and 0.4 (with PI controller).
Peak Percentage Rise Settling
KP Eigenvalues
time overshoot time time
-19.947
-10.148
0.05 2.409 79.744 0.741 69.677
-0.0539 j1.4982
-3.297
-19.869
-10.495
0.1 2.405 56.240 0.834 18.305
-0.2038 j1.6108
-2.7288
-19.704
-11.117
0.2 2.249 21.041 0.942 5.998
-0.5202 j1.9771
-1.6384
-19.526
-11.681
0.3 4.550 1.039 1.161 3.946
-0.6462 j2.4817
-1.000
-19.332
-12.213 6.974e006
0.4 14.735 2.782 5.549
-0.6183 j2.9103 0
-0.7177
51 | P a g e
Chapter 3 Voltage Control of Power System using PID
-19.713
-11.064
0.4 -0.2987 j2.0553
2.042 41.605 0.769 11.548
-2.1260
-19.721
-11.009
0.5 -0.1346 j2.1419
1.931 59.648 0.668 26.963
-2.500
52 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.31): System time response due to a variation in the parameter KI (with PI
controller).
Table (3.8): System poles and specifications due to a variation in the parameter
KP between KP = 0.5 and 2.0 (with PD controller).
53 | P a g e
Chapter 3 Voltage Control of Power System using PID
54 | P a g e
Chapter 3 Voltage Control of Power System using PID
(With PD controller).
Table (3.10): System poles and specifications due to a variation in the parameter
KP between KP = 0.1 and 4.5 (with PID controller).
55 | P a g e
Chapter 3 Voltage Control of Power System using PID
56 | P a g e
Chapter 3 Voltage Control of Power System using PID
57 | P a g e
Chapter 3 Voltage Control of Power System using PID
58 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.37): System time response based on nominal values of the system
and controller parameters (without and with PI controller).
3.10.10.2 Comparison between terminal voltage step response with /
without PD control
59 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.38): System time response based on nominal values of the system
and controller parameters (without and with PD controller).
3.10.10.3 Comparison between Terminal Voltage Step Response with /
without PID Control
Fig. (3.39): System time response based on nominal values of the system
60 | P a g e
Chapter 3 Voltage Control of Power System using PID
The system poles without controller based on the nominal values of the
system parameters given in section (2.8.1) are computed as:
(-0.2021 j4.4753, -16.5480 j0.4681)
The system with stabilizer controller based on the nominal values of the
system parameters given in section (3.9.3) are computed as:
(-18.726 j111.73, -0.52108 j0.51377) and the corresponding time response
specifications are given as:
Peak time = 0.792 sec Percent overshoot = 82.469
Rise time = 0.247 sec Settling time = 19.046 sec
With stabilizer, the corresponding time response specifications of the closed
– loop system are obtained as:
Peak time = 6.084 sec Percent overshoot = 4.135
Rise time = 2.955 sec Settling time = 8.079 sec
In the following, the system poles are computed and the corresponding time
responses are plotted at different values of the system parameters.
Table (3.13) gives the closed-loop poles of the system for different values of the
stabilizer gain KF between KF = 0.1 and 7.0. System specifications such as peak
time, percentage overshoot, rise time and settling time are included in the same
table. Fig. (3.40) shows the system time response for three extreme values of KF
(KF = 0.1, 2.0 and 7.0. The corresponding results for a variation in KA between 5
and 100 are shown in Table (3.14) and Fig. (3.41), While Table (3.15) and Fig.
(3.42) show the results for a variation in KE between 0.2 and 100. Table (3.15)
and Fig. (3.43) show the results for a variation in KE between 0.5 and 10.0,
Table (3.16) and Fig. (3.44) show the corresponding results for a variation in KR
between 0.5 and 2.0.
61 | P a g e
Chapter 3 Voltage Control of Power System using PID
62 | P a g e
Chapter 3 Voltage Control of Power System using PID
63 | P a g e
Chapter 3 Voltage Control of Power System using PID
64 | P a g e
Chapter 3 Voltage Control of Power System using PID
-18.75 j1118i
10
-20.005 6.210 4.460 3.014 8.400
0
-0.4976 j0.5026
65 | P a g e
Chapter 3 Voltage Control of Power System using PID
66 | P a g e
Chapter 3 Voltage Control of Power System using PID
67 | P a g e
Chapter 3 Voltage Control of Power System using PID
The damping ratio () of the dominant closed – loop poles is selected as = 0.4
and undamped natural frequency (n) is same as the case without controller.
Then, the closed – loop poles of system will be:
(-1.5000 j4.4753, -16.548 j0.4681)
Using MATLAB software package, the state - feedback gain matrix (K) is
calculated as:
68 | P a g e
Chapter 3 Voltage Control of Power System using PID
In the following, the system time response is plotted and the system poles are
calculated for different values of system parameters based on pole placement
controller.
Table (3.18) gives the closed-loop eigenvalues of the system for different
Values of the parameter KA. System specifications in terms of peak time,
percentage overshoot, rise time and settling time are included in the same table.
Fig. (3.46) shows the system time response for three extreme values of KA (KA =
5, 10 and 15). The corresponding results for a variation in T A between 0.02 and
0.5 sec are shown in Table (3.19) and Fig. (3.47), while Table (3.20) and Fig.
(3.48) show the results for a variation in K E between 0.5 and 1.5, Table (3.21)
and Fig. (3.49) show the results for a variation in KR between 0.5 and 2.0.
From the above results, it can be seen that the system with pole placement
controller has fast response in terms of less peak time, less overshoot/
undershoot and less settling time compared the case without controller over a
wide range variation of the system parameters.
69 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.46): System time response due to a variation in the amplifier gain KA
(with pole placement controller).
Table (3.19) System poles and specifications due to a variation in the amplifier
time constant TA between TA = 0.02 and 0.5 sec (with pole placement
controller).
70 | P a g e
Chapter 3 Voltage Control of Power System using PID
71 | P a g e
Chapter 3 Voltage Control of Power System using PID
Percentag
Peak Setting
KE Eigenvalues e Rise time
time time
overshoot
-18.958
0.5 -13.953 1.068 20.073 0.452 2.412
-1.5922 j3.1931
-18.391
0.7 -14.606 0.910 26.213 0.374 2.136
-1.5494 j3.7700
-1.500 j4.4753
1.0 0.780 32.914 0.307 2.433
-16.548 j46812
-1.4750 j4.8777
1.2 0.719 36.269 0.278 2.712
-16.573 j1.6224
-1.4472 j5.4129
1.5 0.649 40.178 0.242 2.564
-16.601 j2.4702
Fig. (3.48): System time response due to a variation in the exciter gain KE (with
pole placement controller).
Table (3.21) System poles and specifications due to a variation in the sensor
gain KR between KR = 0.5 and 2.0 (with pole placement controller).
72 | P a g e
Chapter 3 Voltage Control of Power System using PID
Percentag
Peak Setting
KR Eigenvalues e Rise time
time time
overshoot
-19.089
0.5 -2.1617 j3.3859 1.022 12.627 0.458 1.531
-12.684
1.8629 j3.8989
0.7 -18.554 0.891 20.976 0.376 2.013
-13.816
-1.500 j4.4753
1.0 0.780 32.914 0.307 2.433
-16.548 j46812
-1.0247 j5.1786
1.5 0.673 50.805 0.244 3.796
-17.023 j2.8610
-0.6436 j5.7128
2.0 0.606 66.527 0.218 5.687
-17.404 j3.8538
Fig. (3.49): System time response due to a variation in the sensor gain KR
(with pole placement controller).
73 | P a g e
Chapter 3 Voltage Control of Power System using PID
Fig. (3.50): System time response based on nominal values of the system and
controller parameters (without and with pole placement controller).
74 | P a g e
Chapter 4
:
Conclusion of the present
work
Chapter 4 Conclusion of the Present Work
Chapter 4
Conclusion of the Present Work
Conclusion
From the results obtained in this project, the following items can
be concluded:
73
References
References
1. O.I. Elgard, “Electric Energy Systems Theory”, Mc Graw-Hill, New York, pp. 299-
362.
2. HadI Saadat, “Power System Analysis”, Tata Mc Graw- hill, New York, pp ,555-
564.
3. ALAzzam, H.W. Lewis, “A New Optimization Algorithm for Combinatorial
Problems”, (IJARAI) International Journal of Advanced Research in Artificial
Intelligence, vol.2, no.5, 2013.
4. J.W. Fitch, K.J. Zachariah, M. Farsi, “Turbo generator Self-Tuning Automatic
Voltage Regulator”, IEEE Transactions on Energy Conversion, vol.14, No.3, pp.843-
848, 1999.
5. 1766 R. Tapia et al.5. Gibbard, M. J., and Vowels, D. J., “Reconcilation of methods
of compensation for PSSs inmultimachine systems,” IEEE Trans. Power Syst., Vol.
19, No. 1, pp. 463–472, February 2004.
6. Qiu, W., Vittal, V., and Khammash, M., “Decentralized power system stabilizer
design usinglinear parameter varying approach,” IEEE Trans. Power Syst., Vol. 19,
No. 4, pp. 1951–1960,November 2004.
7. Do Bomfim, A. L. B., Taranto, G. N., and Falcao, D. M., “Simultaneous tuning of
power systemdamping controllers using genetic algorithm,” IEEE Trans. Power Syst.,
Vol. 15, pp. 163–169,February 2000.
8. Abdel-Magic, Y. L., Abido, M. A., Al-Baiyat, S., and Mantawy, A. H.,
“Simultaneous sta-bilization of multimachine power systems via genetic algorithms,”
IEEE Trans. Power Syst.,Vol. 14, pp. 1428–1437, November, 1999.
9. Abdel-Magic, Y. L., Abido, M. A., and Mantawy, A. H., “Robust tuning of power
system stabilizer in multimachine power systems,” IEEE Trans. Power Syst., Vol. 15,
pp. 735–740, May 2000
10. Kenné, G., Gomab, R., Nkwawo, H., Lamnabhi-Lagarrigue, F., Arzandé, A., and
Vannier, J. C.,“An improved direct feedback linearization technique for transient
stability enhancement and voltage regulation of power generators,” Int. J. Elect.
Power Energy Syst., Vol. 32, pp. 809–816,September 2010.
11. Joe H.Chow, G.E. Boukarim, A.Murdoch, “Power System Stabilizers as
Undergraduate Control Design Projects”, IEEE Transactions on Power
systems,vol.19, no.1, Feb.2004
12. E.V.Larsen, D.A.Swann, “Applying Power System Stabilizers”, Part-1, Part-
2,Part-3, IEEE Trans. on Power App. Syst, vol. PAS-100, pp. 3017-3046, June1981.
13. K. Bollinger, A. Laha, R. Hamilton, T. Harras, “Power Stabilizer Design using
root locus methods”, IEEE Transactions on power apparatus and systems, vol.PAS-
94, no. 5, September/October 1975.
14. M.Z. El-Sadek, "Power System Control", Faculty of Engineering, Assiut
University, Assiut, Egypt (2004).
References
75
الملخص العربي
من المع روف أن ه يمكن التحكم في الطاق ة الكهربائي ة المول دة بواس طة الق وة
الميكانيكية للمحرك الرئيسي .يمكن أن يؤدي فتح أو إغالق صمام البخار أو الماء
إلى التحكم في القدرة الميكانيكية أو التوربينات الهيدروليكية .يحتوي نظام الطاق ة
على نظ امين أساس يين للتحكم ،وهم ا حلق ة التحكم في الجه د التف اعلي وحلق ة
التحكم في تردد الطاقة.
ركزالبحث التطبيقي الحالي على مشاكل إنشاء حالة التشغيل العادية والجدولة المثلى لتولي د
نظام الطاقة وتتعامل مع التحكم في القوى التفاعلي ة من أج ل الحف اظ على النظ ام في حال ة
مستقرة .الهدف من نظام التحكم في الجهد هو توليد الطاقة في نظام مترابط بشكل اقتصادي
وموثوق قدر اإلمكان ،مع الحفاظ على الجهد ضمن الحدود المسموح بها.
الزيادة في حمل الطاقة التفاعلية للمولد مصحوبة بانخف اض في حجم الجه د الط رفي ل ذا تم
استشعار مقدار الجهد من خالل محول محتم ل في مرحل ة واح دة وتم تص حيح ه ذا الجه د
ومقارنته بإشارة نقطة ضبط التيار المستمر .تتحكم إشارة الخطأ المضخمة في مجال المثير
وتزيد من جهد طرف المثير .وبالتالي ،يتم زيادة تيار مجال المولد ،مما ي ؤدي إلى زي ادة
emfالمتولدة وتم زيادة توليد الطاقة التفاعلية إلى توازن جديد ،مما يرف ع الجه د الط رفي
إلى القيمة المطلوبة .تم أوالً تحليل دور التحكم التلقائي في التوليد ( )AGCفي تشغيل نظام
الطاقة ،مع اإلشارة إلى التحكم في طاقة خط الربط في ظل ظروف التشغيل العادية .أخيرً ا
،يتم فحص متطلبات القدرة التفاعلية وتنظيم الجهد والتأثير على اس تقرار ك ل من عناص ر
التحكم في السرعة واإلثارة ،مع استخدام إشارات التغذية الراجعة المناسبة.
تم إجراء الوصف والنمذجة أعاله لنظام التحكم في الجهد الف ردي .تم تص ميم وح دة التحكم
التقليدية المتناسبة والتكاملية والمشتقة ( )PIDإلنشاء نظام التحكم في ت ردد تحمي ل التغذي ة
المرتدة .يتم تحديد معلمات وحدة التحكم PIDداخل نطاق استقرار نظام الطاقة.
تم تمثيل نهج التحكم الحديث في تقنية وضع العم ود ال ذي يتم تطبيق ه لتص ميم نظ ام التحكم
في الجهد الكهربائي ذي الحلقة المغلقة .تم تصميم نظام التحكم في الجهد الكهربائي للمنطق ة
الواحدة باستخدام طرق التحكم المقترحة .للتحقق من فعالية طرق التحكم المقترح ة لتص ميم
نظ ام التحكم في جه د الحلق ة المغلق ة ،تتم محاك اة أنظم ة الق درة ذات المنطق ة الواح دة
وتعريضها الضطرابات مختلفة.
طالما أن هذا البحث التطبيقي يقدم دراسة نظرية ،فان هذا البحث التطبيقي يستعين ب برامج
المحاكاة لفحص كفاءة المتحكم المق ترح في ه ذا البحث التط بيقي ،وعلي ه ذا يتم اس تخدام
برنامج ( . ) Simulink / Matlab
يحتوي البحث التطبيقي علي أربعة أبواب وقائم ة المراج ع ال تي تم الرج وع اليه ا في ه ذا
البحث التطبيقي وفيما يلي محتوي هذه األبواب :
الباب األول :بعنوان " المقدمة " وفيه تم تقديم مراجعة موجزة للنقاط األساسية التي س وف
يتم التعرض لها خالل أبواب البحث التطبيقي المختلفة وك ذلك يوض ح ه ذا الب اب األه داف
المرجوة من هذا البحث التطبيقي مع توضيح سريع وموجز لكل باب من االبواب األربعة.
الباب الثاني :تحت عنوان " وصف ونمذجة نظام التحكم في الجهد" وفيه تم اعطاء مقدمة
عامة عن توص يف ونمذج ة التحكم في جه د الحم ل حيث أن الوس يلة األساس ية للتحكم في
القدرة التفاعلية للمولد هي التحكم في إث ارة المول د باس تخدام ( )AVRوال ذي يتمث ل دور (
)AVRفي االحتفاظ بحجم الجهد الطرفي للمولد المتزامن عن د مس توى مح دد م ع دراس ة
نظام طاقة التحكم في الجهد بدون جهاز تحكم.
الباب الثالث :تحت عنوان " التحكم في الجهد لنظام الطاقة باستخدام PID
" في هذا الفصل تقرر دراسة تأثير التحكم باستخدام ال PIDودراسة تأثير وحدات تحكم
موضع القطب علي التحكم في جهد الحمل ،وتم استعراض نبذة تاريخية عن طريق ة التحكم
باستخدام PIDونظرية عمله ومكوناته تس تخدم وح دات التحكم PIDع اد ًة تعليق ات حلق ة
التحكم في تطبيقات األنظمة الصناعية وأنظمة التحكم .تقوم وحدة التحكم أوالً بحس اب قيم ة
الخطأ على أنها الفرق بين متغير العملية المقاسة ونقطة الض بط المفض لة .ثم يح اول تقلي ل
الخطأ عن طري ق زي ادة أو تقلي ل م دخالت أو مخرج ات التحكم في العملي ة بحيث يق ترب
متغير العملي ة من نقط ة التحدي د .تك ون ه ذه الطريق ة مفي دة للغاي ة عن دما يك ون النم وذج
الرياضي للعملية أو التحكم معق ًدا ج ًدا أو غير مع روف للنظ ام .لزي ادة األداء ،مث ل زي ادة
استجابة النظام ،يجب ضبط معلمات PIDوف ًقا للتطبيق المحدد
الب اب الراب ع :تحت عن وان " االس تنتاجات والش غل المس تقبلي " وفي ه يتم ايج از أهم
االستنتاجات التي تم الحصول عليه ا في ه ذا البحث التط بيقي والنق اط المقترح ة لدراس تها
مستقبليا في مجال موضوع البحث التطبيقي .
التحكم في القدرة الغير فعالة والجهد لمنظومة قوى
باستخدام تقنيات تحكم مختلفة
مقدمه من
م /نعمة عصر فكري
للحصول على درجة الماجستير في الهندسة الكهربائية
لجنه االشراف:
ا .د /النوبى أحمد ابراهيم
(استاذ متفرغ بقسم الهندسة الكهربائية – كلية الهندسة – جامعة أسيوط )
لجنه الحكم
ا .د /حمدي أحمد زيدان
(استاذ الهندسة الكهربائية – كلية الهندسة – جامعه اسيوط)
ا .د /فريد نجيب عبد البر
(استاذ الهندسة الكهربائية – كلية الهندسة – جامعه اسيوط)
ا .د /النوبى أحمد ابراهيم
(استاذ متفرغ بقسم الهندسة الكهربائية – كلية الهندسة – جامعه اسيوط)
2022
التحكم في القدرة الغير فعالة والجهد لمنظومة قوى
باستخدام تقنيات تحكم مختلفة
مقدمه من
م /نعمة عصر فكري
للحصول عل درجه الماجستير في الهندسة الكهربائية
لجنة االشراف:
2022