Professional Documents
Culture Documents
Trenter2004 - Approaches To The Design of Cantilever Retaining Walls
Trenter2004 - Approaches To The Design of Cantilever Retaining Walls
Trenter2004 - Approaches To The Design of Cantilever Retaining Walls
Civil Engineers
Geotechnical Engineering 157
January 2004 Issue GE1
Pages 27–35
Paper 13301
Received 10/3/2003
Accepted 4/9/2003
Keywords: N. A. Trenter
codes of practice & standards/ Consulting geotechnical
design methods & aids/retaining engineer
walls/
Cantilever (stem and pad) retaining walls are among PPH horizontal component of passive force
the simplest earth-retaining structures to construct, PPV vertical component of passive force
and accordingly may offer significant economic q vertical effective stress at foundation level
benefits. Their design involves use of bearing capacity R resultant disturbing force
and sliding stability theory, and application of the RH horizontal component of resultant disturbing force
factors of safety laid down in the code to which the RV vertical component of resultant disturbing force
designer is working. Two typical L-shaped cantilever S sliding resistance
walls founded on and retaining dry cohesionless soil SH horizontal component of sliding resistance
are considered, designed in accordance with the SV vertical component of sliding resistance
procedures given in CP2:1951 and BS 8002:1994. It is W total weight of wall (concrete and included virtual wall)
shown that the width of the foundation base depends Æ angle to vertical made by resultant disturbing force
upon which philosophy of factor of safety, and hence angle to horizontal made by backfill surface behind
which code, is adopted. It is also shown that BS wall
8002:1994 produces larger (more conservative) A angle of wall friction (active force CP2:1951)
foundation bases than the CP2:1951 it replaces, P angle of wall friction (passive force CP2:1951)
although the difference is significant only for more D angle of interface friction (foundation and underlying
steeply sloping backfills and deeper foundations. soil CP2:1951)
9A angle of wall friction (active force BS 8002:1994)
NOTATION 9P angle of wall friction (passive force BS 8002:1994)
a length of heel of foundation measured from back of 9D angle of interface friction (foundation and underlying
stem soil BS 8002:1994)
B width of foundation ªsoil unit weight of soil
B9 effective width of foundation ªconc unit weight of concrete
d q , dª depth factors º angle to horizontal made by soil wedge forming part of
D foundation depth virtual wall
e eccentricity of resultant disturbing force 9 angle of friction of soil and backfill
F factor of safety 9m angle of friction of soil and backfill after application of
FB factor of safety against bearing capacity failure partial factor M
FS factor of safety against sliding instability 9FB angle of friction mobilised at required factor of safety
FV sum of vertical forces against bearing capacity failure
H height of wall measured from formation level in front 9FS angle of friction mobilised at required factor of safety
of wall against sliding instability
i q , iª inclination factors sin1 (sin /sin 9)
L height of wall measured from top of heel
M partial safety factor (BS 8002:1994) 1. INTRODUCTION
M O sum of moments about toe of wall
Nq , Nª bearing capacity factors 1.1. General
p ultimate bearing pressure per metre run of wall One of the principal differences between the Code of Practice
1 2
P ultimate bearing capacity per metre run of wall BS 8002:1994 and the earlier CP2:1951 lies in the
PA active force philosophy of factor of safety, dealt with in more detail below.
PA1 active force on soil wedge forming part of virtual wall BS 8002:1994 introduced the concept of a ‘partial factor of
PA2 active force on back of stem forming part of virtual safety’. The advantage of this is its ability to operate directly
wall upon those parts of the calculation subject to the greatest
PAH horizontal component of active force unknowns, usually the soil strength. In BS 8002 : 1994 the
PAV vertical component of active force partial factor is applied to tan 9, where 9 is the angle of
PP passive force friction of the soil. Properties such as soil unit weight, which
Restoring force
1
¼ PP cos P þ (W þ PA sin 9 PP sin P )tan D
PAV
W
PAH 2 Disturbing force ¼ PA cos 9
tan 9
4 9m ¼ tan 1
RV 1:2
R
α In addition, BS 8002 : 1994 also requires that the ratio of
restoring to disturbing forces should be greater than unity for
equilibrium. Although not so named in BS 8002 : 1994, this
ratio is termed stability ratio for brevity here. That is:
O
e Restoring forces
5 Stability ratio ¼ .1
B′ Disturbing forces
B
(c) Therefore for BS 8002 : 1994 there are effectively two
components to the factor of safety: the active earth pressure is
increased and the passive earth pressure is decreased by
Fig. 1. Forces and their components acting on L-shaped
retaining wall (for definition of symbols, see text) application of the partial factor M to the angle of friction
(equation (4)). This adjustment having been made, a lumped
PA
Assuming that no special tests are made to determine the
sliding resistance between the underside of the wall foundation φ′
and the soil, BS 8002 : 1994 requires an interface friction, 9D ,
to calculate sliding resistance, where
W
λ
O PA
6 tan 9D ¼ 0:75 tan 9m δA
D C
(a)
It is easy to see that the interface friction given by equation (6)
leads to markedly lower sliding resistance, noting that
A
B
tan 9
tan 9D ¼ 0:75
1:2
PA
or
φ′
virtual wall described in CP2 : 1951, and to assume that the line W
of action of the active force will be at an angle ¼ 9m to the λ
horizontal on the back of the virtual wall, as a ‘soil on soil’ O
condition exists. (See also discussion below.)
D
Substituting 9D for D, 9P for P and 9m for 9 in equations (1) (c)
and (2), the expressions for the restoring and disturbing forces
according to BS 8002 : 1994 become
Fig. 2. Approaches to computing magnitude and line of action
of active forces on back of cantilever retaining walls
Restoring force
8
¼ PP cos 9P þ (W þ PA sin 9m PP sin P )tan 9D
Rankine procedures. The component of active force PA2 is
calculated for the length of stem AB, using Coulomb
procedures. An active force PA would also act on the back of
9 Disturbing force ¼ PA cos 9m the foundation heel OD. The virtual wall would be defined by
the wedge of soil contained by the line OA, the back of the
2.3. Note on derivation of active force stem and the top of the heel.
6
Terzaghi discussed the active thrust on cantilever walls, and 7
suggested that the surface of sliding could be represented by Clayton et al. pointed out that, if the heel is sufficiently long,
the lines OA and OC in Fig. 2(a). Lines OA and OC rise at º ¼ an active Rankine zone develops behind the wall (OAC in Fig.
45 + 9/2 to the horizontal from the heel. The active force PA1 2(b)). The criterion for Rankine zone formation according to
acts at an angle 9 to the normal to OA and is computed using the authors is
6
Terzaghi Rankine/Coulomb Horizontal backfill only. Surfaces of sliding determined by planes at 45 þ 9=2.
Line of action of active force at angle ¼ 9 to normal of OA. Must compute
active force on upper part of stem (Fig. 2(a))
7
Clayton et al. Mueller-Breslau (see Clayton Horizontal and sloping backfill and long-heeled walls (a > L cot º). Line of action
et al. for details) of active force at angle ¼ 9 to normal of OA (Fig. 2(b))
7
Clayton et al. Rankine Horizontal and sloping backfill and long-heeled walls (a > L cot º). Line of action
of active force at angle ¼ to the normal of OE (Fig. 2(c)). Virtual wall as CP2
2 8
CP2 : 1951 Coulomb (Kerisel and Absi Horizontal and sloping backfill. Line of action of active force at angle ¼ 9 to
also assumed to apply) the back of virtual wall (see section 2.1)
1 8
BS 8002:1994 Kerisel and Absi Horizontal and sloping backfill. Limited guidance given by code on location of
active forces. This paper assumes virtual wall as CP2 and location of active force
also as CP2 (see section 2.2)
Table 1. Approaches to calculating active force on back of cantilever walls (see Fig. 2)
3. BEARING CAPACITY 9
16a N q ¼ e tan 9 tan2 45 þ
2
3.1. CP2 : 1951 method
CP2 : 1951 requires that the bearing pressure on the foundation
soil should be less than the appropriate safe bearing capacity of Nª ¼ 2(N q 1)tan 9
16b
the foundation soil, and Table 8 of this code gives safe bearing
pressures (factor of safety at least 2) for cohesionless soils.
CP2 : 1951 predates the introduction of inclination factors (see Eurocode 7 also provides formulae for the relevant inclination
below), and the maximum (and minimum) bearing pressures at factors
the toe and the heel of the foundation base, respectively, are
estimated using the following formulae
17a i q ¼ (1 0:7 tan Æ)3
RV 6e
11a max ¼ 1þ
B B
17b iª ¼ (1 tan Æ)3
and
where Æ is the angle to the vertical made by the resultant
disturbing force, R (see Fig. 1(c) and equation (13)).
RV 6e
11b min ¼ 1
B B CP2 : 1951 predates the development of the bearing capacity
and inclination factors quoted in the Eurocode by many years.
However, to maintain consistency in the work to be described,
where RV is the vertical component of the resultant disturbing they were adopted in calculating bearing capacity using both
force, B is the foundation width, and e is the eccentricity (Fig. the CP2 : 1951 and the BS 8002 : 1994 procedures. Direct
1(c)). comparisons may then be made between the approaches of
both codes, without allowances having to be made for
3.2. BS 8002 : 1994 method differences in computing bearing capacity. The depth factors
10
The resultant disturbing force behind the wall, R, and its line of due to Brinch Hansen were also employed. That is
18b dª ¼ 1
Because the resultant disturbing force behind the wall acts at H⫽ Soil
an angle to the vertical, the eccentricity e (Fig. 1(c)) should be 5·5 and 7 m ⫽ 19 kN/m3 Back of
calculated. The following equation may be adopted virtual
wall
X
MO
B
19 e¼ X
2 FV
D⫽
where M O is the sum of the moments of forces acting about 0, 0·5, 1·0 m
Conc
0·75 m
⫽ 24 kN/m3
the toe of the wall (point O in Fig. 1(c)), FV is the sum of the
vertical forces (Fig. 1(b)), and B is the foundation width. This
yields an effective foundation width (Fig. 1(c)) of
B⫽
3·25, 3·75 m
20 B9 ¼ B 2e
Fig. 3. Definition diagram for retaining walls studied (not to
scale)
to be used in bearing capacity calculations. Note that, for
stability, the line of action of the resultant must lie within the
middle third of the foundation base, or e , B/6.
The factor of safety, FB , against bearing capacity failure for a with groundwater below influencing distance of the
particular angle of friction is then foundation.
Calculated ultimate bearing capacity The angles of friction 9FB and 9FS were determined using a
21 FB ¼ spreadsheet prepared for the purpose. Initially, graphs were
Calculated vertical disturbing force
plotted of the calculated factor of safety against bearing
capacity failure, FB , and sliding stability failure, FS , against
A factor of safety of 2 was adopted for calculations made with angle of friction, 9, for each case. Values of 9FB and 9FS that
CP2 : 1951 and of unity for those made with BS 8002 : 1994. corresponded to the required factors of safety were read off the
graphs and were subsequently checked by direct calculation.
4. ANALYSIS
In order to investigate the relative foundation widths using the With 9FB and 9FS calculated, the percentage difference between
CP2 : 1951 and BS 8002 : 1994 procedures, calculations were the foundation base width designed using bearing capacity
first made to determine 9FB and 9FS , the values of angle of theory and the CP2 : 1951 and BS 8002 : 1994 procedures was
friction corresponding to the required factor of safety for the investigated. The percentage difference, ˜BC , expressed in
bearing capacity and sliding stability conditions. The following terms of the effective foundation width, B9, is
cases were treated (see definition diagram, Fig. 3)
B9CP B9BS
(a) height, H ¼ 5.5m; foundation width, B ¼ 3.25m; depth of 22 ˜BC ¼ (%)
B9CP
foundation, D ¼ 0m, 0.5m, 1.0m; slope of backfill, ¼ 08,
12.58, 258 (nine cases)
(b) height, H ¼ 7.0m: foundation width, B ¼ 3.75m; depth of Using equation (20), it can be readily shown that this is
foundation, D ¼ 0m, 0.5m, 1.0m; slope of backfill, ¼ 08, equivalent to
12.58, 258 (nine cases).
2(eBS eCP )
The backfill was assumed to have identical geotechnical 23 ˜BC ¼ (%)
B 2eCP
properties to those of the foundation soil. A unit weight of
19 kN/m3 was employed for the foundation soil and backfill,
and 24 kN/m2 for the reinforced concrete. The reinforced where the symbols have the significance already introduced,
concrete section was taken as being 0.75 m thick throughout. and the subscripts refer to the respective code of practice. The
The foundation soil and retained backfill were assumed dry percentage difference expressed by equation (23) was then
Eccentricity e: m
0·2 0·2
0 0
0 12·5 25 0 12·5 25
Slope of backfill, β: degrees Slope of backfill, β: degrees
(a) (b)
Fig. 4. Variation of eccentricity, e, with slope of backfill, , for two L-shaped retaining walls: (a) H ¼ 5.5 m, B ¼ 3.25 m; (b) H ¼
7.0 m, B ¼ 3.75 m
4·0 4·0
2·0 2·0
0 0
0 12·5 25 0 12·5 25
Slope of backfill, β: degrees Slope of backfill, β: degrees
(a) (b)
Fig. 5. Difference in effective foundation width ˜BC (%) for two L-shaped retaining walls: (a) H ¼ 5.5 m, B ¼ 3.25 m; (b) H ¼ 7.0 m,
B ¼ 3.75 m
approach produced a smaller (more economic) foundation base 1951, Civil Engineering Code of Practice No. 2 (CP2).
width than the corresponding BS 8002 : 1994, although the 3. CARDER D. R. A Comparison of Embedded and Conventional
difference was significant only for more steeply sloping Retaining Wall Design Using Eurocode 7 and Existing UK
backfills and deeper foundations. However, the use of BS Design Methods. Transport Research Laboratory,
8002 : 1994 produced designs with unacceptably large Crowthorne, 1998, TRL Report 320.
eccentricities (e . B/6) in two of the cases studied: these 4. HIGHWAYS AGENCY. Backfilled Retaining Walls and Bridge
designs would have been admissible adopting CP2 : 1951 Abutments. Design Manual for Roads and Bridges,
procedures. Volume 2, Section 1. Highways Agency, London, 1987,
BD30/87.
Only a small difference between the foundation widths was 5. BRITISH STANDARDS INSTITUTION. Eurocode 7. Geotechnical
predicted on the basis of sliding stability theory for the two Design: Part 1. British Standards Institution, Milton
codes investigated. Keynes, 1995, DD ENV 1997-1.
6. TERZAGHI,1943.
7. ACKNOWLEDGEMENTS 7. CLAYTON C. R. I., MILITITSKY J. and WOODS R. I. Earth
The author is grateful to Mr K. R. Smyth Osbourne for reading Pressures and Earth Retaining Structures. Blackie
through the manuscript and for making several helpful Academic and Professional, London, 1993.
comments and suggestions. 8. KERISEL J. and ABSE E. Active and Passive Earth Pressure
Tables, 3rd edn. Balkema, Rotterdam, 1990.
REFERENCES 9. SIMPSON B. and DRISCOLL R. Eurocode 7: A Commentary.
1. BRITISH STANDARDS INSTITUTION. Code of Practice for Earth Building Research Establishment, Garston, 1998,
Retaining Structures. British Standards Institution, Milton Construction Research Communications.
Keynes, 1994, BS 8002. 10. BRINCH HANSEN J. A revised and extended formula for
2. INSTITUTION OF STRUCTURAL ENGINEERS. Earth Retaining bearing capacity. Danish Geotechnical Institute Bulletin,
Structures. Institution of Structural Engineers, London, 1970, 28.
Please email, fax or post your discussion contributions to the secretary by 1 July 2004: email: mary.henderson@ice.org.uk;
fax: þ44 (0)20 7799 1325; or post to Mary Henderson, Journals Department, Institution of Civil Engineers, 1–7 Great George Street,
London SW1P 3AA.