PART - D2

NAME OF PROJECT - CONSTRUCTION OF CENTRE FOR PROPULSION TECHNOLOGY (COPT) BUILDING


(GROUND PLUS 6 UPPER FLOORS) INCLUDING FINISHING WORKS, INTERNAL WATER SUPPLY, SANITARY AND
ELECTRICAL INSTALLATIONS, FIRE FIGHTING, FIRE ALARM & ELV SYSTEMS, LIFTS, AIRCONDITIONING,
INTERNAL FURNITURE AND EXTERNAL DEVELOPMENT WORKS AT IIT BOMBAY, POWAI, MUMBAI - 400076
ABSTRACT OF PRICE
SR. NO. ITEM DESCRIPTION AMOUNT

PART - I CIVIL WORKS 43,79,09,710 A


PART - II PLUMBING WORK 1,06,19,122 B

TOTAL FOR CIVIL WORK 44,85,28,832 C


PART - III FIRE FIGHTING WORKS 1,65,40,444

PART - IV HVAC WORKS 4,10,83,089

PART - V ELECTRICAL WORKS 10,69,99,407

PART - VI LOW VOLTAGE SYSTEM 2,30,44,376

PART - VII DG SET WORKS 45,59,252

PART - VIII ELEVATOR WORKS 1,10,74,206

TOTAL FOR MEP WORK 20,33,00,774 D


PART - IX 2,66,96,201
FURNITURE WORKS E

TOTAL AMOUNT( WITHOUT GST)( C+D+E) 67,85,25,807 F

18% GST 12,21,34,645 G

TOTAL AMOUNT INCLUDING GST( F+G) 80,06,60,452


NAME OF PROJECT - CONSTRUCTION OF CENTRE FOR PROPULSION TECHNOLOGY (COPT)
BUILDING (GROUND PLUS 6 UPPER FLOORS) INCLUDING FINISHING WORKS, INTERNAL WATER
SUPPLY, SANITARY AND ELECTRICAL INSTALLATIONS, FIRE FIGHTING, FIRE ALARM & ELV
SYSTEMS, LIFTS, AIRCONDITIONING, INTERNAL FURNITURE AND EXTERNAL DEVELOPMENT WORKS
AT IIT BOMBAY, POWAI, MUMBAI - 400076

SUMMARY OF PRICES: TRADE-WISE


SR. NO. TRADE DESCRIPTION AMOUNT
I CIVIL WORKS
1 EARTH WORK 39,67,952
2 CONCRETE WORK 22,77,32,040
3 MASONRY WORK 2,32,45,535
4 WOOD WORK 4,13,00,777
5 STEEL WORK 59,90,448
6 FLOORING & WALL LINING WORKS 5,96,77,407
7 ROOFING 1,75,30,289
8 FINISHING 2,74,77,381
9 ROAD WORK 60,22,159
10 ALUMINIUM WORK 1,50,64,670
11 WATER PROOFING 73,62,824
12 LAND SCAPE WORK 4,60,875
13 MISCELLANOUS WORK 19,43,651
14 SIGNAGES WORK 1,33,703
TOTAL OF CIVIL WORKS (A) 43,79,09,710
II PLUMBING WORK
A SANITARY WARES AND CP APPURTENANCES 43,23,572
B WATER SUPPLY SYSTEM 28,21,225
C INTERNAL DRAINAGE (SOIL, WASTE & VENT, RAIN WATER ) 22,83,012
D EXTERNAL SEWERAGE & STORM WATER DRAINAGE SYSTEM 7,84,308

E WATER SUPPLY PUMPS AND ACCESSORIES / EQUIPMENT 4,07,005


TOTAL OF PLUMBING WORKS (B) 1,06,19,122

TOTAL OF CIVIL AND PLUMBING WORK (C=A+B) 44,85,28,832


III FIRE FIGHTING WORKS
A FIRE PUMPS & RELATED EQUIPMENT / ACCESSORIES 28,77,431
B INTERNAL & EXTERNAL HYDRANT SYSTEM 46,65,903
C AUTOMATIC SPRINKLER SYSTEM 87,59,631
D FIRE EXTINGUISHERS 2,37,479
TOTAL OF FIRE FIGHTING WORKS (D) 1,65,40,444
IV HVAC WORKS
A VRF AIR COOLED HVAC SYSTEM 2,39,84,022
B AIR HANDLING UNITS (AHUs) 11,15,708
C SHEET METAL WORK 1,42,62,959
D VENTILATION FANS 17,20,400
TOTAL OF HVAC WORKS (E) 4,10,83,089
SR. NO. TRADE DESCRIPTION AMOUNT
V ELECTRICAL WORKS
1 MEDIUM VOLTAGE PANELS 3,61,25,651
2 DISTRIBUTION BOARDS 50,03,669
3 LT CABLES, TERMINATIONS, CABLE TRAYS AND RACEWAYS, 1,12,65,043
ETC.
4 POINT WIRING IN PVC CONDUIT, ETC. 3,53,88,521
5 LIGHT FIXTURES AND FITTINGS, CEILING FANS, EXHAUST FANS, 67,18,737
ETC.
6 LIGHTNING PROTECTION SYSTEM 18,61,810
7 EARTHING SYSTEM 63,73,316
8 UPS SYSTEM 40,07,060
9 SAFETY EQUIPMENTS FOR ELECTRICAL INSTALLATION 2,55,600
TOTAL OF ELECTRICAL WORKS (F) 10,69,99,407
VI LOW VOLTAGE SYSTEM
1 DATA NETWORKING AND TELEPHONE SYSTEM 65,67,829
2 FIRE ALARM SYSTEM 76,19,333
3 DIGITAL PUBLIC ADDRESS CUM EMERGENCY VOICE 19,37,281
EVACUATION SYSTEM
4 CCTV SYSTEM 58,83,490
5 ACCESS CONTROL SYSTEM 10,36,443
TOTAL OF LOW VOLTAGE SYSTEM WORKS (G) 2,30,44,376
VII DG SET WORKS
TOTAL OF DG SET WORKS (H) 45,59,252
VIII ELEVATOR WORKS
1 FREIGHT LIFT 50,79,588
2 PASSENGER LIFTS 59,94,618
TOTAL OF ELEVATORS WORKS (I) 1,10,74,206
IX FURNITURE WORKS
A LOOSE / CUSTOM MADE FURNITURE 2,66,96,201
TOTAL OF FURNITURE WORKS (J) 2,66,96,201

GRAND TOTAL (C TOJ) 67,85,25,807


PART -D2-COMMERCIAL
NAME OF PROJECT - CONSTRUCTION OF CENTRE FOR PROPULSION TECHNOLOGY (COPT) BUILDING (GROUND PLUS 6 UPPER FLOORS) INCLUDING
FINISHING WORKS, INTERNAL WATER SUPPLY, SANITARY AND ELECTRICAL INSTALLATIONS, FIRE FIGHTING, FIRE ALARM & ELV SYSTEMS, LIFTS,
AIRCONDITIONING, EXTERNAL DEVELOPMENT WORKS AND FURNITURE WORKS AT IIT BOMBAY, POWAI, MUMBAI - 400076

BILL OF QUANTITIES (BOQ)


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
Note : -
1) All the items of substructure include the cost of dewatering, wherever necessary during
the progress of work till its completion without any extra cost to IITB. Tenderers are advised
to visit site of work to acquaint themselves about the level of subsoil water, drainage facility
for dewatering, accessibility to the site.

2) All items of work shall be carried out as per specifications, standards, manufacture's
recommendations where applicable, drawings and as directed by Engineer-in-charge.

CIVIL WORKS
1 EARTH WORK
1.1 Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over
areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting
out and disposal of excavated earth lead up to 50 m and lift up to 1.5 m.

1.1.1 All kinds of soil up to 1.5m. cum 6498 223.78 14,54,118.63


1.1.2 All kinds of soil For lift beyond 1.5 m up to 3 m. cum 343 337.05 1,15,608.54
1.2 Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over
areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting
out and disposal of excavated earth lead up to 50 m and lift up to 1.5 m.

1.2.1 Ordinary rock cum 10 447.61 4,476.13


1.2.1.1 for lift beyond 1.5 m up to 3 m. cum 53 650.74 34,489.40
1.2.1.2 for lift beyond 3 m up to 4.5 m. cum 92 853.83 78,552.76
1.2.2 Hard rock (blasting prohibited). cum 10 1,178.68 11,786.76
1.3 Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in
foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including
dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the
excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.

1.3.1 All kinds of soil. cum 10 310.39 3,103.86


1.4 Excavating trenches of required width for pipes, cables, etc including excavation for sockets,
and dressing of sides, ramming of bottoms, depth up to 1.5 m, including getting out the
excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in
depth, including consolidating each deposited layer by ramming, watering, etc. and disposing
of surplus excavated soil as directed, within a lead of 50 m.

1.4.1 All kinds of soil


1.4.1.1 Pipes, cables etc, not exceeding 80 mm dia. Rmt 15 277.00 4,154.94
1.4.1.2 Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia. Rmt 18 452.38 8,142.88
1.5.2 For excavating trenches for pipes, cables etc. in all kinds of soil for depth exceeding 1.5 m,
but not exceeding 3 m. (Rate is over corresponding basic item for depth up to 1.5 metre). Rmt 10 137.66 1,376.60

1.6 Filling available excavated earth for filling shall be from the approved borrow pits within IITB
campus, including excavation, transportation, stacking, filling, compaction etc.(excluding
rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, cum 1746 250.24 4,36,923.11
consolidating each deposited layer by watering, ramming and consolidation.

1.7 Carriage of Excavated earth including rock by mechanical transport including loading,
unloading and stacking beyond 50 metres and average up to 1 km lead within the IITB cum 263 177.77 46,752.50
campus including dressing in the required area and shape.
1.8 Providing & Laying stone soling with available stone boulders including breaking to required
size, transporting, by hand packing and filling the gaps with smaller stones and stone dust /
cum 259 494.67 1,28,119.74
grit , consolidation with watering and ramming etc. complete.

1.8.1 230 mm thick with Contractor supply of stone cum 259 1,443.53 3,73,874.83
1.9 Filling in plinth with soil approved by approved by Engineer-in-Charge with soil brought from
borrow pits identified by the Contractor outside IITB campus and filling in layers of 15 cm to
20 cm including all the required lead, excavations, loading, unloading, laying, borrowing cum 1746 625.67 10,92,419.60
necessary permissions, royalty charges, watering, compaction etc. complete.

1.10 Supplying chemical emulsion in sealed containers including delivery as specified. etc.
Complete.
1.10.1 Chlorpyriphos emulsifiable concentrate of 20% Litres. 648 197.97 1,28,282.53
1.11 Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment
(excluding the cost of chemical emulsion) :
Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres /
sqm of the vertical surface of the substructure to a depth of 300 mm including excavation
channel along the wall & rodding etc. complete:
1.11.1 With Chlorpyriphos E.C. 20% with 1% concentration Rmt 1438 31.83 45,769.27
TOTAL OF EARTH WORK 39,67,952.08

PART D2_BOQ_COPT,IIT BOMBAY 4 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
2 CONCRETE WORK
2.1 Providing and laying in position ready mixed concrete (RMC) or batched design mix cement
concrete (BMC) of specified grade for cement concrete work, using fly ash and cement
content as per approved design mix, and manufactured in fully automatic batching plant and
transported to site of work in transit mixer for all leads, having continuous agitated mixer,
manufactured as per mix design of specified grade for cement concrete work, including
pumping of R.M.C. from transit mixer to site of laying, including the cost of centering,
shuttering, finishing, admixtures in recommended proportions as per IS : 9103 to accelerate /
retard setting of concrete, improve workability without impairing strength and durability etc.
complete for all works up to plinth level.

NOTE-
(1) The cementitious content will be as per approved design mix .
(2) Fly ash conforming to grade I of IS 3812 (Part-1)
only be used as part replacement of OPC as per IS :
456. Uniform blending with cement to be ensured in accordance with clauses 5.2 and 5.2.1 of
IS:456 -2000 in the items of RMC.
2.1.1 Plain Cement Concrete M15 (zone-III) derived from natural sources : 4 graded stone
cum 1092 7,257.62 79,25,319.74
aggregate 20 mm nominal size derived from natural sources)
Reinforcement Cement Concrete Work
a) All RCC shall be as specified and shall be carried out strictly in accordance with the
drawings and specifications.
b) The rates for RCC works shall be inclusive of all depths below grade / ground levels and
at all heights as detailed in the drawing but exclusive of cost of reinforcement unless
otherwise mentioned.
c) All coarse aggregate to be 20 mm maximum size and uniformly graded unless otherwise
mentioned.
d) For all RCC items, the rates quoted shall include the following without any extra cost to
IITB.
i) Spacers to maintain clear cover for reinforcement.
ii) Fixing at correct level & in proper alignment the inserts, pipe sleeves, pipe bends, fan
hooks, other pipe specials etc. supplied IITB or Contractor unless otherwise mentioned as a
separate item.
iii) Test for concrete shall be done as per IS 456-2000 and the cost of the testing to be carried
out shall be borne by the Contractor.
d) Precaution to be taken to avoid uplifting forces on the raft of water tanks.
As per the soil report, water table is expected near the ground level and Contractor is
advised to use following sequence during concreting in water tanks, and Sub-Structure and
plinth level works:
1) Dewatering to keep the area dry during construction
2) Plum concrete to be completed as shown in the drawing.
3) Keeping the tank filled with water for at least half the depth.
2.2 Providing and laying in position ready mixed concrete (RMC) or batched design mix cement
concrete (BMC) of specified grade for reinforced cement concrete work, using fly ash and
cement content as per approved design mix, and manufactured in fully automatic batching
plant and transported to site of work in transit mixer for all leads, having continuous agitated
mixer, manufactured as per mix design of specified grade for reinforced cement concrete
work, including pumping of R.M.C. from transit mixer to site of laying, finishing, excluding the
cost of centering, shuttering, reinforcement, including cost of admixtures in recommended
proportions as per IS : 9103 to accelerate / retard setting of concrete, improve workability
without impairing strength and durability.

NOTE-
(1) The cementitious content shall be as per
approved design mix.
(2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC
as per IS : 456.
(3) Uniform blending with cement to be ensured in accordance with clauses 5.2 and 5.2.1 of
IS:456 -2000 in the items of BMC and RMC.
2.2.1 All works up to plinth level.
2.2.1.2 Concrete of M20 grade cum 507 8,264.70 41,90,201.69
2.2.1.3 Concrete of M25 grade cum 430 8,557.02 36,79,517.10
2.2.1.4 Concrete of M30 grade cum 1213 8,696.50 1,05,48,854.37
2.2.1.5 Concrete of M40 grade cum 328 8,975.52 29,43,969.22
2.2.2 All works above plinth level up to floor V level.
2.2.2.1 Concrete of M25 grade cum 70 10,155.73 7,10,901.06
2.2.2.2 Concrete of M30 grade cum 2792 10,324.77 2,88,26,771.38
2.2.2.3 Concrete of M40 grade cum 893 10,574.23 94,42,786.37
2.2.3 All works above floor V level.
2.2.3.1 Concrete of M30 grade cum 1864 10,601.62 1,97,61,425.23
2.5 Providing and laying Damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement :
2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 12.5mm
sqm 110 365.44 40,197.91
nominal size derived from natural sources) including necessary form work, compaction,
finishing etc. complete.

PART D2_BOQ_COPT,IIT BOMBAY 5 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
2.6 Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand
(zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size
derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size,
sqm 278 671.70 1,86,732.02
well rammed and consolidated and grouted with fine sand, including necessary excavation,
levelling , dressing , finishing the top smooth or as directed.

2.7 Centering and shuttering where ever required with adequate bracing, propping etc.,
including cost of de-shuttering and de-centering at all levels, including strutting, propping
and removal of form.
2.7.1 Foundations, footings, bases of columns, etc. for mass concrete sqm 2602 303.45 7,89,587.13
2.7.2 Walls (of any thickness) including attached pilasters, buttresses, plinth and string courses etc
sqm 1541 659.77 10,16,712.61
2.7.3 Suspended floors, roofs, landings, balconies and access platforms. sqm 12407 755.36 93,71,731.30
2.7.4 Lintels, beams, plinth beams, girders, bressummers and cantilevers. sqm 15467 599.47 92,71,972.95
2.7.5 Columns, Pillars, Piers, Abutments, Posts and Struts sqm 9979 792.51 79,08,436.83
2.8 Centering and shuttering where ever required with adequate bracing, propping etc.,
including cost of de-shuttering and de-centering at all levels, over a height of 3.5 m, for every
additional height of 1 metre or part thereof (Plan area to be measured).: as per specification,
drawings and directed.
2.8.1 Suspended floors, roofs, landing, beams and balconies (Plan area to be measured).

2.8.1.1 For 1st Floor with floor to floor height of 6m. sqm 1872 943.77 17,66,731.54
2.8.1.2 For 2nd Floor with floor to floor height of 4.2m and for third to terrace floor with floor to floor
sqm 11969 314.59 37,65,315.14
height of 3.84m, including staircase cap slab.
2.9 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in
position and binding with two strands annealed steel wire of 0.90 mm to 1.6mm twisted
tight etc. all complete.
2.9.1 Thermo-Mechanically Treated bars of grade Fe-550D Up to Plinth Level Kg 258200 88.34 2,28,09,674.60
2.9.2 Thermo-Mechanically Treated bars of grade Fe-550D Above Plinth Level kg 911000 88.34 8,04,78,751.21
2.10 Providing and fixing in position Stainless steel Grade 304 plate-1.0 mm thick as per design for
expansion joints. etc all complete as per the Architectural drawings, as specified and as
directed by the Engineer- in-Charge.
2.10.1 300 mm Wide Rmt 121 1,038.02 1,25,600.46
2.11 Providing and fixing of expansion joint system related with floor location as per drawings.
The joints system shall be of extruded aluminium base members, self aligning / self centering
arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it
provides floor to floor /floor to wall expansion control system for various vertical location in
load application areas that accommodates multi directional seismic movement without
stress to it's components. System shall consist of metal profiles with a universal aluminium
base member designed to accommodate various project conditions and finish floor
treatments. The cover plate shall be designed of width and thickness required to satisfy
projects movement and loading requirements and secured to base members by utilizing
manufacturer's pre-engineered self- centering arrangement that freely rotates / moves in all
directions.

The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside
the corresponding aluminium extrusion cavity to allow freedom of movement and flexure in
all directions including vertical displacement. Provision of Moisture Barrier Membrane in the
Joint System to have watertight joint is mandatory requirement all as per the manufacture's
design and as approved by Engineer-in- Charge. (Material shall confirm to ASTM 6063).etc all
complete as per the drawings.

2.11.1 Floor expansion Joint of 100 mm wide Rmt 121 5,715.47 6,91,571.61
2.12 Providing and fixing of expansion joint system related with wall joint (internal/external)
location as per drawings and direction of Engineer-In-Charge. The joints shall be of extruded
aluminium base members, self aligning / centering arrangement and support plates as per
ASTM B221- 02. The material shall be such that it provides an Expansion Joints System
suitable for vertical wall to wall/ wall to corner application, both new and existing
construction in office Buildings & complexes with no slipping down tendency amongst the
components of the Joint System. The Joint System shall utilize light weight aluminium profiles
exhibiting minimal exposed aluminium surfaces mechanically snap locking the multicellular
to facilitate movement. (Material shall confirm to ASTM 6063).

2.12.1 Wall expansion Joint of 100 mm wide RMT 63 4,764.90 3,00,188.81


2.13 Providing and fixing of expansion joint system of approved make and manufactures for
various roof locations as per approved drawings and direction of Engineer-In-Charge. The
joints shall be of extruded aluminium base members with, self aligning and self centering
arrangement support plates asper ASTM B221-02. The system shall be such that it provides
watertight roof to roof/roof to corner joint cover expansion control system that is capable of
accommodating multidirectional seismic movement without stress to its components.
System shall consist of metal profile that incorporates a universal aluminium base member
designed to accommodate various project conditions and roof treatments.

The cover plate shall be designed of width and thickness required to satisfy movement and
loading requirements and secured to base members by utilizing manufacturer’s pre-
engineered self-centering arrangement that freely rotates /

PART D2_BOQ_COPT,IIT BOMBAY 6 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
moves in all directions. The Self centering arrangement shall exhibit circular sphere ends that
lock and slide inside the corresponding aluminium extrusion cavity to allow freedom of
movement and flexure in all directions including vertical displacement. The Joint System shall
resists damage or deterioration from the impact of falling ice, exposure to UV, airborne
contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture
Barrier Membrane in the Joint System to have water tight join is mandatory requirement.
(Material shall confirm to ASTM 6063). etc all complete as per the Architectural drawings, as
specified and as directed .

2.13.1 Roof expansion Joint of 100 mm wide Rmt 18 5,345.01 96,210.12


2.14 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with
stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including
supply of all the required material, necessary collers, testing of joints etc.all complete as per
the drawings and as directed.
2.14.1 300 mm dia. R.C.C. pipe Rmt 20 888.88 17,777.60
2.15 Providing and placing in position 100 mm thick factory made machine batched & machine
mixed Precast RCC Rectangular Covers on drains of footpath of various sizes, of M-25 grade
cement concrete for RCC work, Precast concrete Trench cover slab for Heavy Vehicular load
including cost of centering, shuttering, reinforcement of 8 mm dia TMT bars of Fe550D grade
@ maximum 100mm c/c on both ways , neat cement punning on finished surface, properly
Sqm 413 2,578.94 10,65,102.06
encased on all edges with 1.6 mm thick , 100 mm wide MS sheet duly painted over priming
coat, reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12 mm dia
bar for hooks etc i/c cost of cartage, all leads & lifts, handling at site etc. all complete as per
the Drawing and as directed.

TOTAL OF CONCRETE WORK 22,77,32,040.06


3 MASONRY WORK
Note : -
(a) All blocks shall be solid and factory made / cast at site and the Contractor shall get
approved the samples of blocks from the Engineer-In- Charge before procurement on large
scale and shall maintain the same for the entire work.
The manufacturer shall conform to the requirements of IS 2185 part 3-1994, shall furnish a
certificate to this effect.
b) Necessary Openings/niches/cut-outs, wherever required as per drawings and instructed by
the Engineer-In-Charge, shall be provided by the Contractor without any extra cost.

c) The rate shall include cost of AAC Blocks/ bricks, labour and making to all geometrical
shapes and sizes, testing, transporting, wastages, handling, scaffolding ,curing etc without
any extra cost to the IITB.
d) The Contractor to indemnify IITB for the payment against taxes, levies, etc. in connection
with the manufacturing of concrete block if precast blocks casted at site are used for
construction.
3.1 Providing and laying Autoclaved Aerated concrete (AAC) blocks masonry with 150mm and
200mm thick with Grade-I AAC blocks of density 551 to 650 kg/ cum, strength of 4 N/mm2
conforming to IS: 2185 (Part 3) in super structure, with RCC band at sill level and lintel level
with approved block laying polymer modified adhesive mortar all complete as per direction
of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for
separately). etc all complete as per the Architectural drawings and as directed.

3.1.1 From plinth level up to floor V level cum 2930 6,892.04 2,01,93,663.75
3.1.2 In super structure above V floor cum 434 7,031.96 30,51,871.60
TOTAL OF MASONRY WORK 2,32,45,535.35
4 WOOD WORK
NOTE:-
a) The item door / window frames shall include sealing the joints all round the brick work /
concrete / block masonry and doors or windows with approved mastic filler or by any other
approved means, by the Contractor at his own cost all as directed by the Engineer-in-Charge
to make the joints water tight.
b) The work contemplated under the item for supplying and fixing the windows / door
frames shall be got done by the Contractor through specialised agencies in the field,
approved by the Engineer-In-Charge.

c) One sample, each of the door frame, shutter and window with all fittings and fixtures
along with locking arrangement including glass panes etc. complete as per schedule of
quantities, drawings and specifications shall be submitted by the Contractor for preliminary
inspection of Engineer in charge before procurement on large scale. The Contractor shall
submit copies of shop drawings for windows, ventilators and steel door frames showing
dimensional details of construction etc. for approval of the Engineer-in-charge. After the
preliminary inspection, the sample shall be fixed at site to ascertain its performance. Large
scale manufacturing shall be taken up only after rectification of defects etc. to the full
satisfaction of the Engineer-in-charge and after obtaining formal approval from the Engineer-
in-charge.

PART D2_BOQ_COPT,IIT BOMBAY 7 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
d) Door frames, shutters and the windows to be supplied and fixed in position should cater
the dimensional tolerance of the openings to an extent of + or -2%. The rates quoted by the
tenderers shall hold good for such variations.
e) Test shall be conducted for the flush doors as per IS-2202-latest revision Part-I from each
consignment and the cost incurred on this account shall be borne by the Contractor.
f) For bonding the flush doors, block boards, ply wood and all types of wood works, phenol
formaldehyde synthetic resin type adhesives conforming to IS 848-1957 shall be used.
g) Mode of measurement shall be as per the specification.

h) Door shutters size mentioned in the item description for structural opening. Shutters size
as per drawing shall be provided after taking consideration of door frames and bottom
clearances.
4.1 Providing and fixing Door frame of 143mm x 57mm and Shutter made of 45mm thick steel
fire check door of 120 minutes fire rating confirming to BS: 476 Part 22 and IS: 3614 Part II
for stability and integrity, fabricated with 2 nos. 18 BWG thick galvanized steel sheet with
infill of fire rated Acrylic Sealant and non-combustible core bonded to both faces of sheet
with lock seam joints at stile edges and internal reinforcement at top, bottom and stile edges
for Fire Rating. The door frames are manufactured from 16 BWG thick galvanized steel sheet
pressed from to double rebate profile of size 143mm x 57mm. The frames shall be fixed using
canon/Hilti anchor bolts of size 10mm dia x 100mm long. The door frames and door shutters
are finished with powder coating etc. all complete as per the Architectural drawings and as
directed by the Engineer- in-Charge.

The cost includes providing and fixing of minimum two-hour fire rated stainless steel ball
bearing hinges 100 mm x 75mm x 3mm (4 hinges per leaf of shutter). The cost shall including
provision for vision panel of required size in shutters etc. all complete as per the
Architectural drawings and as directed.
Note :Providing and fixing Vision Panel shall be paid under relevant Item.
4.1.1 Door Type D2.1, D2.3, D2.4, D3.1, D3.3 D3.5. sqm 392 7,062.00 27,68,304.00
4.2 Wooden Fire Door 45mm 1HR FRL (60/60) 3 Criteria - INTEGRITY / INSULATION/ STABILITY
WOODEN DOOR - Fire Door Tested in accordance to IS: 3614 Part2.
Providing 60 min Fire rated doors system duly tested for 3 criteria - Integrity, Insulation and
Stability Criteria as per the IS: 3614 Part 2 and BS: 476 part 22 at National Test House, Govt of
India laboratory and/or with Central Building Research Institute, Govt of India undertaking
with standard heating conditions as specified in IS:3614 Part II 1992 and BS: 476 part 20 & 22
1987 to achieve the required integrity, insulation and stability (i.e. to restrict the heat
radiation, temperature rise on the non fire side to the maximum of 140° C above the
ambient temperature on the exposed surface of the shutter. The fire doors are tested with
NCBN technology ("Non Combustible by Nature"). with prior approval of the Engineer- in-
Charge.

4.2.1 a) Door Frame: Supplying frames for Fire resistant door shutters 1st class Teakwood Frame
densified at 810 Kilogram/cum and pressure treated with fire retardant chemicals in vacuum
impregnation vessel under 160 psi pressure as per IS:401 and kiln seasoned to moisture
below 15% as per IS:1141 of section 120 X 60 mm spray quoted with 2 coats of intumescent
paint of minimum 200 micron, with single row of Brush, the frame is fitted with intumescent
strip of size 10mm x 4mm of Type ASTROFLAME in the slit of the Frame for fire and smoke
sealing, etc. all complete as per drawings and as directed.

4.2.1.1 Door Type D2.2, D3.2, D3.4 Rmt 504 2,062.00 10,39,248.00
4.2.2 b) Wooden Shutter : Providing and fixing of 45mm thick asbestos free composite - 3 criteria -
fire, heat and smoke check Acoustic Door Shutter with flame guard of 120 minutes IS3614
part -II comprising of 2x9mm Calcium Silicate boards, Chemical treated internal timber with
Fire retardant chemicals in pressure impregnation vessels under 160 PSI pressure as per
IS:401 and kiln seasoned to moisture below 15% as per IS:1141, frame work of 100x32 mm
with 32mm thick infill of ceramic fibre (density 128 Kilograms/Cum), vermiculite mix faced
with 6mm Fire retardant High Density ply, internally lipped with hardwood beading, and
pasted in Hydraulic Press under 50 tonnes pressure, spray quoted with 2 coats of
Intumescent paint of minimum 200 micron, and with 1 row of Brush- Type Astroflame®
intumescent strip (imported) of size 10mmx4mm concealed for fire and smoke sealing in the
grooves for the shutter on all edges except bottom, without any external lipping etc all
complete as per the Architectural drawings, as specified and as directed.

4.2.2.1 Door Type D2.2, D3.2, D3.4 Sqm 210 7,645.00 16,05,450.00
4.2.3 c) Providing and fixing Fire Door Vision Panel: 1 HR rated E Class clear high stress fire rated
glass is pre fabricated strategically inside the shutter structure with 10 mm inside on all sides
with U- glazing. An additional insulated powder coated 'Z' channel of 16 swag MS sheet to be
fixed for reinforcement of the joints including clear fire resistant glass panes 11 mm thick
having minimum 120 minutes fire resistant, and fixing vision panels of specified size with
complete fire rated gasket channel & moulding beading and filling the gap between moulding
/beading and glass with suitable sealant. etc all complete as per the Architectural drawings,
as specified and as directed.
(Note: Mode of measurement of Vision Panel shall be measured only the elevational area
and embedded areas shall not be measured.)

For Door Type D2.1,D2.2,D2.3,D3.1 D3.2, D3.3 D3.4, D3.5 Sqm 87 33,539.00 29,17,893.00

PART D2_BOQ_COPT,IIT BOMBAY 8 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
4.3 Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative
type, core of block board construction with frame of 1st class hard wood and well matched
teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of
shutters. lipping with 2nd class teak wood battens 12 mm minimum depth on all edges of
flush door shutters. The visible external surfaces of the lipping shall be finished with 3 coats
of melamine polish as per approved samples complete as per Architectural drawings and as
directed.
4.3.1 35 mm thick shutter including ISI marked Stainless Steel butt hinges with necessary SS
screws, stainless steel butt hinges (heavy weight) 100x60x2.5mm shall be conforming to IS :
12817.

For Door Type D5.1 sqm 71 2,542.33 1,80,505.57


4.4 Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-
decorative type, core of block board construction with frame of 1st class hard wood and well
matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on
both faces of the shutter, including supply and fixing with Heavy Hinges 100mm x 50mm
x2.5mm, S.S. finish Handle Profile, Ball catch, Tower bolt, lock etc. all complete as per the
Architectural drawings and as directed.

4.4.1 25 mm thick including ISI marked S.S. hinges with necessary size SS screws. sqm 1125 5,528.09 62,19,105.75
4.5 Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss /
matt / suede finish with high density protective surface layer and reverse side of adhesive
bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved
quality. etc all complete as per the Architectural drawings, as specified and as directed.

4.5.1 For all Types of Wooden Doors 1.0 mm thick and for Partitions sqm 10454 752.85 78,70,247.90
4.6 Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand
and manufacture, including providing and fixing top & bottom pivot & double acting
hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing
Sqm 24 4,474.41 1,07,385.74
required door fittings, all complete as per direction of Engineer in charge (Door handle, lock
and stopper etc. to be paid separately) all complete as per the Architectural drawings, as
specified and as directed.
4.7 Providing and fixing 12 mm thick frameless toughened glass for Sliding door shutter of
approved brand and manufacture, including providing and fixing top & bottom pivot and
making necessary holes etc. for fixing required door fittings, all complete as per the drawing Sqm 6 3,111.89 18,671.36
and as directed.
Note: Door Sliding System to be paid under relevant item.
4.8 Providing and fixing IS: 12817 marked Stainless steel satin finish butt hinges (heavy weight)
of size 100mm x 75mm x 3mm of approved make along with necessary SS screws, bolts, nuts,
Nos. 1314 654.31 8,59,757.56
washers etc. as per approved samples all complete as per the Architectural drawings, as
specified and as directed..
Fittings and Fixtures
Note :-
1. One sample board consisting of each item of schedule of quantities with approved quality
fittings & fixtures & necessary accessories including chromium plated brass screws, bolts,
nuts, washers should be submitted for approval of engineer - in - charge. Large scale
procurement shall be taken up only after approval of the Engineer-in-charge. After approval,
the samples shall be kept in the office of the Engineer-in-charge to ascertain the approved
quality.
2. All fittings & fixtures shall conform to relevant IS codes & standards available.
3. Cost of supplying and fixing the fittings and fixtures included in the respective items of
doors mentioned herein above.
4.9 Providing and fixing Stainless steel 304 grade satin finish D' type handle of approved make 19
mm dia (minimum) & 300 mm long, 1.2 mm tube thickness (minimum) back to back (in pair)
with rose, with adjustable fixing for wood and metal door with required brass bush insert, Nos. 86 1,888.00 1,62,368.00
necessary SS screws, bolts, nuts, washers etc. as per approved samples etc. as per drawings,
as directed.
4.10 Providing and fixing Stainless steel 304 grade satin finish D' type handle of approved make 25
mm dia (minimum) & 600 mm long, 1.2 mm tube thickness (minimum) back to back (in pair)
with rose, with adjustable fixing for wood and metal door with required brass bush insert,
Nos. 194 3,771.00 7,31,574.00
necessary SS screws, bolts, nuts, washers etc. as per approved samples complete etc as per
drawings, as specified and as directed.

4.11 Providing and fixing stainless steel 304 grade satin finish square Concealed tower bolt of
approved make 600 mm long, 10mm width along with necessary SS screws, bolts, nuts,
Nos. 49 3,775.00 1,84,975.00
washers etc. as per approved samples complete etc as per the drawings, as specified and as
directed.
4.12 Providing and fixing Dead Lock from approved make of 50 mm (minimum) back set, with
cylinder type one side key and knob on other side, front and strike plate of stainless steel 304
grade, bolt, cylindrical lock & keys (3 set) of brass material along with necessary SS screws, Nos. 224 1,834.00 4,10,816.00
bolts, nuts, washers etc. as per approved samples complete etc as per drawings and as
directed.

PART D2_BOQ_COPT,IIT BOMBAY 9 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
4.13 Panic Bar: (For 2 Hr fire Rated single Panic bar)
Supplying, fitting & fixing Surface mounted Crash Bar/ panic Bar of touch pad style, made of
heavy duty cast iron/ steel body & latches with SS,BHMA certified & conforming to ANSI A
156.3 for grade-1(2 hours fire rated) and suitable for surface mounting to wooden / hollow
Nos. 35 10,800.34 3,78,011.90
metal/ Aluminium framed door, with maximum operating force 8 Kilogram for unlocking
easily & outwardly during emergency complete in all respect as per drawing and as directed.

4.14 Concealed Door Closer : (For 2 Hr fire Rated EN-3 Door Closer) Supplying, fitting & fixing
Surface mounted overhead Door Closer for 2 hour fire rated doors of different size (e.g. size -
EN-3 for leaf width up to 900 mm) CE certified, marked & conforming to EN - 1154 of Nos. 236 4,082.00 9,63,351.95
approved quality . all complete as per the Architectural drawings, as specified and as
directed.
4.14A Providing and fixing aluminium extruded section body tubular type universal hydraulic door
closer (having brand logo with ISi, IS : 3564, embossed on the body, door weight upto 36 kg
to 80 kg and door width from 701 mm to 1000 mm),with double speed adjustment with Nos. 21 843.80 17,719.76
necessary accessories and screws etc. complete for Door types D4.1, D4.2 and D4.3

4.15 Providing and fixing stainless steel 304 grade satin finish Baby Latch of approved quality and
brand fitted and fixed all complete as per the Architectural drawings and as directed. Nos. 30 498.00 14,940.00

4.16 Providing and fixing stainless steel 304 grade satin finish Door Stopper of approved quality
and brand fitted and fixed all complete as per the Architectural drawings and as directed. Nos. 227 228.00 51,756.00

4.17 Providing and fixing Automatic Sliding Single leaf Door Operator Mounted on beam : 4.15
mtrs System application Track passage width up to 2400 mm x 2400 mm Height , including
Floor Guide for Glass Door - 2 Nos, Nemo Motion + Nemo Dual ( Safety& Motion) Combo
Pack, 5 position Program Switch with knob and cable, Cable For Program Switch, Electro
Magnetic Lock - Fail Safe, seals (2nos) max leaf wt. 2*120kg running track, module mounting,
cover profile, end cover, mechanical program switch, door suspension, adjustable floor guide
for glass door, inside & outside clamping rail, glazing gasket, combined detector, for Nos. 1 1,96,722.30 1,96,722.30
automatic sliding door for opening & closing safety, key operated switch, with profile half
cylinder, surface mounted, electromagnetic locking for EC device, overhead safety sensor,
infrared safety beam, Glass holding bracket, bulb seal for fixed glass etc. complete as per
drawing, manufacture specifications and as directed.

4.18 Providing and fixing at all heights and all levels 12 mm thick marine plywood conforming to
IS: 710 for partition / wall lining / frames etc. as required sizes and shapes and fixing to
Aluminium frame work for partition/ wall panelling / counter using drive all, countersunk
stainless steel screws (grade 304) on studs, members of the frame work of the partition, Sqm 3724 1,393.36 51,88,856.25
floors and ceiling channels at a spacing not more than 300 mm centre to centre, etc. all
complete as per the Architectural drawings and as directed.

4.19 Providing & fixing Acoustic fabric panel with 20 mm square natural edge manufactured from
High density glass wool, demountable panels( with standard fabric approved by the Engineer-
In-Charge) and wrapped around in concealed system with grippers.
Size 600x600x20mm, 1200x600mm Acoustics-Sound absorption(Alpha W) - 1 at 200 mm o.d.s
as per EN ISO 354.
Acoustics-Sound absorption Class - Class A at 200mm o.d.s as per EN ISO 11654
NRC - 0.7 NRC as per ASTM C 423.
Indoor Air quality - Complying with the French regulation on VOC emissions, A level. Certified
by the Finnish Building Information Group (RTS) with the M1 label Certified by Eurofins
Indoor Air comfort, Product Certified under GRIHA council of India for Green Ratings,
Environmental Footprint - Environmental Product declaration (EPD) acc to international ISO
14025 & EN 15804 series of standards.

Circularity - Minimum post-consumer recycled content 51%, Fully recyclable.


Fire Safety - Tested and classified as non combustible according to EN ISO 1182 with reaction
to fire classification class A2 s1 d0 according to EN 13501-1 - European Standard.
Humidity Resistance -Class C, relative humidity 95% and 30°C, according to EN 13964:2014.
Light Reflectance - 85% light reflectance.
Sqm 284 6,000.00 17,04,000.00
Cleanability- Daily dusting and vacuum cleaning. Weekly wet wiping.
Accessibility - The tiles are easily demountable
etc. all complete as per the Architectural drawings and as directed.

4.20 Providing and fixing Thermal insulation with Resin Bonded rock wool conforming to IS: 8183,
having density of 48 kg/cum, 50 mm thick, wrapped in 200 G Virgin Polythene Bags fixed to
wall with screws, rowel plugs & washers and held in position by criss crossing GI wire etc. all sqm 1615 273.84 4,42,255.90
complete as per the Architectural drawings and as directed.

4.21 Providing & Fixing Bakelite decorative high pressure laminated sheet of plain / wood grain in
gloss / matt/ suede finish with high density protective surface layer and reverse side of
adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of
approved quality. etc all complete as per the Architectural drawings, as specified and as
directed.
4.21.1 For all Type Wooden Door 2.5 mm thick sqm 71 303.00 21,513.00

PART D2_BOQ_COPT,IIT BOMBAY 10 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
4.22 Providing and fixing Soft board panel of specified sizes having 12 mm thick soft board with 6
mm thick commercial ply back, covered with felt fabric of approved make and shade of
premium quality and cost of fabric of minimum Rs. 300/- per meter. The board shall have 1
mm thick laminate on edge all-round. The board shall be fixed on prepared surface with Sqm. 63 1,826.93 1,15,096.69
necessary hardware fittings etc. Including the complete finished work, all the materials and
labour complete as per the Architectural drawings and as directed.

4.23 Providing and fixing 6mm thk mirror of superior glass (of approved quality) of size 800 X 900
mm with 12 mm thick marine plywood backing, including with mirror, marine plywood, Nos. 93 2,486.16 2,31,213.27
hardware, fixing charges, cleaning etc complete as per directed.
4.24 Providing and fixing Overhead Storage 375 mm Depth . Top, bottom and Shutter is with 19
mm thick and back panel is of 12 mm thick with external side decorative and inside side
1mm laminate factory pressed BWP grade marine ply as per IS 710 of approved brand
Sqm 95 17,161.00 16,30,295.00
including 2mm thick PVC edge banding tape with hot glue by edge bending machine etc. with
DUBB hinges etc. complete as per the directed.
Note. Elevational area shall be measured for payment.
4.25 Providing and fixing Shutter of 19 mm thick BWP grade marine ply as per IS 710 of approved
brand, one side decorative lamination and other side balancing lamination, factory pressed
including 2mm thick PVC edge banding tape with hot glue by edge bending machine for
Sqm 79 2,526.32 1,99,579.22
cupboard, kitchen cabinet under kitchen counter etc. with auto closing spring loaded hinges
(hydraulic type), complete as per the drawing and as directed.

4.26 Providing and fixing at all heights and all levels MDF on partition / wall lining/frames etc. as
required sizes and shapes and fixing to Aluminium frame work for partition/ wall panelling
using drive all, countersunk stainless steel screws (grade 304) on studs, members of the
frame work of the partition, floors and ceiling channels at a spacing not more than 300 mm
centre to centre, etc. all complete as per the Architectural drawings, as specified and as
directed. (Aluminium Frame work will be paid separately)

4.26.1.1 Exterior Grade - I MDF Board 6 mm thick confirming to IS:14587 Sqm 86 631.00 54,518.40
4.26.1.2 Exterior Grade - I MDF Board 8 mm thick confirming to IS:14587 Sqm 58 714.00 41,126.40
4.26.1.3 Exterior Grade - I MDF Board 12 mm thick confirming to IS:14587 Sqm 43 908.00 39,225.60
4.27 Providing and fixing 19 mm thick, 200 mm wide x 200 mm high, Pelmet of flat pressed three
layer or graded plain wood particle board medium density grade I, ISI marked and
conforming to IS : 3087, including top cover of 6 mm commercial ply wood conforming to IS:
303 BWR grade, nickel plated M.S. pipe 20 mm dia ( heavy type) curtain rod with nickel
Rmt 930 2,149.16 19,98,716.38
plated brackets, including fixing with 25x3 mm M.S. flat 10 cm long fixed to pelmet with
hollock wood cleats of size 100 mm x 40 mm x 40 mm on both inner side of pelmet and rawl
plugs 75 mm long etc. all complete.

4.28 Providing & fixing of ISI marked wooden flush door shutter confirming to IS-2202 Part-1,
made from seasoned & chemically treated wood. All Flush doors shall be solid core
construction bonded with pinewood, duly Factory pressed and structurally & dimensionally
stable. The core shall be cladded with 5mm thick ply on both side and shall be finished with 1
mm thick Laminate on both sides, complete. Shutter Edges shall be finished matching to the
door finishing.
Note:
i) Granite Frame work shall be paid under relevant item
ii) Door handle, Hydaulic Door Closer, lock and stopper shall be paid unbder relevant item.

35mm thick solid core Marine Ply shutter fixing with approved Stainless Steel butt Hinges.
sqm 71 3,867.00 2,74,557.00
(the cost of Hinges shall be paid separately)
Fixed Furniture
4.29 Providing & placing in position 30 seater Conference table, made out of marine plywood (
BWP 710 ), base structure made up of Teak wood framing, 50 mm ( d ) x 35 mm ( w ), placed
vertically at 600 mm centre to centre in both directions, curved as per design, covered with 2
layers of 6 mm thick flexible marine plywood from outside for 2 rows of partition one under
table top & other 100 mm above the table on the inner edge of table inclined as per design,
both partitions to be finished with 1 mm thick approved laminate externally as per design.
Top of higher partition to be in BTC of size 50 mm x 25 mm, matt PU polish finish, Stainless
Steel skirting of 1 mm thick, 50 mm high, matt finish to be provided on external surface of
both partitions. Lower partition under table includes bend openable shutters in 19 mm thick
flexible marine plywood at 8 locations as per design,laminate on both sides with

necessary Teak wood framing all around the shutters covered with 1 mm thick approved
laminate, hinges 2 Nos. for each shutter, ball catches, concealed teak wood handles at top
level of shutters & shutter lock as per design. Size of shutter to be 400 mm wide x 690 mm
high ( in case of two shutters - 8 Nos.) & 600 mm wide X 690 mm high ( In case of single
shutter - 2 Nos.). The top of table, made up of 25 mm thick marine plywood finished with 1
mm thick approved laminate.

PART D2_BOQ_COPT,IIT BOMBAY 11 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
Thickness of exposed part of table will be 60 mm, made up of 25 mm thick marine plywood +
Teak wood framing 28 mm + 6 mm thick bottom marine plywood finished with 1 mm thick
approved laminate as per detailed drawing. The edge of table top to be in BTC wood, 60 mm
x 75 mm, as per profile shown in detailed drawing, finished with matt PU polish to match the
colour of laminate. POP UP wire manager system ( 8/12 module for Power/Data/USB etc. to
be provided as required on table top at the centre of table at around 2000 mm centre to
centre distance, complete as per drawing and as directed by Architect/Site in charge.
Size : 10300 mm Length x 4250 mm Width x 750 mm Height Refer Drawing No. JB17-094-A-
TD-931

30 Seater Conference table ( Oval shaped with void in centre ) Nos. 2 4,90,779.00 9,81,558.00
4.30 Providing & placing in position 16 seater meeting table, made out of marine plywood ( BWP
710 ), base structure made up of Aluminium framing, 50 mm ( d ) x 35 mm ( w ), 16 gauge,
placed vertically at 600 mm centre to centre in both directions as per design, covered with 9
mm thick marine plywood from outside, finished with 1 mm thick approved laminate and
matt finish 1 mm thick Stainless Steel ( 304 grade ) skirting of 50 mm height externally. It also
includes 2 openable shutters in 19 mm thick marine plywood finished with 1 mm thick
laminate on both sides including necessary Teak wood framing all around the shutters
covered with 1 mm thick approved laminate, hinges 2 Nos. for each shutter, 2 Nos. of ball
catch,

concealed Teak wood handles at top level of shutters & shutter lock etc. as per design. Size of
each shutter to be 500 mm wide x 690 mm high. The top of the table, made up of Aluminium
framing, 35 mm x 35 mm, 16 gauge, placed horizontally at 600 mm centre to centre (
approx.) covered with 19 mm thick marine plywood on top and 6 mm thick marine plywood
from bottom finished with 1 mm thick laminate on both sides. The edge of table top to be in
BTC wood, 75 mm x 100 mm, as per profile shown in detailed drawing, finished with matt PU
polish to match the colour of laminate. POP UP wire manager system ( 8/12 module for
Power/Data/USB etc. to be provided as required on table top at the centre of table at around
1200 mm centre to centre distance, complete as per drawing and as directed by
Architect/Site in charge.
Size : 5600 mm Length x 1500 mm Width x 750 mm Height Refer Drawing No. JB17-094-A-TD-
930 .

16 Seater Meeting table ( Rectangular ) Nos. 1 1,17,917.00 1,17,917.00


4.31 Providing & placing in position 14 seater meeting table, made out of marine plywood ( BWP
710 ), base structure made up of Teak wood framing, 50 mm ( d ) x 35 mm ( w ), placed
vertically at 600 mm centre to centre in both directions, curved as per design, covered with 2
layers of 6 mm thick flexible marine plywood from outside, finished with 1 mm thick
approved laminate and matt finish 1 mm thick Stainless Steel ( 304 grade ) skirting of 50 mm
height externally. It also includes 2 openable bend shutters in 19 mm thick flexible marine
plywood finished with 1 mm thick laminate on both sides including necessary Teak wood
framing all around the shutters covered with 1 mm thick approved laminate, hinges 2 Nos.
for each shutter, 2 Nos. of ball catch, concealed Teak wood handles at top level of shutters &
shutter lock etc. as per design.

Size of each shutter to be 500 mm wide x 690 mm high. The top of the table, made up of
Aluminium framing, 35 mm x 35 mm, 16 gauge, placed horizontally at 600 mm centre to
centre ( approx.) covered with 19 mm thick marine plywood on top and 6 mm thick marine
plywood from bottom finished with 1 mm thick laminate on both sides. The edge of table top
to be in BTC wood, 75 mm x 100 mm, as per profile shown in detailed drawing, finished with
matt PU polish to match the colour of laminate. POP UP wire manager system ( 8/12 module
for Power/Data/USB etc. to be provided as required on table top at the centre of table at
around 1200 mm centre to centre distance, complete as per drawing and as directed by
Architect/Site in charge.
Size : 4660 mm Length x 1400 mm Width x 750 mm Height Refer Drawing No. JB17-094-A-
TD-931 .

14 Seater Meeting table ( Elliptical ) Nos. 2 1,35,464.00 2,70,928.00


4.32 Providing & placing in position 10 seater meeting table, made out of marine plywood ( BWP
710 ), base structure made up of Teak wood framing, 50 mm ( d ) x 35 mm ( w ), placed
vertically at 600 mm centre to centre in both directions as per design, covered with two
layers of 6 mm thick flexible marine plywood from out side, finished with 1 mm thick
approved laminate and matt finish 1 mm thick Stainless Steel ( 304 grade ) skirting of 50 mm
height externally. It also includes 2 openable bend shutters in 19 mm thick flexible marine
plywood finished with 1 mm thick laminate on both sides including necessary Teak wood
framing all around the shutters covered with 1 mm thick approved laminate, hinges 2 Nos.
for each shutter, 2 Nos. of ball catch, concealed Teak wood handles at top level of shutters &
shutter lock etc. as per design. Size of each shutter to be 400 mm wide x 690 mm high. T

PART D2_BOQ_COPT,IIT BOMBAY 12 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
The top of table to be in 25 mm thick marine plywood finished with 1 mm thick approved
laminate. Thickness of exposed part of table top will be 60 mm, made up of 25 mm thick
marine plywood top + Teak wood framing 27 mm thick + 6 mm thick bottom marine plywood
finished with 1 mm thick laminate as per detailed drawing. The edge of table top to be in BTC
wood, 60 mm x 75 mm, as per profile shown in detailed drawing, finished with matt PU
polish to match the colour of laminate. POP UP wire manager system ( 8/12 module for
Power/Data/USB etc. to be provided as required on table top at the centre of table at around
1200 mm centre to centre distance, complete as per drawing and as directed by
Architect/Site in charge.
Size : 3000 mm Length x 1500 mm Width x 750 mm Height. Refer Drawing No. JB17-094-A-
TD-931.

10 Seater Meeting table ( Elliptical) Nos. 1 82,837.33 82,837.33


4.33 Providing & placing in position 8 seater meeting table, made out of marine plywood ( BWP
710 ), base structure made up of Aluminium framing, 50 mm ( d ) x 35 mm ( w ), 16 gauge,
placed vertically at 600 mm centre to centre in both directions as per design, covered with 9
mm thick marine plywood from out side, finished with 1 mm thick approved laminate and
matt finish 1 mm thick Stainless Steel ( 304 grade ) skirting of 50 mm height externally. It also
includes two openable shutter in 19 mm thick marine plywood finished with 1 mm thick
laminate on both sides including necessary Teak wood framing all around the shutters
covered with 1 mm thick approved laminate, hinges 2 Nos. for each shutter, 2 Nos. of ball
catch, concealed Teak wood handles at top level of shutters & shutter lock etc. as per design.
Size of each shutter to be 400 mm wide x 690 mm high.

The top of table to be in 25 mm thick marine plywood finished with 1 mm thick approved
laminate. Thickness of exposed part of table top will be 60 mm, made up of 25 mm thick
marine plywood top + Teak wood framing 27 mm thick + 6 mm thick bottom marine plywood
finished with 1 mm thick laminate as per detailed drawing. The edge of table top to be in BTC
wood, 60 mm x 75 mm, as per profile shown in detailed drawing, finished with matt PU
polish to match the colour of laminate. POP UP wire manager system ( 8/12 module for
Power/Data/USB etc. to be provided as required on table top at the centre of table at around
1200 mm centre to centre distance, complete as per drawing and as directed by
Architect/Site in charge.
Size : 2360 mm Length x 1060 mm Width x 750 mm Height . Refer Drawing No. JB17-094-A-
TD-930.
8 Seater Meeting table ( Rectangular ) Nos. 1 67,761.00 67,761.00
4.34 Providing & placing in position 10 seater meeting table, made out of marine plywood ( BWP
710 ), base structure made up of Aluminium framing, 50 mm ( d ) x 35 mm ( w ), 16 gauge,
placed vertically at 600 mm centre to centre in both directions as per design, covered with 9
mm thick marine plywood from out side, finished with 1 mm thick approved laminate and
matt finish 1 mm thick Stainless Steel ( 304 grade ) skirting of 50 mm height externally. It also
includes 2 openable shutters in 19 mm thick flexible marine plywood finished with 1 mm
thick laminate on both sides including necessary Teak wood framing all around the shutters
covered with 1 mm thick approved laminate, hinges 2 Nos. for each shutter, 2 Nos. of ball
catch, concealed Teak wood handles at top level of shutters & shutter lock etc. as per design.
Size of each shutter to be 400 mm wide x 690 mm high.

The top of table to be in 25 mm thick marine plywood finished with 1 mm thick approved
laminate. Thickness of exposed part of table top will be 60 mm, made up of 25 mm thick
marine plywood top + Teak wood framing 27 mm thick + 6 mm thick bottom marine plywood
finished with 1 mm thick laminate as per detailed drawing. The edge of table top to be in BTC
wood, 60 mm x 75 mm, as per profile shown in detailed drawing, finished with matt PU
polish to match the colour of laminate. POP UP wire manager system ( 8/12 module for
Power/Data/USB etc. to be provided as required on table top at the centre of table at around
1200 mm centre to centre distance, complete as per drawing and as directed by
Architect/Site in charge.
Size : 3100 mm Length x 1060 mm Width x 750 mm Height . Refer Drawing No. JB17-094-A-
TD-930 .

10 Seater Meeting table ( Rectangular ) Nos. 3 77,034.00 2,31,102.00


4.35 Providing & fixing 6mm thick colour lacquered glass to be fixed on existing ply, lacquered
glass is pasted or fixed with SS studs/adessive with grooves and edge polish as per details
Sqm. 226 1,893.00 4,27,818.00
complete. all complete as per the Architectural drawings and as directed.

4.36 Providing and fixing 75mm height SS skirting made up of 2mm thick plate of 304 grade fixed
on 12 mm thick Marine Plywood at all height of approved make, complete as directed. etc.
Rmt. 439 460.00 2,01,940.00
wherever required all complete as specified, as per Architectural drawings and as directed .

4.37 Providing and fixing Fully Glazed Partition of 12 mm thick toughened float glass fixed at the
floor level with teak wood beading fixed on both sides of the glass finished with polishing as
directed. The toughened float glass to be etched as per approved design (film etching to be
paid separately). The beading for fixing glass to be fixed on both sides of the partition in such
Sqm. 86 3,231.00 2,79,158.40
a way that it would be projected from the partition. Etc all complete as per the Architectural
drawings, as specified and as directed.
Note:- Laminate and aluminium frame work shall be paid under relevant item.

TOTAL OF WOOD WORK 4,13,00,776.63


PART D2_BOQ_COPT,IIT BOMBAY 13 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
5 STEEL WORK
5.1 Structural steel work riveted, bolted or welded in built up sections, trusses and framed
work, including cutting, hoisting, fixing in position and applying a priming coat of approved
Kg 11495 110.32 12,68,077.02
steel primer etc. all complete as per the Architectural drawings, as specified and as directed.

5.2 Steel work welded in built up sections/ framed work using structural steel, including cutting,
hoisting, fixing in position and applying a priming coat of approved steel primer etc. as
required all complete as per the Architectural drawings and as directed.

5.2.1 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works Kg 12200 140.22 17,10,713.52
5.3 Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates
etc., including welding, grinding, buffing, polishing and making curvature (wherever required)
and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the
railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc.,
of required size, on the top of the floor or the side of waist slab with suitable arrangement as
Kg 4710 603.31 28,41,595.52
per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel
members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
, etc. all complete as per the Architectural drawings, as specified and as directed.

5.4 Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in
position and applying a priming coat of approved steel primer etc. as required all complete
as per the Architectural drawings and as directed.
5.4.1 In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever
Kg 13 100.76 1,309.84
required, all complete as per the Architectural drawings and as directed.
5.5 Supplying and fixing Rolling shutters of approved make, made of required size M.S. laths,
interlocked together through their entire length and jointed together at the end by end
locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements
for inside and outside locking with push and pull operation complete, including the cost of
providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile
steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of
required thickness for rolling shutters., etc. all complete as per the Architectural drawings, as
specified and as directed.

5.5.1 80x1.25 mm M.S. laths with 1.25 mm thick top cover sqm 45 2,964.87 1,33,419.22
5.5.2 Providing and fixing ball bearing for rolling shutters. Nos. 4 418.01 1,672.03
5.6 Extra on item 5.5 for providing mechanical device chain and crank operation for operating
rolling shutters.

5.6.1 Exceeding 16.80 sqm in area sqm 29 1,092.51 31,682.88


Note:- Area beyond 16.80 sqm. To be pay for the Payment
5.7 Extra on item 5.5 for providing grilled rolling shutters manufactured out of 8 mm dia M.S.
bar instead of laths as per design approved by Engineer-in- charge, (area of grill to be
measured)., etc. all complete as per the Architectural drawings, as specified and as directed. sqm 3 659.18 1,977.55

TOTAL OF STEEL WORK 59,90,447.58


6 FLOORING & WALL LINING WORKS
Note:
a) The floor finish level shall be generally in level matching with the surrounding floor finish
level & as per drawing. No extra payment shall be entertained for matching the floor
differences.
b) Adjustment of levels in thickness of mortar bedding due to different types of flooring, if
any, shall be done by the Contractor without any extra cost to the Department.

c) The Contractor shall submit and get approved the samples for flooring , skirting, dado tiles
for approval of the Engineer-in- Charge before bulk procurement.

d) Pattern & design of flooring/ skirting/ dado shall be approved by the Engineer-in- Charge
before commencement of work.
e) Exposed edges of all natural stones used for the works like Kotah, Marble, Granite etc.
Shall be machine cut and shall have uniform thickness and mirror polished unless otherwise
mentioned.
f) All polishing shall be mirror polished unless otherwise specified.
6.1 Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey
cement slurry mixed with pigment to match the shade of the slab, including rubbing and
polishing with three grooves as per detail drawing complete with base of cement mortar 1 :
4 (1 cement : 4 coarse sand) :, etc. all complete as per the Architectural drawings and as
directed.
6.1.1 25 mm thick sqm 716 1,681.09 12,03,662.16
6.2 Kota stone slabs of 25mm thick for treads of stairs in single piece laid over 20 mm (average)
thick base and jointed with grey cement slurry mixed with pigment to match the shade of
the slab, including rubbing and polishing with three grooves as per detail drawing complete sqm 403 2,474.00 9,97,022.00
with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) etc. all complete as per the
Architectural drawings and as directed.

PART D2_BOQ_COPT,IIT BOMBAY 14 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
6.3 Kota stone of 20 mm thick for risers of stairs single piece with 12 mm (average) thick cement
mortar 1:3 (1 cement: 3 coarse sand) backing and jointed with grey cement slurry mixed with
pigment to match the shade of the slabs, including rubbing and polishing complete. , etc. all sqm 305 2,590.00 7,89,950.00
complete as per the Architectural drawings and as directed .

6.4 Providing and laying River washed Granite stone in flooring, ramps, treads of steps etc. in
required design and patterns, in linear as well as curvilinear portions of the building all
complete as per the architectural drawings with 18 mm thick stone slab over 20 mm
(average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with
cement slurry and pointing with white cement slurry admixed with pigment of matching
shade including rubbing, curing and polishing etc. all complete as per the Architectural
drawings and as directed .
6.4.1 18mm thick River Finish Granite stone sqm 103 6,182.00 6,36,746.00
6.5 Providing and laying Polished Granite stone in single piece for ramps, treads of steps,
door/window thresholds, top of bund walls etc. in required design and patterns, in linear as
well as curvilinear portions of the building, all complete as per the architectural drawings,
with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1
cement : 4 coarse sand), laid and jointed with cement slurry and pointing with white cement
slurry admixed with pigment of matching shade, including rubbing, curing and polishing,
making 3 nos. grooves 6mm x 3mm complete etc. all complete as per the drawing and as
directed.
6.5.1 18mm thick Polish Granite stone slab : 'Light Grey' sqm 755 2,552.09 19,26,826.03
6.6 Providing and fixing machine cut, 18 mm thick pre-polished granite stone in single piece for
wall lining, dado, skirting, risers of steps, columns etc. of required design and pattern, on 12
mm (average) thick cement mortar 1:3 (1 cement : 3 coarse sand) laid and jointed with
cement slurry @ 3.3 kg/sqm including pointing with white cement slurry admixed with
pigment of matching shade including rubbing, curing and polishing etc. wherever required all
complete as per Architectural drawings and as directed.

6.6.1 Polished 'Light Grey' granite stone sqm 189 3,060.16 5,78,370.18
6.7 Providing edge moulding to 18 mm thick granite steps, including machine polishing to edge
to give high gloss finish etc. wherever required all complete as per Architectural drawings Rmt 79 412.73 32,606.05
and as directed.
6.8 Providing and fixing machine cut, polished , Composite marble stone work for wall lining
including dado, skirting, risers of steps etc., in required design and pattern wherever
required, stones of different finished surface texture, on 12 mm (average) thick cement
mortar 1:3 (1 cement : 3 coarse sand) laid and jointed with white cement slurry @ 3.3
kg/sqm including pointing with white cement slurry admixed with pigment of matching
shade, including rubbing, curing, polishing etc. all complete as per drawings and as directed.

6.8.1 15 mm Thick Composite Marble sqm 1421 6,816.00 96,85,536.00


6.9 Providing and laying Vitrified floor tiles in different sizes (thickness to be specified by the
manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of
approved makes, in all colours and shades, laid on 20 mm thick cement mortar 1:4 (1 cement
: 4 coarse sand), including grouting the joints with white cement and matching pigments etc.
all complete as per Architectural drawings and as directed.

6.9.1 MATT finish heavy duty industrial Vitrified Tiles of size 600x600 mm sqm 5655 1,462.00 82,67,610.00
6.9.2 600X600 mm thick Soluble salt Vitrified tile below carpet sqm 861 1,139.00 9,80,679.00
6.9.3 MATT finish GVT Vitrified Tiles of size 600x600 mm sqm 3760 1,151.00 43,27,760.00
6.10 Providing and laying Vitrified tiles in different sizes (thickness to be specified by
manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of
approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of
cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm
including grouting the joint with white cement & matching pigments etc. complete. etc.
wherever required all complete as specified, as per Architectural drawings and as directed.

6.10.1 From heavy duty industrial Size of Tile 600x600 mm sqm 3679 1,506.00 55,40,574.00
6.10.2 From GVT Vitrified Tiles Size of Tile 600x600 mm sqm 1332 1,195.00 15,91,740.00
6.11 Providing and fixing Ist quality ceramic glazed wall tiles of size 600 x 300 mm conforming to
IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours,
shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge,
in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement :
sqm 142 1,281.00 1,81,902.00
3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in
white cement mixed with pigment of matching shade etc. wherever required all complete as
specified, as per Architectural drawings and as directed.

6.12 Providing and fixing Crazy ceramic tile flooring, with under layer 12 mm thick cement mortar
1:4 (1 cement: 4 coarse sand), with joints not exceeding 5 mm, including filling the gaps with
ordinary cement mixture & mixing with synthetic polyester fibre, triangular in shape having
specific gravity of 1.34 to 1.40, cross section size ranging from 10 to 40 micron & length up to
sqm 2928 803.54 23,52,778.09
6mm , mixing fibre @ 125 grams per 50 kg of cement in cement mortar, including providing
and mixing water proofing material in mortar @ 1 kg per 50 kg of cement, all complete as
per Architectural drawings and as directed.

PART D2_BOQ_COPT,IIT BOMBAY 15 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
6.13 Providing and fixing at all heights ceramic mosaic tiles of approved make, size of 50mm x
25mm, of approved colour and texture and in the approved pattern in combination with
other cladding material including scaffolding, up to 20 mm thick CM 1:4 cement mortar
backing (in two coats) and matching the surface of other cladding materials used in the
sqm 8176 2,036.00 1,66,46,336.00
pattern, including necessary adhesives as per manufacturers specifications and finished with
grouting materials in the joints in approved colour as directed with, including curing, cleaning
with soap water and acid complete as per the drawing and as directed.

6.14 Providing and fixing 18 mm thick Composite Marble of approved colour and shade, mirror
polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters,
window sills, door jambs, soffits, facias and similar locations of required size, approved
shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse
sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups,
including rubbing, curing, moulding and polishing to edges to give high gloss finish etc.at all
levels complete as per Architectural drawings and directed.

6.14.1 Area of slab over 0.50 sqm sqm 152 4,347.00 6,60,744.00
6.15 Providing and fixing stone slab with table rubbed, edges rounded and polished, of size
90cmx50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of
appropriate width with chase cutter and embedding the stone in the chase with epoxy grout
or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm
nominal size) as per direction of Engineer-in-charge and finished smooth.

6.15.1 Composite Marble of any colour and shade sqm 51 8,206.00 4,18,506.00
6.16 Providing 25 mm to 30 mm thick partition of polished black kadappa stone slab of approved
quality including giving required size and shape etc. Fixing in cement mortar 1:3 curing
complete.Both side polish all complete at all levels, etc. wherever required all complete as sqm 105 1,210.60 1,27,113.35
specified, as per Architectural drawings and as directed..

6.16 Providing and laying Vinyl Hetrogeneous Composite flooring of approved brand &
manufacturer, in all colours and shade, in flooring , skirting, riser of steps, laid with cement
based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477,
in average 6 mm thickness, including grouting of joints etc. wherever required all complete
as specified, as per Architectural drawings and as directed.

6.16.1 Vinyl Hetrogeneous Composite flooring. sqm 284 3,111.00 8,83,524.00


6.17 Providing and laying 100 % Nylon Multilevel loop pile Carpet Tiles of Brand shade approved
by architect in 18oz Quality having 100 % solution dyed, of 1/12th gauge having pile thickness
of 3mm total thickness 6.5mm. PIt should be antimicrobial and with soil/stain protection. Tile
size 50cm x 50cm and tile backing should be of glass bac having minimum 32 % recycle
content including minimum 30 % post consumer content. Product should comply with CRI sqm 577 2,238.00 12,91,326.00
Green label plus standards. Floor carpet for inside Hall flooring which shall be free from dust
completed as per Architect instruction and design/approval etc all complete as per the
Architectural drawings, as specified and as directed.

6.18 Providing and fixing removable raised / false access flooring with system and its
Components of approved make for different plenum height with possible height adjustment
up to 50 mm, comprising of modular load bearing floor panels supported on G.I. rectangular
stinger frame work and G.I. Pedestal etc. all complete, as per the architectural drawings, and
as directed.
(a) Providing at required spacing to form modular framework, pedestals made out of GI tube
of thickness minimum 2 mm and 25 mm outer diameter, fully welded on to the G.I. Base
plate of size 100mm x 100mm x 3mm at the bottom of the pedestal tube, G.I. pedestal head
of size 75mmx75mmx3.5 mm welded with GI fully threaded stud 16 mm outer
diameter with two GI Check nuts screwed on the stud for level adjustment up to 50mm,
locking and stabilizing the pedestal head in position at the required level. The pedestals shall
be fixed to the subfloor (base) through
base plate using epoxy based adhesive of approved make or the machine screw with rawl
plug.

(b) Stringers system in all steel construction hot dipped galvanized of rectangular size
570x20x30x0.80mm thick having holes at both ends for securing the stringers on to the
pedestal head using fully threaded screws ensuring maximum lateral stability in all directions,
the grid formed by the pedestal and stringer assembly shall receive the floor panel, this
system shall provide adequate solid, rigid support for access floor panel, the system shall
provide a minimum clear uninterrupted clearance between the bottom of the floor for
electrical conduits and wiring etc. all complete as per the architectural drawings, as specified
and as directed by the Engineer-in-charge.

(c) Providing and fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti
static high pressure Lamination of 800H grade (FS800H). Access Floor panel shall be steel
welded construction with an enclosed bottom pan with uniform pattern of 64 hemispherical
cones. The top and bottom plates of Steel Gauges: top 0.6 mm and bottom 0.7 mm fused
spot welded together (minimum 64 welds in each dome and 20 welds along each flange). The
panel should be Corroresist epoxy coated for lifetime rust protection and cavity formed by
the top and bottom plate is filled with Pyrogrip non-combustible Portland cementitious core
mixed with lightweight foaming compound.

PART D2_BOQ_COPT,IIT BOMBAY 16 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
The access floor shall be factory finished with Anti-static High Pressure laminate with Non
Warp technology up to 1mm thickness for superior adhesion and Surface flatness within
0.75mm.The panel is to withstand a Concentrated Load of 363 kgs applied on area 25mm x
25mm without collapse in the centre of the panel which is placed on four steel blocks. The
panel will withstand and Uniformly Distributed Load (UDL) minimum 1250 kg/sqm and an
impact load of 50kg all complete as per the approved manufacturers specification and as per
the direction of Engineer-in-charge. All specification must be printed on the side of the panel
to ensure the quality of the product.

6.18.1 150 mm Finished Floor Height (FFH) sqm 45 5,019.73 2,25,887.68


6.18.2 300 mm Finished Floor Height (FFH) sqm 35 5,019.73 1,75,690.41
6.18.3 450 mm Finished Floor Height (FFH) sqm 29 5,328.21 1,54,517.96
TOTAL OF FLOORING & WALL LINING WORKS 5,96,77,406.91
7 ROOFING
7.1 Providing & fixing false ceiling at all height including providing & fixing of framework made of
special section, power pressed from M.S. sheets and galvanised with zinc coating of 120 gms/
sqm (both side inclusive) as per IS : 277 and consisting of angle cleat of size 25mm wide x
1.6mm thick with flanges of 27mm and 37 mm, at 1200 mm c/c, one flange fixed to the
ceiling with dash fastener 12.5mm dia x 50mm long with 6mm dia bolts, other flange of cleat
fixed to the angle hangers of 25 x10 x0.50mm of required length with nuts & bolts of
required size and other end of angle hanger fixed with intermediate G.I channels 45 x15 x
0.90mm running at the spacing of 1200 mm c/c, to which the ceiling section 0.5mm thick
bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5mm, at 450
mm c/c, shall be fixed in a direction perpendicular to

G.I intermediate channel with connecting clip made out of 2.64mm dia x 230 mm long G.I
wire at every junction, including fixing perimeter channels 0.50mm thick 27mm high having
flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/ partitions with the
help of Rawl plugs at 450 mm centre, with 25mm long dry wall with 25mm long

long dry wall screws @ 230 mm interval, including fixing of Calcium Silicate Board to ceiling
section and perimeter channels with the help of dry wall screws of size 3.5 x25mm at 230
mm c/c, including jointing & finishing to a flush finish of tapered and square edges of the
board with recommended jointing compounds, jointing tapes, finishing with jointing
compounds in three layers covering up to 150mm on both sides of joints and two coats of
primer suitable for boards, all as per manufacture's specification and also including the cost
of making opening for light fittings, grills, diffusers, cut outs made with frame of perimeter
channels suitably fixed, all complete as per drawings, specification and direction of the
Engineer in charge but excluding the cost of painting etc. all complete as per the
Architectural drawings, and as directed.

7.1.1 10 mm thick Calcium Silicate Board made with Calcareous & Siliceous materials reinforced
sqm 7663 1,521.46 1,16,58,929.59
with cellulose fibre manufactured through autoclaving process.
7.2 Providing & Fixing horizontal level suspended ceiling comprising of Armstrong GI Microlook
Lay-in Micro Perforated metal ceiling consisting of 600x600mm (Nominal Size) Lay-in tiles of
120 gsm galvanized steel as per IS 277 (2003) suitable for architectural finishes in 0.5 mm
thickness as per IS:513 (1994) in Global white color with Square Tegular/Microlook 90˚ edge
having 8mm drop and 5.5mm flange. Tile shall have perforation having hole diameter 1.8mm
and open area 20% with linear and diagonal pitch of 5mm and 3.5mm respectively and a
border of 9.1mm. The difference between the 2 diagonal dimensions of the tile to be less
than 1mm. Tiles shall be flattened by precision leveller to minimize sag to less than 1/400
mm. The tile shall be electrostatically polyester powder coated using RoHS compliant powder
having coating thickness ranging from 60-80 microns.

The powder coating shall pass Salt Spray Test for 750 Hours as per ASTM B117, QUV –A Test
for 1000 hours as per ASTM G-154 – (Cycle – 1) and Humidity test for 1000 hours as per DIN
50017. The powder coating shall have an adhesion of GT0 as per EN ISO 2409. The shade
variation across batches shall be delta E<1 using Excite/BYK Gardner instrument and gloss
level 25±5% at 60˚ as per ASTM D523. The tile shall have a Light Reflectance of ≥ 63% in
accordance to ASTM 1477-98.
Back side of the tile will have Soundtex fleece hot pressed mechanically for uniform bonding
to achieve NRC up to 0.7 (Average value of Absorption Co-efficient readings taken at 250 Hz,
500 Hz, 1000 Hz and 2000 Hz) as per ASTM C-423 and Fire Performance of Class 0/1 as per BS
476 Part 6 & 7 in module size of 600x600mm. All border cut tiles shall be laid, using
Armstrong lay-in end cap for installation to have a Microlook effect on perimeters. all
complete as per drawings, specification and direction of the Engineer in charge but excluding
the cost of painting with:, etc. all complete as per the Architectural drawings, as specified
and as directed by the Engineer- in-Charge.

7.2.1 GI Metal Ceiling sqm 897 1,568.46 14,06,909.68

PART D2_BOQ_COPT,IIT BOMBAY 17 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
7.3 Providing and fixing Mineral fibre false ceiling tiles at all heights of size 595X595mm of
approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of
99%, Light Reflectance >85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance
as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot
dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising
of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200
mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid
module of size 600x600 mm suspended from ceiling using galvanized mild steel item
(galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter
fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2
mm, spaced at 1200 mm centre to centre along main ‘T’.

The system should rest on periphery walls /partitions with the help of GI perimeter wall
angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help
of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The
exposed bottom portion of all T-sections used in false ceiling support system shall be pre-
painted with polyester baked paint, for all heights. The work shall be carried out as per
specifications, drawings and as per directed.

7.3.1 With 20 mm thick bevelled tegular mineral fibre false ceiling tile (NRC 0.7) sqm 1243 2,327.61 28,93,223.38
7.4 Providing & Fixing Of Classic Axiom Perimeter Trim with 19 mm face for perimeter solution
of acoustical ceiling using appropriate Accessories Classic Vector Axiom (AX4VESTRI/
AX4VECURI xx) to offer perimeter solution with acoustical ceiling system. Classic Vector
Axiom (AX2STR42I/ AX2CUR42Ixx) is made of extruded aluminium of O/L dimension of 19.3 x
100 x 3000 mm. The inverted F- Shape section provides 2 flanges and 19 mm face for resting
of tiles. Classic Axiom must be powder coated in Global White. Profile to have engineered
design boss for fitment of Tee bar connector, Splice plate Corner connector & hanger clips.
Classic Axiom ( AX4VECURI xx) can be curvered to a minimum radius of 600 mm Axiom Splice
Plate
(AX4SPLICEI/AXSPLICEI): Formed to fit into special boss in the Axiom and locked in place with
factory-installed screws.

These Steel splice plates (AX4SPLICEI) are used to align and secure all joints between sections
of Axiom trims. Corners are to be formed by mitring the end of axiom and splice plate
(AXSPLICE) to be bent at right angle for connecting the end pieces. Axiom Tee-Bar
Connection Clip (AXTBCI): Commercial quality G.I formed to fit into special boss of trim and
locked in place by factory-installed screws and attached to (XL-24 / XL- 15/Silhouette)
suspension system members. T-Bar connection clips are used to attach the Axiom to the
supporting Suspension system members. One clip is required at each location where the grid
system intersects the Axiom trim. Hanging Grid clips (AXHGCI): Axioms to be hung
independently to the structural soffit by engaging the Hanging Grid Clip into the boss of the
Axiom trim channel and securing it to structural soffit Suspension .

INSTALLATION: Hang the sections of Axiom


Trim onto the grid system by engaging the top ear of the connection clip under the boss of
the channel trim. Slide the lower leg downward to engage the lower boss on the trim and
secure by tightening the locking screw. Complete the installation of all channel trims
Rmt 75 1,302.74 97,705.50
sections. Install and secure the splice plates, corner pieces, and alignment plate’s etc. Make
adjustments as necessary to properly align the complete installation.

7.5 Acoustical microlook tegular edge tile with 15 mm thickness ,easily demountable tile ,
manufactured from High density glass wool , visible surface is a batch painted glass tissue in
white, back of the tile covered with glass tissue. Size 600 x 600 x 15 mm, 1200 x 600 x 15 mm
Acoustics-Sound absorption(Alpha W) - 0.95 at 200 mm o.d.s as per EN ISO 354.
Acoustics-Sound absorption Class - Class A at 200 mm o.d.s as per EN ISO 11654.
Acoustics-Articulation class - 180 as per ASTM E1111, ASTM E1110
NRC - 0.9 NRC as per ASTM C 423.
Humidity Resistance -Permanent ambient RH up to 95% at 30*C without sagging, warping
and delaminating ( 13964:2014).

Fire Safety - Tested and classified as non combustible according to EN ISO 1182 with reaction
to fire classification class A2 s1 d0 according to EN 13501-1 - European Standard.
Light Reflectance - 83% light reflectance.
Indoor Health & Well-being - Complying with the French regulation on VOC emissions, A+
level. Certified by the Finnish Building Information Group (RTS) with the M1 label. Free from
substances of very high Concern (SVHC) above 100 ppm as defined by the European REACH
regulation (No1907/2006).Product Certified under GRIHA council of India for Green Ratings.
Environmental Product declaration (EPD) acc to international ISO 14025 & EN 15804 series of
standards.

Circularity - Re-cycled content of more than 70%


Environmental Footprint - Environmental Product declaration (EPD) acc to international ISO
14025 & EN 15804 series of standards sqm 490 3,007.18 14,73,520.45
CE marking - CE-marked according to the harmonised standard EN 13964:2014
Maintenance - Weekly dusting and vacuum cleaning.
PART D2_BOQ_COPT,IIT BOMBAY 18 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
TOTAL OF ROOFING 1,75,30,288.60
8 FINISHING
PLASTERING WORKS
Note : -
a) Before commencement of plastering, the area shall be cleaned, wetted and shall be
marked with 'Thiyyas' or 'Tapanis' and shall be got approved by the Engineer-in-charge.

b) Whenever the electrical Contractor/ agency has to fix up switch boxes in walls, necessary
Thiyyas or 'Dhadas' shall be arranged prior to plastering so that the electrical boxes are fixed
the finished plastered surfaces. Properly in line with
c) Finishing around the junction boxes shall be done at all floor, level and position to the line,
level and right angles as required while carrying out plastering work.
d) No extra claim/cement consumption shall be entertained by the Department for the
plastering done more than the specified thickness shown in the schedule of quantities, to
bring the plastered surface to perfect line, level and plumb with adjoining columns and
beams.
e) Rate quoted shall include cost of double scaffolding , cleaning of surfaces, curing, hacking
the surface for applying plaster etc at all heights.
f) Rate quoted shall include cost of providing PVC wire mesh strips with 200 mm width at
junctions of concrete and masonry or any dissimilar materials
8.1 Providing and applying 18 mm thick (average) in two coats under layer 12 mm thick cement
plaster 1:5 and a top layer 6mm thick cement plaster (1:3). complete as per manufacturer's
sqm 625 455.11 2,84,441.87
specifications up to 10 meters form ground level etc. all complete as per the Architectural
drawings and as directed.
8.2 Providing and applying 18 mm thick (average) in two coats under layer 12 mm thick cement
plaster 1:5 and a top layer 6mm thick cement plaster (1:3). complete as per manufacturer's
specifications and height more than 10 m from ground level for every additional height of 3
m or part thereof including scaffolding as per direction of , etc. all complete as per the
Architectural drawings and as directed.

8.2.1 Above 10m to 13m sqm 98 526.84 51,630.72


8.2.2 Above 13m to 16m sqm 98 598.58 58,660.96
8.2.3 Above 16m to 19m sqm 107 670.32 71,724.06
8.2.4 Above 19m to 22m sqm 98 742.06 72,721.44
8.2.5 Above 22m to 25m sqm 98 813.79 79,751.67
8.2.6 Above 25m to 28m sqm 98 885.53 86,781.91
8.3 Providing and applying CEMENT PLASTER 15 mm cement plaster 1:4 (1 cement: 4 coarse
sand) on rough side of single or half brick wall up to 10 meters height from ground level,
including levelling, leaving the surface rough to receive Ceramic Mosaic Tile Cladding,
sqm 8141 349.32 28,43,849.13
scaffolding, curing etc. all complete as per the Architectural drawings and as directed.

8.4 Providing and applying CEMENT PLASTER 15 mm cement plaster 1:4 (1 cement: 4 coarse
sand) on rough side of single or half brick wall above 10 meters height including levelling,
leaving the surface rough to receive Ceramic Mosaic Tile Cladding, scaffolding, curing etc.
all complete as per the Architectural drawings and as directed.

8.4.1 Above 10m to 13m sqm 770 421.06 3,24,217.29


8.4.2 Above 13m to 16m sqm 901 492.80 4,44,011.48
8.4.3 Above 16m to 19m sqm 785 564.54 4,43,160.49
8.4.4 Above 19m to 22m sqm 754 636.27 4,79,749.68
8.4.5 Above 22m to 25m sqm 754 708.01 5,33,839.46
8.4.6 Above 25m to 28m sqm 751 779.75 5,85,590.01
8.4.7 Above 28m to 30m sqm 625 851.48 5,32,177.59
8.5 Providing and applying 12 mm thick (average) ready mixed cement plaster mortar 1:4 ((1
cement: 4 fine sand ) complete as per manufacturer's specifications and direction of
Engineer-in-charge at all heights and levels including preparing the surface, hacking the sqm 6498 290.55 18,87,962.64
surfaces. scaffolding, curing etc. all complete as per the Architectural drawings and as
directed.
8.6 Providing and applying white Cement based putty of average thickness 1 mm to 2 mm, of
approved brand and manufacturer, over the plastered wall surface to prepare the surface
sqm 135 122.04 16,475.64
even and smooth complete etc. all complete as per the Architectural drawings and as
directed.
8.7 Providing and applying 12 mm thick (average) premixed formulated one coat gypsum
lightweight plaster having additives and light weight aggregates as vermiculite/ perlite
respectively conforming to IS: 2547 (Part - 1 & II) 1976, applied on hacked / uneven
sqm 27883 358.14 99,86,118.84
background such as bare brick/ block/ RCC work on walls and similar locations etc. at all
floors and locations, finished in smooth line and level etc. all complete as per the
Architectural drawings and as directed.
8.8 Providing & applying in desired finish , on exterior surface at all heights and levels acrylic
texture plaster 'Apex Duracast Roughtex' of Asian paints or equivalent as given in list of
approved make, overall thickness up to 1.5mm applied @ 3.08kg per sqm. As per
manufacture's specification and direction of Engineer-in-Charge etc. all complete as per the sqm 692 241.42 1,67,064.72
Architectural drawings and as directed.

PART D2_BOQ_COPT,IIT BOMBAY 19 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
8.9 Providing and Finishing walls with anti-fungal, Premium 100% Acrylic Smooth exterior paint
with Silicone additives of to give an even shade, in required colours and shades etc.

8.9.1 Two or more coats applied @ 1.43 litre/ 10 sqm over and including priming coat of exterior
primer applied @ 2.20 kg/ 10 sqm etc. all complete as per the Architectural drawings and as sqm 692 159.98 1,10,705.95
directed.
8.10 Providing and applying Plastic emulsion paint for Ceiling of approved quality, colour and
shade to new surface in three coats including scaffolding, preparing the surface. etc. all
sqm 8872 141.01 12,51,047.29
complete as per the Architectural drawings, as specified and as directed.

8.11 Providing and applying Luster paint of approved make on internal wall surface as detailed
below , Scrapping the surface with emery paper and wipe clean wall primer with brush with
mineral turpentine with brush 8 to 10% and oil 15 to 20% with roller and allowing to dry for a
period 6 to 8 hours. wall putty with appropriate proportion of water allowing to dry for a
period of 4 to 6 hours. Scrapping with Emery paper 180 and wipe clean. applying wall primer
with brush with mineral turpentine 8 to 10% and oil 15 to 20% with roller Scrapping Emery
paper 320 and wipe clean, interior wall finish luster 1st coat with rush/rubber/spray with sqm 27883 248.60 69,31,622.12
mineral turpentine 7 to 9% and Oil with roller 19 to 21% ,after 8 hours of activity applying
2nd coat of wall finish Lustre with mineral turpentine 7 to 9 % with brush and Oil with roller
19 to 21% after allowing dry for the period of 6 to 8 hours activity. etc all complete as per the
Architectural drawings and as directed.

8.12 Painting with synthetic enamel paint of approved brand and manufacture to give an even
shade etc. all complete as per the Architectural drawings, as specified and as directed.

8.12.1 Two or more coats on new work sqm 1179 129.53 1,52,716.85
8.13 Finishing walls with Apex ultima Exterior paint of required shade : (Two or more coats
applied @ 3.28 litre/10 sqm) over and including priming coat of exterior primer applied @
sqm 337 241.42 81,359.55
2.20kg/10 sqm all complete as per the Architectural drawings, as specified and as directed.

TOTAL OF FINISHING WORK 2,74,77,381.36


9 ROAD WORK
9.1 Providing and laying 60 mm thick factory made cement concrete interlocking paver block of
M -30 grade made by block making machine with strong vibratory compaction, of approved
size, design & shape, laid in required colour and pattern over and including 50mm thick
sqm 1091 937.12 10,22,392.90
compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the
Architectural drawings, as specified and as directed by the Engineer- in-Charge.

9.2 Construction of granular sub-base by providing close graded Material conforming to


specifications, mixing in a mechanical mix plant at optimum moisture content (OMC) ,
carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform
layers of specified thickness with motor grader on prepared surface and compacting with
vibratory power roller to achieve the desired density, complete as per specifications etc. all
complete as per the Architectural drawings, as specified and as directed by the Engineer- in-
Charge.
9.2.1 With material conforming to Grade-I (size range 75 mm to 0.075 mm) having CBR Value-30
cum 419 2,619.29 10,97,483.24
9.3 Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to
0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with
water at Optimum moisture content (OMC) in for all leads & lifts, laying in uniform layers
with mechanical paver finisher in sub- base / base course on well prepared surface and cum 419 2,762.72 11,57,578.30
compacting with vibratory roller of 8 to 10 tonne capacity to achieve the desired density, all
complete as per the Architectural drawings etc and as directed.

9.4 Providing and laying factory made chamfered edge Cement Concrete paver blocks In foot
path, park & lawns driveway or light & traffic parking etc. of required strength, thickness &
size/ shape, made by table vibratory method using PU mould, laid in required colour &
pattern over 50mm thick compacted bed of course sand, compacting and proper
embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory
compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as
per required size and pattern, finishing and sweeping extra sand, all complete as per
manufacturer's specifications & direction etc. all complete as per the Architectural drawings
and as directed.

9.4.1 80 mm thick Cement concrete paver block of M-30 grade with approved colour, design &
sqm 1700 996.44 16,93,942.02
pattern.
9.5 Providing and laying at or near ground level factory made kerb stone/water table of M-25
grade cement concrete in position to the required line, level and curvature, jointed with
cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without
grooves (thickness of joints except at sharp curve shall not be more than 5mm), including
cum 99 8,487.79 8,40,291.42
making drainage opening wherever required complete etc. all complete as per the
Architectural drawings, as specified and as directed. (length of finished kerb edging shall be
measured for payment). (Precast C.C. kerb stone/water table shall be approved by Engineer-
in-charge).
9.6 Plain Cement Concrete M15 (zone-III) derived from natural sources : 4 graded stone
cum 29 7,257.62 2,10,470.95
aggregate 20 mm nominal size derived from natural sources)
TOTAL OF ROAD WORK 60,22,158.83
10 ALUMINIUM WORK
PART D2_BOQ_COPT,IIT BOMBAY 20 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
Note: -
i) The Contractor shall submit 3 copies of shop drawings for each windows, ventilators
showing dimension details of construction etc. for approval of the Engineer - in - charge.
According to the approved shop drawing a sample of each of windows with all fittings and
fixtures with locking arrangement including glass panes etc. complete as per schedule of
quantities, specifications and drawings.
ii) All doors, windows, ventilators section shall be anodized of approved colour extruded
sections of approved make along with certificate of primary biller manufacturer.

iii) All fittings / fixtures shall be of approved make / quality and as approved by engineer-
in -charge.
iv) All dimensions mentioned in the drawing are approximate. Necessary allowance for
fixing over granite frame and also necessary allowances for fixing tolerances to be
considered while manufacturing. While manufacturing, actual site measurement shall be
considered. Necessary planning for fixing the unit has to be carried out by the Contractor
without any extra cost to the IITB .
v) Payment shall be made per Kg basis. Aluminium sections such as shutter frames, track
window / door frame/beading channel for glass adjustable louvers etc., shall only be
measured linearly as per actual / finished cutting size nearest to centimetre and multiplied
with approved sectional weight of the individual section and the total quantity of aluminium
section will be arrived at for payment without any allowance for wastage.

vi) All glass panes shall be of approved makes. The glasses will be measured for payment
separately under relevant item.
vii) Glass panes shall be fixed with approved EPDM gasket ting, beading, to be free from
settling. Necessary polysulphide sealant to be provided against seepage of rain water.

viii) All top hung/side hung shutters to be provided with approved quality of stainless
steel friction hinges.
ix) In case of damage of any existing work, the same has to be made good/restored to
original condition by the Contractor at his own cost.
x) Item rates are inclusive of the cost of all fittings, fixtures, locking arrangement , handles,
pegstays, gaskets, screws, hinges etc., while quoting the rate for unit weight of aluminium
sections for windows .
xi) Shall furnish guarantee of one year on a stamp paper for performance of smooth
operation and leakage.
10.1 Providing and fixing aluminium doors, windows, ventilators and partitions with extruded
built up standard tubular sections/appropriate Z sections and other sections of approved
make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size,
including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required
EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight,
mitred and jointed mechanically wherever required including cleat angle, Aluminium snap
beading for glazing / panelling, C.P. brass / stainless steel screws, all complete as per
architectural drawings and the directed. (Glazing, panelling to be paid for separately) :

10.1.1 For fixed portion


10.1.1.1 Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868,
Kg 8396 427.61 35,90,249.91
Minimum anodic coating of grade AC 15)
10.1.2 For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots
and making provision for fixing of fittings wherever required including the cost of EPDM
rubber / neoprene gasket required.
10.1.2.1 Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868,
Kg 3708 524.04 19,43,124.45
Minimum anodic coating of grade AC 15)
10.2 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions
etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings
and the directions of Engineer-in-charge . (Cost of aluminium snap beading shall be paid in
basic item):
10.2.1 With 6.0 mm thick panes with SHGC value between 0.29 to 0.36, VLT between 23 - 39%, U-
Sqm. 1221 2,147.00 26,21,487.00
value between 3.8 to 4.5
10.3 Providing and fixing Toilet Cubicle System ( L Shape ) in HPL Boards with Standard Dimension
of 1950 mm Height x 900 mm Width x 1500 mm Depth, Which Includes a 600 mm Width x
1800 mm Height Door. Accessories Details : Stainless Steel ( Grade - 316 ), including SS
Gravity Hinges, SS Adjustable leg, SS Coat Hook, SS Door stopper ( SS Grade- 304 ), SS Top rail
hollow circular pipe, SS Tabular holder, SS Wall Bracket, SS Corner Connector, SS U- Channel,
Screws ( SS Grade- 304 ) & Wall Plugs, Noise Deafening tapes for grooves in doors, Ten (10) Nos 77 39,227.79 30,20,539.72
years of warranty for the partitions against any moisture related defects and one (1) year
warranty for the Restroom workmanship and hardware (accessories) against any
manufacturing defect etc. all complete as per the Architectural drawings and as directed.

PART D2_BOQ_COPT,IIT BOMBAY 21 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
10.4 Supply, fixing and installation of 4mm thick Aluminium Composite Panel (ACP) of approved
colour for external cladding in combination of solid and metallic colours, including all
necessary Framework, support and complete weather sealing as per architectural drawing.
The Aluminium Composite Panel (ACP) should be made out of thermoplastic core of low-
density polyethylene LDPE (100% virgin mix), sandwiched between two aluminium sheets of
ALLOY GRADE- 5000 series, each not less than 0.50 mm thick, total thickness of aluminium
composite panels not to be less than 4 mm, the exposed surface thereof shall have Stove
lacquered finishing coat not less than (26 + - 2) micron (containing minimum 70% kynar 500
based PVDF) of colour and shade etc. all complete as per the Architectural drawings, as
specified and as directed.

The inside surface (facing the building exterior surface)shall have polyester based powder
coating not less than 25 Micron with protective peel-off foil on the exterior face (peel off film
will in no case leave any adhesive mark over the composite panel surface after it is peeled
off). The supporting framework shall be made out of 50 mm X25mm X 3mm thick Aluminium
section to be spaced horizontally and vertically for fixing of panel of size 900 mm X 1200 mm
Sqm. 533 3,449.02 18,38,326.73
and fixed to the building structure as per design through 50mm X50mm X5 mm MS angle
clamps prefixed to masonry or slab, columns with Hilti make anchor fastener screws. The
fixing of panel to be done with the help of VHB tapes and screws and all the sealing of joints
to be done with weather sealant Silicon as directed.

10.5 Providing and supplying aluminium extruded tubular and other aluminium sections as per
the architectural drawings and approved shop drawings , the aluminium quality as per grade
6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns
conforming toAAMA2604 of required colour and shade as approved by the Engineer-in-
Charge. ( The item includes cost of material such as cleats, sleeves, screws etc. necessary for
fabrication of extruded aluminium frame work. The weight of aluminium extruded section Sqm. 421 3,065.92 12,90,754.13
shall be taken for purpose of payment. Designing, fabricating, testing, protection, installing
and fixing in position semi (grid) unitized system of structural glazing (with open joints) for
linear as well as curvilinear portions of the building for all heights and all levels, including:

a) Structural analysis & design and preparation of shop drawings for the specified design
loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design
wind pressure without any failure), including functional design of the aluminium sections for
fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc.
gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants,
flashings, fire stop (barrier)-cum-smoke seals, microwave cured EPDM gaskets for water
tightness, pressure equalisation & drainage and protection against fire hazard .

b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5
brackets of required sizes, sections and profiles etc. to accommodate 3 Dimensional
movement for achieving perfect verticality and fixing structural glazing system rigidly to the
RCC/ masonry/structural steel framework of building structure using stainless steel anchor
fasteners/ bolts, nylon separator to prevent bimetallic contacts with nuts and washers etc. of
stainless steel grade 316, of the required capacity and in required numbers.

c) Providing and filling, two part pump filled, structural silicone sealant and one part weather
silicone sealant compatible with the structural silicone sealant of required bite size in a clean
and controlled factory / work shop environment, including double sided spacer tape, setting
blocks and backer rod, all of approved grade, brand and manufacture, as per the approved
sealant design, within and all around the perimeter for holding glass.

d) Providing and fixing in position flashings of solid aluminium sheet1 mm thick and of sizes,
shapes and profiles, as required as per the site conditions, to seal the gap between the
building structure and all its interfaces with curtain glazing to make it watertight.

e) Making provision for drainage of moisture/ water that enters the curtain glazing system to
make it watertight, by incorporating principles of pressure equalization, providing suitable
gutter profiles at bottom (if required), making necessary holes of required sizes and of
required numbers etc. Complete. This item includes cost of all inputs of designing, labour for
fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding
and other incidental charges including wastages etc., enabling temporary structures and
services, cranes or cradles etc. as described above and as specified. The item includes the
cost of getting all the structural and functional design including shop drawings checked by a
structural designer, dully approved by Engineer-in-charge. The item also includes the cost of
all mock ups at site, cost of all samples of the individual components for testing in an
approved laboratory, field tests on the assembled working structural glazing as specified,
cleaning and protection till the handing over of the building for occupation. In the end, the
Contractor shall provide a water tight structural glazing having all the performance
characteristics etc. all complete as required, as per the Architectural drawings, as per item
description, as specified, as per the approved shop drawings and as directed by the Engineer-
in-Charge.

PART D2_BOQ_COPT,IIT BOMBAY 22 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
The item includes the cost of getting all the structural and functional design including shop
drawings checked by a structural designer, dully approved by Engineer-in-charge. The item
also includes the cost of all mock ups at site, cost of all samples of the individual components
for testing in an approved laboratory, field tests on the assembled working structural glazing
as specified, cleaning and protection till the handing over of the building for occupation. In
the end, the Contractor shall provide a water tight structural glazing having all the
performance characteristics etc. all complete as required, as per the Architectura drawings,
as per item description, as specified, as per the approved shop drawings and as directed.

Note:- 1.The cost of providing extruded aluminium frames, shadow boxes, extruded
aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof
stainless steel wire mesh shall be paid for separately under relevant items under this
subhead. However, for the purpose of payment, only the actual area of structural glazing
(including width of grooves) on the external face shall be measured in sqm. up to two
decimal places.
Note:-2. The following performance test are to be conducted on structural glazing system if
area of structural glazing exceeds 2500 Sqm from the certified laboratories accredited by
NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of
Science & Technologies, India. Cost of testing is payable separately.

IITB will decide the necessity of testing on the basis of cost of the work, cost of the test and
importance of the work. Performance Testing of Structural glazing system Tests to be
conducted in the NABL accredited lab or by any other accreditation body which operates in
accordance with ISO / IEC 17011 and accredits labs as per ISO/ IEC 17025

1) Performance Laboratory Test for Air Leakage Test (-50 pa to - 300 pa) & (+50 pa to +300
pa) as per ASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr

2) Static Water Penetration Test. (50 pa to 1500p) as per ASTME- 331-09 testing method for a
range up to 2000 ml.
3) Dynamic Water Penetration (50 pa to 1500pa) as perAAMA 501.01- 05 testing method for
a range up to 2000 ml
4) Structural Performance Deflection and deformation by static air pressure test (1.5 times
design wind pressure without any failure) as per ASTME-330-10 testing method for arrange
up to 50 mm
5) Seismic Movement Test (up to 30 mm) as per AAMA501.4-09 testing method for
Qualitative test, Tests to be conducted on site.
6) Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) up to 2000 ml

10.6 Providing and l Fixing Fly proof stainless steel grade 304 wire gauge with 0.5 mm dia. wire
and 1.4mm wide aperture with matching wood beading etc. all complete as per the Sqm. 507 1,499.38 7,60,188.01
Architectural drawings, as specified and as directed.
TOTAL OF ALUMINIUM WORK 1,50,64,669.95
11 WATER PROOFING
Note : -
a) The Contractor shall get written approval from the Engineer -in -charge, if the water
proofing agency is engaged other than specified in the schedule of item/specification and
shall submit the specification of the waterproofing agency before commencement of work.

b) The Contractor shall test the surface where water proofing treatment provided for bone
dry condition by filling up with water. No wet patches or leaks shall appear on the
surrounding wall or under side of the slab.
c) The Contractor shall furnish guarantee bond on appropriate stamp paper in the proforma
the entire waterproofing treatment for maintaining the surroundings and under side
surfaces of the waterproofing treated area in bone dry condition for 10 years. During the
guarantee period the Contractor shall attend all leakages, defects etc. if noticed, free of cost,
starting the work of checking up and rectification within a week's time from the date of
intimation about such leakages/defects

d) The Contractor shall keep the water tank filled with water after the water proofing work
has been completed and shall clean it before handing over and the filled water to be tested
in approved laboratory for potability. At no time shall the water tank be kept empty. Testing
for the bone dry condition for the water proofing work carried out shall again be done,
before handing over, if found necessary by the Engineer- in-charge.

e) Cost of Testing for bone dry condition shall be carried out by the Contractor and the
item rate includes the same.

PART D2_BOQ_COPT,IIT BOMBAY 23 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
11.1 Providing and laying integral cement based water proofing treatment including preparation
of surface as required for treatment of roofs, balconies, terraces etc consisting of following
operations:
(a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water
proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC
slab including adjoining walls up to 300 mm height including cleaning the surface before
treatment.
(b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with
50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing
compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick
layer of cement mortar of mix 1:5 (1 cement :5 coarse sand) admixed with water proofing
compound conforming to IS : 2645 and approved by Engineer-in-charge.

to required slope and treating similarly the adjoining walls up to 300 mm height including
rounding of junctions of walls and slabs. (c) After two days of proper curing applying a second
coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound
conforming to IS : 2645 and approved by Engineering-charge.
(d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4
coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved
by Engineering-charge including laying glass fibre cloth of approved quality in top layer of
plaster and finally finishing the surface.
(e) The whole terrace so finished shall be flooded with water for a minimum period of two
weeks for curing and for final test. All above operations to be done in order and as directed :

11.1.1 With average thickness of 120 mm and minimum thickness at khurra as 65 mm. sqm 3103 1,500.71 46,56,718.43
11.2 Providing and fixing 20 to 25 mm thick rough Shahabad box type waterproofing for
basement or underground floor on a base of Cement concrete, including sub base of 2.50
centimetre thick Cement mortar 1:3 with conceal, secrete (RMW), Algae proof or other alike
waterproofing liquids, raking of joints up to 35 mm depth, filling the joints with 6 mm size
sqm 291 1,252.38 3,64,443.82
crushed metal, hand grouting with cement slurry, curing and cleaning, with 10 years
guarantee on court fee stamp of Rs. 100/- with ponding test etc. complete as directed.
Note: Base Cement concrete shall be paid under relevant item.

11.3 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing
treatment to the RCC structures like retaining
walls of the basement, water tanks, roof slabs, podiums, reservoir, sewage & water
treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 :
2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts
integral
crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative
(internal) side with the help of synthetic fibre brush.
The material shall meet the requirements as specified in ACI- 212-3R-2010 i.e by reducing
permeability of concrete by more than 90% compared with control concrete as per DIN 1048
and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be
capable of self- healing of cracks up to a width of 0.50mm. The work shall be carried out all
complete as per specification and the direction of the engineer-in-charge. The product
performance shall carry guarantee for 10 years against any leakage.

11.3.1 For vertical surface two coats @ 0.70 kg per sqm sqm 302 400.32 1,20,896.26
11.3.2 For horizontal surface one coat @1.10 kg per sqm sqm 682 306.95 2,09,341.33
11.4 Providing and fixing 20 to 25 mm thick rough Shahabad box type waterproofing treatment
to vertical outside faces of Reinforced Cement concrete walls of basement or underground
floor including filling the gap of 25 mm between rough Shahabad and R.C.C. walls with
cement grout mixed with water proofing liquid Algae proof or other alike with one tile lift
method, brushing the joints horizontally with cement slurry mixed with water proofing liquid
for width 30 to 35 mm and sloping coping over topmost tile with cement mortar 1:3, butting sqm 221 1,298.34 2,86,933.88
the bottom most with Cement concrete 1:2:4 mixed with water proofing liquid, curing, with
10 years guarantee on court fee stamp of Rs 100/- with ponding test etc complete as
directed.

11.5 Providing Waterproof plaster in W.C. and bath 12 mm thick for dado in cement mortar 1:3
with neat finishing, floating using waterproofing compound at the rate of 1 Kilogram. per bag
sqm 758 418.85 3,17,491.43
of cement of approved make and manufacturer and curing etc. complete as directed.

11.6 Providing Waterproofing in W.C. and bath including brick bat coba in all position including
providing and laying 12 mm bedding in cement mortar 1:3 on vergin concrete slab with
waterproofing compound @ 1Kilogram/per bag of cement laying brick bat coba of required
thickness in cm 1:5 with waterproofing compound 1 Kilogram/bag of cement grouting and
finishing the top layer with 20 mm thick brick bedding in cm mortar 1:3 with waterproofing cum 228 6,171.05 14,06,998.90
compound 1 Kilogram/per bag of cement and testing the treated portion for 48 hours by
pond test and covering ten years' guarantee on requisite stamp paper including curing etc.
complete. as directed.

TOTAL OF WATER PROOFING WORK 73,62,824.05


12 LANDSCAPE WORK

PART D2_BOQ_COPT,IIT BOMBAY 24 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
12.1 Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width
as well as 10 sqm on plan including getting out and disposal off etc. all complete as per the
Architectural drawings, as specified and as directed.
12.1.1 All kinds of soil cum 157 78.49 12,322.48
12.2 Supplying and stacking of good earth at site including royalty and carriage complete (earth
measured in stacks will be reduced by 20% for payment). etc. all complete as per the cum 157 462.65 72,635.31
Architectural drawings, as specified and as directed.
12.3 Supplying and stacking at site dump manure from approved source, including carriage
complete (manure measured in stacks will be reduced by 8% for payment) : etc. all complete
as per the Architectural drawings, as specified and as directed.

12.3.2 Screened through sieve of I.S. designation 16 mm cum 49 258.22 12,652.98


12.4 Spreading of sludge, dump manure and/or good earth in required thickness as per direction
of Engineer-in-charge (cost of sludge, dump manure and/ or good earth to be paid
cum 157 45.48 7,139.76
separately). etc. all complete as per the Architectural drawings, as specified and as directed.

12.5 Mixing earth and sludge or manure in the required proportion specified or directed by the
Engineer -in-charge etc. all complete as per the Architectural drawings, as specified and as cum 205 31.63 6,484.42
directed.
12.6 Grassing with selection No. 1/ Doob grass including watering and maintenance of the lawn
for 30 days or more till the grass forms a thick lawn, free from weeds and fit for mowing
including supplying good earth, if needed (the grass and good earth shall be paid for
separately). etc. all complete as per the Architectural drawings, as specified and as directed.

12.6.1 In rows 5 cm apart in both directions Sqm. 400 15.32 6,129.19


Ground Cover
12.7 Providing and Planting of Rhoeo discolor compacta and above, with fresh and healthy
variegated foliage in 25 cm size of Earthen Pot/Plastic Pot & as per direction of the Engineer-
in-charge etc. all complete as per the Architectural drawings, as specified and as directed by
Sqm. 816 394.16 3,21,634.56
the Engineer- in-Charge. Spacing 300mm Centre to Centre etc. all complete as per the
Architectural drawings and as directed.

12.8 Providing and Planting Wadelia trilobata,full of leaves in 15 cm size of Earthen Pot / Plastic
Pot Spacing 500 mm Centre to Centre etc. all complete as per the Architectural drawings, as Nos. 390 49.27 19,215.30
specified and as directed.
Shrubs
12.9 Providing and Planting of Nerium oleander variegated of height 60-75 cm., multibranched in
earthen pots of size 25 cm as per direction of the officer-in-charge. etc. all complete as per
the Architectural drawings, as specified and as directed by the Engineer- in-Charge. etc. all Nos. 45 59.12 2,660.58
complete as per the Architectural drawings and as directed.

TOTAL OF LANDSCAPE WORK 4,60,874.58


13 MISCELLANEOUS WORK
13.1 Providing and fixing Wall Paper fixing on wall / column / partition. providing and fixing of
digitally reproduced 3M scotch print decorative graphics (with controltac & comply feature
for direct, bubble-free application on walls) as per the theme selected by clients with UV
protective matte over laminate. Customized imagery. Warranty of 5 yrs must be endorsed by
Sqm. 252 2,362.00 5,95,224.00
Brand. The rate shall be inclusive of material, hardware for fixing the graphics and fixing
charges etc all complete as per the Architectural drawings, as specified and as directed. (
Basic Price of wall paper is Rs 150 / Sqft.)

13.2 Providing and fixing 10mm thickness (without frame )Whiteboard as per approval on
partitions/walls/ other substrates in various areas of the office including training room,
cabins etc. complete including all ribs, adhesives etc as required. etc. all complete as per the
Architectural drawings, as specified and as directed.
13.2.1 600 mm x 900 mm Nos. 5 2,771.00 13,855.00
13.2.2 900 mm x 1200 mm Nos. 6 5,164.00 30,984.00
13.2.3 1200 mm x 2400 mm Nos. 8 9,950.00 79,600.00
13.3 Providing & Fixing in position, 1000 mm wide Auto-glow Aluminium extruded strips on
Nos. 6 1,494.60 8,967.60
auditorium steps as per Design , Instructions & Complete in all aspects.
13.4 Supplying and Fixing Trap door/Access Panel, with outer-inner aluminium frame 1.5 mm
thick + 0.2 mm thick powder coating, corner fittings outer-inner frame 2 mm thick with zinc
coating of 200g. Includes 12 mm Knauf plasterboard moisture resistant (MR), self drilling
screws mild steel black phosphate. Sealing strip 9mm width, 4mm thick. With snap lock
(spring catch) and Hinge 4mm thick. Powder coated to white, RAL9010

13.4.1 Size 600 mm x 600 mm Nos. 56 2,806.00 1,57,136.00


13.4.2 Size 1200 mm x 600 mm Nos. 42 6,110.00 2,56,620.00
13.5 Providing and fixing S.S. Transition Strip Profile 25mm x 33 mm TEE Shape Stainless steel
Grade 304 plate rate include with hardware, fixing charges, cleaning etc as per design all
Rmt 23 1,143.00 26,289.00
complete as per the Architectural drawings, as specified and as directed.

13.6 Providing and Fixing Manual Roller Blackout Blinds of approved make & shade of 38 mm
round Aluminium channel with Blackout fabric & telting with chain (Ball) system with all
necessary fixtures and fitting etc. complete. Sample to be approved by Engineer In-charge Sqm 100 904.00 90,400.00
prior to execution of work.
(Basic rate of the Manual Roller Blackout Blinds shall be minimum Rs 700 / Sq.M)

PART D2_BOQ_COPT,IIT BOMBAY 25 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
13.7 Providing and Fixing Manual Roller Translucent Blinds of approved make & shade of 38 mm
round Aluminium channel with Translucent fabric & telting with chain (Ball) system with all
necessary fixtures and fitting etc. complete. Sample to be approved by Engineer In-charge Sqm 100 1,220.00 1,22,000.00
prior to execution of work. (Basic rate of the Manual Roller Translucent Blinds is Rs 970 /
Sq.m)
13.8 Providing and Fixing Motorised Roller Blackout Blinds of approved make & shade of 38 mm
round Aluminium channel with Blackout fabric & Auto senor system with all necessary
fixtures and fitting etc. complete. Sample to be approved by Engineer In-charge prior to Sqm 100 2,370.00 2,37,000.00
execution of work.
(Basic rate for Roller Blackout Blinds shall be minimum Rs 700 / Sq.m)
13.9 Providing and Fixing Motorised Roller Translucent Blinds of approved make & shade of 38
mm round Aluminium channel with Translucent fabric & Auto senor system with all
necessary fixtures and fitting etc. complete. Sample to be approved by Engineer In-charge Sqm 100 2,686.00 2,68,600.00
prior to execution of work.
(Basic rate for Roller Translucent Blinds shall be minimum Rs 970 / Sq.m)
13.10 Providing and fixing of Branded Frosted film as per design on toughened glass in cabins door
etc. complete as per direction. all complete as per the Architectural drawings, as specified
Sqm 25 1,081.00 27,025.00
and as directed.
(Basic rate for Branded Frosted film shall be minimum Rs 850 / Sq.m)
13.11 Providing and fixing of Branded Black out film as per design on toughened glass in cabins
door etc. complete as per direction. all complete as per the Architectural drawings, as
Sqm 25 1,198.00 29,950.00
specified and as directed.
(Basic rate for Branded Blackout film shall be minimum Rs 950 / Sq.m)
TOTAL OF MISCELLANEOUS WORK 19,43,650.60
14 SIGNAGES WORK
STATUTORY SIGNAGES
14.1 Manual Call Point :
Approx. Size: 100mm x 100mm
Providing and fixing Self Adhesive Vinyl with Glow in Dark Vinyl Stuck on Foam Board and
Installed Directly on Wall. Rate to be inclusive all necessary hardwares, Screw etc all
Nos. 21 72.00 1,512.00
complete as per the Architectural drawings, as specified and as directed.

14.2 Fire Hose Reel :


Approx. Size: 125 mm x 125 mm
Providing and fixing Self Adhesive Vinyl Stuck on Foam Board and Installed Directly on Wall.
Rate to be inclusive all necessary hardwares, Screw etc all complete as per the Architectural Nos. 21 116.00 2,436.00
drawings, as specified and as directed.
14.3 Floor Evaluation Plan :
Approx. Size 457 mm x 300mm ( Size & Fabrication might vary post finalisation of design)

Providing and fixing Self Adhesive Glow in Dark Sticker stuck on 5MM Foam Board and
Installed on Walls. Rate to be inclusive all necessary etc all complete as per the Architectural Nos. 21 1,353.00 28,413.00
drawings, as specified and as directed.
14.4 Fire Exit :
Approx. Size: 150mm x 400 mm Showing Staircase
Providing and fixing Self Adhesive Glow in Dark Sticker stuck on 5MM Foam Board and
Hanged on Ceiling with SS Chain 6mm Diameter as per Drawing. Rate to be inclusive all
Nos. 21 478.00 10,038.00
necessary etc all complete as per the Architectural drawings, as specified and as directed.

14.5 Fire Exit :


Approx. Size: 150mm x 400 mm showing Arrow
Providing and fixing Self Adhesive Glow in Dark Sticker stuck on 5MM Foam Board and
Hanged on Ceiling with SS Chain 6mm Diameter as per Drawing. Rate to be inclusive all
Nos. 70 478.00 33,460.00
necessary etc all complete as per the Architectural drawings, as specified and as directed.

14.6 Floor Name :


Approx. Size: 150mm x 300mm
Providing and fixing Self Adhesive Glow in Dark Sticker stuck on 5MM Foam Board and
Installed on Walls. Rate to be inclusive all necessary etc all complete as per the Architectural Nos. 79 308.00 24,332.00
drawings, as specified and as directed.
14.7 Staircase Name :
Approx. Size: 150mm x 300mm
Providing and fixing Self Adhesive Glow in Dark Sticker stuck on 5MM Foam Board and
Installed on Walls. Rate to be inclusive all necessary etc all complete as per the Architectural Nos. 48 308.00 14,784.00
drawings, as specified and as directed.
14.8 Midlanding Name :
Approx. Size: 150mm x 300mm
Providing and fixing Self Adhesive Glow in Dark Sticker stuck on 5MM Foam Board and
Installed on Walls. Rate to be inclusive all necessary etc all complete as per the Architectural Nos. 24 308.00 7,392.00
drawings, as specified and as directed.
14.9 Booster Pump :
Approx. Size: 250 mm x 250 mm.
Providing and fixing Self Adhesive Glow in Dark Sticker stuck on 5MM Foam Board and
Installed on Walls. Rate to be inclusive all necessary etc all complete as per the Architectural Nos. 1 423.00 423.00
drawings, as specified and as directed.
14.10 Booster Pump Start and Stop :
Approx. Size: 250 mm x 250 mm showing Start and Stop.
Providing and fixing Self Adhesive Glow in Dark Sticker stuck on 5MM Foam Board and
Nos. 1 423.00 423.00
Installed on Walls. Rate to be inclusive all necessary etc complete
PART D2_BOQ_COPT,IIT BOMBAY 26 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
14.11 In Case of Fire Break Glass :
Approx. Size: 165 mm x 120 mm
Providing and fixing Self Adhesive Glow in Dark Sticker stuck on 5MM Foam Board and
Nos. 21 141.00 2,961.00
Installed on Walls. Rate to be inclusive all necessary etc complete
14.12 In Case of Fire don’t use Lift use Staircase :
Approx. Size: 165 mm x 120 mm
Providing and fixing Self Adhesive Glow in Dark Sticker stuck on 5MM Foam Board and
Nos. 21 141.00 2,961.00
Installed on Walls. Rate to be inclusive all necessary etc complete
14.13 Fire Exit :
Approx. Size: 150mm x 150mm Pasting on Door
Providing and fixing Self Adhesive Glow in Dark Sticker stuck on 5MM Foam Board and
Nos. 21 160.00 3,360.00
Installed on Walls. Rate to be inclusive all necessary etc complete
14.14 Ramp Signage :
Approx. size: 300 mm x 300 mm
Providing and fixing 3mm Aluminium Composite Panel 0.25mm skin thickness or MS Brushed
Finished with PU Finish, Paperlam SCVM Wall Graphic with OLCM over lamination UV Printing
at 1200x800 DPI and directly stuck on ACP with warranty of internal graphics 5 years. The Nos. 2 604.00 1,208.00
signage would be stuck directly on the surface using Screw or Studs. Rate to be inclusive all
necessary etc. complete.
TOTAL OF SIGNAGES WORK 1,33,703.00
PART - II PLUMBING WORK
GENERAL NOTES:
1) All sanitary wares & CP brass fittings & fixtures shall be of first quality with ISI mark ( unless
otherwise specified ) and shall be of the make as per the latest approved list of materials as
per list of approve make / model as per APPENDIX “A” and should be of low flow type as per
GRIHA requirements. They shall be got approved by the Engineer- in- charge before
incorporating in the work.
2). All the items of work which are to be carried out below the ground level involving
earthwork excavation, the Contractor shall bear the cost of Shoring / dewatering during the
progress and till the completion of work irrelevant of the mentioning of the same in the
description of particular item of the schedule of quantities.

3) The rate for the items such as sanitary wares, CP brass fittings, GI / UPVC pipes which are
to be fixed on the walls / dado, floors etc. includes the cost of fixing materials and matching
colour cement required for reinstating the surface to the entire satisfaction of the Engineer-
in- Charge
4) All the items include testing after completion of the work.
5) Concealed / underground GI pipe line is to be wrapped with hessian cloth and painted
with two coats of anticorrosive paint.
6) The excavated / transported materials shall be stacked at convenient places before
spreading, filling & compacting at required locations.
A SANITARY WARES AND CP APPURTENANCES
1.0 Supplying, Installing, testing and commissioning I) Providing Vitreous China wall hung type
wash down pattern Water Closet ( EWC ) conforming to IS 2556 (part XVI) with integral "P"
trap outlet with water seal not less than 50 mm with vent and necessary C.I. brackets
supports. with 100 mm P or S trap, Inlet Connection Pipe 32 mm dia Pipe of required length
from flushing cistern to Water Closet concealed in the wall making connection with W.C pan
and cistern including the cost of uPVC fittings, fixtures and jointing materials n, including
flush pipe, with manually controlled device (handle lever) with all fittings and fixtures
complete, including cutting and making good the walls and floors wherever required Testing
the system to the full satisfaction.

Recommended manufacturers are :-1)Parryware 2)Hindware 3)Jaquar


1.1 i) Providing & fixing Vitreous China European Wall Mounted Water Closet of pure china
white as per approved sample by Eng-in-charge with P trap with prior approval of Engineer-in-
14,71,138.00
Charge. (Model No.:Splendor Wall Mounted Closet 92574 OR Equivalent)
No. 79 18,622.00
ii) Providing & fixing Concealed Flushing Cistern including inlet / outlet connections, G.I.
fittings fixtures, cutting hole, testing etc. (Model No. : CC 77.5 Flush Plate Loop - CH Part Code
PE-H 520401 OR Equivalent)
1.2 i) Providing & fixing Vitreous China European Water Closet For Physically Handicap of pure
china white as per approved sample by Eng-in-charge with P trap with prior approval of
No. 7 31,458.00 2,20,206.00
Engineer-in-Charge. (Model No.: Matrix Set Catalogue 70002 OR Equivalent)

ii) Providing & fixing Concealed Flushing Cistern including inlet / outlet connections, G.I.
fittings fixtures, cutting hole, testing etc. (Model No. : CC 77.5 Flush Plate Loop - CH Part Code
PE-H 520401 OR Equivalent)
1.3 i) Providing & fixing Vitreous China Indian Water Closet of pure china white as per approved
sample by Eng-in-charge with P trap with prior approval of Engineer-in-Charge. (Model No. : No. 28 8,632.00 2,41,696.00
Comfort Orrisa Pan 23 inch OR Equivalent)
ii) Providing & fixing Concealed Flushing Cistern including inlet / outlet connections, G.I.
fittings fixtures, cutting hole, testing etc. (Model No. : CC 77.5 Flush Plate Loop - CH Part Code -
PE-H 520401 OR Equivalent)
1.4 Providing & fixing Health Faucet with PVC / flexible tube with check nuts, wall hook etc. of
following type & fixing using white Zinc, spun yarn etc. and wall hook on the wall at the
appropriate location using 40 mm long CP brass screws, rawl plug etc. including testing the No. 114 927.00 1,05,678.00
joints for leak proofness all complete on prior approval of Engineer-in-Charge. (Model No.
F160023CP OR Equivalent)

PART D2_BOQ_COPT,IIT BOMBAY 27 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
1.5 Providing & fixing Stainless steel recessed type Toilet paper Roll Holder with prior approval of
No. 114 886.00 1,01,004.00
Engineer-in-Charge. (Model No. F880003 OR Equivalent)
1.6 Providing & fixing C.P. brass twin coat hook with prior approval of Engineer-in-Charge.
No. 114 554.00 63,156.00
(Model No. Rubbic, F870007 OR Equivalent)
1.7 Providing & fixing C.P brass two way Bib tap -15mm with wall flange with prior approval of
No. 114 1,505.00 1,71,570.00
Engineer-in-Charge. (Model No. : Element, F360005 OR Equivalent)
1.8 Providing & fixing foldable seat for physically handicapped common toilets equivalent with
prior approval of Engineer-in-Charge. (Model No. - K-20526IN-0 OR Equivalent) No. 7 5,985.00 41,895.00

2.0 Supplying, Installing, testing and commissioning Undercounter Wash hand basin with one
tap holes and chain stay hole, 32mm diameter chrome plated chain waste, chrome plated
non-conclusive time delay press action pillar tap , concealed wall brackets with screw, Rawal
plug and bottle trap (32mm 'P' trap)40 mm upvc pipe with 40mm seal. wherever required
Testing the system to the full satisfaction of the E.I.C.

2.1 i) Providing & Fixing White glazed Vitreous China Wash Hand Basin with prior approval of
No. 92 4,126.00 3,79,592.00
Engineer-in-Charge. (Model No. - CNS-WHT-705 OR Equivalent)
ii) Providing & Fixing C.P brass waste coupling of 32 mm size, full threaded with grating with
prior approval of Engineer-in-Charge. (Model No. - F860052 OR Equivalent)

iii) Providing & Fixing C.P brass Pillar Cock 15 mm size having long neck with Aerator with
prior approval of Engineer-in-Charge. (Model No. : F400021CP OR Equivalent)

(iv) Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings
No. 92 103.00 9,476.00
complete. (Flexible Pipe)
2.2 i) Providing & Fixing White glazed Vitreous China Wash Hand Basin with prior approval of
Engineer-in-Charge. (Jaquar. Model No. - JDH-WHT-13253N OR Equivalent)) (For Director's No. 1 6,708.00 6,708.00
Room)
ii) Providing & Fixing C.P brass waste coupling of 32 mm size, full threaded with grating with
prior approval of Engineer-in-Charge. (Model No. - F860052 OR Equivalent)

iii) Providing & Fixing C.P brass Pillar Cock 15 mm size having long neck with Aerator with
prior approval of Engineer-in-Charge. (Model No. : F400021CP OR Equivalent)

(iv) Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings
No. 1 103.00 103.00
complete. (Flexible Pipe)
2.3 C.P brass Bottle Trap ( with internal partition ), 32 mm size and 300 mm long wall connection
pipe with wall flange with prior approval of Engineer-in-Charge. (Model No. : F850015 OR No. 93 1,088.00 1,01,184.00
Equivalent)
3.0 Supplying, Installing, testing, cutting, fixing and commissioning sink with single bowl
manufactured from 1mm thick stainless steel, 18G high grade indestructable chrome nickel
steel with top quality polish, 1no. 40mmdia CP waste coupling, with 1no. 40mm dia CP bottle
trap with extension pipe, Single Lever Sink tap with. Swinging Spout etc., complete. wherever
required Testing the system to the full satisfaction of the E.I.C.

3.1 Providing & Fixing Heavy duty stainless steel sink : SS 304 Single Bowl Silent square (Model :
No. 9 4,981.00 44,829.00
Orbis OR Equivalent)
3.2 Providing & Fixing C.P brass waste coupling of 32 mm size, full threaded with grating with
prior approval of Engineer-in-Charge. (Model No. - F860052 OR Equivalent)

3.3 Providing & Fixing Sink taps with swinging casted spout (Wall Mounted) with connecting legs
and flanges, as per approval of Engineer-in-Charge. . (Model No. : F400021CP OR Equivalent)

3.4 C.P brass Bottle Trap ( with internal partition ), 32 mm size and 300 mm long wall connection
pipe with wall flange with prior approval of Engineer-in-Charge. (Model No. : F850015 OR No. 9 1,088.00 9,792.00
Equivalent)
3.5 Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings
No. 9 103.00 927.00
complete. (Flexible Pipe)
4.0 Providing & fixing, testing and commissioning of white vitreous china large flat back / half
stall urinal SIZE : 270 x 360 x 440 including Push tap for flushing after use, providing & fixing
CI / MS bracket (duly painted with 2 coats of paints over a coat of primer),including CP cast
brass bottle trap, extension piece, wall flanges with urinal partition including providing & No. 84 10,595.00 8,89,980.00
fixing concealed complete with all accessories.(Urinal Model No. : Corto 60022 OR
Equivalent) (Sensor Model No. : 500964 OR Equivalent)

5.0 Providing & fixing push type liquid soap dispenser with prior approval of Engineer-in-Charge.
No. 51 2,318.00 1,18,218.00
(Model No. - ACN 1137N OR Equivalent)
6.0 Providing & fixing of Hand Dryer with prior approval of Engineer-in-Charge. (Model No. - HDR-
No. 16 7,804.00 1,24,864.00
SSF-AK2803D OR Equivalent)
7.0 Providing & fixing of Paper Towel Dispenser with prior approval of Engineer-in-Charge.
No. 14 6,174.00 86,436.00
(Model No. - PTD-SAP-DT0106CS OR Equivalent
8.0 Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved
No. 200 493.00 98,600.00
quality conforming to IS:8931. (15mm nominal bore)
Providing and fixing of stainless steel (SS316) grating 'of 18 gauge thick, with 'circular
perforation including Cockroach trap of 'approved pattern over CI/PVC 'traps. The grating
9.0 shall be of size 100mm x 100mm or circular of 100mm dia '(as directed) and shall 'be set in No 166 220.00 36,520.00
cement, sand mortar 1:3 etc. complete. (Model No. - 7275IN-CP OR Equivalent)

TOTAL OF SANITARY WARES AND CP APPURTENANCES 43,23,572.00


PART D2_BOQ_COPT,IIT BOMBAY 28 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
B WATER SUPPLY SYSTEM
INTERNAL WATER SUPPLY SYSTEM
1.0 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for
hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe
with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC
solvent cement and the cost of cutting chases and making good the same including testing of
joints complete as per directed.
Concealed work, including cutting chases and making good the walls
etc.
1.1 15 mm nominal dia. Rmt. 115 435.00 50,025.00
1.2 20 mm nominal dia. Rmt. 110 506.00 55,660.00
1.3 25 mm. nominal dia. Rmt. 180 617.00 1,11,060.00
1.4 32 mm nominal dia. Rmt. 90 702.00 63,180.00
1.5 40 mm nominal dia. Rmt. 110 809.29 89,022.14
1.6 50 mm nominal dia. Rmt. 80 1,107.00 88,560.00
2.0 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for
hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the
pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step
CPVC solvent cement and testing of joints complete as per directed.

Internal work - Exposed on wall


2.1 15 mm nominal dia. Rmt. 10 239.00 2,390.00
2.2 20 mm nominal dia. Rmt. 5 302.00 1,510.00
2.3 25 mm. nominal dia. Rmt. 65 401.00 26,065.00
2.4 32 mm nominal dia. Rmt. 55 477.00 26,235.00
2.5 40 mm nominal dia. Rmt. 270 610.00 1,64,700.00
2.6 50 mm nominal dia. Rmt. 75 909.00 68,175.00
2.7 65 mm nominal dia. Rmt. 205 1,767.00 3,62,235.00
2.8 80 mm nominal dia. Rmt. 70 2,255.00 1,57,850.00
2.9 100 mm nominal dia. Rmt. 370 3,149.00 11,65,130.00
3.0 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :

3.1 20 mm nominal dia. No. 21 455.00 9,555.00


3.2 25 mm. nominal dia. No. 17 525.00 8,925.00
3.3 32 mm nominal dia. No. 2 581.00 1,162.00
3.4 40 mm nominal dia. No. 27 697.00 18,819.00
3.5 50 mm nominal dia. No. 28 865.00 24,220.00
3.6 65 mm nominal dia. No. 16 1,469.00 23,504.00
3.7 80 mm nominal dia. No. 7 2,195.00 15,365.00
3.8 100 mm nominal dia. No. 2 6,570.00 13,140.00
EXTERNAL WATER SUPPLY SYSTEM
4.0 Providing and fixing G.I. pipes complete with G.I. fittings including
trenching and refilling etc.
4.1 80 mm nominal dia. (Municipal Inlet) Rmt. 100 906.00 90,600.00
4.2 65mm nominal dia. (Domestic Water Supply From UGT To OHT) Rmt. 75 757.00 56,775.00
4.3 50mm nominal dia.(Flushing Water Supply From UGT To OHT) Rmt. 85 645.00 54,825.00
5.0 Making connection of G.I. distribution branch with G.I. main of following sizes by providing
and fixing tee, including cutting and threading the pipe etc. complete :
5.1 50 to 80 mm nominal bore No. 1 1,492.00 1,492.00
6.0 Fixing water meter and stop cock in G.I. pipe line including cutting and threading the pipe
and making long screws etc. complete (cost of water meter and stop cock to be paid No. 1 660.00 660.00
separately).
7.0 Constructing masonry Chamber 60x45x50 cm inside, in brick work in cement mortar 1:4 (1
cement : 4 coarse sand) for water meter complete with C.I. double flap surface box
400x200x200 mm (inside) with locking arrangement and RCC top slab 1:2:4 mix (1 cement : 2
coarse sand : 4 graded stone aggregate 20 mm nominal size) , i/c necessary excavation,
foundation concrete 1:5:10 ( 1 cement : 5 fine sand:10 graded stone aggregate 40 mm No. 1 9,955.00 9,955.00
nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm
thick, finished with a floating coat of neat cement complete as per standard design : With
common burnt clay F.P.S.(non modular) bricks of class designation 7.5.

8.0 Providing and fixing enclosed type water meter (bulk type) conforming to IS : 2373 and
tested by Municipal Board complete with bolts, nuts, rubber insertions etc. (The tail pieces if No. 1 3,218.00 3,218.00
required will be paid separately) : 80 mm dia nominal bore
9.0 Providing and fixing C.I. dirt box strainer for bulk type water meter with nuts, bolts, rubber
insertions etc. complete conforming to IS : 2373 : 80 mm dia nominal bore No. 1 4,075.00 4,075.00

10.0 Providing and fixing in position 25 mm diameter mosquito proof coupling of approved
municipal design. . (For Each Domestic OHT & UGT_Drain, Vent & Overflow & Fire OHT & No. 42 45.00 1,890.00
UGT_Drain & Vent)
11.0 Providing and fixing in position C.I. 500 mm dia cover with frame (medium duty) (For UGT)
No. 8 4,336.00 34,688.00
12.0 Providing and fixing in position C.I. Rectangular cover 455x610 mm with frame (low duty) (For
No. 12 1,380.00 16,560.00
OHT)
TOTAL OF WATER SUPPLY SYSTEM 28,21,225.14
C INTERNAL DRAINAGE (SOIL, WASTE & VENT, RAIN WATER )

PART D2_BOQ_COPT,IIT BOMBAY 29 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
Providing fixing, testing and commissioning of Hubless centrifugally cast iron pipes and
fittings (Epoxy coated inside and outside) as per ISO-6594/IS-15905 standard and jointing
with ASTM C 1277 marked stainless steel shielded coupling with a double stainless steel botl
& screw housing incorporating a elastomeric rubber gasket and inclusive of all necessary
specials like bends, tees, offsets, junctions, cowl end plug, inspection pipe, etc. laid under
floor/fixed on walls and in pipe shafts. Rate shall also include Providing and laying 100mm
1.0
thickness cement concrete 1:5:10 (1 cement : 5 coarse sand :10 graded stone aggregate 40
mm nominal size) around the pipe.
The rate shall be including all the engineered support (support, hanger, nuts/bolts, anchor
fasteners, fixing clamp/channels with U-bolts, etc) as per detail technical specification etc.
complete the job.

1.1 50 mm dia Rmt 540 683.00 3,68,820.00


1.2 75 mm dia Rmt 820 855.00 7,01,100.00
1.3 110 mm dia Rmt 620 1,046.00 6,48,520.00
1.4 160 mm dia Rmt 270 1,706.00 4,60,620.00
Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings
2.0
complete. (Semi Rigid Pipe)
2.1 40 mm dia Rmt 150 100.00 15,000.00
Hubless centrifugally cast (spun) iron trap with 100 mm inlet and 100 mm outlet as per IS
3.0 No 166 532.00 88,312.00
15905
Providing and fixing C. I. vertical jalli at the collection point of RWP on terrace to be with
4.0 material and labour including provision of lead sheet flashing of 6mm thickness as per details
etc. complete as per directions of engineer-in-charge.
4.1 C.I. grating 180x180 mm No. 10 64.00 640.00
TOTAL OF INTERNAL DRAINAGE (SOIL, WASTE & VENT, RAIN WATER) 22,83,012.00
D EXTERNAL SEWERAGE & STORM WATER DRAINAGE SYSTEM
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with
stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including
1.0
testing of joints
etc. complete :
1.1 100 mm dia. Rmt 80 441.00 35,280.00
1.2 150 mm dia. Rmt 225 486.00 1,09,350.00
1.3 250 mm dia. Rmt 70 799.00 55,930.00
2.0 Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick
masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the
weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per
standard design to be less than 2.7kg as per standard design)of approved make rate including
of.
2.1 150 x 100 mm size P type, With sewer bricks conforming to IS : 4885 No. 15 2,393.00 35,895.00
3.0 Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with
R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone
aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand
(zone- III) : 8 graded stone aggregate 40 mm nominal size) inside plastering 12 mm thick with
cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and
making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per
standard design :
3.1 Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm
internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of
No. 19 11,398.00 2,16,562.00
cover 23 kg and weight of frame 15 kg), With Sewer bricks conforming to IS : 4885

3.2 Extra for depth for manholes : Size 90x80 cm, With Sewer bricks conforming to IS : 4885
Rmt 10 7,664.00 76,640.00
3.3 Inside size 120x90 cm and 90 cm deep including C.I. cover with frame (medium duty) 500 mm
internal diameter, total weight of cover and frame to be not less than 116 kg (weight of cover
No. 4 23,726.00 94,904.00
58 kg and weight of frame 58 kg), With Sewer bricks conforming to IS : 4885

3.4 Extra for depth for manholes : Size 120x90 cm, With Sewer bricks conforming to IS : 4885
Rmt 10 9,191.00 91,910.00
4.0 Constructing brick masonry road gully chamber 45x45x77.5 cm with bricks in cement mortar
1:4 (1 cement : 4 coarse sand ) with precast R.C.C. vertical grating complete as per standard
design :
4.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 No. 11 6,167.00 67,837.00
TOTAL OF EXTERNAL SEWERAGE & STORM WATER DRAINAGE SYSTEM 7,84,308.00
E WATER SUPPLY PUMPS AND ACCESSORIES / EQUIPMENT
WATER SUPPLY
1.0 Providing, fixing, testing and commissioning pumps of following capacity for Domestic &
Flushing Water supply distribution from UGT to OHT. Pumps to be vertical / Horizontal Split
casing centrifugal stainless steel pumps with suitable for operation on 415 v, 3 phase 50 Hz
Ac supply. Pump head and base shall be of C.I. construction, impellers, diffusers, shaft shall
be in SS 304 construction. Motor shall be squirrel cage, induction motor TEFC, operating at
2900 RPM. including Common bed plate fabricated out of MS channel of size 75 mm x 75mm
x 6 mm for assembling the pump and the motor, flexible coupling and with coupling guard
for protection/safety including painting etc. as required.

1.1 Pumps with following specs of approved make . Set 1 67,012.00 67,012.00
Water Flow Rate : 4.0 LPS each pump
Head : 45 M
PART D2_BOQ_COPT,IIT BOMBAY 30 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
Qty : 2 Nos - (1W+1S)
Purpose : Domestic system Transfer Pump.
1.2 Pumps with following specs of approved make .
Water Flow Rate : 2.5 LPS each pump Set 1 48,032.00 48,032.00
Head : 45 M
Qty : 2 Nos - (1W+1S)
Purpose : Flushing system Transfer Pump
2.0 Providing and fixing heavey duty GI pipe C - Class for all pump suction / discharge line with
common header complete with all fittings like elbow, tee, reducer, flange, union, etc.
conforming to IS:1239 (Part 1) for pipes and IS : 1879 (Part 1 to 10) for fittings including fixing
in wall / ceiling / floor level, supported by galvanized clamps, hangers, vertical pipe support
etc including Anticorrosive Primer and Enamel paint complete etc. as required.

2.1 50 mm dia. Rmt. 10 1,694.00 16,940.00


2.2 65 mm dia. Rmt. 10 2,076.00 20,760.00
3.0 Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with
bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets
conforming to IS 13095 of following sizes as required :
3.1 50 mm dia. No. 5 3,729.00 18,645.00
3.2 65 mm dia. No. 5 4,239.00 21,195.00
4.0 Providing, installation, testing and commissioning of non-return valve of following sizes
confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :

4.1 50 mm dia. No. 2 5,705.00 11,410.00


4.2 65 mm dia. No. 2 6,324.00 12,648.00
5.0 Providing and fixing ISI mark C.I.`Y' strainer with bolted cover & trim SS 304 screen having
1.2 mm dia perforation flanges type as per BS - 10 with working pressure 10 kg /cm2
perforated sheet basket including rubber gasket, flanges, nuts, bolts and washers & other
accessories , complete etc as required.
5.1 50 mm dia No. 2 7,403.00 14,806.00
5.2 65 mm dia No. 2 9,701.00 19,402.00
6.0 Supplying, fixing, testing & commissioning of Flanged Foot Valve of rating PN 1.0 bronze/gun
metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 1538
of following sizes as required :
6.1 50 mm dia No. 2 16,667.00 33,334.00
6.2 65 mm dia No. 2 22,600.00 45,200.00
7.0 Providing, fixing including testing and commissioning 100 mm dia pressure gauge of range
250 PSI working pressure conforming to IS - 3624 having bourdon tube of stainless steel 310
in cast aluminium, stove enamelled, black, weather proof case with outer, screwed
No. 8 2,540.00 20,320.00
aluminium bezel and complete with necessary U-type stainless steel siphon tube and cock
including providing suitably painted angle iron support to the tube etc.as per specification
complete as required.
8.0 Providing and fixing Automatic Pump Control Panel for Operation & Control of pump-sets.
Pump shall start at low level signal from the sensor and stop at high level signal. Controller to
switch pumps alternately for equal run time for both pumps.
The Contractor to consider
-L.T. panel incorporating ammeter, voltmeter switches, change over switch from auto/
manual, earth leakage circuit breaker, single phase preventor, Dry running preventor,
pressure switches.
No. 1 29,822.00 29,822.00
-Panel showing visual indications as below
-Motor status On/ Off/ Fail
-Level Status Low/ Medium/ High in the UGR
-Power On/ Off
-Contractor to submit the GA drawing along with the Control layout to the Consultants
before manufacturing of the same. (FOR DOMESTIC PUMPS)

9.0 Providing and fixing Automatic Pump Control Panel for Operation & Control of pump-sets.
Pump shall start at low level signal from the sensor and stop at high level signal. Controller to
switch pumps alternately for equal run time for both pumps.
The Contractor to consider
-L.T. panel incorporating ammeter, voltmeter switches, change over switch from auto/
manual, earth leakage circuit breaker, single phase preventor, Dry running preventor,
pressure switches.
No. 1 27,479.00 27,479.00
-Panel showing visual indications as below
-Motor status On/ Off/ Fail
-Level Status Low/ Medium/ High in the UGR
-Power On/ Off
-Contractor to submit the GA drawing along with the Control layout to the Consultants
before manufacturing of the same. (FOR FLUSHING PUMPS)

TOTAL OF WATER SUPPLY PUMPS AND ACCESSORIES / EQUIPMENT 4,07,005.00


PART III FIRE FIGHTING WORKS
A FIRE PUMPS & RELATED EQUIPMENT / ACCESSORIES
1.0 DIESEL ENGINE DRIVEN PUMP
Supplying, installation, testing and commissioning of diesel engine driven main fire pump
suitable for automatic operation, capable to deliver 1620 LPM at 70 mtr Head and consisting
of following, complete in all respects, as required :
Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with
stainless steel shaft, mechanical seal conforming to IS 1520.
PART D2_BOQ_COPT,IIT BOMBAY 31 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS
standard complete with auto starting mechanism, 12 /24 volts electric starting equipment,
diesel tank, exhaust pipe extended up to 10 m outside pump house duly insulated with 50
mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer,
Nos. 1 5,83,548.00 5,83,548.00
instruments and protection as per standard specification, stop solenoid for auto stop in the
event of fault with audio indications, painted with post office red colour etc. as required.

M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as
required.
Suitable cement concrete foundation duly plastered and with anti vibration pads.

Note: *The head of the pump is selected in a manner so as to give a minimum 3.5kg/cm2
pressure at the highest/farthest point.
2.0 JOCKEY PUMP
Supplying, installation, testing and commissioning of electric driven pressurisation pump
suitable for automatic operation, capable to deliver 180 LPM at 70 mtr Head and consisting
of following,
complete in all respects, as required :
Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with
stainless steel shaft, mechanical seal conforming to IS : 1520.
Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 Nos. 2 1,01,796.00 2,03,592.00
phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted
type with Class-'F' insulation, conforming to IS : 325.
M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as
required.
Suitable cement concrete foundation duly plastered and with anti vibration pads.

3.0 MAIN HYDRANT / SPRINKLER PUMP


Supplying, installation, testing and commissioning of Electric driven Main Fire Hydrant /
Sprinkler Pump suitable for automatic operation, capable to deliver 1620 LPM at 70 mtr
Head and consisting of following, complete in all respects, as required :

(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze
impeller with stainless steel shaft, mechanical seal conforming to IS 1520.
(b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable
for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, Nos. 2 3,27,125.00 6,54,250.00
horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.

(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as
required.
(d) Suitable cement concrete foundation duly plastered with anti vibration pads.
Note: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2
pressure at the highest/farthest point.
4.0 TERRACE BOOSTER PUMP
Supplying, installation, testing and commissioning of electric driven terrace Booster pump
suitable for automatic operation, capable to deliver 900 LPM at 35 mtr Head and consisting
of following, complete in all respects, as required:
(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze
impeller with stainless steel shaft, mechanical confirming to IS : 1520
b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 Nos. 3 1,00,372.00 3,01,116.00
phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horizontal foot mounted
type with Class-'F' insulation, conforming to IS-325.
(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as
required.
(d) Suitable cement concrete foundation duly plastered with anti vibration pads.
5.0 Providing, laying, testing & commissioning of 'C' class heavy duty GI pipe conforming to IS
3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets
etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting
with two or more coats of synthetic enamel paint of required shade complete as required :
(For Pump Room Area)
5.1 200 mm nominal dia (wall thickness = 6.3 mm) (Main Suction & Main Discharge Header in the
Rmt 20 5,383.00 1,07,660.00
Pump Room)
5.2 150 mm nominal dia (Suction & Discharge Line for Main Hydrant Pump, Main Sprinkler
Rmt 30 5,019.00 1,50,570.00
Pump, Diesel Engine Driven Pump & Booster Pump)
5.3 100 mm nominal dia (Pump Test Drain Line) Rmt 5 3,487.00 17,435.00
5.4 50 mm nominal dia (Suction & Discharge Line for Jockey Pump) Rmt 10 1,679.00 16,790.00
6.0 SLUICE VALVE
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with
non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers,
gaskets and conforming to IS 780 of following sizes as required :

6.1 200 mm nominal dia (On Main Suction & Discharge Header) Nos. 2 38,758.00 77,516.00
7.0 BUTTERFLY VALVE
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with
bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets
conforming to IS 13095 of following sizes as required :
7.1 150 mm nominal dia (For Main Hydrant, Main Sprinkler & Diesel Engine Driven Pump Suction
& Discharge, For Booser Pump Suction & Discharge, For External Hydrant & Sprinkler Line, For Nos. 17 8,829.00 1,50,093.00
2 Way Fire Brigade Inlet)
PART D2_BOQ_COPT,IIT BOMBAY 32 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
7.2 100 mm nominal dia (For Pump Test Drain Line) Nos. 1 6,570.00 6,570.00
7.3 50 mm nominal dia (For Hydrant & Sprinkler Jockey Pump Suction & Discharge line)
Nos. 4 3,729.00 14,916.00
8.0 Y-STRAINER
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out
of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel
flange.
8.1 150 mm nominal dia (For Main Hydrant, Sprinkler, Diesel Engine, Booster Pump Suction Line)
Nos. 6 10,981.00 65,886.00
8.2 50 mm nominal dia (For Jockey Hydrant & Sprinkler Pump Suction Line) Nos. 2 13,800.00 27,600.00
9.0 NON RETURN VALVE
Providing, installation, testing and commissioning of non-return valve of following sizes
confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :

9.1 200 mm nominal dia (For Discharge Header) Nos. 1 28,854.00 28,854.00
9.2 150 mm nominal dia (For Main Hydrant, Main Sprinkler, Diesel Engine Driven & Booster
Nos. 6 17,526.00 1,05,156.00
Pump Discharge)
9.3 50 mm nominal dia (For Hydrant & Sprinkler Jockey Pump Discharge) Nos. 2 5,705.00 11,410.00
10.0 PRESSURE SWITCH
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
Nos. 8 1,523.00 12,184.00
(For All Pump Outlet)
11.0 PRESSURE GAUGES
Providing, fixing including testing and commissioning 150 mm dia pressure gauge of range
250 PSI working pressure conforming to IS - 3624 having bourdon tube of stainless steel 310
in cast aluminium, stove enamelled, black, weather proof case with outer, screwed
aluminium bezel and complete with necessary U-type stainless steel siphon tube and cock
Set 39 2,875.00 1,12,125.00
including providing suitably painted angle iron support to the tube etc.as per specification
complete as required. (For Each Pump Suction & Discharge Line, For Sprinkler & Hydrant
Header in the Pump Room & For Sprinkler Tap off line at each floor of each shaft)

12.0 AIR VESSEL


Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height
with air release valve on top and flanged connection to riser, drain arrangement with 25 mm
dia gun metal wheel valve with required accessories, pressure gauge and painting with Nos 1 17,978.00 17,978.00
synthetic enamel paint of approved shade as required.

13.0 INSTALLATION CONTROL VALVE


Providing, fixing, testing & commissioning of installation control valve of cast iron body,
brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper
arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet
riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure
switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS
pipe of required size, flanges, orifice plate, gasket etc of following sizes as required :

13.1 150 mm nominal dia Nos. 1 47,498.00 47,498.00


14.0 Providing & fixing full way lever operated following size of forged brass ball valve of brass
body with forged brass hard chrome-plated steel ball tested to a pressure not less than 16 Kg
/ sq.cm with threaded / flanged joints complete with nuts, bolts, gaskets, washers etc.

14.1 15 mm nominal dia (For Pressure Gauge Connection) Nos. 39 575.00 22,425.00
14.2 25 mm nominal dia (For Pressure Switch Connection) Nos. 8 748.00 5,984.00
15.0 Supplying, fixing, testing & commissioning of Flanged Foot Valve of rating PN 1.6 bronze/gun
metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 1538
of following sizes as required :
150 mm nominal dia (For Main Hydrant, Sprinkler, Diesel Engine, Pump Suction Line)
15.1 Nos. 3 28,750.00 86,250.00
15.2 50 mm nominal dia (For Jockey Hydrant & Sprinkler Pump Suction Line) Nos. 2 8,625.00 17,250.00
16.0 Providing & fixing MS fabricated, painting, etc. of Priming tank, piping at pump room about
1000 litre. capacity with necessary isolation valve and air release arrangements and leading
the pipes to the pumps at pump room including approved pressure gauge with cock etc.
complete. It shall be fabricated from 8 mm thick MS plate with painting. The scope shall also Job 1 32,775.00 32,775.00
include piping to individual pump suction with fittings & valves, etc. complete (total 5 nos. of
pumps in the pump room)

TOTAL FOR FIRE PUMPS & RELATED EQUIPMENT / ACCESSORIES 28,77,431.00


B INTERNAL & EXTERNAL HYDRANT SYSTEM
1.0 Providing, laying, testing & commissioning of 'C' class heavy duty GI pipe conforming to IS
3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets
etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting
with two or more coats of synthetic enamel paint of required shade complete as required :

1.1 150 mm nominal dia (Internal Hydrant Line & Terrace Level Booster Pump Line) Rmt 150 5,019.00 7,52,850.00
1.2 80 mm nominal dia (Hydrant Stand Post) Rmt 30 2,433.00 72,990.00
2.0 Supplying and fixing of fire brigade connection of cast iron body with gun metal male
instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe
connection conforming to IS 904 as required :
2.1 2 way - 100 mm dia M.S. Pipe Nos. 3 6,644.00 19,932.00
2.2 4 way - 150 mm dia M.S. Pipe Nos. 1 13,770.00 13,770.00

PART D2_BOQ_COPT,IIT BOMBAY 33 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
3.0 Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia
instantaneous FM Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS
5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :

3.1 Single headed Stainless steel Nos. 10 6,049.00 60,490.00


4.0 Supplying and fixing Double headed internal hydrant valve with instantaneous Stainless Steel
coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with
blank Gunmetal/Stainless Steel cap and chain as required :

4.1 Double headed Stainless steel Nos. 21 12,098.00 2,54,058.00


5.0 Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red,
conforming to IS 884 complete with the following as required.
(a) 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type-2 as per IS:
12585.
(b) 20 mm nominal internal dia gun metal globe valve & nozzle.
(c) Drum and brackets for fixing the equipment on wall.
(d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.

5.1 40 m Nos. 31 11,897.00 3,68,807.00


6.0 Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female
couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :

6.1 Stainless Steel (Grade 304) Nos. 31 4,383.00 1,35,873.00


7.0 Supplying & fixing 63 mm dia stainless Steel short branch pipe with 20 mm nominal internal
diameter size nozzle conforming to IS 903 suitable for instantaneous connection to
interconnect hose pipe coupling as
7.1 Stainless Steel (Grade 304) Nos. 31 1,638.00 50,778.00
8.0 Providing and fixing lockable cabinet of size not less than 0.60 mtr x 0.75 mtr (height) x 0.25
mtr made out of MS sheet of 16 gauge thickness having central opening and 4 mm thick
glazed glass doors (Two nos.) suitably marked on the outside with the letters "FIRE HOSE"
including necessary locking arrangement and shall be painted with two coats red colour.
Over a two coats of primer. The cabinet shall be suitable to accommodate 2 nos. 15 mtr long Nos. 21 7,498.00 1,57,458.00
Hose pipe & 1 No branch pipe nozzle. It shall be mounted on raised Brick platform complete
as required.(Cost shall be inclusive of providing break glass box containing key for the cabinet
along with hammer). (For Internal Hydrant)

9.0 Providing and fixing weather proof lockable cabinet of size not less than 0.60 mtr x 0.75 mtr
(height) x 0.25 mtr made out of MS sheet of 16 gauge thickness having central opening and 4
mm thick glazed glass doors (Two nos.) suitably marked on the outside with the letters "FIRE
HOSE" including necessary locking arrangement and shall be painted with two coats red
colour. Over a two coats of primer. The cabinet shall be suitable to accommodate 2 nos. 15 Nos. 10 7,498.00 74,980.00
mtr long Hose pipe & 1 No branch pipe nozzle. It shall be mounted on raised Brick platform
complete as required.(Cost shall be inclusive of providing break glass box containing key for
the cabinet along with hammer). (For External Hydrant)

10.0 Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with
orifice of required size to be fitted between flange & landing valve of external and internal
Nos. 31 1,302.00 40,362.00
hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.

11.0 Providing, fixing and commissioning of spring loaded air release valve : 25 mm dia suitable
for pressure of 15 Kg / sq.cm including flanges, nuts, bolts, washers etc. complete as
Nos. 3 4,025.00 12,075.00
required. (For Vertical Riser Hydrant Line)

12.0 Providing laying, testing & commissioning of 'C' class heavy duty GI Pipe conforming to IS
1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground
including welding, excavation &
providing cement concrete blocks as supports, anticorrosive treatment with coal tar/asphalt
tape as per IS 10221, refilling the trench etc. of following sizes complete as required.

12.1 150 mm nominal dia (External Yard Hydrant Line & Fire Brigade inlet Line) Rmt 520 5,099.00 26,51,480.00
TOTAL FOR INTERNAL & EXTERNAL HYDRANT SYSTEM 46,65,903.00
C AUTOMATIC SPRINKLER SYSTEM
1.0 Providing, laying, testing & commissioning of 'C' class heavy duty GI pipe conforming to IS
3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets
etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting
with two or more coats of synthetic enamel paint of required shade complete as required :

1.1 150 mm nominal dia


Rmt 90 5,019.00 4,51,710.00

1.2 100 mm nominal dia Rmt 45 3,487.00 1,56,915.00


1.3 80 mm nominal dia Rmt 330 2,433.00 8,02,890.00
1.4 65mm nominal dia Rmt 280 2,059.00 5,76,520.00
1.5 50mm nominal dia Rmt 300 1,679.00 5,03,700.00
1.6 40mm nominal dia Rmt 225 1,284.00 2,88,900.00
1.7 32mm nominal dia Rmt 290 1,177.00 3,41,330.00
1.8 25mm nominal dia Rmt 2060 986.00 20,31,160.00

PART D2_BOQ_COPT,IIT BOMBAY 34 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
2.0 Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with
bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets
conforming to IS 13095 of following sizes as required :
2.1 100mm dia Nos 21 6,570.00 1,37,970.00
3.0 Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of
rating 68 degree centigrade with required accessories :
3.1 Pendent Sprinkler Nos 920 514.00 4,72,880.00
3.2 Upright Sprinkler Nos 100 514.00 51,400.00
3.3 Horizontal Side Wall Sprinkler Nos 50 608.00 30,400.00
3.4 Concealed Sprinkler Nos 1 1,414.00 1,414.00
4.0 Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of
stainless steel complete with 15 NPT on reducer thread with maximum working pressure of
175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to
sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, centre
bracket, stockbar of following sizes complete as required.

4.1 1500 mm Nos 920 1,555.00 14,30,600.00


5.0 Providing, fixing, testing and commissioning of drain test assembly complete with pipe, drain
valve, test valve, sight glass, union, tee, elbow etc. complete with bolts, nuts, gasket, washers Nos 21 10,925.00 2,29,425.00
etc. as per NBC and as shown in the drawing.
6.0 Providing and Fixing electrically operated water flow switches (Paddle type) including tamper
switch and accessories, complete with tap off socket arrangement as required..

6.1 100mm dia Nos 21 9,200.00 1,93,200.00


7.0 Providing, fixing and commissioning of spring loaded air release valve : 25 mm dia suitable
for pressure of 15 Kg / sq.cm including flanges, nuts, bolts, washers etc. complete as Nos. 3 4,025.00 12,075.00
required. (For Vertical Riser Sprinkler Line)
8.0 Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with
orifice of required size to be fitted between flange & landing valve of external and internal
Nos. 21 1,302.00 27,342.00
hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.

9.0 Providing laying, testing & commissioning of 'C' class heavy duty GI Pipe conforming to IS
1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground
including welding, excavation &
providing cement concrete blocks as supports, anticorrosive treatment with coal tar/asphalt
tape as per IS 10221, refilling the trench etc. of following sizes complete as required.

9.1 150 mm nominal dia (External Sprinkler Line from Pump Room to Building Shaft-1,2 & 3)
Rmt 200 5,099.00 10,19,800.00

TOTAL FOR AUTOMATIC SPRINKLER SYSTEM 87,59,631.00


D FIRE EXTINGUISHERS
1.0 Supply, installation, testing and commissioning of following types of extinguisher with
provision of wall bracket (fixed with anchor fastener).
1.1 ISI marked (IS:15683:2018 ) ABC type fire extinguisher of 9 Kgs. Capacity, with initial filling in
brand new cylinder with powder coated finish, fitted with EPDM discharge hose, wall
mounting bracket and HELIUM LEAKAGE TEST, checkable pressure gauge and fire rating of
Nos. 41 4,025.00 1,65,025.00
Class A:6A and B: 183B. complete, confirming to IS. (For Each Floor near Staircase, For Each
Floor Electrical Panel Room, UPS Room, ELV Room, For Pump Room & For Lift Machine Room

1.2 Galvanised mild steel Fire bucket with clean sand & stand in accordance with IS 2546. Fire
bucket shall have two coats of anti corrosive paint, two coats of red colour conforming to
shade No. 536 or 538 of IS 5. The paint shall conform to IS 2932 on its outside & two coats of
white paint on the inside. The word "FIRE" shall be clearly stencilled on it in accordance with
IS 2546. Vendor to include in his quote all costs relating to mounting of the bucket at
Nos. 8 863.00 6,904.00
locations stated by the Fire NOC & the architect. Vendor to include in his quote all costs all
accessories, consumables, fittings & rigging equipment necessary for the satisfactory
installation of the same. (For Each Floor Electrical Panel Room, For Fire Pump Room & For Lift
Machine Room)

1.3 ISI marked (IS:15683:2018 ) CO2 type fire extinguisher of 4.5 Kgs. Capacity, with initial filling
in brand new cylinder with powder coated finish, fitted with EPDM discharge hose, wall
mounting bracket and HELIUM LEAKAGE TEST, checkable pressure gauge and fire rating of
Nos. 19 3,450.00 65,550.00
Class A:6A and B: 183B. complete, confirming to IS. (For Each Floor Electrical Panel Room,
UPS Room, ELV Room, For Pump Room & For Lift Machine Room)

TOTAL FOR FIRE EXTINGUISHERS 2,37,479.00


PART IV HVAC WORKS
A VRF AIR COOLED HVAC SYSTEM

PART D2_BOQ_COPT,IIT BOMBAY 35 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
1.0 Outdoor Units of VRF System Supply Installation, Testing & Commissioning of modular type
Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for
cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s),
minimum two compressors for above 14 HP modules, microprocessor based Controller, Side
discharge type condensing unit(s), with R 32 / R 410 Refrigerant, vibration isolators, with
suitable foundation etc. complete as required. The unit shall deliver the rated capacity at
AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall
be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled
with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions
shall not be less than 3.1 and IEER not less than 6.5 . refrigerant gas.

1.1 Capacity : 4.0 HP VRF ODU (Side Discharge) Nos. 6 1,41,638.00 8,49,828.00
1.2 Capacity : 6.0 HP VRF ODU (Side Discharge) Nos. 1 1,57,378.00 1,57,378.00
1.3 Capacity : 10.0 HP VRF ODU (Top Discharge) Nos. 1 2,49,838.00 2,49,838.00
1.4 Capacity : 14.0 HP VRF ODU (Top Discharge) Nos. 2 3,32,937.00 6,65,874.00
1.5 Capacity : 18.0 HP VRF ODU (Top Discharge) Nos. 10 4,23,718.00 42,37,180.00
1.6 Capacity : 20.0 HP VRF ODU (Top Discharge) Nos. 9 4,54,112.00 40,87,008.00
2.0 Four Way Cassette type VRF Indoor Units_ Supply, installation, testing and commissioning of
following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit
equipped with synthetic washable media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil,
electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration
isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%, Nos. 6 37,674.00 2,26,044.00
50Hz AC supply, complete, as required. The unit shall have automatic force shut down
provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor
unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
1.0 TR Four Way Cassette type AC Unit

3.0 Four Way Cassette type VRF Indoor Units_ Supply, installation, testing and commissioning of
following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit
equipped with synthetic washable media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil,
electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration
isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%,
Nos. 28 39,675.00 11,10,900.00
50Hz AC supply, complete, as required. The unit shall have automatic force shut down
provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor
unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
1.3 TR Four Way Cassette type AC Unit

4.0 Four Way Cassette type VRF Indoor Units_ Supply, installation, testing and commissioning of
following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit
equipped with synthetic washable media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil,
electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration
isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%,
Nos. 6 41,803.00 2,50,818.00
50Hz AC supply, complete, as required. The unit shall have automatic force shut down
provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor
unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
1.6 TR Four Way Cassette type AC Unit

5.0 Four Way Cassette type VRF Indoor Units_ Supply, installation, testing and commissioning of
following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit
equipped with synthetic washable media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil,
electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration
isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%,
Nos. 9 44,112.00 3,97,008.00
50Hz AC supply, complete, as required. The unit shall have automatic force shut down
provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor
unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
2.0 TR Four Way Cassette type AC Unit

6.0 Four Way Cassette type VRF Indoor Units_ Supply, installation, testing and commissioning of
following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit
equipped with synthetic washable media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil,
electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration
isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%,
Nos. 2 45,059.00 90,118.00
50Hz AC supply, complete, as required. The unit shall have automatic force shut down
provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor
unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
2.8 TR Four Way Cassette type AC Unit

PART D2_BOQ_COPT,IIT BOMBAY 36 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
7.0 Four Way Cassette type VRF Indoor Units_ Supply, installation, testing and commissioning of
following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit
equipped with synthetic washable media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil,
electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration
isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%,
Nos. 4 47,601.00 1,90,404.00
50Hz AC supply, complete, as required. The unit shall have automatic force shut down
provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor
unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
3.2 TR Four Way Cassette type AC Unit

9.0 One Way Cassette type VRF Indoor Units_ Supply, installation, testing and commissioning of
following minimum capacity 1-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit
equipped with synthetic washable media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil,
electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration
isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%, Nos. 8 53,903.00 4,31,224.00
50Hz AC supply, complete, as required. The unit shall have automatic force shut down
provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor
unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
1.3 TR One Way Cassette type AC Unit

10.0 Ductable type VRF Indoor Units_ Supply, installation, testing and commissioning of following
minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type
Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil,
electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain
pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± Nos. 8 49,261.00 3,94,088.00
10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in
case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be
at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
4.0 TR Ductable type AC Unit

11.0 Ductable type VRF Indoor Units_ Supply, installation, testing and commissioning of following
minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type
Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil,
electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain
pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± Nos. 11 54,701.00 6,01,711.00
10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in
case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be
at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
4.5 TR Ductable type AC Unit

12.0 Ductable type VRF Indoor Units_ Supply, installation, testing and commissioning of following
minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type
Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil,
electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain
pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± Nos. 10 72,605.00 7,26,050.00
10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in
case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be
at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
6.4 TR Ductable type AC Unit

13.0 Ductable type VRF Indoor Units_ Supply, installation, testing and commissioning of following
minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type
Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil,
electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain
pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± Nos. 6 79,233.00 4,75,398.00
10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in
case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be
at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
8.0 TR Ductable type AC Unit

14.0 TFA Ductable Type VRF Indoor Units_ Supply, installation, testing and commissioning of
following minimum capacity and external static pressure VRF/VRV ceiling mounted ductable
type Indoor unit equipped with washable synthetic media pre-filter, fan section with low
noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil,
electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain
pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ±
Nos. 3 86,984.00 2,60,952.00
10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in
case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be
at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
4.0 TR 635 CFM TFA Ductable type AC Unit

PART D2_BOQ_COPT,IIT BOMBAY 37 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
15.0 TFA Ductable Type VRF Indoor Units_ Supply, installation, testing and commissioning of
following minimum capacity and external static pressure VRF/VRV ceiling mounted ductable
type Indoor unit equipped with washable synthetic media pre-filter, fan section with low
noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil,
electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain
pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ±
Nos. 11 1,29,664.00 14,26,304.00
10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in
case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be
at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
6.4 TR 988 CFM TFA Ductable type AC Unit

16.0 VRF System Remote Controller Supply, Installation, testing & Commissioning of Central
Controller for entire VRV system , the scope includes the control wiring and conduting of the
Nos 7 97,011.00 6,79,077.00
same in a lot. The controller shall be programmed for soft integration with the building BMS
system
17.0 VRF System Cordless Remotes Supply, Installation, testing & Commissioning of Cordless
Remotes for cassette type indoor units , the scope includes the control wiring and conduting
Nos. 35 2,141.00 74,935.00
of the same in a lot. The controller shall be programmed for soft integration with the building
BMS system
18,0 VRF System Corded Remotes Supply, Installation, testing & Commissioning of Corded
Remotes for Ductable type indoor units & for TFA Units, the scope includes the control wiring
Nos. 49 3,738.00 1,83,162.00
and conduting of the same in a lot. The controller shall be programmed for soft integration
with the building BMS system
19.0 Branch Distribution refrigerant Pipe joints with precase insulation SITC of Imported Branch
Distribution Joints for VRF system. ( The quantity shown here is indicative - in case the
Nos 100 4,888.00 4,88,800.00
quntity requirement is differ based on the system selection for the specific product the
revised quantity is required to quoted here)
20.0 Refrigeration Copper Piping For VRF System
Supply, Installation, testing and commissioning including vacc-
umiazation and Nitrogen testing of following nominal sizes of soft /hard drawn copper
refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring
type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O Rmt 10 336.00 3,360.00
tubular insulation/with Class-O closed cell elasto metric nitrile rubber tubular sleeves
sections of specified thickness as given below for Suction and Liquid lines, all accessories as
per specifications etc. as required :
6.4mm dia with tube thickness 1.2 mm with 19 mm thick Insulation
21.0 Refrigeration Copper Piping For VRF System
Supply, Installation, testing and commissioning including vacc-
umiazation and Nitrogen testing of following nominal sizes of soft /hard drawn copper
refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring
type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O Rmt 925 470.00 4,34,750.00
tubular insulation/with Class-O closed cell elasto metric nitrile rubber tubular sleeves
sections of specified thickness as given below for Suction and Liquid lines, all accessories as
per specifications etc. as required :
9.5 mm dia with tube thickness 1.2 mm with 19 mm thick Insulation
22.0 Refrigeration Copper Piping For VRF System
Supply, Installation, testing and commissioning including vacc-
umiazation and Nitrogen testing of following nominal sizes of soft /hard drawn copper
refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring
type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O Rmt 620 598.00 3,70,760.00
tubular insulation/with Class-O closed cell elastomeric nitrile rubber tubular sleeves sections
of specified thickness as given below for Suction and Liquid lines, all accessories as per
specifications etc. as required :
12.7 mm dia with tube thickness 1.2 mm with 19 mm thick Insulation
23.0 Refrigeration Copper Piping For VRF System
Supply, Installation, testing and commissioning including vacc-
umiazation and Nitrogen testing of following nominal sizes of soft /hard drawn copper
refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring
type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O Rmt 895 853.00 7,63,435.00
tubular insulation/with Class-O closed cell elastomeric nitrile rubber tubular sleeves sections
of specified thickness as given below for Suction and Liquid lines, all accessories as per
specifications etc. as required :
15.86 mm dia with tube thickness 1.2 mm with 19 mm thick Insulation
24.0 Refrigeration Copper Piping For VRF System
Supply, Installation, testing and commissioning including vacc-
umiazation and Nitrogen testing of following nominal sizes of soft /hard drawn copper
refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring
type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O Rmt 175 868.00 1,51,900.00
tubular insulation/with Class-O closed cell elastomeric nitrile rubber tubular sleeves sections
of specified thickness as given below for Suction and Liquid lines, all accessories as per
specifications etc. as required :
19 mm dia with tube thickness 1.2 mm with 19 mm thick Insulation

PART D2_BOQ_COPT,IIT BOMBAY 38 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
25.0 Refrigeration Copper Piping For VRF System
Supply, Installation, testing and commissioning including vacc-
umiazation and Nitrogen testing of following nominal sizes of soft /hard drawn copper
refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring
type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O Rmt 710 990.00 7,02,900.00
tubular insulation/with Class-O closed cell elastomeric nitrile rubber tubular sleeves sections
of specified thickness as given below for Suction and Liquid lines, all accessories as per
specifications etc. as required :
22.2 mm dia with tube thickness 1.2 mm with 19 mm thick Insulation
26.0 Refrigeration Copper Piping For VRF System
Supply, Installation, testing and commissioning including vacc-
umiazation and Nitrogen testing of following nominal sizes of soft /hard drawn copper
refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring
type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O Rmt 160 1,541.00 2,46,560.00
tubular insulation/with Class-O closed cell elastomeric nitrile rubber tubular sleeves sections
of specified thickness as given below for Suction and Liquid lines, all accessories as per
specifications etc. as required :
28.58 mm dia with tube thickness 1.2 mm with 19 mm thick Insulation
27.0 Refrigeration Copper Piping For VRF System
Supply, Installation, testing and commissioning including vacc-
umiazation and Nitrogen testing of following nominal sizes of soft /hard drawn copper
refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring
type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O Rmt 320 2,185.00 6,99,200.00
tubular insulation/with Class-O closed cell elastomeric nitrile rubber tubular sleeves sections
of specified thickness as given below for Suction and Liquid lines, all accessories as per
specifications etc. as required :
34.9 mm dia with tube thickness 1.62 mm with 19 mm thick Insulation
28.0 Refrigeration Copper Piping For VRF System
Supply, Installation, testing and commissioning including vacc-
umiazation and Nitrogen testing of following nominal sizes of soft /hard drawn copper
refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring
type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O Rmt 420 2,944.00 12,36,480.00
tubular insulation/with Class-O closed cell elastomeric nitrile rubber tubular sleeves sections
of specified thickness as given below for Suction and Liquid lines, all accessories as per
specifications etc. as required :
41.27 mm dia with tube thickness 1.62 mm with 19 mm thick Insulation
29.0 Communication Cabling For VRF System Providing and fixing of Control Cabling between the
indoor units & outdoor units. 4C x 2.5 Sq.mm 2XWY XLPE insulated, PVC inner sheathed,
Rmt 2118 351.00 7,43,418.00
copper conductor, armoured , FRLS PVC outer sheathed cables.

30.0 PVC Drain - Providing and fixing of PVC Drain Piping Duly Insulated with 9 mm Nitrile Rubber
And BOPP Tape Of Following Size Dia.-25 MM Rmt 405 167.00 67,635.00

31.0 PVC Drain - Providing and fixing of PVC Drain Piping Duly Insulated with 9 mm Nitrile Rubber
And BOPP Tape Of Following Size Dia.-32 MM Rmt 260 190.00 49,400.00

32.0 PVC Drain - Providing and fixing of PVC Drain Piping Duly Insulated with 9 mm Nitrile Rubber
And BOPP Tape Of Following Size Dia.-40 MM Rmt 250 236.00 59,000.00

33.0 PVC Drain - Providing and fixing of PVC Drain Piping Duly Insulated with 9 mm Nitrile Rubber
And BOPP Tape Of Following Size Dia.-50 MM Rmt 155 259.00 40,145.00

34.0 Cable Tray with top cover for Terrace Level Refrigeration Piping : Supplying and fixing
following sizes of Hot Dipped G.I Perforated cable trays with GI Suspenders including
couplers, Bends, Reduces and other accessories as required, and duly suspended from the
Rmt 75 1,047.00 78,525.00
ceiling with suspenders/Angle supports, fixed on ceiling/walls/false flooring on fasteners etc
as per specifications complete as required. Size : 150mm x 65mm x 1.6mm

35.0 Cable Tray with top cover for Terrace Level Refrigeration Piping : Supplying and fixing
following sizes of Hot Dipped G.I Perforated cable trays with GI Suspenders including
couplers, Bends, Reduces and other accessories as required, and duly suspended from the
Rmt 25 1,587.00 39,675.00
ceiling with suspenders/Angle supports, fixed on ceiling/walls/false flooring on fasteners etc
as per specifications complete as required. Size : 300mm x 65mm x 1.6mm

36.0 Cable Tray with top cover for Terrace Level Refrigeration Piping : Supplying and fixing
following sizes of Hot Dipped G.I Perforated cable trays with GI Suspenders including
couplers, Bends, Reduces and other accessories as required, and duly suspended from the
Rmt 20 2,139.00 42,780.00
ceiling with suspenders/Angle supports, fixed on ceiling/walls/false flooring on fasteners etc
as per specifications complete as required. Size : 450 mm x 65mm x 1.6mm

TOTAL OF VRF AIR COOLED HVAC SYSTEM 2,39,84,022.00


B AIR HANDLING UNITS (AHUs)

PART D2_BOQ_COPT,IIT BOMBAY 39 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
1.0 Supply, Installation, testing & commissioning of Ceiling Suspended / Floor Mounted Double
Skinned AHU with Sandwiched insulated sectionalized construction having thermal break
profile with Mixing chamber and vibration isolations Comprising of Fan section with
Backward / Forward curved Fan (to be selected by OEM based on the performance curve of
fan & efficiency of the fan) , Connected with fire resistant flexible outlet connection, Filter
Section with Pre filter and MERV-13 Fine Filters, Cooling coil section with 6R Deep Cooling
coils having 13 FPI aluminium fins and copper tubes, 2 Pass PVC Moisture eliminators, UVGI
(Ultra Violet Germicidal Irradiation) system, condensate drain pan duly insulated with cross
linked polymer, insulated drain piping; complete with flexible couplings at each coil
connection to header, including temperature & pressure gauges for each AHU inlet outlet
header; floor mounted unit to be installed on Cushy foot type vibration isolators with 95%
vibration isolation efficiency. AHU starter panel shall be in the scope of AHU Supply.

The starter should be equipped with required DC supply for operation of two way valve. The
DC Voltage shall be as per specific requirement of valve control. Upstream incoming AHU
power cable up to starter panel shall be in electrical Contractor's scope and down stream
cable from panel onwards to filed shall be part of HVAC Contractor's scope including
terminations. The Rate should include the price of AHU kit for integration of AHU with third
party VRF ODU.
1.1 700 CFM / 1.6 TR / 25 mm ESP (Ceiling Suspended) Nos. 2 1,20,750.00 2,41,500.00
1.2 1200 CFM / 4.5 TR / 25 mm ESP (Floor Mounted) (AHU to be provided with Terminal HEPA
Nos. 2 1,75,088.00 3,50,176.00
Filter)
1.3 1650 CFM / 4.0 TR / 25 mm ESP (Ceiling Suspended) Nos. 2 2,45,525.00 4,91,050.00
2.0 Supply / Installation / Testing and Commissioning of BMS Communicable Thermostatic
Decorative LCD Display Room Controller with 10 Rmt control wire and conduit for AHUs Nos. 3 10,994.00 32,982.00

TOTAL FOR AIR HANDLING UNITS (AHUs) 11,15,708.00


C SHEET METAL WORK
1 Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal
rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter
dampers, vanes, hangers, supports etc. as per approved drawings and specifications of Sqm. 5685 1,064.00 60,48,840.00
following sheet thickness complete as required.
Thickness 0.63 mm (24 Guage)
2 Sheet Metal Work_ Supply, installation, balancing and commissioning of factory fabricated
GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows,
splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications
Sqm. 1135 1,245.00 14,13,075.00
of following sheet thickness complete as required.
Thickness 0.8 mm (22 Guage)

3 Duct Damper Supply, installation, testing and commissioning of GI volume control duct
damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as Sqm. 6 6,943.00 41,658.00
per specifications.
4 Supply Grill Supplying & fixing of powder coated extruded aluminium Supply Air Grills with
Sqm. 6 8,972.00 53,832.00
aluminium volume control dampers as per specifications.
5 Return Grill Supplying & fixing of powder coated extruded aluminium Return Air Grills with
Sqm. 24 5,824.00 1,39,776.00
louvers but without volume control dampers complete as required.
6 Continuous Grill Supplying & fixing of powder coated extruded aluminium Continuous Air
Grills with aluminium volume control dampers as per specifications. Sqm. 72 10,638.00 7,65,936.00

7 Supply Diffuser Supplying, fixing testing commissioning of supply air diffusers of powder
coated aluminium with aluminium volume control dampers with anti smudge ring & Sqm. 91 12,006.00 10,92,546.00
removable core.
8 Return Diffuser Supplying, fixing testing commissioning of Return air diffusers of powder
coated aluminium without volume control dampers with anti smudge ring & removable core. Sqm. 80 8,002.00 6,40,160.00

9 Flexible Duct Supply, Installation, Testing and Commissioning of thermal insulated Flexible
Duct of following sizes duly supported at regular interval as per site requirement etc. Mtr 60 576.00 34,560.00
complete as required as per specification. 200 mm dia.
10 Fire Damper Supplying, fixing testing commissioning of Fire Dampers in supply air duct / main
branch and return air path as and where required size including control wiring, the damper
shall be motorized and spring return so as to close the damper in the event of Power failure
automatically and open the same in case of power being restored. The Spring return action
shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in
the event of fire signal complete as required as per specification.

10.1 Fire Damper


Sqm. 1 10,503.00 10,503.00
10.2 Actuator
Nos. 3 9,803.00 29,409.00
11 Flow Controller Supply, Installation, Testing and Balancing of mechanical type constant
volume air flow controller with damper for fresh air distribution to indoor units with all Nos 49 3,036.00 1,48,764.00
necessary accessories. Capacity. 100 mm
12 AHU Room Acoustic Insulation - Supply and fixing of acoustic lining on wall and ceiling of
AHU Rooms with 50 mm thick, density 32 kg/cu.m. resin bonded glass fiber insulation friction
fixed in 610 mm x 610 mm frame work made of 25x50x50x50x25 mm made of 0,6 mm thick
Sqm. 10 1,211.00 12,110.00
GI Sheet U shaped channel & covered witn reinforced fiber glass tissue and finished with 0.8
mm perforated aluminium sheet etc. complete as per specification and as required.

PART D2_BOQ_COPT,IIT BOMBAY 40 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
13 Duct Thermal Insulation - Supplying and fixing of following thickness duly laminated
aluminium foil of mat finish closed cell Nitrile rubber (Class "O") insulation on existing duct
after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide
Sqm. 3840 743.00 28,53,120.00
and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and
as required.
Thickness 19 mm
14 Duct Acoustic Insulation - Supply and fixing of acoustic lining of supply air duct and plenum
with 25 mm thick resin bonded glass wool having density of 32 Kg/mtr3, with 25 mm x 25 mm
GI Section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic
Sqm. 290 698.00 2,02,420.00
tissue paper and 0.5 mm thick perforated aluminium sheet fixed to inside surface of ducts
with cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete as required and as
per specification.
15 Underdeck Insulation - Supply, fixing & thermal lining below RCC slab insulated with Resin
Bonded wool of density of 80 Kg/m³ and thickness of 50 mm covered with one side
aluminium foil (Core material - without any outer facing, Confirming to ASTM E 84, NFPA 90A,
90B, LIFE SAFETY CODE NFPA101 & 120 Minutes fire rating as per building insulation
requirements) , applied below slab with the help of screw & washer - Cross wire system and Sqm. 1350 575.00 7,76,250.00
the joints shall be sealed with 72 mm wide self adhesive aluminium tape having high strengh
(70 microns). Thermal Resistance (R- value) shall be minimum 7 hr*ft²*˚F/BTU at 35 Deg C
mean temperature.

TOTAL FOR SHEET METAL WORK 1,42,62,959.00


D VENTILATION FANS
1 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
Nos 1 1,78,250.00 1,78,250.00
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
10,000 CFM / 40 mm ESP (Floor Mounted Toilet Exhaust Fan at terrace level)

2 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
Nos 1 1,55,250.00 1,55,250.00
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
9,000 CFM / 40 mm ESP (Floor Mounted Toilet Exhaust Fan at terrace level)

3 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3 Nos 1 1,49,500.00 1,49,500.00
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
7,000 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 3)

PART D2_BOQ_COPT,IIT BOMBAY 41 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
4 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
Nos 1 74,750.00 74,750.00
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
5200 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 1)

5 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
Nos 1 74,750.00 74,750.00
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
4100 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 6)

6 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3 Nos 1 74,750.00 74,750.00
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
3700 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 12 & 15)

7 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3 Nos 2 74,750.00 1,49,500.00
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
3500 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 5 & 10)

PART D2_BOQ_COPT,IIT BOMBAY 42 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
8 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3 Nos 2 74,750.00 1,49,500.00
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
3400 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 2 & 8)

9 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3 Nos 1 74,750.00 74,750.00
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
3100 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 14 & 16)

10 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3 Nos 2 74,750.00 1,49,500.00
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
3000 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 4 & 9 Fume
Hood)

11 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3 Nos 2 67,275.00 1,34,550.00
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
2800 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 4 & 11)

PART D2_BOQ_COPT,IIT BOMBAY 43 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
12 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
Nos 1 67,275.00 67,275.00
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
2700 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 9)

13 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
Nos 1 67,275.00 67,275.00
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
2400 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 7)

14 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. 3
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3 Nos 1 43,700.00 43,700.00
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
1400 CFM / 50 mm ESP (Floor Mounted Exhaust Fan at terrace level For Lab - 13)

15 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. Single
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
Nos 1 25,300.00 25,300.00
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
600 CFM / 20 mm ESP (Ceiling Mounted for Ground Floor Pantry area)

PART D2_BOQ_COPT,IIT BOMBAY 44 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
16 Mechanical Ventilation - Centrifugal Exhaust Air Fans_ SITC of Cabinet (Square) Type Inline
Centrifugal Exhaust Air Fan AMCA Certified (For Air and Sound Performance) suitable for
installing in any position in vertical or horizontal ducts. The casing shall be single skin,
internally acoustically lined and constructed of galvanised steel. The inline fan shall be with
Forword curve up to 1500 CFM & above shall be backward curve centrifugal impeller fitted
with maintenance free external rotor motor, flexible connections at the discharge & inlet.
The motor shall be suitable for 220/415±10% volt single/three phase 50 Hz AC supply. Single
phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
Nos 6 25,300.00 1,51,800.00
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3
meter distance. Static pressure calculation of Fans shall be checked by Vendor/Contractor
prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the
Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
The contactor has to consider necessary cowl with bird screen provision
450 CFM / 20 mm ESP (Ceiling Mounted for 1st to 6th Floor Pantry area)

TOTAL FOR VENTILATION FANS 17,20,400.00


PART V ELECTRICAL WORKS
1.0 MEDIUM VOLTAGE PANELS
Supply, installation, testing & commissioning of floor mounting front operated front access
cubicle type, totally enclosed, dust and vermin proof with IP-54 protection with hinged and
lockable doors. Switchboards fabricated from 2 mm thick CRCA sheets including
interconnections, tinned copper crimping lugs, bonding to earth and painting suitable for use
at 415 V, 3 phase 4 wire 50 Hertz system, and suitable for a fault level of as indicated in SLD
symmetrical at 415 V complete as per specifications, as required and as below : All
switchboards shall have provision for entry of cables from the top/bottom as required. All
live accessible parts shall be shrouded and all equipment shall be finger touch proof. The bus
bars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports
shall be used. (Ref SLD-INI-IITB-COPT-EL-SLD-01)

Note :-
1) All G.A. & fabrication drawings shall be got approved from the E.I.C\Consultants. Final
painting of panel to be done with powder coating. Necessary touch up may be done at site,
in case if required. The scope includes all tests Heat run test ( On main LT Panel only) ,
relevant I.S. and as required by E.I.C, shall have to be performed at factory in the presence of
users & at installation site and shall be included in the quoted rate.

2) Stagewise inspection & Heat Run test is to be offered


3) The equipment shall be designed to ensure complete safety during operation inspection,
connection of cables etc.
4) Control wires shall be of 1.1 KV 2.5 sq.mm FRLS copper wires and neatly bunched
separately and adequately supported so as to prevent sagging and strain on termination.

5) A minimum of 10% spare terminals shall be provided on each terminal block.


6) All non current carrying metallic parts of the equipment shall be earthed with copper
material.
7) All concealed hinged doors and covers shall be provided with suitable flexible earthing
connections.
8) The size of the earth bus chosen shall be to withstand full fault current as mentioned
panel wise.
9) Earth bus bar shall be supported at suitable intervals.
10) All the current transformers are resin cast type class-I only.
11) Scope includes cable end boxes, reverse entry boxes as per site conditions and extension
of bus bars as required for terminating the number of cables as per schematic diagram.

12) G.A. & detailed fabrication drawing and short circuit forces and temp rise calculation for
panel including the panel fabricator shall be submitted for dept. approval.

13) Bimetallic washers to be used for all aluminium to copper joints & it shall be of approved
make & quality.
14) Indication lamp shall be cluster type LED.
15) All Outgoing feeders shall have 'ON' indication lamp.
16) All neutral shall be isolatable type.
17) All MCCB shall have minimum breaking capacity (Ics=Icu) as mentioned panel wise &
must be IOT type for remote operation
18) All panel shall be provided with names plates of black perplex in white Engraving and to
be provided on both front and back side of the panels as safety feature and for proper
identification of panel.
Supply, Installation, Testing & Commissioning of free standing, floor mounting
compartmentalized panels fabricated out of CRCA sheet steel sections after carrying out 7
tank cleaning process & duly powder coated using Siemens Grey shade no. RAL- 7032.

1.1 MAIN LT PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-01)


NOTE: i) The two nos.2000A incomers in the main LT panel will be feed from nearest sub-
station/s by IIT B.ii) IIT B will lay necessary cables from the sub-station/s to the main LT
panel.iii) IIT B will also terminate all the cables on the two nos. 2000A incomers iv) The Main
LT Panel will be manufactured as per details in the approved SLD.

PART D2_BOQ_COPT,IIT BOMBAY 45 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
There shall be interlocking of the both incomer and bus coupler in a manner that any given
time Only one incomer supply power with bus -coupler remaining Normally close . Refer sld
also.
A. INCOMERS:
A.1 2 Nos. 2000 amps, 4P, 415V, 50HZ, AC, Ics=Icu=Icw = 65kA for 1 sec., EDO operated fully
draw out type air circuit breaker & with built in microprocessor based release unit for total
LSIG protections, indications and measurement as per specification and with following
accessories :
i. Three nos. phase indicating light through protected by 2 amps MCB’s. - 2 set
ii. Breaker ON / OFF / TRIP /SPRING CHARGE/TRIP CIRCUIT HEALTHY indicating lights with
control MCB’s. - 2 set
iii. Under voltage release - 2 set
iv. 24 V DC Shunt trip coil - 2 set
v. 96 x 96 mm sq. 0-2000/ 5 amps CTR digital ammeter with 3 nos. 2000/ 5 amps, Bar Primary,
15 VA Burden, CL : 1 accuracy CT’s - 2 set
vi. 96 x 96 mm sq. 0-500 Volt digital voltmeter with selector switch and protected by 2 amp
TP MCB’s - 2 set
vii. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 2 set
viii. Breaker control switch - 2 set
B BUS-COUPLER
B.1 1 Nos. 2000 amps, 4P, 415V, 50HZ, AC, Ics=Icu=Icw = 65kA for 1 sec., EDO operated fully
draw out type air circuit breaker & with built in microprocessor based release unit for total
LSIG protections, indications and measurement as per specification and with following
accessories :
i. Three nos. phase indicating light through protected by 2 amps MCB’s. - 1 set
ii. Breaker ON / OFF / TRIP indicating lights with control MCB’s - 1 set.
iii. Breaker control switch - 1 set
C. Bus Bars
2000 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 65 KA for 1 sec.

D. Outgoing
i. 1 no. 630 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA with Energy
meter with RS 485 port. The MCCB shall be complete as per technical specifications and
single line diagram. (For Ground Floor panel)
ii 1 no. 630 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA with Energy
meter with RS 485 port. The MCCB shall be complete as per technical specifications and
single line diagram. (For First floor panel)
iii 1 no. 200 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA with Energy
meter with RS 485 port. The MCCB shall be complete as per technical specifications and
single line diagram. (For Second floor panel)
iv. 1 no. 250 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA with Energy
meter with RS 485 port. The MCCB shall be complete as per technical specifications and
single line diagram. (For Third floor panel)
v. 1 no. 400 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA with Energy
meter with RS 485 port. The MCCB shall be complete as per technical specifications and
single line diagram. (For Fourth floor panel)
vi. 1 no. 400 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA with Energy
meter with RS 485 port. The MCCB shall be complete as per technical specifications and
single line diagram. (For Fifth floor panel)
vii. 1 no. 400 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA with Energy
meter with RS 485 port. The MCCB shall be complete as per technical specifications and
single line diagram. (For Sixth floor panel)
viii. 1 no. 400 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA with Energy
meter with RS 485 port. The MCCB shall be complete as per technical specifications and
single line diagram. (For Common area Emergency panel)
ix. 1 no. 160 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA with Energy
meter with RS 485 port. The MCCB shall be complete as per technical specifications and
single line diagram. (For main UPS panel)
x 1 no. 630 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram. (For APFC panel)

xi 1 no. 630 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram. (For APFC panel)

E. Spare MCCB’s of following :


PART D2_BOQ_COPT,IIT BOMBAY 46 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
i 2 nos 400 amps 4 Pole MCCB, with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram.

ii. 2 no. 630 amps 4 Pole MCCB, with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram.

F. Notes :
i. All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not required for Spare outgoing)
b. Digital electronic ammeter with selector switch and 3 Nos. CT’s.
c. All breakers shall be electrically/ mechanically interlocked as per single line diagram.

ii. All MCCB’s shall be rated for minimum 26 KA (ICS) breaking capacity.
iii. All ACB's shall be suitable for 65kA ( Icu=Ics=Icw for 1 sec.)
iv. 415 / 110 V suitable rating control transformer shall be provided for aux. control supply if
necessary.
v. Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
vi All incoming as well as outgoing feeders shall have pad locking facility.
vii suitable danger board shall be provided.
viii All bus bar section / backside panels shall have pad locking facility and hinged type door.

The Main LT panel-described above complete with wiring, line diagram, specifications and
approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 49,60,319.00 49,60,319.00

1.2 COMMON CUM EMERGENCY PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-01)


A. INCOMER
1 2 no. 400 amps 4 pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram.
There shall be interlocking of the both incomer and bus coupler in a manner that any given
time only one incomer supply power with bus -coupler remaining close while the failure of
any incomer automatically ON other incomer keeping bus coupler close Refer sld also.

i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 400 Amps digital electronic ammeter with selector switch and 3 nos. 400/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 2 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B BUS-COUPLER
B.1 1 Nos. 400 amps, 4P, 415V, 50HZ, AC, Ics=Icu=Icw = 50 kA for 1 sec., MCCB with built in
microprocessor based release unit for total LSIG protections, indications and measurement
as per specification and with following accessories :
i. Three nos. phase indicating light through protected by 2 amps MCB’s. - 1 set
ii. Breaker ON / OFF / TRIP indicating lights with control MCB’s - 1 set.
iii. Breaker control switch - 1 set
C Bus Bars
400 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 50 KA for 1 sec.

D OUTGOINGS
i. 1 no. 250 amps Four Pole MCCB microprocessor based release for complete LSIG protections
and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 36 KA with Energy meter with
RS 485 port. The MCCB shall be complete as per technical specifications and single line
diagram.(For fire fighting panel)
ii. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram(For 50kVA UPS OUTPUT PANEL)

iii. 1 no. 160 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (For HVAC EXHAUST PANEL
TERRACE FLOOR)

iv. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram(For Plumbing panel)

PART D2_BOQ_COPT,IIT BOMBAY 47 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
v. 3 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (For Lift )
vi 3 no. 40 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram (For Lift lighting)

vii 2 no. 40 amps Four pole 100 mA 10 KA RCBO with thermal magnetic based release for
overload and short circuit protections and suitable for 415V, 50 Hz, A.C supply (External DB-
security cabin 1& 2)
viii. 1 no.25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram (PUMP room DB)

E SPARE FEEDERS
i 1 no. 160 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii 1 no. 250 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iv. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

F Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The Emergency Panel described above complete with wiring, line diagram, specifications and
approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 15,01,997.00 15,01,997.00

1.3 Ground Floor Panel- (Ref SLD-INI-IITB-COPT-EL-SLD-03)


A. INCOMER:
1 1 nos. 630 amps, 4 Pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram.

i 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 630 Amps digital electronic ammeter with selector switch and 3 nos. 630/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B BUS-BAR
i. 630 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 50 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 200 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram(For Laboratory 1 & 3).
ii. 2 no. 160 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA
included with Energy meter with RS 485 port. The MCCB shall be complete as per technical
specifications, single line diagram(For Laboratory 2 & 4).

iii. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (For HVAC Panel).

PART D2_BOQ_COPT,IIT BOMBAY 48 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
iv. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (For power DB-CA_GF & DB-office area).

v. 1no. 25 amps Four pole MCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The
MCB shall be complete as per technical specifications, single line diagram (For Light DB-CA).

vi. 1no.40 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram (For DB-Maintenance room).

D Spare MCCB’s of following rating :


i 1 no. 160 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1no.40 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The Ground floor Panel as described above complete with wiring, line diagram, specifications
and approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 11,66,733.00 11,66,733.00

1.4 First Floor Panel (Ref SLD-INI-IITB-COPT-EL-SLD-04)


A. INCOMER:
1 1 nos. 630 amps, 4 Pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram.

i 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii 0- 630 Amps digital electronic ammeter with selector switch and 3 nos. 630/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 630 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 50 KA for 1 sec.

C OUTGOING:
i. 2 no. 200 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu=36 KA included
with Energy meter with RS 485 port. The MCCB shall be complete as per technical
specifications, single line diagram(For Laboratory 5 & 8).

ii. 3 no. 160 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA
included with Energy meter with RS 485 port. The MCCB shall be complete as per technical
specifications, single line diagram(For Laboratory 6,7 & 9).

iii. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA
included with Energy meter with RS 485 port. The MCCB shall be complete as per technical
specifications, single line diagram(1st floor HVAC Panel).

iv. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (Power DB-CA_1F).

PART D2_BOQ_COPT,IIT BOMBAY 49 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
v. 1no.25 amps Four Pole MCB with thermal magnetic based release for overload and short
circuit protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The
MCB shall be complete as per technical specifications, single line diagram (For Light DB-CA-
1F).
D Spare MCCB’s for the following :
i. 1 no. 160 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA . The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1no.25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram
E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The First Floor Panel as described above complete with wiring, line diagram, specifications
and approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 11,91,430.00 11,91,430.00

1.5 Second Floor Panel (Ref SLD-INI-IITB-COPT-EL-SLD-05)


A. INCOMER:
i. 1 nos. 200 amps, 4 Pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram.

ii. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
iii. 0- 200 Amps digital electronic ammeter with selector switch and 3 nos. 200/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iv. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
v. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
vi Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 200 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 50 KA for 1 sec.

C OUTGOINGS:
i. 1 no. 125 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA
included Energy meter with RS 485 port. The MCCB shall be complete as per technical
specifications, single line diagram(For 2nd Floor HVAC panel).

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA
included Energy meter with RS 485 port. The MCCB shall be complete as per technical
specifications, single line diagram(For Laboratory 11 ).
iii. 3 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (For Power DB-CA_2F, DB-Staff room & DB-office area).

iv. 4 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (DB-class room, DB-Director room, DB-faculty room, DB-conference room)

v. 1 no. 25 amps Four pole MCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The
MCB shall be complete as per technical specifications, single line diagram (Light DB-CA_2F)

vi. 3 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram (Light DB-Faculty room, Light
DB-Office, Light DB-Lab 10)
D Spare MCCB’s for the following :

PART D2_BOQ_COPT,IIT BOMBAY 50 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
i. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu=36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 25 amps Four pole MCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The
MCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The Second Floor Panel as described above complete with wiring, line diagram, specifications
and approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 11,79,466.00 11,79,466.00

1.6 Third Floor Panel (Ref SLD-INI-IITB-COPT-EL-SLD-05)


A. INCOMING:
1 1 nos. 250 amps, 4 Pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram.

i 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0-250 Amps digital electronic ammeter with selector switch and 3 nos. 250/5 amps, Bar
primary, 15 VA Burden,, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B BUS BARS
i. 250 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 50 KA for 1 sec.

C OUTGOINGS:
i. 1 no. 160 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA
included with Energy meter with RS 485 port. The MCCB shall be complete as per technical
specifications, single line diagram (For 3rd floor HVAC Panel)

ii. 3 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (Power DB 1 & 2- Faculty Room 1& Power DB 2-Faculty room 2)

iii. 8 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (Power DB 1-Faculty room 2, Power DB-CA_3F, DB1 & 2-HOD staff, DB-
confernace room, DB-Class room, DB-faculty lounge & DB-meeting room 3)

iv. 1 no. 25 amps Four pole MCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The
MCB shall be complete as per technical specifications, single line diagram (For Light DB-
CA_3F)
v. 2 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram (Light DB-Faculty room 1 & 2)

D Spare MCCB’s for the following :


i. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

PART D2_BOQ_COPT,IIT BOMBAY 51 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The Third Floor Panel as described above complete with wiring, line diagram, specifications
and approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 10,80,856.00 10,80,856.00

1.7 Fourth Floor Panel (Ref SLD-INI-IITB-COPT-EL-SLD-06)


A. INCOMER:
1 1 nos. 400 amps, 4 Pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram.

i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 400 Amps digital electronic ammeter with selector switch and 3nos. 400/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 400 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 50 KA for 1 sec.

C OUTGOINGS
i. 4 no. 160 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA
included with Energy meter with RS 485 port. The MCCB shall be complete as per technical
specifications, single line diagram(For Laboratory 12, 13 & 14 & 4th Floor HVAC Panel)

ii. 4 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (For Power DB-CA_4f, Power DB 1& 2-Faculty room 1 & Power DB 2-
Faculty room 3)
iii. 4 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (Power DB 1 & 2-Faculty room 2 & Power DB 1-Faculty room 3 & DB-
Classroom)
iv. 1 no. 25 amps Four pole MCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The
MCB shall be complete as per technical specifications, single line diagram (For light DB-
CA_4F)
v. 3 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram (For Light DB-Faculty room 1,
2& 3)
D Spare MCB’s for the following :
i 1 no. 160 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

PART D2_BOQ_COPT,IIT BOMBAY 52 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
The Fourth Floor Panel as described above complete with wiring, line diagram, specifications
and approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 12,50,418.00 12,50,418.00

1.8 Fifth Floor Panel- (Ref SLD-INI-IITB-COPT-EL-SLD-07)


A. INCOMER:
1 1 nos. 400 amps, 4 Pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram.

i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 400 Amps digital electronic ammeter with selector switch and 3nos. 400/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
400 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 50 KA for 1 sec.

C OUTGOINGS
i. 3 no. 160 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA
included with Energy meter with RS 485 port. The MCCB shall be complete as per technical
specifications, single line diagram(For Laboratory 15, 16 & 5th floor HVAC panel)

ii. 5 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (For Power DB-CA_5F, Power DB 1 & 2 Faculty room 1, Power DB-Faculty
room 3, Power DB 2-Faculty room 4)
iii. 3 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (For power DB 1 & 2-Faculty room 2 & Power DB 1-Faculty room 4)

iv. 1 no. 25 amps Four pole MCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The
MCB shall be complete as per technical specifications, single line diagram (For Light DB-
CA_5F)
v. 4 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram (For Light DB-Faculty room 1,
2, 3 & 4)
D Spare MCB’s for the following :
i 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The Fifth Floor Panel as described above complete with wiring, line diagram, specifications
and approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 12,03,156.00 12,03,156.00

1.9 Sixth Floor Panel (Ref SLD-INI-IITB-COPT-EL-SLD-08)


A. INCOMER:
1 1 nos. 400 amps, 4 Pole MCCB with microprocessor based release for complete LSIG
protections and suitable for 415V, 50 Hz, A.C Supply and having Ics = Icu= 50 KA. The MCCB
shall be complete as per technical specifications and single line diagram.

i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 250 Amps digital electronic ammeter with selector switch and 3nos. 250/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
PART D2_BOQ_COPT,IIT BOMBAY 53 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
400 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 50 KA for 1 sec.

C OUTGOINGS:
i. 1 no. 200 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA
included with Energy meter with RS 485 port. The MCCB shall be complete as per technical
specifications, single line diagram(6th FLOOR HVAC PANEL)

ii. 4 no. 80 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram(For VTPN DB-AREA-7, AREA-8, AREA-10 & AREA-11)

iii. 5 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram(For Power DB-CA_6F, Power DB-Area 1, Power DB-Area 2, Power DB-Area
5 & Power DB-Area 9)
iv. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA with
Energy meter with RS 485 port. The MCCB shall be complete as per technical specifications,
single line diagram (Power DB-Area 3 & Power DB-Area 4)

iv. 1 no. 25 amps Four pole MCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The
MCB shall be complete as per technical specifications, single line diagram (For Light DB-
CA_6F)
v. 2 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram (For Light DB-Area 1& Light
DB-Area 11)
D SPARE FEEDERS
i 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 25 amps FP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The Sixth Floor Panel as described above complete with wiring, line diagram, specifications
and approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 11,31,961.00 11,31,961.00

1.10 FIRE FIGHTING PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-01)


A. INCOMER:
1 1 no.250 amps Four pole MCCB with Microprocessor based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagram and with
following accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 250 Amps digital electronic ammeter with selector switch and 3nos. 250/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
vi. Integration with pressure switch & Fire alarm panel
PART D2_BOQ_COPT,IIT BOMBAY 54 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
B Bus Bars
250 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 nos. 160 amps Triple Pole MCCB with thermal magnetic based release for overload and
short circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA.
The MCCB is connected to Soft starter & Overload relay (Type 2 coordination) .One Set of
ON/OFF/TRIP indicating Lamps & one set of Start/Stop Push Buttons shall be provided. The
MCCB & Star delta starter shall be complete as per technical specifications, single line
diagram and with accessories as shown in SLD.

ii. 5 no. 32 amps Triple pole, MCCB with thermal magnetic trip unit for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having and having Ics=Icu= 25
KA. The MCCB is connected to D.O.L Starter & overload relay starter(Type 2
coordination).One Set of ON/OFF/TRIP indicating Lamps & one set of Start/Stop Push Buttons
shall be provided. The MCCB & starter shall be complete as per technical specifications, single
line diagram and with accessories as shown in SLD.The cost shall include provision for
remote ON/OFF for each Jockey Pump & Booster pump.

D SPARE FEEDERS
i 1 nos. 200 amps Triple Pole MCCB with thermal magnetic based release for overload and
short circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA.
The MCCB is connected to Star Delta starter & Overload relay (Type 2 coordination) .One Set
of ON/OFF/TRIP indicating Lamps & one set of Start/Stop Push Buttons shall be provided. The
MCCB & Star delta starter shall be complete as per technical specifications, single line
diagram and with accessories as shown in SLD.

ii. 1 no. 32 amps Triple pole, MCCB with thermal magnetic trip unit for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having and having Ics=Icu= 25
KA. The MCCB is connected to D.O.L Starter & overload relay starter(Type 2
coordination).One Set of ON/OFF/TRIP indicating Lamps & one set of Start/Stop Push Buttons
shall be provided. The MCCB & starter shall be complete as per technical specifications, single
line diagram and with accessories as shown in SLD.The cost shall include provision for
remote ON/OFF for each Jockey Pump & Booster pump.

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The Fire Fighting Panel as described above complete with wiring, line diagram, specifications
and approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 7,36,736.00 7,36,736.00

1.11 PLUMBING PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-01)


A. INCOMER:
1 1 no. 40 amps Four pole MCCB with with thermal magnetic based release for overload and
short circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36KA.
The MCCB shall be complete as per technical specifications, single line diagramand with
following accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 40 Amps digital electronic ammeter with selector switch and 3nos. 40/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 63 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 32 amps Triple pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D Spare MCB’s for the following :


i. 3 no. 32 amps Triple pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

PART D2_BOQ_COPT,IIT BOMBAY 55 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The Plumbing Panel as described above complete with wiring, line diagram, specifications
and approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 4,90,838.00 4,90,838.00

1.12 HVAC EXHAUST PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-02)


A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos. 160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 18 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 2 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'HVAC EXHAUST PANEL' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 12,85,461.00 12,85,461.00
Consultant.
1.13 MAIN UPS PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-01)
A. INCOMER:
1 1 no. 160 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos. 160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 1 nos. 40 amps FP MCCB with thermal magnetic based release for overload and short circuit
protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA with Energy
meter with RS 485 port.
ii. 5 nos. 25 amps FP MCCB with thermal magnetic based release for overload and short circuit
protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA with Energy
meter with RS 485 port.
PART D2_BOQ_COPT,IIT BOMBAY 56 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
D SPARE FEEDERS
i. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'MAIN UPS PANEL as described above complete with wiring, line diagram, specifications
and approvals, painting and as per direction and final approval of Owner / Consultant. No. 1 7,88,670.00 7,88,670.00

1.14 UPS OUTPUT PANEL-GF (Ref SLD-INI-IITB-COPT-EL-SLD-02)


A. INCOMER:
1 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 100 Amps digital electronic ammeter with selector switch and 3nos. 100/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 2 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 2 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 2 set.
B Bus Bars
63 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 1 nos. 40 amps FP MCB suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA.

ii. 8 nos. 25 amps FP MCB suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA.

iii. 1 nos. 25 amps DP MCB suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA.

D SPARE FEEDERS
i 2 nos. 40 amps FP MCB suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA.

E Notes:-
All MCCB's shall be of 25 KA (Ics) breaking capacity.& MCB of 10KA breaking capacity

The 'UPS OUTPUT Panel' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 1,53,088.00 1,53,088.00
Consultant.
1.15 7.5kVA UPS OUTPUT PANEL-1st Floor
7.5kVA UPS OUTPUT PANEL-2nd Floor
7.5kVA UPS OUTPUT PANEL-3rd Floor
7.5kVA UPS OUTPUT PANEL-4th Floor
7.5kVA UPS OUTPUT PANEL-5th Floor
(Ref SLD-INI-IITB-COPT-EL-SLD-02)
A. INCOMER:
1 1 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 25 Amps digital electronic ammeter with selector switch and 3nos. 25/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 2 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 2 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 2 set.
B Bus Bars
i. 40 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 25 KA for 1 sec.

C OUTGOINGS:
PART D2_BOQ_COPT,IIT BOMBAY 57 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
i. 3 nos. 25 amps FP MCB suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA.

D Notes:-
All MCCB's shall be of minimum 25 KA (Ics) breaking capacity.& MCB of 10KA breaking
capacity
The 'UPS OUTPUT Panel' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 5 1,35,148.00 6,75,740.00
Consultant.
1.16 20kVA UPS OUTPUT PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-02)
A. INCOMER:
1 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 40 Amps digital electronic ammeter with selector switch and 3nos. 40/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 2 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 2 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 2 set.
B Bus Bars
i. 63 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 25 KA for 1 sec.

C OUTGOINGS:
i. 2 nos. 40 amps FP MCB suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA.

ii. 1 nos. 25 amps FP MCB suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10 KA.

D SPARE FEEDERS
i. 2 no. 40 amps Four pole MCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 10KA. The
MCB shall be complete as per technical specifications, single line diagram

E Notes:-
All MCCB's shall be of minimum 25 KA (Ics) breaking capacity.& MCB of 10KA breaking
capacity
The 'UPS OUTPUT Panel' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 1,39,932.00 1,39,932.00
Consultant.

1.17 LABORATORY PANEL-01 (Ref SLD-INI-IITB-COPT-EL-SLD-03)


A. INCOMER:
1 1 no. 200 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 200 Amps digital electronic ammeter with selector switch and 3nos. 200/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 200 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 3 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

PART D2_BOQ_COPT,IIT BOMBAY 58 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
ii. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-01 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 7,79,912.00 7,79,912.00
Consultant.
1.18 LABORATORY PANEL-02 (Ref SLD-INI-IITB-COPT-EL-SLD-03)
A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos. 160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-02 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,30,495.00 5,30,495.00
Consultant.

1.19 LABORATORY PANEL-03 (Ref SLD-INI-IITB-COPT-EL-SLD-03)


A. INCOMER:
1 1 no. 200 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:

PART D2_BOQ_COPT,IIT BOMBAY 59 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 200 Amps digital electronic ammeter with selector switch and 3nos. 200/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 200 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 3 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-03 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 7,44,335.00 7,44,335.00
Consultant.
1.20 LABORATORY PANEL-04 (Ref SLD-INI-IITB-COPT-EL-SLD-03)
A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos. 160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

PART D2_BOQ_COPT,IIT BOMBAY 60 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-04 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,30,495.00 5,30,495.00
Consultant.
1.21 GR. FLOOR HVAC PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-03)
A. INCOMER:
1 1 no. 100 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 100 Amps digital electronic ammeter with selector switch and 3nos. 100/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager /Energeney meterwith ready RS485 communication port and
MODBUS protocol. - 1 set
B Bus Bars
100 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 25amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'GR. FLOOR HVAC PANEL ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,07,855.00 5,07,855.00
Consultant.
1.22 LABORATORY PANEL-05 (Ref SLD-INI-IITB-COPT-EL-SLD-04)
A. INCOMER:
1 1 no. 200 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:

PART D2_BOQ_COPT,IIT BOMBAY 61 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 200 Amps digital electronic ammeter with selector switch and 3nos. 200/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 200 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 3 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-05 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 7,79,912.00 7,79,912.00
Consultant.
1.23 LABORATORY PANEL-06 (Ref SLD-INI-IITB-COPT-EL-SLD-04)
A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos.160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

PART D2_BOQ_COPT,IIT BOMBAY 62 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-06 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,42,159.00 5,42,159.00
Consultant.
1.24 LABORATORY PANEL-07 (Ref SLD-INI-IITB-COPT-EL-SLD-04)
A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos.160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

PART D2_BOQ_COPT,IIT BOMBAY 63 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
The 'LABORATORY PANEL-07 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,42,159.00 5,42,159.00
Consultant.
1.25 LABORATORY PANEL-08 (Ref SLD-INI-IITB-COPT-EL-SLD-04)
A. INCOMER:
1 1 no. 200 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 200 Amps digital electronic ammeter with selector switch and 3nos.200/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 200 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 3 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-08 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 7,44,335.00 7,44,335.00
Consultant.
1.26 LABORATORY PANEL-09 (Ref SLD-INI-IITB-COPT-EL-SLD-04)
A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos.160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:

PART D2_BOQ_COPT,IIT BOMBAY 64 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
i. 2 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-09 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,42,159.00 5,42,159.00
Consultant.
1.27 1st. FLOOR HVAC PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-04)
A. INCOMER:
1 1 no. 100 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 100 Amps digital electronic ammeter with selector switch and 3nos. 100/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 100 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 3 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i 2 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The '1st FLOOR HVAC PANEL ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,00,511.00 5,00,511.00
Consultant.

PART D2_BOQ_COPT,IIT BOMBAY 65 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
1.28 LABORATORY PANEL-11 (Ref SLD-INI-IITB-COPT-EL-SLD-05)
A. INCOMER:
1 1 no. 63 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 63 Amps digital electronic ammeter with selector switch and 3nos.63/5 amps, Bar Primary,
15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 100 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 25 KA for 1 sec.

C OUTGOINGS:
i. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port. (not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-11 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 3,70,841.00 3,70,841.00
Consultant.
1.29 2nd FLOOR HVAC PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-05)
A. INCOMER:
1 1 no. 125 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 125 Amps digital electronic ammeter with selector switch and 3nos. 125/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 125 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 4 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 2 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

PART D2_BOQ_COPT,IIT BOMBAY 66 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
ii. 1 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The '2nd FLOOR HVAC PANEL ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 8,00,071.00 8,00,071.00
Consultant.
1.30 3rd FLOOR HVAC PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-05)
A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos. 160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 5 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The '3rd FLOOR HVAC PANEL ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 8,03,032.00 8,03,032.00
Consultant.
1.31 LABORATORY PANEL-12 (Ref SLD-INI-IITB-COPT-EL-SLD-06)
A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos.160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
PART D2_BOQ_COPT,IIT BOMBAY 67 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-12 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,06,868.00 5,06,868.00
Consultant.
1.32 LABORATORY PANEL-13 (Ref SLD-INI-IITB-COPT-EL-SLD-06)
A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos.160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

PART D2_BOQ_COPT,IIT BOMBAY 68 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-13 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,04,488.00 5,04,488.00
Consultant.

1.33 LABORATORY PANEL-14 (Ref SLD-INI-IITB-COPT-EL-SLD-06)


A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos.160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-14 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,06,868.00 5,06,868.00
Consultant.
1.34 4th FLOOR HVAC PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-06)
A. INCOMER:
1 1 no. 125 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 125 Amps digital electronic ammeter with selector switch and 3nos. 125/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

PART D2_BOQ_COPT,IIT BOMBAY 69 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
C OUTGOINGS:
i. 5 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The '4th FLOOR HVAC PANEL ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 7,65,010.00 7,65,010.00
Consultant.
1.35 LABORATORY PANEL-15 (Ref SLD-INI-IITB-COPT-EL-SLD-07)
A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos.160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
PART D2_BOQ_COPT,IIT BOMBAY 70 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-15 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,10,201.00 5,10,201.00
Consultant.
1.36 LABORATORY PANEL-16 (Ref SLD-INI-IITB-COPT-EL-SLD-07)
A. INCOMER:
1 1 no. 160 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos.160/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 160 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 2 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

iii. 1 no. 25 amps DP MCB with thermal magnetic based release for overload and short circuit
protections and suitable for 230V, 50 Hz, A.C supply and having Ics=Icu= 10 KA. The MCB shall
be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 100 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii 1 no. 63 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The 'LABORATORY PANEL-16 ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 5,10,201.00 5,10,201.00
Consultant.
1.37 5th FLOOR HVAC PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-07)
A. INCOMER:
1 1 no. 125 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 160 Amps digital electronic ammeter with selector switch and 3nos. 125/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 125 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 25 KA for 1 sec.

PART D2_BOQ_COPT,IIT BOMBAY 71 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
C OUTGOINGS:
i. 4 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 1 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 1 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii 2 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The '5th FLOOR HVAC PANEL ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 7,65,069.00 7,65,069.00
Consultant.
1.38 6th FLOOR HVAC PANEL (Ref SLD-INI-IITB-COPT-EL-SLD-08)
A. INCOMER:
1 1 no. 200 amps Four pole MCCB with Thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 36 KA. The
MCCB shall be complete as per technical specifications, single line diagramand with following
accessories:
i. 0-500 volts digital electronic volt meter with selector switch and protected by 2 amps TP
MCB's. - 1 set
ii. 0- 200 Amps digital electronic ammeter with selector switch and 3nos. 200/5 amps, Bar
Primary, 15 VA Burden, CL 1 accuracy CTs . - 1 set
iii. 3 nos. Phase indicating light protected by 2 amps SP MCB's.- 1 set
iv. Breaker ON / OFF / TRIP indicating lights with control MCB’s.- 1 set.
v. Electronic Digital Load Manager with ready RS485 communication port and MODBUS
protocol. - 1 set
B Bus Bars
i. 200 Amps uniformly rated, continuous duty, 415 V AC, 3 Phase and Neutral electrolytic
grade 99.95% purity Tinned Copper (Throughout the length) busbars with colour coded heat
shrink sleeves supported on SMC type grip supports, 36 KA for 1 sec.

C OUTGOINGS:
i. 7 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

ii. 2 no. 25 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

D SPARE FEEDERS
i. 3 no. 40 amps Four pole MCCB with thermal magnetic based release for overload and short
circuit protections and suitable for 415V, 50 Hz, A.C supply and having Ics=Icu= 25 KA. The
MCCB shall be complete as per technical specifications, single line diagram

E Notes:-
All outgoing feeders shall have suitable range of followings:-
a. Digital electronic KWH meter with RS 485 port.(not applicable for Spare outgoing)

Wiring with space heater, thermostat and control MCB’s shall be provided in all vertical
sections of main LT panel.
All incoming as well as outgoing feeders shall have pad locking facility.
suitable danger board shall be provided.
All bus bar section / backside panels shall have pad locking facility and hinged type door.

The '6th FLOOR HVAC PANEL ' as described above complete with wiring, line diagram,
specifications and approvals, painting and as per direction and final approval of Owner / No. 1 9,65,640.00 9,65,640.00
Consultant.
1.39 APFC Panel -1 & 2 (Ref SLD-INI-IITB-COPT-EL-SLD-01)
A Incomer
PART D2_BOQ_COPT,IIT BOMBAY 72 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
630Amp 4P MCCB 50 KA (Ics= 100% Icu= Icw) with standing Capacity and with
Microprocessor based LSIG releases, BMS compatible hardware and software like RS
485/potential free contacts /Modbus/Bacnet card and control MCB- etc as reqd)…01 set

i. (a) PHASE Indication Lamp 230V AC- 1nos.


ii. (b ) 8 Stage APFC Relay -1nos.
iii. (c) 0-180SEC ON Delay Timer -1nos.
iv. (d) AUTO/MANUAL Selector Switch- 1nos.
v (e) Auxiliary Contactor -1nos.
vi. (f) 0-630A Ammeter inbuilt selector switch -1nos.
vii. (g) 0-500V Voltmeter inbuilt selector switch -1nos.
viii. (h) 630/5A 15VA CL-1 CT's- 3nos.
ix. (i) 2A Control MCB Cat "C"-3nos.
x. (j) EFR with CBCT - 1 Set
B Busbar : 630A, TPN Copper Busbar , suitable for 50 KA
C Outgoing
i. 100 Amp TP 25 KA MCCB , (Ics= 100% Icu= Icw) with Thermal magnetic based releases - 08
Nos (For 50 KVAR Capcitor-08 Nos)
ii. (a)Following Capacity APP type Shunt capacitors ISI mark 3phase, 440V :
a. 50KVAR -06 Nos
b. 25KVAR -01 Nos
iii. (b). LED type Indicating lamp with holder: 8 Nos.
iv. (c). Thyristor switching suitable for max 100A Load Current, 480V: 08 Nos.
v. (f) Heat Dissipaters for ES: 8 sets
vi. (g) Auto Manual Selector switch :8 Nos
vii. (h) start/Stop Push Buttons : 8 Set
APFC Panel - 1 & 2 as mentioned above Nos. 2 17,18,117.00 34,36,234.00
TOTAL OF MEDIUM VOLTAGE PANELS 3,61,25,651.00
2.0 DISTRIBUTION BOARDS
READYMADE DISTRIBUTION BOARDS
Fabrication, inspection at works Supply, installation, testing & commissioning of following
readymade distribution boards, double door, IP 42 degree protection complete with
necessary, MCB isolators , MCBs, earth leakage circuit breaker (RCCB) etc including
interconnections with appropriate capacity size of PVC insulated copper conductor wires (ISI
marked),suitable for concealed mounting /wall mounting with MS frame work of 40 x 40 x 5
mm MS angle iron, with M.S. enclosure fabricated out of min 16 SWG thick M.S. CRCA sheet
with concealed hinged door, locking arrangement etc. including earthing clamps for both
incoming & outgoing circuits, interconnections, per phase isolation kit as required,cable end
box & wire way box if required, continuous copper earth wire in the wire way box with
single/duplicate brass earthing terminals, danger board, name plate, flexible earthing for the
door, metal treatment & powder coated painting, Phase Distribution drawing etc. all as per
drawings (G.A. & fabrication drawing to be got approved), etc. relevant IS & instruction of
Engineer-in-charge.

Note:
1.MCBs shall be minimum 10 KA breaking capacity (Type –C)
2. Blanking Plates shall be included in scope of work.
3. DB shall be of standard readymade type as per catalouge No. from approved
manufacturers as indicated in preferred makes of material.
4. Wire way & cable end box also end & locking plates shall be provided.
5. Routine tests will be conducted at factory in presense of user as per relevant IS.
All Electrical component should have IS mark
Refer INI-IITB-COPT-EL-PWR-DB-SLD-GF-02
2.1 POWER-DB1-LAB 1 & 3 (GF) -12 way PPI DB Set 2 8,497.00 16,994.00
2.1.1 63 A 4P 10KA MCB as incomer -- 1 No. Nos 2 1,019.00 2,038.00
2.1.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 7,023.00 42,138.00
2.1.3 16 A SP MCB 10KA-- 36 nos Nos 72 252.00 18,144.00
2.2 POWER-DB2-LAB 1 & 3 (GF)-8 way PPI DB Set 2 7,653.00 15,306.00
2.2.1 63 A 4P 10KA MCB as incomer -- 1 No. Nos 4 1,019.00 4,076.00
2.2.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 7,023.00 42,138.00
2.2.3 16 A SP MCB 10KA -- 24 nos Nos 48 252.00 12,096.00
2.3 POWER DB3-LAB 1 & 3 (GF)-12 way VTPN DB
POWER DB4-LAB 1 & 3 (GF)-12 way VTPN DB
POWER DB5-LAB 1 & 3 (GF)-12 way VTPN DB
Set 10 12,646.00 1,26,460.00
POWER DB2-LAB 2 & 4 (GF)-12 way VTPN DB
POWER DB3-LAB 2 & 4 (GF)-12 way VTPN DB

2.3.1 100A 4P 25KA MCCB as incomer- 1 No. Nos 10 6,236.00 62,360.00


2.3.2 63A TP MCB 10KA -- 12 No. Nos 120 1,324.00 1,58,880.00
2.4 POWER-DB1-LAB 2 & 4 (GF)- 12 way PPI DB Set 2 8,499.00 16,998.00
2.4.1 63 A 4P 10KA MCB as incomer -- 1 No. Nos 2 1,019.00 2,038.00
2.4.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 7,023.00 42,138.00
2.4.3 16 A SP MCB 10KA-- 36 nos Nos 72 252.00 18,144.00
Refer INI-IITB-COPT-EL-PWR-DB-SLD-GF-01
2.5 DB-OFFICE AREA (DB-OFF)-8 way PPI DB Set 1 7,653.00 7,653.00
2.5.1 40A FP MCB 10KA as incomer-1 No. Nos 1 1,635.00 1,635.00
2.5.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.5.3 16 A SP MCB 10KA-- 24 nos Nos 24 252.00 6,048.00
2.6 DB_MAINTENANCE ROOM (LPDB-MR)-8 way SPN DB Set 1 2,535.00 2,535.00
PART D2_BOQ_COPT,IIT BOMBAY 73 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
2.6.1 40A, DP RCBO with 100mA sensitivity as incomer-1 No. Nos 1 7,416.00 7,416.00
2.6.2 16A SP MCB 10KA-- 6 nos. Nos 6 252.00 1,512.00
2.7 POWER-DB_CA (PDB-CA-GF)- 12 way PPI DB Set 1 8,499.00 8,499.00
2.7.1 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.7.2 40A FP MCB 10KA as incomer-1 No. Nos 1 1,635.00 1,635.00
2.7.3 16A SP MCB 10KA -- 36 nos. Nos 36 252.00 9,072.00
2.8 UPS POWER DB-ELV (UDB-ELV)-8 way PPI DB Set 1 7,653.00 7,653.00
2.8.1 40A FP MCB 10KA as incomer-1 No. Nos 1 1,635.00 1,635.00
2.8.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.8.3 32 A SP MCB 10KA -- 6 nos. Nos 6 252.00 1,512.00
2.8.4 16 A SP MCB 10KA-- 18 nos. Nos 18 252.00 4,536.00
First Floor DBs-INI-IITB-COPT-EL-PWR-DB-SLD-1F-01& 02
2.9 POWER-DB1-LAB 6,7 &9 (PDB1-L)-12 way PPI DB Set 3 8,499.00 25,497.00
2.9.1 63 A 4P 10KA MCB as incomer -- 1 No. Nos 3 1,019.00 3,057.00
2.9.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 9 7,023.00 63,207.00
2.9.3 16 A SP MCB 10KA -- 36 nos Nos 108 252.00 27,216.00
2.10 POWER DB_2_LAB 6,7 & 9 (PDB2-L)- 12 way VTPN DB
Set 6 12,646.00 75,876.00
POWER DB_3_LAB 6,7 & 9 (PDB2-L)- 12 way VTPN DB
2.10.1 100A 4P 25KA MCCB as incomer- 1 No. Nos 6 6,236.00 37,416.00
2.10.2 63A TP MCB 10KA -- 12 No. Nos 72 1,324.00 95,328.00
2.11 POWER-DB1-LAB 5 & 8(PDB1-L)- 12 way PPI DB Set 2 8,499.00 16,998.00
2.11.1 63 A 4P 10KA MCB as incomer -- 1 No. Nos 2 1,019.00 2,038.00
2.11.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 7,023.00 42,138.00
2.11.3 16 A SP MCB 10KA -- 36 nos Nos 72 252.00 18,144.00
2.12 POWER-DB2-LAB 5 & 8 (PDB2-L)-8 way PPI DB Set 2 7,653.00 15,306.00
2.12.1 63 A 4P 10KA MCB as incomer -- 1 No. Nos 2 1,019.00 2,038.00
2.12.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 7,023.00 42,138.00
2.12.3 16 A SP MCB 10KA-- 24 nos Nos 48 252.00 12,096.00
2.13 POWER DB_3_LAB 5&8 (PDB3-L)- 12 way VTPN DB
POWER DB_4_LAB 5&8 (PDB3-L)- 12 way VTPN DB Set 6 12,646.00 75,876.00
POWER DB_5_LAB 5&8 (PDB3-L)- 12 way VTPN DB
2.13.1 100A 4P 25KA MCCB as incomer- 1 No. Nos 6 6,236.00 37,416.00
2.13.2 63A TP MCB 10KA -- 12 No. Nos 72 1,324.00 95,328.00
2.14 POWER-DB_CA (PDB-CA-1F)-8 way PPI DB Set 1 7,653.00 7,653.00
2.14.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.14.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.14.3 16 A SP MCB 10KA -- 24nos Nos 24 252.00 6,048.00
2.15 UPS POWER DB-1F (UDB-1F)-4 way PPI DB Set 1 4,954.00 4,954.00
2.15.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.15.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.15.3 16 A SP MCB 10KA -- 12nos Nos 12 252.00 3,024.00
Second Floor DBs-INI-IITB-COPT-EL-PWR-DB-SLD-2F-01/02
2.16 UPS POWER DB-LABORATORY-10- 4 way PPI DB Set 1 4,954.00 4,954.00
2.16.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.16.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.16.3 16 A SP MCB 10KA -- 12nos Nos 12 252.00 3,024.00
2.17 DB-LABORATORY-11 (DB-LAB11)- 4 way PPI DB Set 1 4,954.00 4,954.00
2.17.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.17.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.17.3 16 A SP MCB 10KA -- 12nos Nos 12 252.00 3,024.00
2.18 DB-CLASSROOM (DB-CR)-6 way PPI DB Set 1 5,913.00 5,913.00
2.18.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.18.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.18.3 16 A SP MCB 10KA -- 18nos Nos 18 252.00 4,536.00
2.19 DB-CONFERENCE ROOM (DB-CONF.)-4 way PPI DB Set 1 4,954.00 4,954.00
2.19.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.19.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.19.3 16 A SP MCB 10KA-- 18nos Nos 18 252.00 4,536.00
2.20 DB_STAFF ROOM (DB-SR-2F)-12 way PPI DB Set 1 8,499.00 8,499.00
2.20.1 63 A 4P 10KA MCB as incomer -- 1 No. Nos 1 1,019.00 1,019.00
2.20.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 7,023.00 21,069.00
2.20.3 16 A SP MCB 10KA -- 36 nos Nos 36 252.00 9,072.00
2.21 DB-DIRECTOR ROOM (DB-DR)-8 way PPI DB Set 1 7,653.00 7,653.00
2.21.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.21.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.21.3 16 A SP MCB 10KA -- 24nos Nos 24 252.00 6,048.00
2.22 DB_OFFICE AREA (DB-OFF-2F)-12 way PPI DB Set 1 8,499.00 8,499.00
2.22.1 63 A 4P 10KA MCB as incomer -- 1 No. Nos 1 1,019.00 1,019.00
2.22.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 7,023.00 21,069.00
2.22.3 16 A SP MCB 10KA -- 36 nos Nos 36 252.00 9,072.00
2.23 DB-FACULTY ROOM (DB-FR)-6 way PPI DB Set 1 5,913.00 5,913.00
2.23.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.23.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.3.3 16 A SP MCB 10KA -- 18nos Nos 18 252.00 4,536.00
2.24 POWER-DB_CA (PDB-CA-2F)-12 way PPI DB Set 1 8,499.00 8,499.00
2.24.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,019.00 1,019.00
2.24.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 7,023.00 21,069.00
2.24.3 16 A SP MCB 10 -- 36 nos Nos 36 252.00 9,072.00
2.25 UPS POWER DB-2F (UDB-2F)-4 way PPI DB Set 1 4,954.00 4,954.00
PART D2_BOQ_COPT,IIT BOMBAY 74 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
2.25.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.25.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.25.3 16 A SP MCB 10KA -- 12nos Nos 12 252.00 3,024.00
2.26 Third Floor DBs-INI-IITB-COPT-EL-PWR-DB-SLD-3F-01/02
POWER-DB1-FR1 (PDB1-FR1)-12 way PPI DB
Set 2 8,499.00 16,998.00
POWER-DB2-FR1 (PDB2-FR1)-12 way PPI DB
2.26.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 2 1,019.00 2,038.00
2.26.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 7,023.00 42,138.00
2.26.3 16 A SP MCB 10KA -- 36 nos Nos 72 252.00 18,144.00
2.27 POWER-DB1-FR2 (PDB1-FR2)-8 way PPI DB Set 1 7,653.00 7,653.00
2.27.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.27.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.27.3 16 A SP MCB 10KA -- 24nos Nos 24 252.00 6,048.00
2.28 POWER-DB2-FR2 (PDB2-FR2)-12 way PPI DB Set 1 8,499.00 8,499.00
2.28.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,019.00 1,019.00
2.28.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 7,023.00 21,069.00
2.28.3 16 A SP MCB 10KA-- 36 nos Nos 36 252.00 9,072.00
2.29 DB1_HOD STAFF (DB1-HOD-3F)-8 way PPI DB Set 1 7,653.00 7,653.00
2.29.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.29.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.29.3 16 A SP MCB 10KA -- 24nos Nos 24 252.00 6,048.00
2.30 DB2_HOD STAFF (DB2-HOD-3F)-8 way PPI DB Set 1 7,653.00 7,653.00
2.30.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.30.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.30.3 16 A SP MCB 10KA-- 24nos Nos 24 252.00 6,048.00
2.31 DB-MEETING ROOM-3 (DB-MR3)-4 way PPI DB Set 1 4,954.00 4,954.00
2.31.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.31.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.31.3 16 A SP MCB 10KA-- 12nos Nos 12 252.00 3,024.00
2.32 DB-FACULTY LOUNGE (DB-FL)-4 way PPI DB Set 1 4,954.00 4,954.00
2.32.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.32.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.32.3 16 A SP MCB 10KA-- 12nos Nos 12 252.00 3,024.00
2.33 DB-CONFERENCE ROOM (DB-CONF.)-6 way PPI DB Set 1 5,913.00 5,913.00
2.33.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.33.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.33.3 16 A SP MCB 10KA -- 18nos Nos 18 252.00 4,536.00
2.34 DB-CLASSROOM (DB-CR)-6 way PPI DB Set 1 5,913.00 5,913.00
2.34.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.34.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.34.3 16 A SP MCB 10KA -- 18nos Nos 18 252.00 4,536.00
2.35 POWER-DB_CA (PDB-CA-3F)-8 way PPI DB Set 1 7,653.00 7,653.00
2.35.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.35.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.35.3 16 A SP MCB 10KA -- 24nos Nos 24 252.00 6,048.00
2.36 UPS POWER DB-3F (UDB-3F)-4 way PPI DB Set 1 4,954.00 4,954.00
2.36.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.36.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.36.3 16 A SP MCB 10KA-- 12nos Nos 12 252.00 3,024.00
2.37 Fourth Floor DBs-INI-IITB-COPT-EL-PWR-DB-SLD-4F-01/02/03
POWER-DB1-FR1 (PDB1-FR1)- 12 way PPI DB
Set 2 8,499.00 16,998.00
POWER-DB2-FR1 (PDB2-FR1)- 12 way PPI DB
2.37.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 2 1,019.00 2,038.00
2.37.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 7,023.00 42,138.00
2.37.3 16 A SP MCB 10KA-- 36 nos Nos 72 252.00 18,144.00
2.38 POWER-DB1-FR2 (PDB1-FR2)-8 way PPI DB
Set 2 7,653.00 15,306.00
POWER-DB2-FR2 (PDB2-FR2)-8 way PPI DB
2.38.1 40A 4P 10KA MCB as incomer- 1 No. Nos 2 956.00 1,912.00
2.38.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 6 5,897.00 35,382.00
2.38.3 16 A SP MCB 10KA-- 24nos Nos 48 252.00 12,096.00
2.39 POWER-DB1-FR3 (PDB1-FR3)- 8 way PPI DB Set 1 7,653.00 7,653.00
2.39.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.39.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.39.3 16 A SP MCB 10KA-- 24nos Nos 24 252.00 6,048.00
2.40 POWER-DB2-FR3 (PDB2-FR3)- 12 way PPI DB Set 1 8,499.00 8,499.00
2.40.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,019.00 1,019.00
2.40.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 7,023.00 21,069.00
2.40.3 16 A SP MCB 10KA -- 36 nos Nos 36 252.00 9,072.00
2.41 POWER-DB1-LAB12 (PDB1-L12)- 12 way PPI DB
POWER-DB1-LAB13 (PDB1-L13)- 12 way PPI DB Set 3 8,499.00 25,497.00
POWER-DB1-LAB14 (PDB1-L14)- 12 way PPI DB
2.41.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 3 1,019.00 3,057.00
2.41.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 9 7,023.00 63,207.00
2.41.3 16 A SP MCB 10KA-- 36 nos Nos 108 252.00 27,216.00

PART D2_BOQ_COPT,IIT BOMBAY 75 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
2.42 POWER DB_2_LAB12 (PDB2-L12) & POWER DB_3_LAB12 (PDB3-L12)- 12 way VTPN DB
POWER DB_2_LAB13 (PDB2-L13) & POWER DB_3_LAB13 (PDB2-L13)- 12 way VTPN DB
POWER DB_2_LAB14 (PDB2-L14) & POWER DB_2_LAB14 (PDB2-L14)- 12 way VTPN DB
Set 6 12,646.00 75,876.00

2.42.1 100A 4P MCCB 25KA as incomer- 1 No. Nos 6 6,236.00 37,416.00


2.42.2 63A TP MCB 10KA -- 12 No. Nos 72 1,324.00 95,328.00
2.43 DB-CLASSROOM (DB-CR)-8 way PPI DB Set 1 7,653.00 7,653.00
2.43.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.43.2 40A, DP RCCB with 100mA sensitivity -3 No. Nos 3 5,897.00 17,691.00
2.43.3 16 A SP MCB 10KA -- 24nos Nos 24 252.00 6,048.00
2.44 POWER-DB_CA (PDB-CA-4F)-12 way PPI DB Set 1 8,499.00 8,499.00
2.44.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,019.00 1,019.00
2.44.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 7,023.00 21,069.00
2.44.3 16 A SP MCB 10KA -- 30 nos Nos 30 252.00 7,560.00
2.45 UPS POWER DB-4F (UDB-4F)-4 way PPI DB Set 1 4,954.00 4,954.00
2.45.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.45.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.45.3 16 A SP MCB 10KA -- 9nos Nos 9 252.00 2,268.00
2.45.4 32 A SP MCB 10KA -- 3nos Nos 3 252.00 756.00
Fifth Floor DBs-INI-IITB-COPT-EL-PWR-DB-SLD-5F-01/02/03 -
2.46 POWER-DB1-FR1 (PDB1-FR1)-12 way PPI DB
Set 2 8,499.00 16,998.00
POWER-DB2-FR1 (PDB2-FR1)-12 way PPI DB
2.46.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 2 1,019.00 2,038.00
2.46.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 7,023.00 42,138.00
2.46.3 16 A SP MCB 10KA -- 36 nos Nos 72 252.00 18,144.00
2.47 POWER-DB1-FR2 (PDB1-FR2)-8 way PPI DB
Set 2 7,653.00 15,306.00
POWER-DB2-FR2 (PDB1-FR2)--8 way PPI DB
2.47.1 40A 4P 10KA MCB as incomer- 1 No. Nos 2 956.00 1,912.00
2.47.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 6 5,897.00 35,382.00
2.47.3 16 A SP MCB 10KA-- 24nos Nos 48 252.00 12,096.00
2.48 POWER-DB-FR3 (PDB-FR3)-12 way PPI DB Set 1 8,499.00 8,499.00
2.48.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,019.00 1,019.00
2.48.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 7,023.00 21,069.00
2.48.3 16 A SP MCB 10KA-- 36 nos Nos 36 252.00 9,072.00
2.49 POWER-DB1-FR4 (PDB1-FR4)-8 way PPI DB Set 1 7,653.00 7,653.00
2.49.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.49.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.49.3 16 A SP MCB 10KA-- 24nos Nos 24 252.00 6,048.00
2.50 POWER-DB2-FR4 (PDB2-FR4)-12 way PPI DB Set 1 8,499.00 8,499.00
2.50.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,019.00 1,019.00
2.50.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 7,023.00 21,069.00
2.50.3 16 A SP MCB 10KA -- 36 nos Nos 36 252.00 9,072.00
2.51 POWER-DB1-LAB15 (PDB1-L15)-12 way PPI DB
Set 2 8,499.00 16,998.00
POWER-DB1-LAB16 (PDB1-L16)-12 way PPI DB
2.51.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 2 1,019.00 2,038.00
2.51.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 7,023.00 42,138.00
2.51.3 16 A SP MCB 10KA -- 36 nos Nos 72 252.00 18,144.00
2.52 POWER DB_2_LAB15 (PDB2-L15)-12 way VTPN DB
POWER DB_3_LAB15 (PDB2-L15)-12 way VTPN DB
Set 4 12,646.00 50,584.00
POWER DB_2_LAB16 (PDB2-L15)-12 way VTPN DB
POWER DB_3_LAB16 (PDB2-L15)-12 way VTPN DB
2.52.1 100A 4P MCCB 25KA as incomer- 1 No. Nos 4 6,236.00 24,944.00
2.52.2 63A TP MCB 10KA -- 12 No. Nos 48 1,324.00 63,552.00
2.53 POWER-DB_CA (PDB-CA-5F)-12 way PPI DB Set 1 8,499.00 8,499.00
2.53.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,019.00 1,019.00
2.53.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 7,023.00 21,069.00
2.53.3 16 A SP MCB 10KA -- 30 nos Nos 30 252.00 7,560.00
2.54 UPS POWER DB-5F (UDB-5F)-4 way PPI DB Set 1 4,954.00 4,954.00
2.54.1 40A 4P 10KA MCB as incomer- 1 No. Nos 1 956.00 956.00
2.54.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.54.3 16 A SP MCB 10KA -- 9nos Nos 9 252.00 2,268.00
2.54.4 32 A SP MCB 10KA -- 3nos Nos 3 252.00 756.00
Sixth Floor DBs-INI-IITB-COPT-EL-PWR-DB-SLD-6F-01/02/03
2.55 POWER-DB-A1 (PDB-A1)-12 way PPI DB Set 1 8,499.00 8,499.00
2.55.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,019.00 1,019.00
2.55.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 7,023.00 21,069.00
2.55.3 16 A SP MCB 10KA -- 36 nos Nos 36 252.00 9,072.00
2.56 POWER DB-A2 (PDB-A2)-12 way VTPN DB Set 1 12,646.00 12,646.00
2.56.1 63A 4P MCCB 25KA as incomer- 1 No. Nos 1 7,975.00 7,975.00
2.56.2 20A TP MCB 10KA -- 4 No. Nos 12 992.00 11,904.00
2.56.3 16 A SP MCB 10KA -- 22 nos Nos 22 252.00 5,544.00
2.56.4 20A SP MCB 10KA -- 02 nos Nos 24 252.00 6,048.00
2.57 POWER DB-A3 (PDB-A3)-8 way VTPN DB Set 1 10,017.00 10,017.00
2.57.1 40A 4P MCCB 25KA as incomer- 1 No. Nos 1 8,186.00 8,186.00
2.57.2 25A TP MCB 10KA -- 3 No. Nos 3 992.00 2,976.00
2.57.3 20 A TP MCB 10KA-- 1 nos Nos 1 992.00 992.00
2.57.4 16 A TP MCB 10KA-- 1 nos Nos 1 992.00 992.00
PART D2_BOQ_COPT,IIT BOMBAY 76 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
2.57.5 20 A SP MCB 10KA -- 1 nos Nos 1 252.00 252.00
2.57.6 16 A SP MCB 10KA -- 7 nos Nos 7 252.00 1,764.00
2.57.7 6 A SP MCB 10KA -- 1 nos Nos 1 252.00 252.00
2.58 UPS POWER DB-A3 (UDB-A3)-6 way VTPN DB Set 1 9,458.00 9,458.00
2.58.1 40A 4P MCCB 25KA as incomer- 1 No. Nos 1 8,186.00 8,186.00
2.58.2 20A TP MCB 10KA -- 2 No. Nos 2 992.00 1,984.00
2.58.3 16 A TP MCB 10KA-- 2 nos Nos 2 992.00 1,984.00
2.58.4 20 A SP MCB 10KA-- 1 nos Nos 1 252.00 252.00
2.58.5 16 A SP MCB 10KA-- 5 nos Nos 5 252.00 1,260.00
2.59 POWER DB-A4 (PDB-A4)-8 way VTPN DB Set 1 10,017.00 10,017.00
2.59.1 40A 4P MCCB 25KA as incomer- 1 No. Nos 1 8,186.00 8,186.00
2.59.2 25A TP MCB 10KA -- 1 No. Nos 1 992.00 992.00
2.59.3 20A TP MCB 10KA -- 4 No. Nos 4 992.00 3,968.00
2.59.4 16 A SP MCB 10KA -- 8 nos Nos 8 252.00 2,016.00
2.59.5 6 A SP MCB 10KA-- 1 nos Nos 1 252.00 252.00
2.60 POWER DB-A5 (PDB-A5)-16 way VTPN DB Set 1 24,724.00 24,724.00
2.60.1 63A 4P MCCB 25KA as incomer- 1 No. Nos 1 7,975.00 7,975.00
2.60.2 16 A TP MCB 10KA -- 11 nos Nos 11 992.00 10,912.00
2.60.3 16 A SP MCB 10KA -- 8 nos Nos 8 252.00 2,016.00
2.60.4 6 A SP MCB 10KA-- 1 nos Nos 1 252.00 252.00
2.61 VTPN DB-AREA-7- 4 way VTPN DB Set 1 7,402.00 7,402.00
2.61.1 80A 4P MCCB 35KA as incomer- 1 No. Nos 1 6,236.00 6,236.00
2.61.2 63 A TP MCB 10KA-- 3 nos Nos 3 1,324.00 3,972.00
2.61.3 25 A SP MCB 10KA-- 3 nos Nos 3 252.00 756.00
2.62 POWER-DB1_A7 (PDB1-A7)-12 way PPI DB
Set 2 8,499.00 16,998.00
POWER-DB2_A7 (PDB2-A7)-12 way PPI DB
2.62.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 2 1,019.00 2,038.00
2.62.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 7,023.00 42,138.00
2.62.3 16 A SP MCB 10KA -- 36 nos Nos 72 252.00 18,144.00
2.63 VTPN DB-AREA-8- 4 way VTPN DB Set 1 7,402.00 7,402.00
2.63.1 80A 4P MCCB 36kA as incomer- 1 No. Nos 1 6,236.00 6,236.00
2.63.2 63 A TP MCB 10KA -- 3 nos Nos 3 1,324.00 3,972.00
2.63.3 25 A SP MCB 10KA -- 3 nos Nos 3 252.00 756.00
2.64 POWER DB_1-A8 (PDB1-A8)-16 way VTPN DB Set 1 24,479.00 24,479.00
2.64.1 63A 4P MCCB 25KA as incomer- 1 No. Nos 1 7,975.00 7,975.00
2.64.2 20 A TP MCB 10KA -- 4 nos Nos 4 992.00 3,968.00
2.64.3 16 A TP MCB 10KA -- 11 nos Nos 11 992.00 10,912.00
2.64.4 16 A SP MCB 10KA-- 3 nos Nos 3 252.00 756.00
2.65 POWER DB-2-A8 (PDB2-A8)-16 way VTPN DB Set 1 24,479.00 24,479.00
2.65.1 63A 4P MCCB 25KA as incomer- 1 No. Nos 1 7,975.00 7,975.00
2.65.2 25 A TP MCB 10KA-- 1 nos Nos 1 992.00 992.00
2.65.3 20 A TP MCB 10KA -- 9 nos Nos 9 992.00 8,928.00
2.65.4 16 A TP MCB 10KA-- 5 nos Nos 5 992.00 4,960.00
2.65.5 16 A SP MCB 10KA-- 3 nos Nos 3 252.00 756.00
2.66 POWER DB-3-A8 (PDB3-A8)-16 way VTPN DB Set 1 24,479.00 24,479.00
2.66.1 63A 4P MCCB 25KA as incomer- 1 No. Nos 1 7,975.00 7,975.00
2.66.2 20 A TP MCB 10KA -- 15 nos Nos 15 992.00 14,880.00
2.66.3 16 A SP MCB 10KA -- 3 nos Nos 3 252.00 756.00
2.67 POWER DB-A9 (PDB-A9)-8 way VTPN DB Set 1 10,017.00 10,017.00
2.67.1 63A 4P MCCB 25KA as incomer- 1 No. Nos 1 7,975.00 7,975.00
2.67.2 20 A TP MCB 10KA-- 2 nos Nos 2 992.00 1,984.00
2.67.3 16 A TP MCB 10KA -- 2 nos Nos 2 992.00 1,984.00
2.67.4 20 A SP MCB 10KA -- 11 nos Nos 11 252.00 2,772.00
2.67.5 6 A SP MCB 10KA -- 1 nos Nos 1 252.00 252.00
2.68 UPS POWER DB-6F (UDB-6F)- 4 way PPI DB Set 1 4,954.00 4,954.00
2.68.1 40A FP MCB 10KA as incomer- 1 No. Nos 1 1,635.00 1,635.00
2.68.2 40A, DP RCCB with 100mA sensitivity as incomer-3 No. Nos 3 5,897.00 17,691.00
2.68.3 16 A SP MCB 10KA -- 12nos Nos 12 252.00 3,024.00
2.69 VTPN DB-AREA-10- 4 way VTPN DB Set 1 7,402.00 7,402.00
2.69.1 80A 4P MCCB 36kA as incomer- 1 No. Nos 1 6,236.00 6,236.00
2.69.2 63 A TP MCB 10KA-- 3 nos Nos 3 1,324.00 3,972.00
2.69.3 25 A SP MCB 10KA-- 3 nos Nos 3 252.00 756.00
2.70 POWER DB1-A10 (PDB1-A10)-16 way VTPN DB Set 1 24,479.00 24,479.00
2.70.1 63A 4P MCCB 25KA as incomer- 1 No. Nos 1 7,975.00 7,975.00
2.70.2 16 A TP MCB 10KA-- 16 nos Nos 16 992.00 15,872.00
2.71 POWER DB2-A10 (PDB2-A10)-14 way VTPN DB Set 1 24,479.00 24,479.00
2.71.1 63A 4P MCCB 25KA as incomer- 1 No. Nos 1 7,975.00 7,975.00
2.71.2 16 A TP MCB 10KA -- 12 nos Nos 12 992.00 11,904.00
2.71.3 16 A SP MCB 10KA -- 6 nos Nos 6 252.00 1,512.00
2.72 POWER DB-A11 (PDB-A11)-16 way VTPN DB Set 1 24,479.00 24,479.00
2.72.1 80A 4P MCCB 25KA as incomer- 1 No. Nos 1 6,236.00 6,236.00
2.72.2 40 A TP MCB 10KA -- 5 nos Nos 5 1,324.00 6,620.00
2.72.3 20 A TP MCB 10KA -- 4 nos Nos 4 992.00 3,968.00
2.72.4 16 A SP MCB 10KA -- 21 nos Nos 21 252.00 5,292.00
2.73 POWER-DB_CA (PDB-CA-6F)-12 way PPI DB Set 1 8,499.00 8,499.00
2.73.1 63 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,019.00 1,019.00
2.73.2 63 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 7,023.00 21,069.00
2.73.3 16 A SP MCB 10KA -- 36 nos Nos 36 252.00 9,072.00
Lighting DBs-INI-IITB-COPT-EL-LTG-DB-SLD-01/02/03
PART D2_BOQ_COPT,IIT BOMBAY 77 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
2.74 LIGHT DB-CA (LDB-CA)-GF-4 way PPI DB Set 1 4,954.00 4,954.00
2.74.1 25 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,153.00 1,153.00
2.74.2 25 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 5,106.00 15,318.00
2.74.3 6 A SP MCB 10KA -- 12 nos Nos 36 252.00 9,072.00
2.75 LIGHT DB_LAB-01 (LDB-LAB1)-GF-8 way SPN DB Set 1 2,535.00 2,535.00
2.75.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.75.2 6 A SP MCB 10KA -- 6 nos. Nos 6 252.00 1,512.00
2.76 LIGHT DB_LAB-02 (LDB-LAB2)-GF-6 way SPN DB Set 1 2,174.00 2,174.00
2.76.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.76.2 6 A SP MCB 10KA-- 4 nos. Nos 4 252.00 1,008.00
2.77 LIGHT DB_LAB-03 (LDB-LAB3)-GF-8 way SPN DB Set 1 2,535.00 2,535.00
2.77.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.77.2 6 A SP MCB 10KA -- 6 nos. Nos 6 252.00 1,512.00
2.78 LIGHT DB_LAB-04 (LDB-LAB4)-GF-6 way SPN DB Set 1 2,174.00 2,174.00
2.78.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.78.2 6 A SP MCB 10KA-- 4 nos. Nos 4 252.00 1,008.00
2.79 LIGHT DB-CA (LDB-CA)-1F- 4way PPI DB Set 1 4,954.00 4,954.00
2.79.1 25 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,153.00 1,153.00
2.79.2 25 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 5,106.00 15,318.00
2.79.3 6 A SP MCB 10KA -- 12 nos Nos 12 252.00 3,024.00
2.80 LIGHT DB_LAB-05 (LDB-LAB5)-1F-8 way SPN DB Set 1 2,535.00 2,535.00
2.80.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.80.2 6 A SP MCB -- 6 nos. Nos 6 252.00 1,512.00
2.81 LIGHT DB_LAB-06 (LDB-LAB6)-1F-6 way SPN DB Set 1 2,174.00 2,174.00
2.81.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.81.2 6 A SP MCB 10KA-- 4 nos. Nos 4 252.00 1,008.00
2.82 LIGHT DB_LAB-07 (LDB-LAB7)-1F-6 way SPN DB Set 1 2,174.00 2,174.00
2.82.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.82.2 6 A SP MCB 10KA-- 4 nos. Nos 4 252.00 1,008.00
2.83 LIGHT DB_LAB-08 (LDB-LAB8)-1F-8 way SPN DB Set 1 2,535.00 2,535.00
2.83.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.83.2 6 A SP MCB 10KA -- 6 nos. Nos 6 252.00 1,512.00
2.84 LIGHT DB_LAB-09 (LDB-LAB9)-1F-6 way SPN DB Set 1 2,174.00 2,174.00
2.84.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.84.2 6 A SP MCB 10KA-- 4 nos. Nos 4 252.00 1,008.00
2.85 LIGHT DB-CA (LDB-CA)-2F-4 way PPI DB Set 1 4,954.00 4,954.00
2.85.1 25 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,153.00 1,153.00
2.85.2 25 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 5,106.00 15,318.00
2.85.3 6 A SP MCB 10KA -- 12 nos Nos 12 252.00 3,024.00
2.86 LIGHT DB_LAB-10 (LDB-LAB10)-2F-8 way SPN DB Set 1 2,535.00 2,535.00
2.86.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.86.2 6 A SP MCB 10KA -- 6 nos. Nos 6 252.00 1,512.00
2.87 LIGHT DB_LAB-11 (LDB-LAB11)-2F-6 way SPN DB Set 1 2,174.00 2,174.00
2.87.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.87.2 6 A SP MCB 10KA-- 4 nos. Nos 4 252.00 1,008.00
2.88 LIGHT DB_FR (LDB-FR)-2F-6 way SPN DB Set 1 2,174.00 2,174.00
2.88.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.88.2 6 A SP MCB 10KA-- 4 nos. Nos 4 252.00 1,008.00
2.89 LIGHT DB_OFFICE (LDB-OFF)-2F-6 way SPN DB Set 1 2,174.00 2,174.00
2.89.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.89.2 6 A SP MCB 10KA-- 4 nos. Nos 4 252.00 1,008.00
2.90 LIGHT DB-CA (LDB-C-4 way PPI DB Set 1 4,954.00 4,954.00
2.90.1 25 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,153.00 1,153.00
2.90.2 25 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 5,106.00 15,318.00
2.90.3 6 A SP MCB 10KA -- 12 nos Nos 12 252.00 3,024.00
2.91 LIGHT DB_FR1 (LDB-FR1)-2F-8 way SPN DB
Set 2 2,535.00 5,070.00
LIGHT DB_FR2 (LDB-FR2)-2F-8 way SPN DB
2.91.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 2 6,006.00 12,012.00
2.91.2 6 A SP MCB 10KA -- 6 nos. Nos 12 252.00 3,024.00
2.92 LIGHT DB-CA (LDB-C-4 way PPI DB Set 1 4,954.00 4,954.00
2.92.1 25 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,153.00 1,153.00
2.92.2 25 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 5,106.00 15,318.00
2.92.3 6 A SP MCB 10KA -- 12 nos Nos 12 252.00 3,024.00
2.93 LIGHT DB_FR1 (LDB-FR1)-4F-8way SPN DB
Set 2 2,535.00 5,070.00
LIGHT DB_FR3 (LDB-FR3)-4F-8way SPN DB
2.93.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 2 6,006.00 12,012.00
2.93.2 6 A SP MCB 10KA -- 6 nos. Nos 12 252.00 3,024.00
2.94 LIGHT DB_FR2 (LDB-FR2)-4F-6way SPN DB Set 1 2,174.00 2,174.00
2.94.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.94.2 6 A SP MCB 10KA-- 4 nos. Nos 4 252.00 1,008.00
2.95 LIGHT DB-CA (LDB-C-4 way PPI DB Set 1 4,954.00 4,954.00
2.95.1 25 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,153.00 1,153.00
2.95.2 25 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 5,106.00 15,318.00
2.95.3 6 A SP MCB 10KA -- 12 nos Nos 12 252.00 3,024.00
2.96 LIGHT DB_LAB-15 (LDB-LAB15)-5F-6 way SPN DB
LIGHT DB_LAB-16 (LDB-LAB16)-5F-6 way SPN DB
Set 4 2,174.00 8,696.00
LIGHT DB_FR2 (LDB-FR2)-5F-6way SPN DB
LIGHT DB_FR3 (LDB-FR3)-5F-6way SPN DB
2.96.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 4 6,006.00 24,024.00
PART D2_BOQ_COPT,IIT BOMBAY 78 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
2.96.2 6 A SP MCB 10KA-- 4 nos. Nos 16 252.00 4,032.00
2.97 LIGHT DB_FR1 (LDB-FR1)-5F- 8way SPN DB
Set 2 2,535.00 5,070.00
LIGHT DB_FR4 (LDB-FR4)-5F- 8way SPN DB
2.97.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 2 6,006.00 12,012.00
2.97.2 6 A SP MCB 10KA -- 6 nos. Nos 12 252.00 3,024.00
2.98 LIGHT DB-CA (LDB-CA)-4 way PPI DB Set 1 4,954.00 4,954.00
2.98.1 25 A 4P MCB 10KA as incomer -- 1 No. Nos 1 1,153.00 1,153.00
2.98.2 25 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 5,106.00 15,318.00
2.98.3 6 A SP MCB 10KA -- 12 nos Nos 12 252.00 3,024.00
2.99 LIGHT DB_AREA 1 (LDB-A1)-6F-6 way SPN DB
LIGHT DB_AREA 10 (LDB-A10)-6F-6 way SPN DB Set 3 2,174.00 6,522.00
LIGHT DB_AREA 11 (LDB-A11)-6F-6 way SPN DB
2.99.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 3 6,006.00 18,018.00
2.99.2 6 A SP MCB 10KA-- 4 nos. Nos 12 252.00 3,024.00
2.100 LIGHT DB_AREA 7 (LDB-A7)-6F-8 way SPN DB
Set 2 2,535.00 5,070.00
LIGHT DB_AREA 8 (LDB-A8)-6F-8 way SPN DB
2.100.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 2 6,006.00 12,012.00
2.100.2 6 A SP MCB 10KA -- 6 nos. Nos 12 252.00 3,024.00
2.101 LDB_TERRACE (LDB-TF)-8 way SPN DB Set 1 2,535.00 2,535.00
2.101.1 25A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.101.2 6 A SP MCB 10KA -- 6 nos. Nos 6 252.00 1,512.00
2.102 EMERGENCY LIGHT DB-CA_GF-6 way PPI DB Set 1 5,913.00 5,913.00
2.102.1 25 A 4P MCB, 10kA as incomer -- 1 No. Nos 1 1,153.00 1,153.00
2.102.2 25 A, DP RCCB with 100mA sensitivity-3 No. Nos 3 6,006.00 18,018.00
2.102.3 6 A SP 10KA MCB -- 18 nos Nos 18 252.00 4,536.00
2.103 EMERGENCY LIGHT DB-STAIRCASE (EDB-STAIR) 4WAY PPI DB
EMERGENCY LIGHT DB-CA_1F(EDB-C-4WAY PPI DB
EMERGENCY LIGHT DB-CA_2F(EDB-C-4WAY PPI DB
EMERGENCY LIGHT DB-CA_3F(EDB-C-4WAY PPI DB Set 7 4,954.00 34,678.00
EMERGENCY LIGHT DB-CA_4F(EDB-C-4WAY PPI DB
EMERGENCY LIGHT DB-CA_5F(EDB-C-4WAY PPI DB
EMERGENCY LIGHT DB-CA_6F(EDB-C-4WAY PPI DB
2.103.1 25 A 4P MCB, 10kA as incomer -- 1 No. Nos 7 1,153.00 8,071.00
2.103.2 25 A, DP RCCB with 100mA sensitivity-3 No. Nos 21 5,106.00 1,07,226.00
2.103.3 6 A SP MCB 10KA -- 12 nos Nos 84 252.00 21,168.00
2.104 DB1-EXTERNAL SECURITY CABIN-1-6 way VTPN DB with timer (Fabricated)
DB1-EXTERNAL SECURITY CABIN-2-6 way VTPN DB with timer (Fabricated) Set 2 4,737.00 9,474.00
Refer INI-IITB-COPT-ELE-External Lighting Layout_R1 for DB SLD
2.104.1 40A 4P 100mA RCBO as incomer- 1 No. Nos 2 7,416.00 14,832.00
2.104.2 6 A SP MCB 10kA -- 18 nos Nos 36 252.00 9,072.00
AC DBs-INI-IITB-COPT-ELE_AC Power Layout for DB SLD
2.105 ACDB-GF (ACDB-GF)- 4 way PPI DB (Refer DWG INI-IITB-COPT-ELE-GF-AP-01)
Set 2 4,954.00 9,908.00
ACDB-1F (ACDB-1F)- 4 way PPI DB (Refer DWG INI-IITB-COPT-ELE-1F-AP-01)
2.105.1 40 A 4P MCB 10KA as incomer -- 1 No. Nos 2 956.00 1,912.00
2.105.2 40 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 5,897.00 35,382.00
2.105.3 16 A SP MCB 10KA -- 12 nos Nos 24 252.00 6,048.00
2.106 ACDB-2F (ACDB-2F)-12 way PPI DB (Refer DWG INI-IITB-COPT-ELE-2F-AP-01)
ACDB-3F (ACDB-3F)-12 way PPI DB (Refer DWG INI-IITB-COPT-ELE-3F-AP-01) Set 3 8,499.00 25,497.00
ACDB-6F (ACDB-6F)-12 way PPI DB (Refer DWG INI-IITB-COPT-ELE-6F-AP-01)
2.106.1 40 A 4P MCB 10KA as incomer -- 1 No. Nos 3 956.00 2,868.00
2.106.2 40 A, DP RCCB with 100mA sensitivity-3 No. Nos 9 5,897.00 53,073.00
2.106.3 16 A SP MCB 10KA-- 36 nos Nos 108 252.00 27,216.00
2.107 ACDB-4F (ACDB-4F)-8 way PPI DB (Refer DWG INI-IITB-COPT-ELE-4F-AP-01)
Set 2 7,653.00 15,306.00
ACDB-5F (ACDB-5F)-8 way PPI DB (Refer DWG INI-IITB-COPT-ELE-5F-AP-01)
2.107.1 40 A 4P MCB 10KA as incomer -- 1 No. Nos 2 956.00 1,912.00
2.107.2 40 A, DP RCCB with 100mA sensitivity-3 No. Nos 6 5,897.00 35,382.00
2.107.3 16 A SP MCB 10KA -- 24 nos Nos 48 252.00 12,096.00
2.108 DB1-LMR-6 way SPN DB
DB1-LMR-6 way SPN DB
Set 3 2,174.00 6,522.00
DB1-LMR-6 way SPN DB
(Refer SLD INI-IITB-COPT-EL-PWR-DB-SLD-GF-01)
2.108.1 40A DP RCBO with 100mA sensitivity as incomer- 1 no Nos 3 6,729.00 20,187.00
2.108.2 6 A SP MCB 10kA -- 4 nos. Nos 12 252.00 3,024.00
2.109 DB-PUMP ROOM-6 way SPN DB Set 1 2,174.00 2,174.00
2.109.1 25A, DP RCBO with 100mA sensitivity as incomer- 1 no Nos 1 6,006.00 6,006.00
2.109.2 6 A SP MCB 10kA -- 4 nos. Nos 4 252.00 1,008.00
TOTAL OF DISTRIBUTION BOARDS 50,03,669.00
3 LT CABLES, TERMINATIONS, CABLE TRAYS AND RACEWAYS, ETC.
3.1 LT CABLES
Supply, handling, laying effecting proper connections testing and commissioning of following
sizes of 1.1 KV grade PVC / XLPE core insulated, extruded PVC inner sheath, armoured /
unarmoured extruded outer sheath FRLS PVC, Copper / Aluminium conductor cables as per IS
7098 Part I laid over MS supports, cable racks, trenches, or fixing on walls including clamping
the cable to supports in an approved manner along with cable . (Earthing will be measured
separately and need not be quoted under this item). All complete as required and as per final
instruction as given by E.I.C / Consultants.

3.1.1 3.5 C x 300 sq. mm., XLPE Al. Armoured cable Rmt. 30 1,602.00 48,060.00
3.1.2 3.5 C x 240 sq. mm., XLPE Al. Armoured cable Rmt. 365 1,311.00 4,78,515.00
PART D2_BOQ_COPT,IIT BOMBAY 79 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
3.1.3 3.5 C x 185 sq. mm., XLPE Al. Armoured cable Rmt. 230 1,021.00 2,34,830.00
3.1.4 3.5 C x 150 sq.mm., XLPE Al. Armoured cable Rmt. 114 807.00 91,998.00
3.1.5 3.5 C x 120 sq.mm., XLPE Al. Armoured cable Rmt. 147 688.00 1,01,136.00
3.1.6 3.5 C x 70 sq.mm., XLPE Al. Armoured cable Rmt. 717 447.00 3,20,499.00
3.1.7 3.5 C x 50 sq.mm., XLPE Al. Armoured cable Rmt. 30 336.00 10,080.00
3.1.8 3.5 C x 35 sq.mm., XLPE Al. Armoured cable Rmt. 180 251.00 45,180.00
3.1.9 3.5 C x 25 sq.mm., XLPE Al. Armoured cable Rmt. 40 202.00 8,080.00
3.1.10 4 C x 35 sq.mm., XLPE CU. Armoured cable Rmt. 206 1,924.00 3,96,344.00
3.1.11 4 C x 16 sq.mm.,XLPE Cu. Armoured cable Rmt. 2094 817.00 17,10,798.00
3.1.12 4 Core x 10 sq.mm., XLPE Copper Armoured Cable Rmt. 228 566.00 1,29,048.00
3.1.13 4 Core x 6 sq.mm., XLPE Copper Armoured Cable Rmt. 2966 373.00 11,06,318.00
3.1.14 4 Core x 4 sq.mm., XLPE Copper Armoured Cable Rmt. 869 251.00 2,18,119.00
3.1.15 3 Core x 4 sq.mm., XLPE Copper Armoured Cable Rmt. 833 209.00 1,74,097.00
3.1.16 3 Core x 6 sq.mm., XLPE Copper Armoured Cable Rmt. 1428 286.00 4,08,408.00
3.1.17 3 C x 70 sq.mm.,XLPE AL. Armoured cable Rmt. 45 386.00 17,370.00
3.1.18 1 C x 25 sq.mm.,XLPE Cu. Flexible cable Rmt. 300 297.00 89,100.00
3.1.19 1 C x 10sq.mm.,XLPE Cu. Flexible cable Rmt. 1575 69.00 1,08,675.00
3.1.20 1 C x 16sq.mm.,XLPE Cu. Flexible cable Rmt. 225 192.00 43,200.00
3.1.21 3Cx1.5sqmm 2XFY (Cu) Rmt. 150 120.00 18,000.00
3.2 CABLE TERMINATIONS
Supply and making end termination with brass compression gland & aluminium lugs joints for
the following sizes of 1.1KV grade PVC / XLPE Insulated armoured / unarmoured Copper /
Aluminium conductor cables including providing heavy duty bimetallic, crimping type
terminal lugs wherever Aluminium conductor cables are used & Copper terminal lugs to be
used for copper cable & Gland Earthing as directed by E.I.C., insulation tape, heavy duty
double compression type brass glands effecting terminal connection to the equipment/Panel
complete as required as per final direction and approval of the Owner/Consultant.

3.2.1 3.5 C x 300 sq. mm., XLPE Al. Armoured cable Nos 4 2,086.00 8,344.00
3.2.2 3.5 C x 240 sq. mm., XLPE Al. Armoured cable Nos 16 2,004.00 32,064.00
3.2.3 3.5 C x 185 sq. mm., XLPE Al. Armoured cable Nos 8 1,346.00 10,768.00
3.2.4 3.5 C x150 sq.mm., XLPE Al. Armoured cable Nos 4 1,145.00 4,580.00
3.2.5 3.5 C x 120 sq.mm., XLPE Al. Armoured cable Nos 8 1,028.00 8,224.00
3.2.6 3.5 C x 70 sq.mm., XLPE Al. Armoured cable Nos 26 803.00 20,878.00
3.2.7 3.5 C x 50 sq.mm., XLPE Al. Armoured cable Nos 6 681.00 4,086.00
3.2.8 3.5 C x 35 sq.mm., XLPE Al. Armoured cable Nos 68 478.00 32,504.00
3.2.9 3.5 C x 25 sq.mm., XLPE Al. Armoured cable Nos 2 386.00 772.00
3.2.10 4 C x 35 sq.mm., XLPE CU. Armoured cable Nos 8 544.00 4,352.00
3.2.11 4 C x 16 sq.mm.,XLPE Cu. Armoured cable Nos 134 413.00 55,342.00
3.2.12 4 Core x 10 sq.mm., XLPE Copper Armoured Cable Nos 6 306.00 1,836.00
3.2.13 4 Core x 6 sq.mm., XLPE Copper Armoured Cable Nos 140 296.00 41,440.00
3.2.14 4 Core x 4 sq.mm., XLPE Copper Armoured Cable Nos 40 228.00 9,120.00
3.2.15 3 Core x 4 sq.mm., XLPE Copper Armoured Cable Nos 62 223.00 13,826.00
3.2.16 3 Core x 6 sq.mm., XLPE Copper Armoured Cable Nos 28 227.00 6,356.00
3.2.17 3 C x 70 sq.mm.,XLPE AL. Armoured cable Nos 4 692.00 2,768.00
3.2.18 1 C x 25 sq.mm.,XLPE Cu. Flexible cable Nos 40 192.00 7,680.00
3.2.19 1 C x 10sq.mm.,XLPE Cu. Flexible cable Nos 210 160.00 33,600.00
3.2.20 1 C x 16sq.mm.,XLPE Cu. Flexible cable Nos 30 128.00 3,840.00
3.2.21 3Cx1.5sqmm 2XFY (Cu) Nos 42 150.00 6,300.00
3.3 CABLE TRAYS
Supplying and installing following size of perforated painted with
powder coating M.S. cable trays with perforation not more than
17.5%, in convenient sections, joined with connectors,
suspended from the ceiling with M.S. suspenders including bolts
& nuts, painting suspenders etc. as required.
3.3.1 900mm Width X 75mm Depth X 2mm Thickness Rmt. 5 2,494.00 12,470.00
3.3.2 600mm Width X 50mm Depth X 2mm Thickness Rmt. 32 1,346.00 43,072.00
3.3.3 450mm Width X 50mm Depth X 2mm Thickness Rmt. 56 1,120.00 62,720.00
3.3.4 300mm Width X 50mm Depth X 1.6mm Thickness Rmt. 769 766.00 5,89,054.00
3.3.5 200mm Width X 50mm Depth X 1.6mm Thickness Rmt. 684 679.00 4,64,436.00
3.3.6 150mm Width X 50mm Depth X 1.6mm Thickness Rmt. 242 595.00 1,43,990.00
3.4 UNDER FLOOR RACEWAYS / TRUNKING JUNCTION BOXES
Supply and installation of Hot dip galvanised, GI fabricated floor junction boxes as per
relevent IS. The job includes aligning of boxes with the raceways and making necessary
arrangement to take the knock outs from them to lay the wires, with all necessary
accessories required to complte the job. (The civil work like cutting of the floor to ambedded
in junction boxes in the floor to be inlcuded in the rate). Top cover shall be made up from 2.5
mm thick GI steel plate.
3.4.1 450 (L) x 450 (W) x 50 (H) mm JB - 2 mm thick No. 16 2,080.00 33,280.00
3.4.2 350 (L) x 350 (W) x 50 (H) mm JB - 2 mm thick No. 31 794.00 24,614.00
3.4.3 300 (L) x 300 (W) x 50 (H) mm JB - 2 mm thick No. 51 1,239.00 63,189.00
3.4.4 250 (L) x 250 (W) x 50 (H) mm JB - 2 mm thick No. 73 1,009.00 73,657.00
3.4.5 200 (L) x 200 (W) x 50 (H) mm JB - 2 mm thick No. 151 804.00 1,21,404.00
3.4.6 150 (L) x 150 (W) x 50 (H) mm JB - 2 mm thick No. 337 638.00 2,15,006.00
3.4.7 100 (L) x 100 (W) x 50 (H) mm JB - 2 mm thick No. 76 536.00 40,736.00
3.4.8 75 (L) x 75 (W) x 50 (H) mm JB - 2 mm thick No. 42 473.00 19,866.00
3.4.9 50 (L) x 50 (W) x 50 (H) mm JB - 2 mm thick No. 48 421.00 20,208.00

PART D2_BOQ_COPT,IIT BOMBAY 80 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
3.5 HUME PIPES FOR UNDERGROUND CABLING
Providing &laying non pressure NP2 class (light duty) RCC pipe with collars jointed with stiff
mixture of cement mortar in the propotion of 1:2 (1 cement: 2fine sand) including testing of
joint etc.
3.5.1 150mm Dia. Rmt. 131 486.00 63,666.00
3.5.2 200mm Dia. Rmt. 55 799.00 43,945.00
3.5.3 300mm Dia. Rmt. 411 889.00 3,65,379.00
Supplying and Laying of following sizes of under floor Raceways made out of 2mm Pre
Galvanised Steel sheet or Hot dip galvanised including Couplers, Jointing sleeves, floor fixing
3.6
supports, Concealed in floor with chipping and levelling that portion of the floor wherever
required as per specifications complete as required.
3.6.1 400 (W) x 38 (H) mm Mtrs. 29 1,819.00 52,751.00
3.6.2 300 (W) x 38 (H) mm Mtrs. 97 1,431.00 1,38,807.00
3.6.3 250 (W) x 38 (H) mm Mtrs. 138 1,237.00 1,70,706.00
3.6.4 200 (W) x 38 (H) mm Mtrs. 263 1,056.00 2,77,728.00
3.6.5 150 (W) x 38 (H) mm Mtrs. 818 861.00 7,04,298.00
3.6.6 100 (W) x 38 (H) mm Mtrs. 707 668.00 4,72,276.00
3.6.7 50 (W) x 38 (H) mm Mtrs. 1030 485.00 4,99,550.00
3.7 MANHOLE
Constrution of man holes as per following specifications for providing passages to lay the
cables.
Providing 900 mm(B) x 800 mm(W) X 750 mm(D) manhole complete with 6" thick brickwall,
3.7.1 plastering on both sides and providing C.I. hinged cover complete in all respect. Nos. 7 11,398.00 79,786.00

Providing 900 mm(B) x 800 mm(W) X 1000 mm(D) manhole complete with 6" thick brickwall,
3.7.2 plastering on both sides and providing C.I. hinged cover complete in all respect. Nos. 7 23,726.00 1,66,082.00

Providing 1500 mm(B) x 900 mm(W) X 1350 mm(D) manhole complete with 6" thick
3.7.3 brickwall, plastering on both sides and providing C.I. hinged cover complete in all respect. Nos. 8 29,479.00 2,35,832.00

TOTAL OF LT CABLES, TERMINATIONS, CABLE TRAYS AND RACEWAYS, ETC. 1,12,65,043.00


4 POINT WIRING IN PVC CONDUIT, ETC.
GENERAL NOTES
Required clearances from the concerned statutory authorities are in the scope of this
work.Statutory fees paid will be reimbursed on production of original receipts in the name of
IITB.
Please follow the GRIHA norms for luminous efficacy, lighting levels, illumination level
etc.without extra cost.
Mode of measurement shall be as per point basis.The extent of wires/cables required will
be as per the dimensional details available in the respective drawings.

4.1 Point wiring in PVC conduit


Point wiring for light/ceiing fan/6A/ 16A/ socket outlet /6A outlet for exhaust fan , bell point
etc. with 1.1 KV grade FRLS PVC insulated multistranded copper conductor wire(ISI marked),
in 25 to 40 mm dia High mechanical stress (MMS) rigid PVC conduit / PVC trunking having ISI
marked IS 9537 Part - 3, including fixing accessories & hardware concealed /exposed in
slab/wall or on 5mm. thick G.I. spacers fixed with no. 10 nettle within the box piece fold
wood screws with nylon plug complete with all conduit accessories 20 SWG G.I. Saddles,
ready made MS switchboxes, socket outlet boxes of approved makes zinc chromate
passivated, brass earthing stud 1/2 nos, controlling modular switches & sockets with
moulded front plate and inner plate etc. including appropriate size of FRLS PVC insulated
copper earth wire , brass/bakelite (straight / angular) lamp holders, 3 plate ceiling rose,16 A,
connectors, painting etc. as per specifications and drawings and as per instructions of E-I-C
and as detailed below : (sample switch Box etc. to be got approved before fabrication) as per
specification.

NOTE:
1. Connections shall be done with crimped type tinned copper lugs & washers.
2. All switches & socket outlets shall be as per preferred makes.
3. All sample boxes with accessories /fixtures shall be got approved from Department.

4. All 16 A socket outlets should be with 6 pin & shuttered type


5. MS boxes other than switch boxes & socket outlet boxes shall be fabricated out of 16 SWG
thickness MS sheet duly painted with red oxide primer & 2 coats of synthetic enamel paint.

6. Minimum size of the FRLS insulated copper earth wire continuity shall be 2.5 sq.mm.

7. The colour shade of switches & cover plates shall be white /off white & to be approved by
E-I-C
8. The scope also includes supply of modular blanking plates where ever required.
9. The maximum permissible number of PVC insulated wires through PVC conduits shall be as
per IS/NBC : 2016.
10.All FRLS Wires Should be tested at factory before despatch
11. Wiring from DB to Main Switch, From Main Switch to Switch Board & if any Looping from
Switch board to Switch board shall be part of point wiring .
12. MS pull out boxes of required size & of 16Guage with cover are to be provided at both
the ends of expansion joint as per the instructions of EIC for each & every conduit included in
this schedule & passing through expansion joint, irrelevant of the type of service it is carrying,

PART D2_BOQ_COPT,IIT BOMBAY 81 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
13.Mode of measurement shall be as per point basis.The extent of wires/cables required
will be as per the dimensional details available in the respective drawings.

4.1.1 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable in surface / recessed HMS class PVC conduit,
with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm Point 319 1,000.00 3,19,000.00
FRLS PVC insulated copper conductor single core cable etc. as required. (Primary point)

4.1.2 Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point
(without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor
single core cable in surface/ with 1.5 sq. mm FRLS PVC insulated copper conductor single Point 1773 640.00 11,34,720.00
recessed HMS class PVC conduit, and earthing the point core cable etc. as required.
(Secondary Point)
4.1.3 Wiring for circuit/submain wiring along with earth wire with the following sizes of FRLS PVC
insulated copper conductor, single core copper in surface/recessed PVC conduit as required.

4.1.3.1 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire Mtr 18387 230.00 42,29,010.00
4.1.3.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire Mtr 15689 271.00 42,51,719.00
4.1.3.3 2 X 4 sq. mm + 1 X 4 sq. mm earth wire Mtr 21872 329.00 71,95,888.00
4.1.3.4 4R X 2.5 sqmm Mtr 285 404.00 1,15,140.00
4.1.3.5 4R X 4 sqmm wire Mtr 2016 529.00 10,66,464.00
4.1.3.6 4R X 6 sqmm wire Mtr 2062 743.00 15,32,066.00
4.1.3.7 4 C x 16 sq.mm.,XLPE Cu. Armoured cable Mtr 1958 817.00 15,99,686.00
4.1.4 Supplying and fixing of following sizes of Heavy class PVC
conduit along with accessories in surface/recess including
cutting the wall and making good the same in case of recessed
conduit as required.
4.1.4.1 25 mm PVC HMS conduit Mtr 43980 143.00 62,89,140.00
4.1.5 Supplying and fixing following modular switch/ socket on the existing modular plate & switch
box including connections but excluding modular plate etc. as required.

4.1.5.1 16A Switch Nos 1464 154.00 2,25,456.00


4.1.5.2 6-16A Socket Nos 1058 194.00 2,05,252.00
4.1.5.3 6A Switch Nos 746 101.00 75,346.00
4.1.5.4 6A Socket Nos 1858 120.00 2,22,960.00
4.1.5.5 32A 1Ph. INDUSTRIAL Switch-IP 42 wall mounted Nos 14 8,792.00 1,23,088.00
4.1.5.6 32A 1Ph. INDUSTRIAL Socket-IP 42 wall mounted Nos 14 15,640.00 2,18,960.00
4.1.5.7 SITC of USB point including USB socket Nos 9 10,925.00 98,325.00
4.1.5.8 SITC of USB cable Mtr. 360 299.00 1,07,640.00
4.1.5.9 SITC of HDMI point including HDMI socket Nos 9 8,625.00 77,625.00
4.1.5.10 SITC of HDMI cable. Mtr. 360 368.00 1,32,480.00
4.1.5.11 SITC of audio point including Audio socket 3.5mm jack Nos 9 7,429.00 66,861.00
4.1.5.12 SITC of audio cable Mtr. 360 477.00 1,71,720.00
4.1.5.13 SITC of 10 module pop up box with configuration of 2 nos power, 2 nos data . 2 nos USB , 1
Nos 9 32,200.00 2,89,800.00
no HDMI, 1 no Audio 3.5mm jack (table mounted)
4.1.6 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate
for modular switches in recess etc. as required.
4.1.6.1 1 or 2 Module Nos 398 294.00 1,17,012.00
4.1.6.2 3 Module Nos 1401 322.00 4,51,122.00
4.1.6.3 4 Module Nos 38 338.00 12,844.00
4.1.6.4 6 Module Nos 779 396.00 3,08,484.00
4.1.6.5 8 Module Nos 5 447.00 2,235.00
4.1.6.6 12 Module Nos 69 539.00 37,191.00
4.1.6.7 16 Module Nos 3 1,703.00 5,109.00
4.1.7 Supplying and fixing 63 A, 415 V, TPN Industrial type socket outlet,wall mounted with
enclosure IP 42 & all fixing arrangement, switch with 3 pole and earth, metal enclosed plug
top alongwith 63 A, “C” curve, TPN, MCB, in sheet steel enclosure, on surface or in recess, Nos. 262 10,497.00 27,50,214.00
with chained metal cover for the socket out let and complete with connections, testing and
commissioning etc. as required.
4.1.8 Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, wall mounted with
enclosure IP 42 & all fixing arrangement , switch with 2 pole and earth, metal enclosed plug
top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with Nos. 6 1,597.00 9,582.00
chained metal cover for the socket out let and complete with connections, testing and
commissioning etc. as required.
4.1.9 Supplying and fixing 32 A, 415 V, TPN Industrial type socket outlet, wall mounted with
enclosure IP 42 & all fixing arrangement, switch with 3 pole and earth, metal enclosed plug
top alongwith 32 A, “C” curve, TPN, MCB, in sheet steel enclosure, on surface or in recess, Nos. 94 5,772.00 5,42,568.00
with chained metal cover for the socket out let and complete with connections, testing and
commissioning etc. as required.
4.1.10 Supplying and fixing 63 A, 415 V, TPN Industrial type socket outlet,wall mounted with
enclosure IP 42 & all fixing arrangement, switch with 3 pole and earth, metal enclosed plug
top alongwith 63 A, “C” curve, TPN, MCB, in sheet steel enclosure, on surface or in recess, Nos. 5 12,981.00 64,905.00
with chained metal cover for the socket out let and complete with connections, testing and
commissioning etc. as required.
4.1.11 Supplying and fixing 40 A, 100mA RCBO TPN, 415 V, alongwith in sheet steel enclosure IP 42,
and complete with connections, testing and commissioning, fixing arrangement on wall etc. Nos. 2 9,192.00 18,384.00
as required.(for UPS)

PART D2_BOQ_COPT,IIT BOMBAY 82 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
4.1.12 Supplying and fixing 40 A, 300mA RCBO TPN, 415 V, alongwith in sheet steel enclosure IP 42,
and complete with connections, testing and commissioning, fixing arrangement on wall etc. Nos. 3 7,070.00 21,210.00
as required.(for Lift)
4.1.13 Supplying and fixing 40 A, 300mA RCBO TPN, 415 V, alongwith in sheet steel enclosure IP 65,
and complete with connections, testing and commissioning, fixing arrangement on wall etc. Nos. 22 7,070.00 1,55,540.00
as required.(for AC ODU)
4.1.14 Supplying and fixing 25 A, 100mA RCBO, 415 V,alongwith in sheet steel enclosure IP 42, and
complete with connections, testing and commissioning fixing arrangement on wall etc. as Nos. 28 9,192.00 2,57,376.00
required.(for UPS & vent fans)
4.1.15 Supplying and fixing 25 A, 300mA RCBO TPN, 415 V, alongwith in sheet steel enclosure IP 65,
and complete with connections, testing and commissioning, fixing arrangement on wall etc. Nos. 7 6,956.00 48,692.00
as required.(for AC ODU)
4..1.16 Supplying and fixing 63 A, 100mA RCBO TPN, 415 V,alongwith in sheet steel enclosure IP 42,
and complete with connections, testing and commissioning fixing arrangement on wall etc. Nos. 2 9,192.00 18,384.00
as required.(for UPS)
4.1.17 Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling
fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm
long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not
less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350
RPM (tolerance as per IS : 374-2019), THD less than 10%, regulator unit for speed control
No. 288 2,690.00 7,74,720.00
mounted on the switch board and manually operated and all remaining accessories including
Hook,back box, safety pin, nut bolts, washers, temperature rise=75 degree C (max.),
insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC
Supply, wire,earthing etc. complete as required.

4.1.18 Supply, installation, testing of Exhaust Fan, single phase complete with blades, motor, scope
includes supply of 3C copper 1.5 sq. mm. flexible chord of suitable length with 6A 3 pin plug
top, aluminum louvers shutters, rag bolt/ anchor fastener suitable MS angle iron frame made
of 30x30x5mm, 4 corners converged with 2mm thick MS sheet to form suitable circular No. 2 2,194.00 4,388.00
opening with necessary fixing arrangement painting as per specification, drawing and as
directed by E.I.C
300mm dia,900rpm
Push Button
4.1.19 Supplying, Installing, Testing and Commissioning of Remote Push button station for booster
No. 21 1,915.00 40,215.00
pumps
TOTAL OF POINT WIRING IN PVC CONDUIT, ETC. 3,53,88,521.00
5 LIGHT FIXTURES AND FITTINGS, CEILING FANS, EXHAUST FANS, ETC.
Light Fixtures, Fittings & Lamps
Supply, installation, testing & commissioning of fixtures & fittings, ceiling fans, exhaust fans,
etc. complete with accessories, tube/lamp etc in on surface of slab/beam by 2 nos
(minimum) of 6 mm anchor fasteners or on wall with 2 nos of wood screws, nylon plug etc.,
suitable supporting frame fixed with rag bolts grouted on the wall/anchor fastener on the
beam/on the column & other fixing accessories etc provision & connection with 1.5 sq.mm
multistranded copper conductor FRLS PVC wires etc., all as per drawing, specifications & as
per the instruction of E.I.C.

Note:
1) Sample fixture/fittings/lamps shall be got approved from Department and Architects with
complete technical data.
2) Cost of lamps to be included in installation rate.
3) All fixtures shall be with low loss electronic ballast
5.1 Supply, Installation Testing and Commissioning of LED batten light having system wattage of
maximum 29W to 34W with System Efficacy >120 lm/W, delivering minimum 4000 lumens,
THD <10%, Power Factor >0.95, CRI >80, CCT 6500, IP20 CRCA housing , Life L70B50 @ 50k
hrs, Ripple <5%, . BIS compliant driver High low cut with auto restart feature @ 140-270V,
EMC -EMI compliant. Driver shall have 4KV Surge protection. Driver should have Class B No. 40 2,390.00 95,600.00
servicability (mainatainable at site). LM79 and LM80 reports must be submitted from a NABL
accredited laboratory. BIS certificate for driver as well as the luminaire must be submitted for
records. Driver and luminaire shall be of same make.

5.2 Supply, Installation Testing and Commissioning of LED batten light having system wattage of
maximum 42W to 48W with System Efficacy >120 lm/W, delivering minimum 5700 lumens,
THD <10%, Power Factor >0.95, CRI >80, CCT 6500, IP20 CRCA housing , Life L70B50 @ 50k
hrs, Ripple <5%, . BIS compliant driver High low cut with auto restart feature @ 140-270V,
EMC -EMI compliant. Driver shall have 4KV Surge protection. Driver should have Class B No. 529 2,926.00 15,47,854.00
servicability (mainatainable at site). LM79 and LM80 reports must be submitted from a NABL
accredited laboratory. BIS certificate for driver as well as the luminaire must be submitted for
records. Driver and luminaire shall be of same make.

PART D2_BOQ_COPT,IIT BOMBAY 83 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
5.3 Supply, Installation, Testing and Commissioning of Recessed Mounted 2X2 LED Luminaire
with system lumen output of 3600 lumens and minmum system efficacy of 120lm/W. Power
consumption of luminaire shpuld be 28W to 32W with color temperature of 5700K and
CRI>80, . The luminaire shall meet IP20 rating with Ripple <5%, THD<10% and PF >0.95. The
luminaire housing should made of powder coated CRCA with high efficiency PS diffuser and
having surge protection up to 4kV. The driver must have operating voltage range from 120-
No. 243 2,743.00 6,66,549.00
270VAC and EMI/EMC compliant. Luminaire should have Class B serviceability. Luminaire
should accommodate different color tiles & also accommodate Services like-AC Grill & Smoke
detector etc. LM79 and LM80 reports must be submitted from a NABL accredited laboratory,
Luminaire and Driver must have BIS certificate and same must be submitted for
records.Driver and luminaire shall be of same make.

5.4 Supply, Installation, Testing and Commissioning of Recessed Mounted 2X2 LED Luminaire
with system lumen output of 4200 lumens and minmum system efficacy of 120lm/W. Power
consumption of luminaire shpuld be 33W to 37W with color temperature of 5700K and
CRI>80, . The luminaire shall meet IP20 rating with Ripple <5%, THD<10% and PF >0.95. The
luminaire housing should made of powder coated CRCA with high efficiency PS diffuser and
having surge protection up to 4kV. The driver must have operating voltage range from 120-
No. 73 1,877.00 1,37,021.00
270VAC and EMI/EMC compliant. Luminaire should have Class B serviceability. Luminaire
should accommodate different color tiles & also accommodate Services like-AC Grill & Smoke
detector etc. LM79 and LM80 reports must be submitted from a NABL accredited laboratory,
Luminaire and Driver must have BIS certificate and same must be submitted for
records.Driver and luminaire shall be of same make.

5.5 Supply, Installation, Testing and Commissioning of Recessed Mounted 2X2 LED Luminaire
with system lumen output of 4200 lumens and minmum system efficacy of 120lm/W. Power
consumption of luminaire shpuld be 33 to 37W with color temperature of 5700K and CRI>80,
. The luminaire shall meet IP20 rating with Ripple <5%, THD<10% and PF >0.95. The luminaire
housing should made of powder coated CRCA with high efficiency PS diffuser and having
surge protection up to 4kV. The driver must have operating voltage range from 120-270VAC
No. 24 2,390.00 57,360.00
and EMI/EMC compliant. Luminaire should have Class B serviceability. Luminaire should
accommodate different color tiles & also accommodate Services like-AC Grill & Smoke
detector etc. LM79 and LM80 reports must be submitted from a NABL accredited laboratory,
Luminaire and Driver must have BIS certificate and same must be submitted for
records.Driver and luminaire shall be of same make.

5.6 Supply, Installation Testing and Commissioning of maximum 17W to 20W downlight
mounted High quality polycarbonate diffuser and PDC Al housing recessed design 150 mm
Cutout for visual comfort Downlighter delivering >2000 Lumen, 4000K CRI>80, THD <10%,,
Input voltage Range 140-270 VAC , EMI EMC Complient (as per CISPR 15)Replacable driver
Luminaire driver both BIS Complient and having CRS ( R No ) , Power factor>0.95, IP20
No. 29 1,402.00 40,658.00
protection, operating temperature range from 0 to 45 deg C, internal surge protection of
2.5kV. LM79 and LM80 reports must be submitted from a NABL accredited laboratory. BIS
certificate for driver as well as the luminaire must be submitted for records. Driver and
luminaire shall be of same make.

5.7 Supply, Installation Testing and Commissioning of maximum 17W to 20W Surface mounted
High quality polycarbonate diffuser and PDC Al housing recessed design 160 mm Dia for
visual comfort Downlighter delivering >2000 Lumen, 4000K CRI>80, THD <10%,, Input voltage
Range 140-270 VAC , EMI EMC Complient (as per CISPR 15)Replacable driver Luminaire driver
both BIS Complient and having CRS ( R No ), Power factor>0.95, IP20 protection, operating
No. 110 2,133.00 2,34,630.00
temperature range from 0 to 45 deg C, internal surge protection of 2.5kV. LM79 and LM80
reports must be submitted from a NABL accredited laboratory. BIS certificate for driver as
well as the luminaire must be submitted for records. Driver and luminaire shall be of same
make.

5.8 Supply, Installation Testing and Commissioning of maximum 10W to 12W Surface mounted
High quality polycarbonate diffuser and PDC Al housing recessed design 160 mm Dia for
visual comfort Downlighter delivering >1200 Lumen, 4000K CRI>80, THD <10%,, Input voltage
Range 140-270 VAC , EMI EMC Complient (as per CISPR 15)Replacable driver Luminaire driver
both BIS Complient and having CRS ( R No ), Power factor>0.95, IP20 protection, operating
No. 175 1,232.00 2,15,600.00
temperature range from 0 to 45 deg C, internal surge protection of 2.5kV. LM79 and LM80
reports must be submitted from a NABL accredited laboratory. BIS certificate for driver as
well as the luminaire must be submitted for records. Driver and luminaire shall be of same
make.

5.9 Supply, Installation Testing and Commissioning of maximum 12 to 15W Surface mounted
High quality polycarbonate diffuser and PDC Al housing recessed design 160 mm Dia for
visual comfort Downlighter delivering >1200 Lumen, 4000K CRI>80, THD <10%,, Input voltage
Range 140-270 VAC , EMI EMC Complient (as per CISPR 15)Replacable driver Luminaire driver
both BIS Complient and having CRS ( R No ), Power factor>0.95, IP20 protection, operating
No. 6 2,011.00 12,066.00
temperature range from 0 to 45 deg C, internal surge protection of 2.5kV. LM79 and LM80
reports must be submitted from a NABL accredited laboratory. BIS certificate for driver as
well as the luminaire must be submitted for records. Driver and luminaire shall be of same
make.

PART D2_BOQ_COPT,IIT BOMBAY 84 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
5.10 Supply, Installation Testing and Commissioning of maximum 16 to 20W deep recessed
mounted High quality glossy reflector & PDC Al Deep recessed design ensures Low Glare
(UGR <= 19, shielding 38°) 125 mm Cutout for visual comfort Downlighter delivering >2000
Lumen, 6500K CRI>80 with Ra>0, THD <10%, SDCM<5, Beam angle 60-65 Deg Input voltage
Range 140-270 VAC , EMI EMC Complient (as per CISPR 15)Replacable driver Luminaire driver
both BIS Complient and having CRS ( R No ) L70B50 @ 50K Hrs, Power factor>0.9, IP20 No. 21 2,133.00 44,793.00
protection, operating temperature range from 0 to 45 deg C, internal surge protection of
2.5kV. LM79 and LM80 reports must be submitted from a NABL accredited laboratory. BIS
certificate for driver as well as the luminaire must be submitted for records. Driver and
luminaire shall be of same make.

5.11 Supply, Installation Testing and Commissioning of maximum 16 to 20W deep recessed
mounted High quality glossy reflector & PDC Al Deep recessed design ensures Low Glare
(UGR <= 19, shielding 38°) 125 mm Cutout for visual comfort Downlighter delivering >2000
Lumen, 6500K CRI>80 with Ra>0, THD <10%, SDCM<5, Beam angle 60-65 Deg Input voltage
Range 140-270 VAC , EMI EMC Complient (as per CISPR 15)Replacable driver Luminaire driver
both BIS Complient and having CRS ( R No ) L70B50 @ 50K Hrs, Power factor>0.9, IP20 No. 597 3,291.00 19,64,727.00
protection, operating temperature range from 0 to 45 deg C, internal surge protection of
2.5kV. LM79 and LM80 reports must be submitted from a NABL accredited laboratory. BIS
certificate for driver as well as the luminaire must be submitted for records. Driver and
luminaire shall be of same make.

5.12 Supply, Installation Testing and Commissioning of LED suspended/surface mounted


Cylinderical downlighter with system lumen output of 2000 lumens with system efficacy of
125lm/W. Power consumption : 16 to 20W, CRI >80 & luminaire should have beam angle No. 79 3,620.00 2,85,980.00
option of 24°/36°/60°. Luminaire should have extruded alumunium housing with life class of
50Khrs @ L70.
5.13 Supply, Installation Testing and Commissioning of LED recessed/ suspended linear light
having system wattage of maximum 20 to 24W with System Efficacy >=110 lm/W, delivering
minimum 2500 lumens, THD <10%, Power Factor >0.95, CRI >80, CCT 6500, IP20 extruded
aluminium housing , Life L70B50 @ 50k hrs, Ripple <5%,. BIS compliant driver High low cut
with auto restart feature @ 140-270V, EMC -EMI compliant. Driver shall have 4KV Surge
protection. Luminaire should have option for both standalone as well as continuous No. 3 4,132.00 12,396.00
mounting. Driver should have Class B servicability (mainatainable at site). LM79 and LM80
reports must be submitted from a NABL accredited laboratory. BIS certificate for driver as
well as the luminaire must be submitted for records. Driver and luminaire shall be of same
make.

5.14 Bulkhead light for lift shaft -6 to 10W (6-16Socket & back box for light installation is part of
No. 24 975.00 23,400.00
point wiring)
5.15 LED profile light with supporting Driver as required- 10 to 12W Mtr 313 1,965.00 6,15,045.00
5.16 6-10 W wall braket light for Electrical Shaft No. 24 975.00 23,400.00
Outdoor
5.17 Terrace Light-Supply, Installation Testing and Commissioning of Compound wall light fitting of
8 to 12W w having System Efficacy >110 lm/W, system output >700 Lumens for 1100 lumens
for 10W, THD <10%, Power Factor >0.95, CRI >80, CCT 6500, Full IP 66 protected single
piece die cast aluminium housing having toughned PC with Impact resistance IK09, Life
L70B50 @ 50k hrs . BIS compliant driver, EMC -EMI compliant. Driver shall have 2.5KV Surge No. 53 969.00 51,357.00
protection. LM79 and LM80 reports must be submitted from a NABL accredited laboratory.
BIS certificate for driver as well as the luminaire must be submitted for records. Driver and
luminaire shall be of same make.

5.18 Supply, Installation Testing and Commissioning of Compound wall light fitting of 8 to 12W w
having System Efficacy >110 lm/W, system output >700 Lumens for 1100 lumens for 10W,
THD <10%, Power Factor >0.95, CRI >80, CCT 6500, Full IP 66 protected single piece die
cast aluminium housing having toughned PC with Impact resistance IK09, Life L70B50 @ 50k
hrs . BIS compliant driver, EMC -EMI compliant. Driver shall have 2.5KV Surge protection. No. 79 969.00 76,551.00
LM79 and LM80 reports must be submitted from a NABL accredited laboratory. BIS
certificate for driver as well as the luminaire must be submitted for records. Driver and
luminaire shall be of same make.

5.19 Supply, Installation, Commissioning of post top luminaire having symmetrical beam angle
with housing material of Die-cast aluminium, UV protected polycarbonate diffuser, system
wattage not exceeding 40 to 50W and system lumen output of not less than 5000 lumens
with efficacy > 110 lumens/W. CCT of 5700K and CRI>=70 with SDCM<5; luminaire
dimensions top Dia 450-455 mm and weight not more than 4.5kgs. Fixture shall operate in a
temperature range of 0°C to 50°C. Fixture shall have input voltage for 120-277 VAC. Lifetime
should be at least 50,000 burning hours at L70 at 50 degree centigrade ambient. Fixture shall
equipped with total IP66 protection and mechanical impact of minimum IK10. The LED used
in the luminaire shall be SMD type. The Driver should be potted /encapsulated & should be a No. 50 12,275.00 6,13,750.00
BIS approved driver and not a printed circuit board without casing, mounted inside the
luminaire. The luminaire should be capable of auto shutdown @ 325V and have an auto
recovery feature, with THD<10% (at full load). It should have a provision of 10KV series SPD
inside the housing. BIS approval for both Driver and the luminaire needs to be submitted for
records. Also, LM79 and LM80 reports must be submitted from a NABL accredited laboratory.

TOTAL OF LIGHT FIXTURES AND FITTINGS, CEILING FANS, EXHAUST FANS, ETC. 67,18,737.00
PART D2_BOQ_COPT,IIT BOMBAY 85 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
6 LIGHTNING PROTECTION SYSTEM
6.1 Providing and fixing of lightning conductor finial, made of 8mm dia 3000 mm long, Aluminium
tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes Nos 6 7,021.00 42,126.00
etc. complete as required.
6.2 Providing and fixing G.I. tape 25 mm X 5 mm thick on parapet or surface of wall for lightning
conductor complete as required.(For horizontal run on terrace)-Down conductor Mtr 600 101.00 60,600.00

6.3 Providing and fixing testing joint, made of 25 mm X 5 mm thick G.I. strip, 125 mm long, with 4
nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. Nos 15 765.00 11,475.00

6.4 EXANSION CONNECTOR Nos 9 575.00 5,175.00


6.5 Clamp at every 1 mtr Nos 600 121.00 72,600.00
6.6 Cross connector Nos 5 338.00 1,690.00
6.7 Cross Bonding to HVAC, Pumps etc item on terrace floor-copper wire Nos 100 1,139.00 1,13,900.00
6.8 20 mm X 5 mm GI strip Mtr 2306 674.00 15,54,244.00
TOTAL OF LIGHTNING PROTECTION SYSTEM 18,61,810.00
7 EARTHING SYSTEM
Supply, installation, testing & commissioning of earthing system & associated accessories,
etc. complete all as per the instructions of E.I.C.
Note :
1) Measurements of resistance of each earth station & resistance of complete scheme of
earthing layout must be measured recorded & got approved by E.I.C.
2) Jointing of the earth strip shall be with brass nuts bolts and also with solder joints.

3) Jointing of the earth wire shall be with solder joints with tinned cable sockets
7.1 Supply, Unloading, Handling, Installation, testing & commissioning of Chemical Earthing,
equivalent to Ashlok Length 3000mm, 50mm dia electrode, It shall also have provision for
connecting 50 x 10 mm. G.I. Flat on two sides. A masonry structure shall be constructed to a
depth of 750mm.and with 450 x 450 mm (clear) chamber, and a heavy duty Cast Iron Cover
shall be used to cover the pit. Excavation of Hard Rock, Boring, Drilling, backfilling, removal of
excess soil/Rock, supply of Back filling compound is included in the scope complete as per
technical specifications, drawings, relevant standards & site conditions.
Note:
1) All earth pits shall be as per IS 3043 with latest amendments.
2) Earthing stations should contain relevant grade of BFC packed around the earth earth
electrode as called for in the item. Set 12 7,596.00 91,152.00
3) Earthing shall be done at indicted location by the Consultants. The minimum distance
between the two earth station shall be 3 meters and that from the building is 2500 mm.
4) An earth ring with relevant earth test terminal boxes shall to be provided at regular
intervals.
5) Adequate number of earth strips with proper sized holes shall be provided for extending
earthing/looping earth connections at various floors shall be provided and executed as per
the requirement.
6) Rate Quoted shall include the 2Bags of (BFC) Back filling compound as required.

7.2 Supply, Unloading, Handling, Installation, testing & commissioning of Chemical Earthing,
equivalent to Ashlok Length 3000mm, 50mm dia electrode, It shall also have provision for
connecting 50 x 10 mm. Copper. Flat on two sides. A masonry structure shall be constructed
to a depth of 750mm.and with 450 x 450 mm (clear) chamber, and a heavy duty Cast Iron
Cover shall be used to cover the pit. Excavation of Hard Rock, Boring, Drilling, backfilling,
removal of excess soil/Rock, supply of Back filling compound is included in the scope
complete as per technical specifications, drawings, relevant standards & site conditions.
Note:
1) All earth pits shall be as per IS 3043 with latest amendments.
2) Earthing stations should contain relevant grade of BFC packed around the earth earth
electrode as called for in the item. Set 10 33,643.00 3,36,430.00
3) Earthing shall be done at indicted location by the Consultants. The minimum distance
between the two earth station shall be 3 meters and that from the building is 2500 mm.
4) An earth ring with relevant earth test terminal boxes shall to be provided at regular
intervals.
5) Adequate number of earth strips with proper sized holes shall be provided for extending
earthing/looping earth connections at various floors shall be provided and executed as per
the requirement.
6) Rate Quoted shall include the 2Bags of (BFC) Back filling compound as required.

7.3 Supply, laying, connection and testing bare earthing conductor for inter-connecting the
earthing stations and various equipment in built up trenches, walls/ceiling, buried in ground
generally as specified and shown on the drawing complete with :

7.3.1 25 mm X 5 mm copper strip Rmt. 1666 1,145.00 19,07,570.00


7.3.2 50 mm X 6 mm copper strip Rmt. 99 3,774.00 3,73,626.00
7.3.3 75 mm x 10 mm thick GI Strip. Rmt. 360 905.00 3,25,800.00
7.3.4 25 mm x 5 mm thick GI Strip. Rmt. 5514 240.00 13,23,360.00
7.3.5 6 SWG Copper wire Rmt. 652 1,751.00 11,41,652.00
7.3.6 50 mm X 6 mm GI strip Rmt. 2100 396.00 8,31,600.00

PART D2_BOQ_COPT,IIT BOMBAY 86 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
7.4 Providing and fixing earth bus of 1metre long 50 mm X 6 mm copper strip with 8nos tapping
holes mounted on insulators & enclosed in IP 42 metal enclosurewith all accessories etc. as Nos 6 4,468.00 26,808.00
required.
7.5 Providing and fixing earth bus of 1metre long 50 mm X 6 mm GI strip with 8nos tapping holes
mounted on insulators & enclosed in IP 42 metal enclosurewith all accessories etc. as Nos 6 2,553.00 15,318.00
required.
TOTAL OF EARTHING SYSTEM 63,73,316.00
8 UPS SYSTEM
8.1 50 KVA UPS with isolation transformer & Maintenance Bypass switch `
8.1.1 Supplying, erecting, testing and commissioning of three-phase continuous duty, on-line,
double conversion, solid-state IGBT based 50KVA UPS 3 PHASE INPUT & 3 PHASE OUTPUT
with reversal protection, Nominal Voltage 415 V AC (3 Ph + N), +/- 15% Frequency 50 Hz Set 1 11,79,210.00 11,79,210.00
Power Factor -  0.99 IGBT Technology. UPS shall be supplied with and neccesary hardwares,
accessories complete
Battery Bank for 30 minutes Back up
8.1.2 Supply, Installation, Testing & Commissioning of Battery bank of SMF batteries Rocket /
Amco / Exide for 30 mins Total Backup time and supply custom made MS rack to suit UPS
room, battery connecting cables etc.
8.2 20 KVA UPS with isolation transformer & Maintenance Bypass switch
8.2.1 Supplying, erecting, testing and commissioning of three-phase continuous duty, on-line,
double conversion, solid-state IGBT based 20KVA UPS 3 PHASE INPUT & 3 PHASE OUTPUT
with reversal protection, Nominal Voltage 415 V AC (3 Ph + N), +/- 15% Frequency 50 Hz Set 1 6,09,500.00 6,09,500.00
Power Factor -  0.99 IGBT Technology. UPS shall be supplied with and neccesary hardwares,
accessories complete
Battery Bank for 30 minutes Back up
8.2.2 Supply, Installation, Testing & Commissioning of Battery bank of SMF batteries Rocket /
Amco / Exide for 30 mins Total Backup time and supply custom made MS rack to suit UPS
room, battery connecting cables etc.
8.3 7.5 KVA UPS with isolation transformer & Maintenance Bypass switch
8.3.1 Supplying, erecting, testing and commissioning of three-phase continuous duty, on-line,
double conversion, solid-state IGBT based 7.5KVA UPS 3 PHASE INPUT & 3 PHASE OUTPUT
with reversal protection, Nominal Voltage 415 V AC (3 Ph + N), +/- 15% Frequency 50 Hz Set 5 4,43,670.00 22,18,350.00
Power Factor -  0.99 IGBT Technology. UPS shall be supplied with and neccesary hardwares,
accessories complete
Battery Bank for 30 minutes Back up
8.3.2 Supply, Installation, Testing & Commissioning of Battery bank of SMF batteries Rocket /
Amco / Exide for 30 mins Total Backup time and supply custom made MS rack to suit UPS
room, battery connecting cables etc.
TOTAL OF UPS SYSTEM 40,07,060.00
9 SAFETY EQUIPMENTS FOR ELECTRICAL INSTALLATION
9.1 Supplying & fixing "Shock Treatment Chart" in English, Hindi, Local languages directly fixed
onto the wall shall be framed in teak wood frame and covered with glass with necessary Nos 14 2,500.00 35,000.00
screws etc.
Supplying and fixing PVC Synthetic elastomer electrically insulating mat with class C insulation
9.2 conforming to IS: 15652 – 2006 & CPRI tested having 3mm thickness , 1000mm wide Role , Mtr 70 3,000.00 2,10,000.00
for upto 11 kV
9.3 Providing & fixing M.V. Danger notice plate of 200 MM X 150 MM made of mild steel, at least
2mm thick, & vitreous enameled whitr on both sides, and with inscription in single red color Nos 40 265.00 10,600.00
on front side as required.
TOTAL OF SAFETY EQUIPMENTS FOR ELECTRICAL INSTALLATION 2,55,600.00
PART VI LOW VOLTAGE SYSTEM
1 DATA NETWORKING AND TELEPHONE SYSTEM
1.1 TELEPHONE SYSTEM
Supply, Installation, Testing and Commissioning of UTP, Categary6 Information outlet (RJ45)
1.1.1 with in-built shutter for protection from Dust for Telephone points workstation end Nos 7 254.00 1,778.00

Supply, Installation, Testing and Commissioning of UTP, Categary6 Information outlet (RJ45)
1.1.2 with in-built shutter for protection from Dust for Telephone points Rack end Nos 7 254.00 1,778.00

1.1.3 Supply, Installation, Testing and Commissioning of UTP, Categary6 LSZH Patch cord, 1 Mtr for
Nos 7 217.00 1,519.00
telephone Patch panel end/rack end
1.1.4 Supply, Installation, Testing and Commissioning of UTP, Categary6 LSZH Patch cord, 2 Mtr for
Nos 7 322.00 2,254.00
telephone Patch panel end/Workstation end
1.1.5 Supplying and installing cat-6 LSZH cable suitable for networking Rmt 168 56.00 9,408.00
1.1.6 Supply, Installation, Testing and Commissioning of 1M/2M port Faceplate including GI back
No. 7 269.00 1,883.00
box of 1M/2M for telephone points to fix Cat6 Information outlet
1.1.7 Supply and Installation of following sizes HMS FRLS PVC conduit concealed in slab / wall or
surface mounted on wall / ceiling, including cost of junction boxes, bends, elbows, sockets,
tees etc. laying in slab, cutting chasis and making good wherever called for or surface
mounted including all fixing hardware as per specification.
1.1.7.1 25 mm dia 2mm thick PVC Conduits Rmt 112 143.00 16,016.00
1.1.8 Supply, Installation, Testing and Commissioning of 24PORT UTP, Categary6 Unloaded patch
panel to accommodate Cat6 UTP information outlet (RJ45) for Telephone points No. 6 2,025.00 12,150.00

1.1.9 Supply, Installation, Testing and Commissioning of 48PORT UTP, Categary6 Unloaded patch
panel to accommodate Cat6 UTP information outlet (RJ45) for Telephone points No. 1 4,434.00 4,434.00

1.1.10 Supply, Installation, Testing and Commissioning of Fiber optic LSZH Patch cord, 3 Mtr- To
No. 14 2,293.00 32,102.00
connect Switch to LIU
PART D2_BOQ_COPT,IIT BOMBAY 87 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
1.2 DATA, WIFI AND Newtorking System
Supply, installation, testing & commissioning of LAN/Wi-Fi system comprising of passive &
active components like CAT-6 UTP or improved data cable, patch panels,racks with wire
manager ,flexible G.I pipe, PVC Conduit HMS variety conforming to IS 9537 Part - III, etc
complete with labeling/identification on the cable ,patch panels etc required as per
standards, drawings and specifications.
1.2.1 Supplying and installing cat-6 LSZH cable suitable for networking Rmt 16690 56.00 9,34,640.00
1.2.2 Supplying, installing, Testing and Commissioning of UTP, Categary6 Information outlet (RJ45)
with in-built shutter for protection from Dust for DATA points workstation end No. 758 254.00 1,92,532.00

1.2.3 Supplying, installing, Testing and Commissioning of UTP, Categary6 Information outlet (RJ45)
with in-built shutter for protection from Dust for Wifi points & Projector points at No. 144 254.00 36,576.00
workstation end
1.2.4 Supply, Installation, Testing and Commissioning of 1 port Faceplate for Data and Wi-Fi points
No. 902 217.00 1,95,734.00
to fix Cat6 Information outlet
1.2.5 Supply, Installation, Testing and Commissioning of UTP, Categary6 Information outlet (RJ45)
with in-built shutter for protection from Dust for Data points Patch panel end No. 758 254.00 1,92,532.00

1.2.6 Supply, Installation, Testing and Commissioning of UTP, Categary6 Information outlet (RJ45)
with in-built shutter for protection from Dust for Wi-Fi points & Projector points Patch panel No. 144 254.00 36,576.00
end
1.2.7 Supply, Installation, Testing and Commissioning of 1M/2M GI Back box required to mount
No. 902 217.00 1,95,734.00
face plate
1.2.8 Supply, Installation, Testing and Commissioning of 24PORT UTP, Categary6 Unloaded patch
panel to accommodate Cat6 UTP information outlet (RJ45) for Data points No. 34 2,025.00 68,850.00

1.2.9 Supply, Installation, Testing and Commissioning of 48PORT UTP, Categary6 Unloaded patch
panel to accommodate Cat6 UTP information outlet (RJ45) for Data points No. 10 3,651.00 36,510.00

1.2.10 Supply, Installation, Testing and Commissioning of UTP, Categary6 LSZH Patch cord, 1 Mtr for
No. 902 276.00 2,48,952.00
Data Patch panel end
1.2.11 Supply, Installation, Testing and Commissioning of UTP, Categary6 LSZH Patch cord, 2 Mtr for
No. 902 343.00 3,09,386.00
Data Workstation end
1.2.12 Supplying and erecting FR grade, pvc armoured multimode optical fibre cable with 6 fibres,
with core dia 50/125 Lm (OM3) on wall/ceiling or laid in provided Cable tray /pipe / trench as Rmt 5331 146.00 7,78,326.00
per drawing & specifications.
1.2.13 Supply, Installation, Testing and Commissioning of Fiber optic LSZH Patch cord, 3 Mtr- To
No. 88 775.00 68,200.00
connect Switch to LIU
1.2.14 12 Port Rack mount Sliding Fibre optic LIU (fully loaded) To be supplied with 6 nos LC Duplex
No. 40 11,719.00 4,68,760.00
Adapter & 12 nos Pigtail 1M LSZH
1.2.15 24 Port Rack mount Sliding Fibre optic LIU (fully loaded) To be supplied with 12 port LC
No. 20 28,434.00 5,68,680.00
Duplex Adapter & 24 nos Pigtail 1M LSZH
Supply and installation of following sizes Floor Mount Network Rack Side Integrated with
Front Glass Door, Rear Mesh Door, Castors, 2 Fans, PDU 6 Soc 5 Amps, Tray , Cable
1.2.16
Manager, Mounting Hardware Pkt Set of 20, depth of rack-600mm

1.2.16.1 Supply, Installation, Testing and Commissioning of 9U Rack. No. 24 11,034.00 2,64,816.00
1.2.16.2 Supply, Installation, Testing and Commissioning of 15U Rack. No. 13 14,229.00 1,84,977.00
1.2.16.3 Supply, Installation, Testing and Commissioning of 22U Rack. No. 2 36,041.00 72,082.00
1.2.16.4 Supply, Installation, Testing and Commissioning of 42U Rack. No. 1 39,483.00 39,483.00
1.2.17 Supply and Installation of following sizes HMS FRLS PVC conduit concealed in slab / wall or
surface mounted on wall / ceiling, including cost of junction boxes, bends, elbows, sockets,
tees etc. laying in slab, cutting chasis and making good wherever called for or surface
mounted including all fixing hardware as per specification.
1.2.17.1 25 mm dia 2mm thick PVC Conduits Rmt 11127 143.00 15,91,161.00
TOTAL OF DATA NETWORKING AND TELEPHONE SYSTEM 65,67,829.00
2 FIRE ALARM SYSTEM
2.1 Supplying, installation, testing and commissioning of micro
processor based Ten loop intelligent addressable main fire alarm panel With Auto dialer,
central processing unit with the following loop modules and capable
of supporting not less than 240 devices (including detectors) and
minimum 120 detectors per loop and loop length up to 2 km, network
communication card, minimum 320 character graphics/ LCD display
with touch screen or other keypad and minimum 4000 events history
log in the non volatile memory (EPROM), power supply unit (230 + 5
Set 1 4,48,883.00 4,48,883.00
% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free
batteries with automatic charger. The panel shall have facility to
connect printer to printout log and facility to have seamless
integration with analog/digital voice evacuation system (which is part
of the schedule of work under SH: PA System) and shall be
complete with all accessories . The panel shall be compatible for
IBMS system with open protocol BACnet/ Modbus over IP complete
as per specifications.
2.2 Supplying, installation, testing & commissioning of central graphical fire alarm management
system to centrally monitor and operate the fire alarm system complete as required. Set 1 1,97,682.00 1,97,682.00

PART D2_BOQ_COPT,IIT BOMBAY 88 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
2.3 Supply, installation, testing & commissioning of Client Workstation as per following
specifications: Intel® Core™ i7 2400 or better ,2.8GHz, OS - Genuine Microsoft Windows 10
Professional or above with Colour Monitor, RAM - 8GB DDR3, 667MHz SDRAM Memory - 1
TB HDD, Graphic Card - Integrated Intel Graphics Media Accelerator (Dedicated 1 GB in case
Set 1 1,59,933.00 1,59,933.00
of video Integration), Two(2) PCI-Express Expansion Slots 2/4 USB, 2 serial, and 2 HDMI/VGA
Adaptor, CD/DVD ROM.; USB Keyboard and Mouse, UPS, associated cables etc complete as
required along with 32' LED monitor.

2.4 Supplying, installation, testing & commissioning of repeater panel with 320 character/Touch
screen LCD display and inbuilt reset, acknowledge and silence switches complete as required. Nos. 7 1,07,101.00 7,49,707.00

2.5 Supplying, installation, testing and commissioning of Intelligent analog Addressable


Nos. 461 2,816.00 12,98,176.00
photothermal detector complete with mounting base as required
2.6 Supply, installation, testing and commissioning of addressable photoelectric type Smoke
Detectors with mounting base, blinking LED etc. surface mounted above false ceiling
Nos. 239 4,012.00 9,58,868.00
complete as required. The detector shall not require any special tool/PC/Software/Dongle to
set address to each device.
2.7 Supplying, installation, testing & commissioning of response indicator on surface/recessed
MS Box having two LED, metallic cover complete with all connections etc as required. Nos. 239 272.00 65,008.00

2.8 Supplying, installation, testing and commissioning of Intelligent analog Addressable


photoelectric type multicriteria detectors complete with mounting base as required Nos. 44 3,100.00 1,36,400.00

2.9 Supplying, installation, testing & commissioning of intelligent addressable thermal detector
with rate of rise cum fixed tempreature thermistor complete with base as required. Nos. 9 2,686.00 24,174.00

2.10 Supplying, installation, testing & commissioning of horn cum strobe complete as required.
Nos. 29 3,455.00 1,00,195.00
2.11 Supplying, installation, testing & commissioning of addressable manual call point complete as
Nos. 29 3,814.00 1,10,606.00
required.
2.12 Supply, Installation,Testing & Commisioning of Analogue Addressable Monitor or input
module. The module shall not require any special tool/PC/Software/Dongle to set address to Nos. 24 3,912.00 93,888.00
each device.
2.13 Supplying, installation, testing & commissioning of fault isolator complete with base as
Nos. 35 3,222.00 1,12,770.00
required.
2.14 Supply, Installation,Testing & Commisioning of Addressable fire Control module complete as
Nos. 29 2,959.00 85,811.00
required.
2.15 Supply, Installation,Testing & Commisioning of 24V DC supply unit with accessories complete.
Nos. 21 56,130.00 11,78,730.00
2.16 Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with
annealed copper conductor having glass mica fire barrier tape covered by an extruded layer
of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel Mtr 5363 354.00 18,98,502.00
wire armouring & LSZH outer sheath complete as required.

TOTAL OF FIRE ALARM SYSTEM 76,19,333.00


3 DIGITAL PUBLIC ADDRESS CUM EMERGENCY VOICE EVACUATION SYSTEM
Supply, Installation, testing & Commissioning of EN 54 Certified, 8 zone Digital Voice Alarm
controller expandable up to 128 zones. Shall support single line switching or redundant
group A/B switching, amplifier redundancy. The Voice alarm controller should also have the
3.1 following functions: Nos 1 3,29,312.00 3,29,312.00
. 100 Priorities
. 8 trigger inputs/outputs
. Should be provided with a Configuration and Graphics User Interface Software.
Supplying, Installation, Testing & Commissioning 1.5/3/6 watt ceiling speaker complete as
3.2 Nos. 324 951.00 3,08,124.00
required
Supplying, Installation, Testing & Commissioning 20 watt Wall mounted speaker complete
with line matching transformer, Effective frequency range 150-15,000Hz ,
3.3 Nos. 7 4,560.00 31,920.00
SPL@1m/1W=86dB, 180 deg dispertion, spring mounting, complete with necessary mounting
hardware & accesories.
Supply, installation, testing and commissioning of EN 54 Certified Call station with keypad
3.4 Nos. 1 4,05,092.00 4,05,092.00
minimum 24 zones capacity.
Supply, installation, testing & commissioning of Rack Mount EN 54 Certified Power Amplifiers
500W with all required accessories etc., complete as per directions of Engineer In charge.
3.5 (OEM to conisder amplifier configuration & quantity sufficient to drive speakers at Full Nos. 4 73,161.00 2,92,644.00
wattage with 20% spare)

3.6 Speaker cable single pair, 2 core , 1.5 sqmm Mtrs. 2711 53.00 1,43,683.00
Supply,laying, testing & comissioning of 25 mm dia Rigid PVC HMC FR conduit including PVC
3.7 junction boxes, couplers, bends etc with all accessories in wall/ceiling/concealed/open Mtrs. 2711 143.00 3,87,673.00
manner.
Supply, installation, testing & commissioning of 24U Prewired rack with provision to mount
controller,amplifier, mains panel with front glass door , rear door field terminations on rear
3.8 Nos. 1 38,833.00 38,833.00
side duly wired, with all required accessories etc.., complete as per directions of Engineer In
charge.
TOTAL OF DIGITAL PUBLIC ADDRESS CUM EMERGENCY VOICE EVACUATION SYSTEM
19,37,281.00
4 CCTV SYSTEM

PART D2_BOQ_COPT,IIT BOMBAY 89 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
4.1 2Megapixel IP IR Dome Camera Supply, Installation, Testing & Commissioning of 2 MP with
4mm fixed lens ,True day/night (IR-cut filter) , UL listed, WDR (120DB) , supports upto 64 GB
SD card, 3DNR, with 15 m (50 ft) viewing distance,Motion, tamper detection,Dyamic
range,Day/night,Electronic shutter,White balance, H.264/H.265, PoE, DC12V/AC24V, ONVIF
Nos. 122 4,888.00 5,96,336.00
profile S & G, Data encryption with all accessories like tamper proof screws, clamps, wiring
etc. to mount the camera should be included as required. Ref Make & model no :- Prama PT-
NC321P3-ISF(D) (4mm) or upgraded version

4.2 5Megapixel IP IR OUtdoor Bullet Network Camera with required outdoor accesories Supply,
Installation, Testing & Commissioning of 5MP 25FPS (2560x1920P) ,Image sensor - 1/2.7 inch
Progressive Scan CMOS, Illumination - Colour: 0.005 Lux @ (F1.6, AGC ON) with 4mm fixed
lens ,True day/night (IR-cut filter) , CE, FCC, UL/BIS, WDR (120DB) , supports upto 256 GB SD
card, 3DNR, with IR Up to 60 m viewing distance,Motion detection, tamper detection, Dyamic
range,Day/night,Electronic shutter,White balance, H.264/H.265, PoE, DC12V/AC24V, ONVIF Nos. 23 12,363.00 2,84,349.00
profile S & G, Three streams, IP67, Data encryption with all accessories like tamper proof
screws, clamps, wiring etc. to mount the camera should be included as required. Ref Make &
model no - Prama -PT-NC35TP3-IUF(D)

4.3 SITC of UL Listed 32 Chs NVR 4K Support, H.265/H.264, 16 Chs PoE, Stream Encryption,
Support Min 10 TB HDD, Min 4 SATA Support , For use as part of video systems which comply
with NDAA Section 889, The TPM (Trusted Platform Module) provides end-to-end stream and
command encryption through integrated cryptographic keys Together cameras, provides an
end-to-end encrypted solution with video streaming and control encrypted between NVR
and web client / viewer / mobile app, ONVIF Profile s, PCI-DSS compliance. Secure boot for
cybersecurity standards to ensure data protection, Supports visual or auditory notifications
Nos. 5 2,38,021.00 11,90,105.00
such as a flashing light, bell, or siren, Events Camera alarm in, (Smart) motion detection,
Video loss, Camera tamper, Intrusion, Multi loitering, Crowd detection, Video recording, Push
message to App, Pop up mesasge to monitor, Send email, Buzzer, FTP, PTZ-Preset, Full
screen, Camera alarm out, System alarm out, Recording Throughput 320, HDMI x 2 (only
HDMI1 support 4 k), VGA x 1 (1080 P), Mbps, -10°C ~ 55°C (14°F ~ 131°F), FCC, ROHS,CE, UL

4.4 SITC of centralized system Software to record, view live footage, playback, manage via the
network or DDNS, 24/7 surveillance with Key functions includes device management, user
management, log management, alarm trigger, E-map with video verification, PTZ Nos. 1 2,03,766.00 2,03,766.00
control,preset, cruise setting, picture capture, instant playback, real time recording and
remote device configuration.
4.5 Supply, Installation, Wiring, Programming of i7 (or latest available at the time of supply) Intel
processor with minimum 1TB HDD (or latest available at the time of supply), 2Gb Graphic
Card, 16 GB RAM, DVD Writer, two serial and one parallel ports, multimedia speakers, Nos. 2 1,55,995.00 3,11,990.00
infrared mouse; Work station shall be preloaded with requisite Licensed MS Windows
Software. Approved
4.6 SITC of Enterprise surveilliance HDD 10 TB for 30 days storage at D1 resolultion. Nos. 16 34,287.00 5,48,592.00
4.7 SITC of 55" LED Monitor 24x7 Application with keyboard & mouse Nos. 6 92,217.00 5,53,302.00
4.8 24 port POE Switch
Nos. 10 50,600.00 5,06,000.00
24-Port Gigabit WebSmart PoE Switch with 24 UTP and 4 SFP Ports.
4.9 Core Switch
Nos. 1 1,38,731.00 1,38,731.00
24 port L2/L3 switch shall support multimode fiber cable
4.10 Patch Panel
Nos. 10 6,564.00 65,640.00
Patch Panel Cat 6 UTP Keystone Type- 24 Port-Fully Loaded.
4.11 Patch Cord
Nos. 290 273.00 79,170.00
Cat-6 patch cord; 1.5/3/6 mtr(For Rack & Camera end).
4.12 Information Outlet
Supply, Installation, Testing and Commissioning of UTP, Categary6 Information outlet (RJ45) Nos 145 254.00 36,830.00
with in-built shutter for protection from Dust for CCTV
4.13 6 Port Rack mount Sliding Fibre optic LIU (fully loaded) To be supplied with 6 port LC Single-
Nos 7 7,238.00 50,666.00
mode Duplex Adapter & 12 nos Pigtails 1M LSZH.
4.14 24 Port Rack mount Sliding Fibre optic LIU (fully loaded) To be supplied with 12 port LC Single-
Nos 2 28,434.00 56,868.00
mode Duplex Adapter & 24 nos Pigtails 1M LSZH.
4.15 Supplying and erecting LSZH armoured multimode optical fibre cable with 6 fibres, with core
dia 50/125 Lm (OM3) suitable for 1 gbps ethernet distance at 850 nm of wavelength, on
Mtr 1337 146.00 1,95,202.00
wall/ceiling or laid in provided pipe/trench/Cable tray as per drawing and specifications.

4.16 Supply, Installation, Testing and Commissioning of UTP, Categary6 Cable, PVC, TIA/EIA
568.C.2 23 AWG solid bare copper with CM rated, UL Listed, ETL verified with Star Filler (No Bi- Mtr 6122 56.00 3,42,832.00
sector Tape)
4.17 Supply, laying, testing and commisioning of 25 mm dia Rigid HMS FR PVC conduit in
Mtr 4082 143.00 5,83,726.00
wall/ceiling/concealed/open manner.
4.18 SITC of 6U 600 mm depth Rack With all accessories Power Manager-2 No, Hardware pocket-1
Pkt and Fan-2 no's,Lock etc.) 1 Cable Managers, 2 - 3 pin power stip with 5 plug points
Nos 7 6,758.00 47,306.00
including CKT Breaker, Door Trims - Sheet steel, powder coated RAL 7037 Viewing area -
Toughened tinted glass.
4.19 SITC of 15U 600 mm depth Rack With all accessories Power Manager-2 No, Hardware pocket-
1 Pkt and Fan-2 no's,Lock etc.) 1 Cable Managers, 2 - 3 pin power stip with 5 plug points
Nos 1 14,229.00 14,229.00
including CKT Breaker, Door Trims - Sheet steel, powder coated RAL 7037 Viewing area -
Toughened tinted glass.
4.20 6inch x6 inch PVC box to install CCTV keeping cables inside Nos. 145 161.00 23,345.00

PART D2_BOQ_COPT,IIT BOMBAY 90 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
4.21 Supply, Installation, Testing and Commissioning of UTP, Fiber optic LSZH Patch cord, 3 Mtr- To
Nos 20 775.00 15,500.00
connect Switch to LIU
4.22 Supply, Installation, Testing and Commissioning of 1M/2M port Faceplate including GI back
Nos 145 269.00 39,005.00
box of 1M/2M for telephone points to fix Cat6 Information outlet
TOTAL OF CCTV SYSTEM 58,83,490.00
5 ACCESS CONTROL SYSTEM
Vingcard RFID Electronic Locking System (Complete)
5.1 Finish: Satin Chrome Nos 33 15,330.00 5,05,890.00
Handle: Straight
5.2 Mechanical Override Lock Cylinder with Key Nos 33 2,996.00 98,868.00
Vingcard Visionline Software system (4 check in station) with RFID Encoder and set of
5.3 Nos 1 1,74,225.00 1,74,225.00
connecting cables
5.4 RFID Cards Nos 500 59.00 29,500.00
5.5 4K Master Cards Nos 5 291.00 1,455.00
Supply Installation Testing & Commissioning of 2 Door (4 Reader) Intelligent Controller with
Built in LAN/Web server, Real-time clock, Dedicated tamper and Power fail alarm, Onoard
Upgradeable flash memory, Reader Compatibility: OSDP:V2 and Standard Wiegand Protocol
supported, 8 Configurable four state supervised Inputs, 4 SPDT relay outputs and 4 Open
Collector Output;Credential Holder capacity: 100,000 and event Buffer capacity: 100,000;
Support Anti Pass back (Global & Local with Hard/Soft implementation), Door Control:
Credential only; Credental and PIN; credential or PIN; PIN only; Lockdown; Disabled;
5.6 Nos 1 60,560.00 60,560.00
Supervisor; Escort; Limited use credential; Expire on date; First Credential Rule; Time Zone
Toggle; 8 Credential formats and 8 site codes, 65000 access levels, 255 holidays and 127 time
zones, Built-in Communication Options: Ethernet; RS-485; USB; CE, FCC and UL294 Listed.
Complete with Cabinet, power supply, mounting bracket, 3-Pin top with 1.5 mts power cable,
4 hrs Battery backup and all necessary accessories & peripheral items for civil, electrical
works as required.

5.7 Time Attendance Module/Software


Supply installation testing & commissioning of web based Time & Attendance software
application supporting multiple sites, Multiple operator login with 3 operator partitioning as
Super User/HR Admin/Normal Use. Various T&A reports such as Attendance details with IN-
5.7.1 Set 1 14,680.00 14,680.00
Out time and total Manhours, overtime, Leave Management, out duty, online leave
application and approval as a minimum.
(Attendance Machine & Software)
5.8 Hardware for Client workstation
Supply, installation, testing & commissioning of Client Workstation with 21 inch Monitor as
per following specifications:Intel® Core™ Intel Core i7-8700, 3.2 GHz, OS - Genuine Microsoft
Windows® 10 Enterprise 64-bit, RAM - 16GB, Hard Drives - 1 TB 7200RPM SATA3, Video
5.8.1 Adaptor - Integrated Intel UHD graphics 630 supporting 2 Monitors over HDMI/VGA, Network Set 1 1,40,185.00 1,40,185.00
Connection - 1 Gbit/sec or greater, Two(2) PCI-Express Expansion Slots 2/4 USB, CD/DVD
ROM, USB Keyboard and Mouse, UPS, associated cables etc complete as required

Supplying, laying & terminations of 8 Core x 0.75 sq MM copper conductor PVC insulated and
5.9 sheathed unarmoured Cable in provided PVC conduit, including all accessories complete. Mtr 20 255.00 5,100.00

Supplying, laying & terminations of 4 Core x 1 Sq mm copper conductor PVC insulated &
5.10 sheathed unarmoured cable in provided PVC conduit, including all accessories complete. Mtr 20 156.00 3,120.00

Supply,laying, testing & comissioning of 25 mm dia Rigid PVC HMC FR conduit including PVC
5.11 junction boxes, couplers, bends etc with all accessories in wall/ceiling/concealed/open Mtr 20 143.00 2,860.00
manner.
TOTAL OF ACCESS CONTROL SYSTEM 10,36,443.00
PART VII DG SET WORKS
1 DG SET AND ALTERNATOR
Supply, Installation, Testing & Commissioning of 320 KVA rating, Standby duty, outdoor
type,silent , acoustically enclosed diesel generating set Radiator water cooled along with day
oil fuel tank as part of enclosure with fuel piping including anti-vibration mounts, spring
isolators, rubber pads, base frame, hardware, Batteries, Engine control panel with
1.1 Each 1 34,08,232.00 34,08,232.00
accessories first fill of lube oil residential silencer, flexible connection bellow / expansion
joints etc. complete and with all associated equipment / work as per specifications
(attached). Along with AMF changeover panel as described below.

Water cooled turbo charged Diesel Generating set with CPCB IV approved acoustic enclosure
, Electric start developing required BHP at 1500 rpm with class A-2 or better, governing to
deliver specified continuous kVA output at 0.8 power factor lag ,The engine shall comply to
IS13018/1990 (reaffirmed 2005) and IS:10,000 series (with latest amendments) Specific fuel
consumption shall be as per IS specification. Make: As per attached list

Fuel tank with air breather and drain plug,


Engine instrument panel consisting of starting switch with key/Password protection, lube oil
temperature and pressure gauges, RPM indicator and hour meter with additional feature of
auto start/remote start and auto stop.
Gives an alarm & trip in case of Low lub oil pressure and high Fresh water temp and high Lub
oil temperature
Safety control to shut down the engine in the event of overspeed, low lube oil pressure and
high engine radiator coolent temperature.

PART D2_BOQ_COPT,IIT BOMBAY 91 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
Lead Acid / semi-maintenance free batteries of suitable ratings with connecting cables. The
batteries shall be supplied dry and in uncharged condition and shall conform to relevant IS.
Only, the following make of batteries shall be accepted.
The fuel level should be indicated with the help of fuel gauge meter
First fill of oil and diesel over & above that required for testing as per contract.
Diesel shall be filled fully in tank after testing & commissioning. Tank shall be of maximum
available capacity from manufacturer
Alternator shall be self excited and self regulated of specified kVA rating in three phases at
415 Volts, 50 Hz, & 0.8 power factor and shall confirm to IS 13364(Part 2)/1992 (reaffirmed
2008). The alternator shall be of brushless type only with VG-2 Grade of voltage regulation.
The alternator shall be screen protected, drip proof with IP21 or better degree of protection
as per IS4691/85 (reaffirmed 2004). It should be suitable for unbalanced loads as per
IS:13364 (Part 2)/1992 (reaffirmed 2008)

DG set controller with GSM/SMS based device for alerts


Controller with remote monitoring software and compatible with BMS systems.
Factory acceptance test will be witnessed by institute representatives. Factory inspection will
be carried out at manufacturer’s premises by 2 engineers from IITB before dispatch.
Contractor to arrange for travel, boarding & lodging if the inspection is to be done outside
MMR region. If within MMR region only transport to be arranged.

12 hours of Load trails at full load and 1 hour of Full Load trails in factory to be carried out.

Make of DG set : List attached


Guarantee/ Warrantee as applicable for IIT Bombay be considered including 2 DLP post
Commissioning
2 Copies of Spare Part catalogue with sources of Supply be provided
4 Copies of Documents - Technical Description, Operating Instructions and Album of
Illustrations in Hard and Soft Copy be provided
Training and Hand holding support to be provided to EMD staff during Commissioning/
Handing Over period
Printed Running Log Books be provided to sustain for 2 year Operation period
2 AMF CONTROL PANEL, WITH CHANGEOVER PANEL
Supply installation, testing & comissioning of AMF control panel shall be able to start the DG
set and transfer the load to DG set on the Mains failure without requiring any human
2.1 intervention. Similarly on restoration of the main supply it shall be able to transfer the load Nos. 1 5,48,550.00 5,48,550.00
to main supply and switch off the DG set automatically

AMF control panel shall be fabricated from steel sheet of 2.0 mm thickness duly pretreated
with 7 tank process and painted with one coat of red oxide and 2 coats of enamel paint of
Admiralty grey colour The control panel shall be outdoor type totally enclosed, dust and
vermin proof, floor mounted type with degree of protection IP-56 as per IS / IEC 60947 (part
1) / 2004., Double door with canopy, vision glass, mounting stand etc. Complete.

The AMF control panel shall consist of the following instruments;


a) Microprocessor based AMF relay.
b) Multifunction meter (load manager).
c) AC voltmeter(s) of class 1.0 accuracy 0-500 volts with selector switch for reading L-L as well
as phase voltage. Separate voltmeter shall be provided for mains and alternator.

d) AC ammeter of class 1.0 accuracy and of suitable range with selector switch for reading L-L
as well as phase voltage.
e) Mode selector switch for setting the panel on any one position such as off or manual or
auto or test
f) Engine On-off switch push button
g) HRC fuses of suitable ratings
h) Rectangular electrolitic copper bus bar (one number for each phase neutral and earthing
terminal) of adequate rating (1.6A/mm2, phase & neutral of same size, earthing bus bar for
30kA short circuit level) duly colour coated with heat shrinkable PVC sleeves.

i) Two numbers of 400A FP power contactors (one for Mains and one for Generator)

ii) Two numbers of 400Amp, Icu=Ics=50kA, 4 pole MCCB with neutral link manually operated
as Incoming.
iii) one numbers of 400Amp, Icu=Ics=50kA, 3 pole MCCB with neutral link manually operated
for outgoing.
j) Under voltage relay for mains
k) Three attempts engine start / engine cranking relay
l) On delay timer for load change over
m) On delay timer for engine shut off
n) Pilot lamps three numbers for 3 phase DG sets
o) Battery charger complete with voltage regulator, float or booster selector switch, on-off
switch, voltmeter and ammeter for charging the battery from mains. This will be in addition
to the battery charging alternator fitted on the engine.

p) Instruments and controls fuses 6 numbers power fuses of suitable rating


q) 5 numbers indicating lamps to indicate mains low voltage, load on mains, DG set running,
load on set and battery charger ON.

PART D2_BOQ_COPT,IIT BOMBAY 92 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
r) Audio visual alarm for mains & DG breaker trip, main LVM, DG LVM, Emergency stop, DG
fault may be provided (All electrical and mechanical alarms and trips to be included).

s) Make of AMF panel/components: List attached & IF AMF Panel proposed with ATS, Asco
make to be considered for ATS
t) All control cables required with termination from AMF panel to DG set, within AMF panel,
and controller.
u) Foundation of AMF panel & DG Set (done as per approval from structural consultant/ DG
manufacturer)
v) DG is to be provided with an In-built remote monitoring arrangement

3 STATUTORY APPROVALS
Electrical Inspector's Approval/CEIG from PWD-Liasion charges for obtaining approval of
Statutory authorities. Required clearances from the concerned statutory authorities are in
the scope of work: Preparation and submission of drawing to electrical inspector (CEA) and Job 1 51,750.00 51,750.00
obtaining approval of electrical inspector. Inspection Fees (receipt to be submitted to IITB)

Approval from Local Pollution Control Board


4 EXHAUST PIPING
Providing, fixing & installing MS class-B exhaust pipe/ silencer 6" dia (for 320 kVA DG set &
approx 2 mtrs of vertical run for standalone outdoor installation) and all necessary supports
fixing accessories and hardwares , The exhaust pipes be insulated with 75 mm thick mineral
wool (density 150Kg/m3) insulation wrapped in chicken mesh and clad with 26gauge Set 1 7,021.00 7,021.00
aluminum sheet including all hot dip galvanized structural support as required. Shall be
protected from water entering in pipe by providing elbow and damper.

5 EARTHING
Rates shall also include the following
1 . All fixing accessories such as brass saddles, brass screws, wall plugs etc
2. Joints by rivetting and brazing after rivetting in case of copper and by welding or bolting
for GI.
3. Cutting chases holes and making good the same wherever required.
4. Effecting adequate and power interconnections.
5. Use of copper thimbles.
6. Earthing system shall comply to IS:3043-1987
7. All earthing pits shall be interconnected.
8. All equipment motors, DB's, panels to be connected on either ends (double earthing) with
suitable strip/wires.
Supply and fixing of following bare copper strips / GI Strips/ wires including all necessary
fixing accessories and effecting connections as per specifications.
5.1 50 x 6 mm thick GI strip (for DG body earthing) Rmt 22 396.00 8,712.00
5.2 50 x 6 mm thick GI Strip (for DG neutral earthing) Rmt 22 396.00 8,712.00
Supply, Unloading, Handling, Installation, testing & commissioning of Chemical Earthing,
equivalent to Ashlok Lenght 3000mm, 50mm dia electrode, It shall also have provision for
connecting 50 x 10 mm. Copper. Flat on two sides. A masonry structure shall be constructed
to a depth of 750mm.and with 450 x 450 mm (clear) chamber, and a heavy duty Cast Iron
Cover shall be used to cover the pit. Excavation of Hard Rock, Boring, Drilling, backfilling,
removal of excess soil/Rock, supply of Back filling compound is included in the scope
complete as per technical specifications, drawings, relevant standards & site conditions.
Note:
1) All earth pits shall be as per IS 3043 with latest amendments.
2) Earthing stations should contain relevant grade of BFC packed around the earth earth
5.3 electrode as called for in the item. Nos. 4 33,643.00 1,34,572.00
3) Earthing shall be done at indicted location by the Consultants. The minimum distance
between the two earth station shall be 3 meters and that from the building is 2500 mm.
4) An earth ring with relevant earth test terminal boxes shall to be provided at regular
intervals.
5) Adequate number of earth strips with proper sized holes shall be provided for extending
earthing/looping earth connections at various floors shall be provided and executed as per
the requirement.
6) Rate Quoted shall include the 2Bags of (BFC) Back filling compound as required.

6 CABLES, TERMINATIONS AND RCC PIPES


The rate shall also include the following
Providing all accessories such as clamping devices nuts bolts and screws
Wherever the cables are of aluminium and bus bars of copper bimetallic lugs shall be used

All cables shall be laid with one diameter gap


All cables shall be IS approved
Double compression glands
Fire retardant paint 1 metre on both side of wall penetration and at termination as per
specifications
Buried LT cables to be laid in hume pipes.
Supplying and laying of the following sizes Al.Cable 1100V XLPE insulated, FRLS PVC outer
sheathed & flat galvanised (strip) armoured cable and Laying in hume pipe provided,
6.1
existing trench saddling on wall with 25X3mm GI strip/ clamp with SS screws, nut bolts as
directed.
6.1.1 3.5 core X 185 sq mm Al armoured cable Rmt 160 1,021.00 1,63,360.00
PART D2_BOQ_COPT,IIT BOMBAY 93 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
6.1.2 4 core 2.5 sq.mm control cable- Copper Armoured Cable Rmt 80 383.00 30,640.00
6.1.3 4 core 2.5 sq.mm control cable - Copper Armoured Cable Rmt 80 383.00 30,640.00
Providing & laying non pressure NP2 class (light duty) RCC pipe with collars jointed with stiff
6.2 mixture of cement mortar in the propotion of 1:2 (1 cement: 2fine sand) including testing of
joint etc.
6.2.1 200mm Dia. Rmt 150 799.00 1,19,850.00
Cable end termination of the following XLPE / PVC core insulated FRLS PVC outer sheathed
aluminum/Copper conductor armoured cables of 1100 volt grade including supply and fixing
6.3 of double compression metallic brass glands with earthing heavy duty bimetallic, crimping
type terminal lugs wherever Aluminium conductor cables are used & Copper terminal lugs to
be used for copper cable
6.3.1 3.5 core x 185 sq mm Aluminium cable Nos. 8 1,346.00 10,768.00
6.3.2 4 core 2.5 sq.mm control cable Nos. 2 383.00 766.00
6.3.3 4 core 2.5 sq.mm control cable Nos. 2 383.00 766.00
7 RUBBER MATTING AND FIRE BUCKETS
7.1 Supply and fixing in position rubber matting of 11 KV grade as per electricity rules. Set 1 3,000.00 3,000.00
Supply of five fire bucket duly filled with fine sand and fixed on an angle iron frame as per the
requirement of local authorities.
Galvanised mild steel Fire bucket with clean sand & stand in accordance with IS 2546. Fire
bucket shall have two coats of anti corrosive paint, two coats of red colour conforming to
shade No. 536 or 538 of IS 5. The paint shall conform to IS 2932 on its outside & two coats of
7.2 white paint on the inside. The word "FIRE" shall be clearly stencilled on it in accordance with Set 1 31,913.00 31,913.00
IS 2546. Vendor to include in his quote all costs relating to mounting of the bucket at
locations stated by the Fire NOC & the architect. Vendor to include in his quote all costs all
accessories, consumables, fittings & rigging equipments necessary for the satisfactory
installation of the same

TOTAL OF DG SET WORKS 45,59,252.00


PART VIII LIFTS
1 FREIGHT LIFT
Supplying, installation, testing and commissioning of 2500 Kg Freight lift having stainless
steel enclosure with SS 304 Moon rock finish with contract speed of 1 mps to serve G +6 ( 7
1.1
floors) with machine room as per detailed specifications mentioned below:-

Location of Lifts : Centre of Populsion Technology at IIT Bombay


Type of lift : Freight Lift Nos. 1 50,79,588.00 50,79,588.00
Number of person & load : 2500 kg
Contract Speed:- : 1 mtr per sec
Travel in metre (Approx) : As per the drawings
Number of Floors served : 7 floors (G + 6)
PIT Depth : As per the drawings
Overhead : As per the drawings
Position of the machinary : Directly above the lift shaft.
Type of Controller : Microprosseror based AC VVVF
Type of Operation: : Microprocessor based Simplex selective
collective with/without attendent.
Machine: : Permanent magnet gearless motor with
regenerative drive
BMS Compatibility: - Potential free contacts/ RS 485/Modbus/ BACNet card in the controller
shall be provided for monitoring position, up and down movement of the lift etc which can
be used for building automation system at later stage.
Car entrance door size
Minimum opening - 2200 mm (H) x 1700 mm (W)
SS doors with SS Honeycomb finish
Type of door - Power operated horizontal sliding centre opening doors
Car open in front only : Yes
Fire resistance rating : Minimum 1 Hr Fire Rated
Shaft Size : 3100mm (Length) x 3100mm (W)
Lift Car
a) Inside car size : To be given to suit to available lift shaft.
b) Interior finish :
i) Panel : Shall be Stainless Steel of SS 304 doors with SS Honeycomb finish
ii) Flooring : Aluminum chequered plate
iii)Ceiling Finish: Shall be Stainless Steel of SS 304 mirror finish
iv) Lighting : Shall be ‘LED’ lights in recess
v) Ventilation : Shall be cross flow blower / fan with louver with at least 2 Nos. fans in recess.

Type of signal system


i) Digital floor position indicator in the car and at all landings TFT/LED type.
ii) Detailed Travel direction indicator in the car and at all landings (to be provided above the
car /landing Doors)
iii) Gongs and visual indication on all landing for the arrival of the car
iv) Overload Warning audio and Visual Indicator inside the car (lift should not start on
overload)
v) Battery operated alarm bell and Emergency light
vi) Car Operating Panel with Luminous Buttons and 3-way Intercom with (Vandal Proof
Covers)
vii) Luminous hall Buttons at all landings and inside car with Braille language signage.

PART D2_BOQ_COPT,IIT BOMBAY 94 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
viii) Firemen’s switch at ground floor
ix) Display inside the car shall be ‘TFT/LED’ type with time and date indication.
x) Floor announcement in the car.
xi) Lift in use / lift out of order sign: lift out of order indication shall be in-built with floor
position indicator.
xii) Power supply : 400/415 V, 3 phase AC, 50 Hz,4 wire System.
xiii) Auxiliary power Supply :230 V, +5% to -10% , 50 Hz AC supply
xiv) The entire lift equipment should be suitable for operation at +5% to -10% of the rated
supply voltage
Leveling accuracy : + / - 5 mm at all load conditions.
Speed variation : + / - 10% of the rated speed.
Counter weight : Cast iron fillers fitted in steel channel frame of size and numbers as per
manufacturers standred
Car and counter weight guide rails : Machined guide rails of suitable size and fish plates.

Hand rail - Hand rail shall be provided at 900 mm inside lift.


Emergency supply
i) Inverter backup with trickle/boost charges arrangement for at least 30 minutes with
maintenance free batteries for emergency light, alarm bell and inter-com system

ii) An automatic rescue device in case of mains failure shall be provided.


Door Close Safety : Full height Infrared light curtain door safety.
COP : Suitable for physically challenge person with braille encrypt car button. - 2 nos. in
either side with SS 304 Honeycomb finish, Vandal proof.
Firemen switch for the fire lift shall be provided at ground floor to enable the fire service
personnel to ground the lift in case of emergency .
Intercom: The 3 way intercom system provided in the lift car has to be hands free and with
lifting cradle in the machine room and Control room with telephone /intercom wiring shall
be provided. Pocket provision shall be made inside the car to provide IITB intercom flush to
car which will be connected to IITB EPABX system.

Automatic rescue device


a) ARD should monitor the normal power supply in the main controller and shall activate
rescue operations within ten seconds of normal power supply failure. It should bring the
elevator to the nearest floor at a slower speed than the normal run. While proceeding to the
nearest floor the elevator will detect the zone and stop. After the elevator has stopped, it
automatically opens the doors and parks with door open. After the operation is completed
by the ARD the elevator is automatically switched over to normal operation as soon as
normal power supply resumes.

b) In case the normal supply resumes during ARD in operation the elevator will continue to
run in ARD mode until it reaches the nearest landing and the doors are fully opened. If
normal power supply resumes when the elevator is at the landing it will automatically be
switched to normal power operation.
c) All the lift safeties shall remain active during the ARD mode of operation.
d) The battery capacity should be adequate so as to operate the ARD at least Seven times a
day. Provided the duration between usages is at least 30 miniutes.
Voice announcement system in the car to announce the position of the elevator as the car
stops at a floor served by the elevator
Transmission : Steel ropes/belts
Hall Fixture: TFT /LED position indicators with physically challenge person friendly
Direction & position indicator : large display TFT/LED car position indicator in top of the lift
door
Standard features: Anti- nuisance car call protection, independent service, overload device,
Nudging, Emergency firemen’s service , Emergency car light unit, infrared curtain door
protection, door time protection, emergency alarm button, extra door time of lobby and
parking, door open/close button, manual rescue operation, auto fan cut off shall be
Provided.
The DLP period/warantee should be 2 years (24 months ) from the date of taking over by the
department.
Please refer attached specifications for lifts.
TOTAL OF FREIGHT LIFT 50,79,588.00
2 PASSENGER LIFTS
2.1 Supplying, installation, testing and commissioning of 20 passenger (1360 kg) lifts having
stainless steel enclosure of SS 304 with Honey comb finish, contract speed of 1.5 mps to
Nos. 2 29,97,309.00 59,94,618.00
serve G + 6 ( 7 floors) with machine room as per detailed specifications mentioned below:-

Location of Lifts : Centre of Populsion Technology at IIT Bombay


Type of lift : Passenger lift
Number of person & load : 20 passenger- 1360 kg
Contract Speed : 1.5 mtr per sec
Travel in metre (Approx) : As per the drawings
Number of Floors served : 7 floors (G + 6)
PIT Depth : As per the drawings
Overhead : As per the drawings
Position of the machinary : Directly above the lift shaft.
Type of Controller : Microprosseror based AC VVVF
Type of Operation: : Microprocessor based Duplex selective
collective with/without attendent
PART D2_BOQ_COPT,IIT BOMBAY 95 of 92
Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
Machine: : Permanent magnet gearless motor with
regenerative drive
BMS Compatibility: - Potential free contacts/ RS 485/Modbus/ BACNet card in the controller
shall be provided for monitoring position, up and down movement of the lift etc which can
be used for building automation system at later stage.
Car entrance door Size
Minimum opening - 2100 mm (H) x 1000 mm (W)
SS doors with SS Honeycomb finish
Type of door :Power operated horizontal sliding centre opening doors
Car open in front only : Yes
Fire resistance rating : Minimum 1 Hr Fire Rated
Shaft Size : 2860mm (Length) x 2400mm (W)
Lift Car
a) Inside car size : To be given to suit to available lift shaft.
b) Interior finish :
i) Panel : Shall be Stainless Steel of SS 304 with Honeycomb finish
ii) Flooring : Minimum 25 mm thick Granite flooring.
iii)Ceiling Finish: Shall be Stainless Steel of SS 304 with Mirror finish.
iv) Lighting : Shall be ‘LED’ lights in recess
v) Ventilation : Shall be cross flow blower / fan with louver with at least 2 Nos. fans in recess.

Type of signal system


i) Digital floor position indicator in the car and at all landings TFT/LED type.
ii) Detailed Travel direction indicator in the car and at all landings (to be provided above the
car /landing Doors)
iii) Gongs and visual indication on all landing for the arrival of the car
iv) Overload Warning audio and Visual Indicator inside the car (lift should not start on
overload)
v) Battery operated alarm bell and Emergency light
vi) Car Operating Panel with Luminous Buttons and 3-way Intercom with (Vandal Proof
Covers)
vii) Luminous hall Buttons at all landings and inside car with Braille language signage.

viii) Firemen’s switch at ground floor


ix) Display inside the car shall be ‘TFT\LED' type with time and date indication.
x) Floor announcement in the car.
xi) Lift in use / lift out of order sign: lift out of order indication shall be in-built with floor
position indicator.
xii) Power supply : 400/415 V, 3 phase AC, 50 Hz,4 wire System.
xiii) Auxiliary power Supply :230 V, +5% to -10% , 50 Hz AC supply
xiv) The entire lift equipment should be suitable for operation at +5% to -10% of the rated
supply voltage
Leveling accuracy : + / - 5 mm at all load conditions.
Speed variation : + / - 10% of the rated speed.
Counter weight : Cast iron fillers fitted in steel channel frame of size and numbers as per
manufacturers standred
Car and counter weight guide rails : Machined guide rails of suitable size and fish plates.

Emergency supply
i) Inverter backup with trickle/boost charges arrangement for at least 30 minutes with
maintenance free batteries for emergency light, alarm bell and inter-com system

ii) An automatic rescue device in case of mains failure shall be provided.


Door Close Safety : Full height Infrared light curtain door safety.
COP: Suitable for physically challenge person with braille encrypt car button. - 2 nos. in either
side with SS 304 hairline finish, Vandal proof.
Firemen lift
i. Designated Lifts shall be used as fire lifts.
ii. Firemen switch for the fire lift shall be provided at ground floor to enable the fire service
personnel to ground the lift in case of emergency .
iii. The word ‘fire lift’ shall be Conspicuously displayed in fluorescent paint on all the fire lifts
landing doors at ground floor .
Intercom: The 3 way intercom system provided in the lift car has to be hands free and with
lifting cradle in the machine room and Control room with telephone /intercom wiring shall
be provided. Pocket provision shall be made inside the car to provide IITB intercom flush to
car which will be connected to IITB EPABX system.

Automatic rescue device


a) ARD should monitor the normal power supply in the main controller and shall activate
rescue operations within ten seconds of normal power supply failure. It should bring the
elevator to the nearest floor at a slower speed than the normal run. While proceeding to the
nearest floor the elevator will detect the zone and stop. After the elevator has stopped, it
automatically opens the doors and parks with door open. After the operation is completed
by the ARD the elevator is automatically switched over to normal operation as soon as
normal power supply resumes.

PART D2_BOQ_COPT,IIT BOMBAY 96 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
b) In case the normal supply resumes during ARD in operation the elevator will continue to
run in ARD mode until it reaches the nearest landing and the doors are fully opened. If
normal power supply resumes when the elevator is at the landing it will automatically be
switched to normal power operation.
c) All the lift safeties shall remain active during the ARD mode of operation.
d) The battery capacity should be adequate so as to operate the ARD at least Seven times a
day. Provided the duration between usages is at least 30 miniutes.
Voice announcement system in the car to announce the position of the elevator as the car
stops at a floor served by the elevator
Hand rail:- At 900 mm above floor level on all sides adjacent COP
Machine: Permanent magnet gearless motor with regenerative drive
Provision of mirror shall be made inside the car on rear side.
Transmission : Steel ropes/belts
Hall Fixture: TFT /LED position indicators with physically challenge person friendly
Direction & position indicator : large display TFT/LED car position indicator in top of the lift
door
Standard features: Anti- nuisance car call protection, independent service, overload device,
Nudging, Emergency firemen’s service , Emergency car light unit, infrared curtain door
protection, door time protection, emergency alarm button, extra door time of lobby and
parking, door open/close button, manual rescue operation, auto fan cut off shall be
Provided.
The DLP period/warantee should be 2 years (24 months ) from the date of taking over by the
department.
Please refer attached specifications for lifts.
TOTAL OF PASSENGER LIFTS 59,94,618.00
IX FURNITURE WORKS
A LOOSE / CUSTOM MADE FURNITURE
Note:
1. The specifications provided below for modular furniture and storage units are the broad
specifications.
2. Before taking up the work under this subhead, the contractor shall get the series and make
of the modular furniture approved from the EIC .
3. Before proposing any make and series, the contractor shall ensure that the same meet the
functional requirement and specifications as specified under this subhead for the respective
of item of work.

4. The furnitures are required to place at several floors & locations as per layout / drawings
and directions of Engineer-in-Charge.
5. All furnitures shall be fully Knock Down with joineries made up of metal inserts wherever
required.
6. All Particle boards / MDF Board shall be of E-1 Grade.

7. Approved Makes:
7.1. All type of chairs : Godrej,HNI, Rockworth, Steelcase, Featheralite, Spacewood
7.2. Rest of the furniture: Godrej,HNI, Rockworth, Steelcase, Featheralite, Spacewood
8. Loose furniture vendor to co-ordinate with Electrical and other agencies wherever
required while installation/placement of furniture.
9. Refer General Arrangement furniture Layout drawings for understanding the location of
items.

9.1 Providing & placing VIP Lounge chair as per indicative image. Chair should have cushioned
back & cushioned seat assembly made up of twin shell plywood and upholstered with
moulded polyurethane foam & synthetic Leather.
Back size:550- 600mm (W), 750 - 800 mm (H), Nos. 12 14,200.00 1,70,400.00
The understructure is made up of MS powder coated tubes.
The chair Swivels at 360 degree to sensibly allows comfortable ingress/egrees. Type -
CH01
9.2 Providing & placing Single/Two/Three seater Sofa as per indicative image. Understructure of
sofa to be fabricated using good quality hardwood & 12mm thk commercial plywood.
Double Webbing with spring and nylon belt shall be placed on Understucture. seat is made
up of slab stack foam with density of 32kg/cum & having minimum thickness of foam
100mm. The back & side should be made up of Recron with thickness of 100 to 150mm. The
legs shall be made up of PVC/S.S. . Sofa to be fully upholstered using approved combination
of leatherite with thickness of 1mm and Leather with thickness of 1.00mm of desired shade
and colour including providing and fixing of all other related required materials including
hardwares etc. complete as per indicative image and as directed by the Engineer-in-Charge

Frame : The sofa’s frame is made from solid, sustainable T.W. wood and commercial ply (IS-
303)
Upholstery: Fabric upholstered cushions and seat
Base-frame: 40x20x2mm thk MS
Base frame finish: Powder coating (black)
9.2.1 Single seater sofa of Overall Size : 800 mm plus minus 50 mm(L), Depth : 800mm plus minus
50 mm,Height : 800 mm plus minus 50 mm with approved leatherite Nos. 20 18,150.00 3,63,000.00
Location : Ground floor and all Waiting area Type - SF01

PART D2_BOQ_COPT,IIT BOMBAY 97 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
9.2.2 Two seater sofa of Overall Size : 1400 mm plus minus 50 mm(L), Depth : 920mm plus minus
50 mm,Height : 890mm plus minus 50 mm with approved leatherite Nos. 2 25,750.00 51,500.00
Location : Ground floor waiting Type - SF02
9.3 Providing & placing Single/Two/Three seater Sofa as per indicative image. Understructure of
sofa to be fabricated using good quality hardwood & 12mm thk commercial PLY. Double
Webbing with spring and nylon belt shall be placed on Understucture. seat is made up of slab
stack foam with density of 32kg/cum & having minimum thickness of foam 100mm. The back
& side should be made up of Recron with thickness of 100 to 150mm. The legs shall be made
up of PVC. Sofa to be fully upholstered using approved leatherite with thickness of 1mm of
desired shade and colour including providing and fixing of all other related required materials
including hardwares etc. complete as per indicative image and as directed by the Engineer-in-
Charge 3D woven fabric upholstered on slab stock cushions with tropical hardwood under
structure and rubberwood legs.

9.3.1 Single seater sofa of Overall Size :850 mm plus minus 50 mm(L), Depth :850mm plus minus
50 mm,Height : 800mm plus minus 50 mm with approved leatherite Nos. 3 19,150.00 57,450.00
Location : Director's Cabin Type - SF04
9.3.2 Three seater sofa of Overall Size :2100 mm plus minus 50 mm(L), Depth :830mm plus minus
50 mm,Height : 820mm plus minus 50 mm with approved leatherite Nos. 1 37,650.00 37,650.00
Location : Director's Cabin Type - SF05
9.4 Providing & placing Single/Two/Three seater Sofa as per indicative image. Understructure of
sofa to be fabricated using good quality hardwood & 12mm thk commercial PLY. Double
Webbing with spring and nylon belt shall be placed on Understucture. seat is made up of slab
stack foam with density of 32kg/cum & having minimum thickness of foam 100mm. The back
& side should be made up of Recron with thickness of 100 to 150mm. The legs shall be made
up of PVC. . Sofa to be fully upholstered using approved fabric of desired shade and colour
including providing and fixing of all other related required materials including hardwares etc.
complete as per indicative image and as directed by the Engineer-in-Charge 3D woven fabric
upholstered on slab stock cushions with tropical hardwood under structure and rubberwood
legs.

9.4.1 Single seater sofa of Overall Size :800 mm plus minus 50 mm(L), Depth :800mm plus minus
50 mm,Height : 800mm plus minus 50 mm with 3D woven fabric upholstered on slab stock
cushions Nos. 10 15,500.00 1,55,000.00
Location : Faculty Lounge & Students' Lounge at 3rd Lounge
Type - SF06
9.4.2 Three seater sofa of Overall Size :2100 mm plus minus 50 mm(L), Depth :800mm plus minus
50 mm,Height : 800mm plus minus 50 mm with 3D woven fabric upholstered on slab stock
Nos. 1 25,750.00 25,750.00
cushions
Location : Faculty Lounge at 3rd floor Type - SF07
9.5 Supplying and installation of Corner/ Side/ Centre Tables/ End table of size 500x 500 x
475mm as per indicative image. The structure of table shall be made up of SS 304 12 mm
solid pipe buffed and polished / Wooden legs out of BTC 45mm dia at the top tapering to
25mm dia at the bottom including PVC buffer, matt PU polish finish so as to give proper
finish. The table top shall be provided with 12 mm thick plain clear Toughened glass, edges
Nos. 27 4,650.00 1,25,550.00
suitably bevelled and polished and UV glued with bushes made in SS 304 grade for focing
with understructure and other related materials, including all required hardwares etc.
complete in all respect and as directed .
Location : As indicated on drawings. Type - T01

9.6 Supplying and installation of Coffee table/Centre Tables/end table of size 350mm DIA X 475
MM height as per indicative image. The structure of table shall be made up of SS 304 12 mm
solid pipe buffed and polished / Wooden legs out of BTC 45mm dia at the top tapering to
25mm dia at the bottom including PVC buffer, matt PU polish finish so as to give proper
finish. The table top shall be provided with 12 mm thick plain clear Toughened glass, edges
Nos. 14 4,650.00 65,100.00
suitably bevelled and polished and UV glued with bushes made in SS 304 grade for focing
with understructure and other related materials, including all required hardwares etc.
complete in all respect and as directed.
Location : As indicated on drawings Type - T02

9.7 Supplying and installation of Centre Tables of size 900x 500 x 450mm & shall be of as per
indicative image mentioned in the tender documents. The structure of table shall be made
up of SS 304 12 mm solid pipe buffed and polished / Wooden legs out of BTC 45mm dia at
the top tapering to 25mm dia at the bottom including PVC buffer, matt PU polish finish so as
to give proper finish. The table top shall be provided with 12 mm thick plain clear Toughened
glass, edges suitably bevelled and polished and UV glued with bushes made in SS 304 grade Nos. 7 5,150.00 36,050.00
for focing with understructure and other related materials, including all required hardwares
etc. complete in all respect and as directed by the Engineer-in- Charge.

Location : As indicated on drawings Type - T03

PART D2_BOQ_COPT,IIT BOMBAY 98 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
9.8 Supplying and installation of Centre Tables/end table of size 500x 500 x 450mm as per
indicative image. The structure of table shall be made up of SS 304 12 mm solid pipe buffed
and polished / Wooden legs out of BTC 45mm dia at the top tapering to 25mm dia at the
bottom including PVC buffer, matt PU polish finish so as to give proper finish. The table top
shall be provided with 12 mm thick plain clear Toughened glass, edges suitably bevelled and
Nos. 3 4,650.00 13,950.00
polished and UV glued with bushes made in SS 304 grade for focing with understructure and
other related materials, including all required hardwares etc. complete in all respect and as
directed by the Engineer-in- Charge.
Location : As indicated on drawings Type - T04

9.9 Supply , assembly and complete installation, levelling positioning as required and approved
by EIC, tables / workstations and accessories of following approved makes of given
description
9.9.1 Providing and fixing at all floors and locations modular fully knockdown workstation with
discussion table as per indicative image, 50-60 mm thk. and 1200mm high. panel based work
station partition with flexible construction offering various functional and decorative finishes
as well as cable management capacity. All trims made of aluminium extrusions. Blocks made
out of a composite construction of MDF and paper honeycomb.Panel Blocks made of Fabric
Tackable , white board and Glass as per design and pattern selected by engineer in charge
Nos. 25 74,360.00 18,59,000.00
(All the combinations/ some of the combinations may be used as per selection).Tiles should
be slide in to the panels from top before fixing the top horizontal. These tiles should be
supported from top & bottom side with clips made from PP co polymer fitted in horizontal
extrusion. Bottom tile and leg made of Mild steel
Type - T05

with epoxy powder coated.Fabricated bottom frame as a welded structure of steel


components. The panels and worktops are supported with MS legs with levelers at various
locations depending on the layout requirements. Worktop: Work top shall be made of 25mm
thick Pre laminated particle board interior grade of approved Architect shade conforming to
IS: 12823. Bottom shall have a backing laminate of minimum 0.6 mm thickness. All the edges
of work surface shall be provided with machine pressed 2 mm thick PVC lipping. Fabric
magnetic tiles are fabric upholstered metal tiles in 0.6 mm thick G.I. Grade, Fabric tack tiles
are fabric upholstered metal tiles in 0.6 mm thick G.I. Grade, with P.E. Foam in the tile for
tack ability, White board tiles are made of 8.0 mm thick particle board laminated with 0.6mm
thick white glossy high pressure laminate on outer side & 0.6mm backing laminate on inner
surface and

having all its edges with minimum 0.5 mm thick PVC edging, Glass tiles 4 mm thick toughened
clear glass is fitted onto both sides of the panel using horizontal and vertical stiffeners made
from 0.6 mm powder coated CRCA steel Grade D as per IS: 513. Plain Metal tiles are made of
0.6 mm thick M.S. CRCA Grade D as per IS: 513 powder coated with Epoxy- Polyester finish.
The groument cap shall be provided for each seat. The panel based workstation shall have
cable management system thought the work panels. Note : The work station is to be
provided in various C shape, L shape, plus shape etc.as per space availibilty, layout
requirement and direction of engineer in charge.For the purpose of payment only number of
seat of size 1500x1800x 600mm, 750mm high shall be measured for payment. Each seat shall
be provided with metal pedstal with castors, and keyboard tray as follows:

Pedestal unit 3 drawer free standing pedastal unit "400Wx550Dx700H" made out 0.8mm th
CRCA sheet for body shell, drawer tray, front & rear side stiffner. Top & bottom stiffner shall
be of 1.2mm thk. All slides shall be with double extension precision ball slide. Drawers to be
without handles for clean finish. For drawer pulling, side wise tapered recess shall be
provided in shell behind drawer fronts. 10 lever cam lock & central locking with actuator &
lock channel mechanism shall be provided. Metal finish to be in epoxy polyster power
coating of 40 to 50 microns. All complete as per drawing and direction of Engineer in charge.
Keyboard pull out tray of size 230mm W -345mm W X 226mm D X 180mm H (+/- 10mm
tolerance for all dimensions) Metal Tray with mouse tray to be provided on Right hand side
or Left hand side as per requirement. Mouse tray size 210w x 210w all complete as per
drawing and direction of Engineer in charge.

9.9.2 Providing and fixing at all floors and locations modular fully knockdown workstation as per
indicative image, 50-60 mm thk. and 1200mm high. panel based work station partition with
flexible construction offering various functional and decorative finishes as well as cable
management capacity. All trims made of aluminium extrusions. Blocks made out of a
composite construction of MDF and paper honeycomb.Panel Blocks made of Fabric Tackable
, white board and Glass as per design and pattern selected by engineer in charge (All the
Nos. 136.00 32,550.00 44,26,800.00
combinations/ some of the combinations may be used as per selection).Tiles should be slid in
to the panels from top before fixing the top horizontal. These tiles should be supported from
top & bottom side with clips made from PP co polymer fitted in horizontal extrusion. Bottom
tile and leg made of Mild steel with epoxy powder coated.

PART D2_BOQ_COPT,IIT BOMBAY 99 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
Fabricated bottom frame as a welded structure of steel components. The panels and
worktops are supported with MS legs with levelers at various locations depending on the
layout requirements. Worktop: Work top shall be made of 25mm thick Pre laminated particle
board interior grade of approved Architect shade conforming to IS: 12823. Bottom shall have
a backing laminate of minimum 0.6 mm thickness. All the edges of work surface shall be
provided with machine pressed 2 mm thick PVC lipping. Fabric magnetic tiles are fabric
upholstered metal tiles in 0.6 mm thick G.I. Grade, Fabric tack tiles are fabric upholstered
metal tiles in 0.6 mm thick G.I. Grade, with P.E. Foam in the tile for tack ability, White board
tiles are made of 8.0 mm thick particle board laminated with 0.6mm thick white glossy high
pressure laminate on outer side & 0.6mm backing laminate on inner surface and

having all its edges with minimum 0.5 mm thick PVC edging, Glass tiles 4 mm thick toughened
clear glass is fitted onto both sides of the panel using horizontal and vertical stiffeners made
from 0.6 mm powder coated CRCA steel Grade D as per IS: 513. Plain Metal tiles are made of
0.6 mm thick M.S. CRCA Grade D as per IS: 513 powder coated with Epoxy- Polyester finish.
The groument cap shall be provided for each seat.

The panel based workstation shall have cable management sysetem thought the work
panels. Note : The work station is to be provided in various C shape, L shape, plus shape
etc.as per space availibilty, layout requirement and direction of engineer in charge.For the
purpose of payment only number of seat of size 1500x1500x 600 mm, 750mm high shall be
measured for payment. Each seat shall be provided with metal pedstal with castors, and
keyboard tray as follows:
Pedestal unit 3drawer free standing pedastal unit "400Wx550Dx700H" made out 0.8mm th
CRCA sheet for body shell, drawer tray, front & rear side stiffner. Top & bottom stiffner shall
be of 1.2mm thk. All slides shall be with double extension precision ball slide. Drawers to be
without handles for clean finish. For drawer pulling, side wise tapered recess shall be
provided in shell behind drawer fronts. 10 lever cam lock & central locking with actuator &
lock channel mechanism shall be provided. Metal finish to be in epoxy polyster power
coating of 40 to 50 microns. All complete as per drawing and direction of Engineer in charge.

Keyboard pull out tray of size 230mm W -345mm W X 226mm D X 180mm H (+/- 10mm
tolerance for all dimensions) Metal Tray with mouse tray to be provided on Right hand side
or Left hand side as per requirement. Mouse tray size 210w x 210w all complete as per
drawing and direction of Engineer in charge.
9.9.3 Providing and fixing at all floors and locations modular fully knockdown workstation as per
indicative image, 50-60 mm thk. and 1200mm high. panel based work station partition with
flexible construction offering various functional and decorative finishes as well as cable
management capacity. All trims made of aluminium extrusions. Blocks made out of a
composite construction of MDF and paper honeycomb.Panel Blocks made of Fabric Tackable
, white board and Glass as per design and pattern selected by engineer in charge (All the
Nos. 347 20,057.00 69,59,779.00
combinations/ some of the combinations may be used as per selection).Tiles should be slid in
to the panels from top before fixing the top horizontal. These tiles should be supported from
top & bottom side with clips made from PP co polymer fitted in horizontal extrusion. Bottom
tile and leg made of Mild steel with epoxy powder coated.Fabricated bottom frame as

a welded structure of steel components. The panels and worktops are supported with MS
legs with levelers at various locations depending on the layout requirements. Worktop: Work
top shall be made of 25mm thick Pre laminated particle board interior grade of approved
Architect shade conforming to IS: 12823. Bottom shall have a backing laminate of minimum
0.6 mm thickness. All the edges of work surface shall be provided with machine pressed 2
mm thick PVC lipping. Fabric magnetic tiles are fabric upholstered metal tiles in 0.6 mm thick
G.I. Grade, Fabric tack tiles are fabric upholstered metal tiles in 0.6 mm thick G.I. Grade, with
P.E. Foam in the tile for tack ability, White board tiles are made of 8.0 mm thick particle
board laminated with 0.6mm thick white glossy high pressure laminate on outer side &
0.6mm backing laminate on inner surface and having all its edges with minimum 0.5 mm
thick PVC edging, Glass tiles

4 mm thick toughened clear glass is fitted onto both sides of the panel using horizontal and
vertical stiffeners made from 0.6 mm powder coated CRCA steel Grade D as per IS: 513. Plain
Metal tiles are made of 0.6 mm thick M.S. CRCA Grade D as per IS: 513 powder coated with
Epoxy- Polyester finish. The groument cap shall be provided for each seat. The panel based
workstation shall have cable management sysetem thought the work panels. Note : The
work station is to be provided in various C shape, L shape, plus shape etc.as per space
availibilty, layout requirement and direction of engineer in charge.For the purpose of
payment only number of seat of size 1200x600x 750 mm high shall be measured for
payment. Each seat shall be provided with metal pedstal with castors, and keyboard tray as
follows:

PART D2_BOQ_COPT,IIT BOMBAY 100 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
Pedestal unit 3drawer free standing pedastal unit "400Wx550Dx700H" made out 0.8mm th
CRCA sheet for body shell, drawer tray, front & rear side stiffner. Top & bottom stiffner shall
be of 1.2mm thk. All slides shall be with double extension precision ball slide. Drawers to be
without handles for clean finish. For drawer pulling, side wise tapered recess shall be
provided in shell behind drawer fronts. 10 lever cam lock & central locking with actuator &
lock channel mechanism shall be provided. Metal finish to be in epoxy polyster power
coating of 40 to 50 microns. All complete as per drawing and direction of Engineer in charge.
Keyboard pull out tray of size 230mm W -345mm W X 226mm D X 180mm H (+/- 10mm
tolerance for all dimensions) Metal Tray with mouse tray to be provided on Right hand side
or Left hand side as per requirement. Mouse tray size 210w x 210w all complete as per
drawing and direction of Engineer in charge.

9.9.4 EXECUTIVE TABLE -Providing and fixing at all floors and locations modular fully knockdown
work table as per indicative image with Primary Work table Surface Made of 25mm Thick Pre-
laminated twin board of E1-P2 grade and approved shade confirming to IS-12823:1990 and
2mm pvc membrane pressed at top and Edge banded with matching 2 mm thick PVC
lipping.Softclosing access flap with in-build power box are provided on work surface for wire
management.Secondary Work table made of 25mm Thick Pre-laminated twin board of E1-P2
grade and approved shade confirming to IS-12823:1990 and finish with 2mm pvc membrane
on work surface, Edge banded with matching 2 mm thick PVC lipping. Modesty Panel:Made
of 25mm thick MDF one side pre-laminate board confirming to IS- 14587:1998 with 0.4mm
PVC membrane pressed

on to top. Under- structure:Made of 25mm Thick Pre-laminated twin board of E1-P2 grade
with 2mm pvc membrane on visible surface and approved shade confirming to IS-
12823:1990, Edge banded with matching 2 mm thick PVC lipping. Integrated Pedestal on both
primary and secondary table of size 325x400x700 Made of 25mm Thick Pre-laminated twin
board of E1-P2 grade with 2 mm pvc membrane with edge banded with matching 2 mm thick
PVC lipping. Drawer fronts made of 25mm thick MDF one side pre-laminate board confirming
to IS-14587:1998 with 0.4mm PVC membrane pressed on to top.

Pedstal construction is BOX-BOX-FILE type which Uses powder coated 400 MM long metal
Panel Drawer Slides. Drawer extension is 325 MM. Drawers have a soft closing & anti slam
mechanism. Handles are provided for ease of opening.
Both Pedestal is provided with lock along with 2 set of keys for security.
9.9.4.1 MAIN TABLE SIZE - 1800 X 750 Type - T08 Nos. 52 24,647.50 12,81,670.00
9.9.4.2 MAIN TABLE SIZE - 2000 X 900 Type - T09 Nos. 1 27,478.00 27,478.00
9.9.4.3 EXECUTIVE SIDE TABLE - 1200 X 450 Type - T10 Nos. 53 10,335.00 5,47,755.00
9.9.4.4 EXECUTIVE BACK TABLE - 1800 X 450 Type - T11 Nos. 52 21,105.00 10,97,460.00
9.9.4.5 EXECUTIVE BACK TABLE - 2000 X 450 Type - T12 Nos. 1 26,708.50 26,709.00
9.10 DIRECTORS' EXECUTIVE TABLE - Providing, supplying & placing in position Director's table,
made out of marine plywood ( BWP 710 ), top & verticals on either side to be 40 mm thick (
19 mm thick marine plywood x 2 Nos. + 1 mm thick approved laminate on either side ), 45
mm thick apron ( Aluminium box framework of 25 mm x 50 mm size, 16 gauge section placed
at 450 mm centre to centre vertically & 350 mm centre to centre horizontally ) of Aluminium
framing with 9 mm thick marine plywood on either side finishes with 1 mm thick approved
laminate on both sides.

All exposed edges of plywood to be finished with 25 mm thick first BTC wood as per detail
drawing. ALL wood edges to be finished with matt PU polish to match colour of laminate.
Table top & bottom will be finished with 1 mm thick approved laminate including brush
Nos. 1 1,04,094.00 1,04,094.00
stainless steel wire manager, complete as per drawing and as directed by Architect/Site in
charge. including Pedestal item no. 14.10.4
Size : 2400 mm Length x 900 mm Width x 750 mm Height Type - T13
a) DIRECTORS' SIDE TABLE - Providing, supplying and placing in position Director's side table,
made out of marine plywood ( BWP 710 ), top to be 40 mm thick ( 19 mm thick marine
plywood X 2 Nos. + 1 mm thick approved laminate on either side ), 21 mm thick verticals ( 19
mm thick marine plywood + 1 mm thick approved laminate on either side ), 21 mm thick
shutters (19 mm thick marine plywood + 1 mm thick approved laminate on either side)
including 19 mm thick loose marine plywood shelves finished with approved laminate on
both sides, rested on heavy Stainless Steel pins including hardware like 75 mm high S S heavy
hinges ( 2 Nos. for each shutter ), Tower bolts, Magnetic ball catches, wooden / ss handles (
concealed or exposed)shutter locks with key holes, wire manager etc. Master lock to be
provided for all shutters.

All plywood edges to be finished with 6 mm thick first BTC wood, edges of all shutters ( hinge
side ) to be finished with 18 mm thick first BTC wood. All wood edges to be finished with matt
PU polish to match colour of laminate. Internal surface of unit to be finished with 1 mm thick
approved laminate on all sides, complete as per drawing and as directed by Architect/ Site in
charge.
Size : 1350 mm Length x 450 mm Width x 750 mm Height Type - T14

PART D2_BOQ_COPT,IIT BOMBAY 101 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
b) DIRECTORS' BACK TABLE - Providing, supplying and placing in position Director's back side
table, made out of marine plywood ( BWP 710 ), top to be 40 mm thick ( 19 mm thick marine
plywood X 2 Nos. + 1 mm thick approved laminate on either side ), 21 mm thick verticals ( 19
mm thick marine plywood + 1 mm thick approved laminate on either side ), 21 mm thick
shutters (19 mm thick marine plywood + 1 mm thick approved laminate on either side)
including 19 mm thick loose marine plywood shelves finished with approved laminate on
both sides, rested on heavy Stainless Steel pins including hardware like 75 mm high heavy S S
hinges ( 2 Nos. for each shutter ),

Tower bolts, Magnetic ball catches, wooden / ss handles ( concealed or exposed) shutter
locks with key holes, wire manager etc. Master lock to be provided for all shutters. All
plywood edges to be finished with 6 mm thick first BTC wood, edges of all shutters ( hinge
side ) to be finished with 18 mm thick first BTC wood. All wood edges to be finished with matt
PU polish to match colour of laminate. Internal surface of unit to be finished with 1 mm thick
approved laminate on all sides, complete as per drawing and as directed by Architect/ Site in
charge.
Size : 1950 mm Length x 450 mm Width x 750 mm Height Type - T15
c) Pedestal unit : 3 drawer free standing pedastal unit "400Wx550Dx700H" made out
0.8mm th CRCA sheet for body shell, drawer tray, front & rear side stiffner. Top & bottom
stiffner shall be of 1.2mm thk. All slides shall be with double extension precision ball slide.
Drawers to be without handles for clean finish. For drawer pulling, side wise tapered recess
shall be provided in shell behind drawer fronts. 10 lever cam lock & central locking with
actuator & lock channel mechanism shall be provided. Metal finish to be in epoxy polyster
power coating of 40 to 50 microns. All complete as per drawing and direction of Engineer in
charge.

Keyboard pull out tray of size 230mm W -345mm W X 226mm D X 180mm H (+/- 10mm
tolerance for all dimensions) Metal Tray with mouse tray to be provided on Right hand side
or Left hand side as per requirement. Mouse tray size 210w x 210w all complete as per
drawing and direction of Engineer in charge. Type - ST13

9.11 RECEPTION TABLE - Providing and fixing at all floors and locations modular fully knockdown
reception table e as per indicative image of size Table with size of 1800x900x750 with return
unit of 1200x600x730mm. Table top panel made up of 25 mm partical board clad with
decorative post formed laminate of the top side and balancing laminate on bottom side with
30 mm MDF PAD. Post forming edge on longitudinal side. Modesty panel made of 18mm pre-
lam partical board. legs are made of 18m & 25mm thick mdf board with 2 side PU painted
finish & hardness 2H. return desk top made up of 25 mm partical board clad with decorative Nos. 2 27,080.00 54,160.00
post formed laminate of the top side and balancing laminate on bottom side with 18 mm
MDF decorative strip of MDF pad. Post forming edge on longitudinal side. legs are made of
18m & 25mm thick mdf board with 2 side PU painted finish & hardness 2H.

Size & Location : L:1800 X D:75O X H:750 at Ground floor


Size & Location : L:1500 X D:75O X H:750 at Director's Cabin
Type - T16 & T19
a) RECEPTION SIDE TABLE - Providing and fixing at all floors and locations modular Low
Height Storage units with 3 number of openable shutters. Body is made from 18mm
Prelaminated particle board, with all the edges sealed with 0.8 mm thick PVC Edgeband. The
Back panel is 9mm Prelaminated particle board. The entire construction is ready to assemble
unit and is assembled with suitable KD fittings/ metal insert. The shelves and separator
panels made from 18 mm prelaminated particle board and edges are sealed with 0.8 mm
edge band. The bottom shelf is fixed and other shelves have one step adjustment for
optimizing the space. Doors : Door Panels ae made from 18 mm PLB with 2 mm Edge band on
all edges and a flush handle/pull handle to be provided as per direction & is to be fitted
vertically at the center of the door.

The each door to be provided with minimum 2 nos soft closing hinges or sliding unit
arrangement as per layout. .All the storages are fitted with a 6 mm leveler at bottom for
leveling. Rate shall be inclusive of all material such as prelaminated particle board,
labour, and all necessary hardware, shelf brackets, levelling screws etc. complete as per
architectural drawing particular specifications and direction of Engineer-In-Charge
complete.However, for the purpose of payment, the actual number of storage units supplied
and fixed in position shall be enumerated.
Size & Location : L:1200 X D:450 X H:750 at Ground floor & Director's Cabin
Type - T17 & T20

PART D2_BOQ_COPT,IIT BOMBAY 102 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
b) RECEPTION BACK TABLE - Providing and fixing at all floors and locations modular Low
Height Storage units with 4 number of openable shutters. Body is made from 18mm
Prelaminated particle board, with all the edges sealed with 0.8 mm thick PVC Edgeband. The
Back panel is 9mm Prelaminated particle board. The entire construction is ready to assemble
unit and is assembled with suitable KD fittings/ metal insert. The shelves and separator
panels made from 18 mm prelaminated particle board and edges are sealed with 0.8 mm
edge band. The bottom shelf is fixed and other shelves have one step adjustment for
optimizing the space. Doors : Door Panels ae made from 18 mm PLB with 2 mm Edge band on
all edges and a flush handle/pull handle to be provided as per direction & is to be fitted
vertically at the center of the door.

The each door to be provided with minimum 2 nos soft closing hinges or sliding unit
arrangement as per layout. .All the storages are fitted with a 6 mm leveler at bottom for
leveling. Rate shall be inclusive of all material such as prelaminated particle board,
labour, and all necessary hardware, shelf brackets, levelling screws etc. complete as per
architectural drawing particular specifications and direction of Engineer-In-Charge
complete.However, for the purpose of payment, the actual number of storage units supplied
and fixed in position shall be enumerated.
Size & Location : L:1500 X D:450 X H:750 at Ground floor & Director's Cabin
Type - T18 & T21

9.12 DISCUSSION TABLE - Providing and fixing at all floors and locations modular fully knockdown
Discussion table as per indicative image of size 1800mm x 1200mm x750 mm (H) with Work
Surface-Made of 25mm Thick Pre-laminated twin board of E1-P2 grade and approved shade
conforming to IS-12823:1990, Edge banded with matching 2 mm thick PVC lipping. Soft
closing access flap provided for access to power supply and audio cables. Side Panel-Made of
25mm Thick Pre-laminated twin board of E1-P2 grade and approved shade conforming to IS-
12823:1990 matching to the Worktop, Edge banded with matching 2 mm thick PVC lipping.
Cutout with Gromet provided for routing cables in case any Audio Visual equipment is to be
fixed later.The Under-structure consists of an Inner Tube Assembly with Top for Worktop
Mounting and Base plate with levellers. The Top Plate is made of 5mm thk hot rolled

steel Plates (HR) (As per IS: 2062) & the bottom plate is made of 8mm thk hot rolled steel
Plates (HR) (As per IS:2062). The Inner Tube Assembly is made of 25.4mmx 25.4mm x 1.2mm
thk round electric resistant welded tube (ERW)(As per IS:7138) welded together using
Tungsten inert gas welding. The whole structure is epoxy polyester powder coated (DFT 40-
60 microns). Cutout for standard 6 Module is provided for electrical fittings.An additional
cutout with a plate is provided for mounting Audio Visual Cables( eg HDMI,VGA-A,etc.).The
Nos. 1 6,072.00 6,072.00
3D removable panels are provided at bottom understructure for ease of servicibility It is
made of 1.2mm CRCA MS IS:513 and EPOXY POLYESTER Powder Coated (DFT 40-60 microns)..
It also provides easy access to internal space in case of any Audio Visual equipment is to be
added later.
Location : Faculty Room at 2nd floor Type - T22

9.13 SMALL DISCUSSION TABLE - 1200 mm dia, Table Top: 25mm thick Pre laminate particle board
with 2mm PVC edge lipping on all exposed edges. End Legs: Brush SS round legs with buffer
Nos. 2 6,201.00 12,402.00
Location : Director's Cabin, HoD' Cabin Type - T23

9.14 TABLE AT CLASSROOM - L:1200 X D:500 X H:750 Providing and fixing at all floors and
locations modular fully knockdown work table as per indicative image of size 1200W X 600D X
750H Main Worktop-Made of 25mm Thick Pre-laminated board (PLB) of E1-P2 grade and
approved shade confirming to IS-12823:1990, Edge banded with matching 2 mm thick PVC
lipping. Access Flap provided on work surface for wire management. Modesty Panel-Made of
18mm Thick Pre-laminated twin board (PLT) of E1-P2 grade and approved shade confirming
to IS-12823:1990, Edge banded with matching 2 mm thick PVC lipping. Legs-Cube legs are
fabricated from MS ERW Tube of 50 mm x 25 mm x 1.2mm thick and 40 mm x 40 mm x 1.2
mm thick (as per IS: 7138). At the top surface of leg, support brackets of 3 mm thick HR (as
per IS: 2062) are welded for fixing worktop. These are welded together by argo shield
welding.

This welded structure is coated with 50 micron epoxy polyester coating. At the base, a plastic
cap with M8 molded insert is fixed, on to which a straight M8 leveler fitted which allows for
adjustment of the height upto 50mm.Cross Members-Cross Members are made from 50mm
X 25mm X 1.2mm thick ERW tube (as per IS:7138). These are coated with 50 micron epoxy
polyester coating. Cross Members are assembled by friction fit PDC joinery and grub screws.
There are always two cross members for one table.Access Flap-Soft closing access flap is used
Nos. 3 9,500.00 28,500.00
. Provision for standard size of 8 module electrical shall be provided. Access flap is made from
Aluminum extrusion, PDC parts made from Aluminum Alloy and plastic parts are made from
Nylon 6 and wire brush with nylon bristles. Power Box-Power box made with 0.8 mm thick
CRCA (IS: 513), for 8 module to be provided.
Location : 3rd & 4th floor Type - T24

PART D2_BOQ_COPT,IIT BOMBAY 103 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
9.15 Providing and fixing at all floors and locations modular fully knockdown meeting table as per
indicative image having following specifications. Work top--Made of 25mm Thick Pre-
laminated twin board of E1-P2 grade and approved shade conforming to , Edge banded with
matching 2 mm thick PVC lipping. Soft closing dual access flap provided for access to power
supply and data cables at 1200mm c/c. The Under-structure legs and modesty panel consists
of mixture of 25mm thk and 18mm thk Pre-laminated twin board of E1-P2 grade and
approved shade conforming to IS-12823:1990, Edge banded with matching 2 mm thick PVC
lipping. Anodised aluminium alloy profile is added at bottom edges for improving the
aesthetics.

The product has a knock-down construction.Wire Management-A wire raiser made of 0.8mm
CRCA MS IS:513. It is epoxy polyester powder coated (DFT 40-60 microns) for flow of wires
and cables. A Power box with 2 cutouts on either sides for standard 8 module is provided.
Beside each cutout, an additional cutout with plate is provided for mounting Audio Visual
Cables(eg. HDMI,VGA-A,etc).
9.15.1 MULTIPURPOSE TABLE - 900 X 900 X 750MM HIGH Type - T30 Nos. 1 5,050.00 5,050.00
9.16 Providing and fixing at all floors and locations modular Low Height Storage units with 2
number of openable shutters. Body is made from 18mm Prelaminated particle board, with all
the edges sealed with 0.8 mm thick PVC Edgeband. The Back panel is 9mm Prelaminated
particle board. The entire construction is ready to assemble unit and is assembled with
suitable KD fittings/ metal insert. The shelves and separator panels made from 18 mm
prelaminated particle board and edges are sealed with 0.8 mm edge band. The bottom shelf
is fixed and other shelves have one step adjustment for optimizing the space. Doors : Door
Panels ae made from 18 mm PLB with 2 mm Edge band on all edges and a flush handle/pull
handle to be provided as per direction & is to be fitted vertically at the center of the door.

The each door to be provided with minimum 3 nos soft closing hinges or sliding unit
arrangement as per layout. .All the storages are fitted with a 6 mm leveler at bottom for
leveling. Rate shall be inclusive of all material such as prelaminated particle board,
labour, and all necessary hardware, shelf brackets, levelling screws etc. complete as per
architectural drawing particular specifications and direction of Engineer-In-Charge
complete.However, for the purpose of payment, the actual number of storage units supplied
and fixed in position shall be enumerated.

9.16.1 LOW HEIGHT STORAGE UNIT 1000 X 1200 X 400 DEEP Type - ST01 Nos. 45 12,403.00 5,58,135.00
9.16.2 LOW HEIGHT STORAGE UNIT 1200 X 1200 X 400 DEEP Type - ST02 Nos. 24 13,397.00 3,21,528.00
9.16.3 LOW HEIGHT STORAGE UNIT 1100 X 1200 X 400 DEEP Type - ST03 Nos. 13 12,403.00 1,61,239.00
916.4 LOW HEIGHT STORAGE UNIT 900 X 1200 X 400 DEEP Type - ST04 Nos. 24 9,498.00 2,27,952.00
9.16.5 FULL HEIGHT STORAGE UNIT 1200 X 2400 X 400 DEEP Type - ST05 Nos. 35 25,148.00 8,80,180.00
9.16.6 FULL HEIGHT STORAGE UNIT 800 X 2400 X 400 DEEP Type - ST06 Nos. 28 17,854.00 4,99,912.00
9.17 Providing and fixing at all floors and locations modular fully knockdown back unit credenza
as per indicative image with Top Panel,side ,back and bottom panel made of 25mm Thick Pre-
laminated twin board of E1-P2 grade with 2 mm pvc membrane on top and Edge banded
with matching 2 mm thick PVC lipping.Shutters are made of 25mm thick MDF one side pre-
laminate board confirming to IS-14587:1998 with 0.4mm PVC membrane pressed on to Nos. 11 18,388.00 2,02,268.00
top.Shutters have a soft closing & anti slam mechanism. Handles are provided for ease of
opening. Storage is provided with lock for security. L:1800 X D:750 X 750 HIGH Type - ST07

9.18 MAGAZINE RACK - Providing, supplying and placing in position Magazine rack, made out of
marine plywood ( BWP 710 ), 19 mm thick finished with 1 mm thick approved laminate on all
exposed surfaces including 12 mm thick plain clear toughened glass shelves with
computerized edge polish and fixed with brush Stainless Steel D brackets/ pins. All plywood
Nos. 4 15,000.00 60,000.00
edges to be finished with 6 mm thick first BTS wood. All wood edges to be finished with matt
PU polish to match colour of laminate, complete as per drawing and as directed by
Architect/Site in charge.
Size : 900 mm Length x 300 mm Width x 1800 mm Height Type - ST08
9.19 ISLAND UNIT - Providing, supplying and placing in position Island unit, made out of marine
plywood ( BWP 710 ), 19 mm thick finished with 1 mm thick approved laminate on all
exposed surfaces, top to be 30 mm thick ( 19 + 9 mm thick marine plywood + 1 mm thick
laminate on either side ), 21 mm thick shutters ( 19 mm thick marine plywood + 1 mm thick
approved laminate on either side ) including 19 mm thick loose marine plywood shelves
finished with approved laminate on both sides, rested on heavy Stainless Steel pins including
hardware like 75 mm high heavy S S hinges ( 2 Nos. for each shutter ),

Tower bolts, Magnetic ball catches, shutter locks with key holes etc. Master lock to be
provided for all shutters. All plywood edges to be finished with 6 mm thick first BTC wood,
edges of all shutters ( hinge side ) to be finished with 18 mm thick first BTC wood. All wood
edges to be finished with matt PU polish to match colour of laminate. Internal surface of unit
Nos. 2 23,234.00 46,468.00
to be finished with 1 mm thick approved laminate on all sides, complete as per drawing and
as directed by Architect/Site in charge.
OVAL SHAPED OUT OF 1500MM X 750MM Type - ST09

PART D2_BOQ_COPT,IIT BOMBAY 104 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
9.20 LOW HEIGHT DISPLAY UNIT - Providing, supplying and placing in position Island unit, partly
open and partly closed, made out of marine plywood ( BWP 710 ), 19 mm thick finished with
1 mm thick approved laminate on all exposed surfaces, top to be 30 mm thick ( 19 + 9 mm
thick marine plywood + 1 mm thick laminate on either side ), 21 mm thick shutters ( 19 mm
thick marine plywood + 1 mm thick approved laminate on either side ) including 19 mm thick
loose marine plywood shelves finished with approved laminate on both sides, rested on
heavy Stainless Steel pins including hardware like 75 mm high heavy S S hinges ( 2 Nos. for
each shutter ), Tower bolts, Magnetic ball catches, shutter locks with key holes etc. Master
lock to be provided for all shutters.

All plywood edges to be finished with 6 mm thick first BTC wood, edges of all shutters ( hinge
side ) to be finished with 18 mm thick first BTC wood. All wood edges to be finished with matt
PU polish to match colour of laminate. Internal surface of unit to be finished with 1 mm thick
approved laminate on all sides, 12 mm thick plain clear glass shelves with computerized edge
Nos. 1 20,000.00 20,000.00
polish in open space, fixed with brush Stainless Steel D brackets/pins, unit partly finished with
approved PU paint, complete as per drawing and as directed by Architect/Site in charge.
Size : 1800 mm Length x 450 mm Width x 750 mm Height Type - ST10

9.21 FULL HEIGHT LIBRARY UNIT GUIDE BOOK RACK -(Singe Side
Stand-Alone)
Upright - MS 40 x 40 x 1.6 Tube.
Side Profile - MS Powder coated metal profile of 1.6mm with Acrylic pouch.
Nos. 1 27,000.00 27,000.00
Band : Made of MS Powder coated metal 1.6mm
Shelves - Made of MS powder coated metal 1.2mm, supported with brackets.
Back Panel - Made of MS Powder coted metal 0.8mm.
Top panel , Side Panel & Bottom Panle - Made of 18mm thk PLT.
9.22 TV UNIT - Providing, supplying and placing in position Island unit, made out of marine
plywood ( BWP 710 ), 19 mm thick finished with 1 mm thick approved laminate on all
exposed surfaces, top to be 30 mm thick ( 19 + 9 mm thick marine plywood + 1 mm thick
laminate on either side ), 21 mm thick shutters ( 19 mm thick marine plywood + 1 mm thick
approved laminate on either side ) including 19 mm thick loose marine plywood shelves
finished with approved laminate on both sides, rested on heavy Stainless Steel pins including
hardware like 75 mm high heavy S S hinges ( 2 Nos. for each shutter ), Tower bolts, Magnetic
ball catches, shutter locks with key holes etc. Master lock to be provided for all shutters. Unit
includes 3 drawers, laminate finished on all sides including telescopic channels and dead
locks with master keys.

All plywood edges to be finished with 6 mm thick first BTC wood, edges of all shutters ( hinge
side ) to be finished with 18 mm thick first BTC wood. All wood edges to be finished with matt
PU polish to match colour of laminate. Internal surface of unit to be finished with 1 mm thick
approved laminate on all sides, 12 mm thick plain clear glass shelves with computerized edge
Nos. 1 26,000.00 26,000.00
polish in open space, fixed with brush Stainless Steel D brackets/pins, unit partly finished with
approved PU paint, complete as per drawing and as directed by Architect/Site in charge.
Size : 1200 mm Length x 300 mm Width x 2100 mm Height Type - ST11

9.23 Supply and complete installation / placing in position as required and approved by EIC chairs
of following makes of given description
9.23.1 HIGH BACK CHAIRS - DIRECTOR - Supply and installtion of High back chair with handrest as
per indicativeimage, The Seat SIZE : 47.0 cm. (W) x 48.0 cm. (D) plus minus 50mm. The
Cushioned seat should be made of Injection molded Plastic outer & inner. Plastic Inner
should be upholstered with leatherette and moulded High Resilience (HR) Polyurethane
foam of Density 45±2 kg/m3,and hardness load 16 ± 2 kgf as per IS:7888 for 25%
compression.: HIGH BACK SIZE: 470mm. (W) x 760 mm plus and minus 50mm. The
Nos. 1 20,800.00 20,800.00
Cushioned back should be made of PU Foam with insitu molded MS E.R.W Round Tube of size
1.9±0.03cm x 0.16 ±0.0128cm. It upholstered with Leatherette.The armrest top should be
moulded from polyurethane(PU) and mounted on to a drop lift adjustable type tubular
armrest support made of M.S. E.R.W tube having chrome plated finish.

ACTIVE BIO-SYNCHRO with adjustable tilting mechanism should be designed with 360'
revolving type, Front-pivot for tilt with feet resting on ground and continuous lumbar
support ensuring more comfort, Tilt tension adjustment can be operated in seating position.
5-position Tilt limiter giving option of variable tilt angle to the chair with locking facility. The
mechanism housing should be made up of HPDC Aluminium black powder coated.
Seat depth adjustment should be integrated in the seat through a sliding mechanism. Seat
depth adjustment range should be of 6.0±0.5 cm.
Back Frame should be connected to the Up/Dn mechanism housed in Plastic T spine.
The pneumatic ht adjustment has an adjustment stroke of 10.0±0.3 cm. The pedestal should
be High Pressure Die cast polished Aluminium and fitted with 5 nos. twin wheel castors. The
twin wheel castors should be injection moulded in black PP. Type - CH02

PART D2_BOQ_COPT,IIT BOMBAY 105 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
9.23.2 HIGH BACK CHAIRS WITH CASTORS - Supply and installtion of Mid back chair as per
indicative image, with SEAT SIZE: 470 mm. (W) x 515 mm. (D)
BACK SIZE :450mm. (W) x 653 mm. (H) . Variation in size shall be plus minus 50 mm.
SEAT/BACK ASSEMBLY: The seat should be made up of 12 mm ± 1mm thk. hot pressed
plywood and shall be fixed with HIGH RESILIENCE (HR) POLYURETHANE FOAM: The HR
polyurethane foam should be moulded with density =55+/-2 kg/m³ and hardness 16 ± 2 kgf
Nos. 128 7,610.00 9,74,080.00
for 25% compression. The seat shall then upholstred with A grade fabric .The Back should be
made up of injection moulded glass filled nylon & upholstered using Net fabric with high
tenacity yarn. The armrests have an Up-Down adjustment , Armrest Top has layer of
Thermoplastic Elastomer (TPE).

The Lumbar support should be made up of polypropylene pad with moulded polyurethane
foam & covered with polyester fabric. The Height of Lumbar pad can be adjusted through
two projecting knobs provided on the rear side of the pad.
FRONT PIVOT SYNCHRO mechanism with adjustable tilting mechanism. Design with 360°
revolving type, Single point control, Front-pivot for tilt with feet resting on ground ensuring
more comfort , Tilt tension adjustment , 4-position locking with anti-shock feature.
-
The pneumatic height adjustment has an adjustment stroke of 10.0 ± 0.3 cm.
The pedestal should be injection moulded in black 30% glass-filled Nylon and fitted with 5
nos. twin wheel castors.
The twin wheel castors should be injection moulded in black Nylon.
Type - CH03

9.23.3 MID BACK CHAIRS WITH CASTORS - Supply and installtion of Mid back chair as per indicative
image, with SEAT SIZE: 470 mm. (W) x 515 mm. (D)
BACK SIZE :450mm. (W) x 653 mm. (H) . Variation in size shall be plus minus 50 mm.
SEAT/BACK ASSEMBLY: The seat should be made up of 12 mm ± 1mm thk. hot pressed
plywood and shall be fixed with HIGH RESILIENCE (HR) POLYURETHANE FOAM: The HR
polyurethane foam should be moulded with density =55+/-2 kg/m³ and hardness 16 ± 2 kgf Nos. 570 6,660.00 37,96,200.00
for 25% compression. The seat shall then upholstred with A grade fabric .The Back should be
made up of injection moulded glass filled nylon & upholstered using Net fabric with high
tenacity yarn.

The Lumbar support should be made up of polypropylene pad with moulded polyurethane
foam & covered with polyester fabric. The Height of Lumbar pad can be adjusted through
two projecting knobs provided on the rear side of the pad.
FRONT PIVOT SYNCHRO mechanism with adjustable tilting mechanism. Design with 360°
revolving type, Single point control, Front-pivot for tilt with feet resting on ground ensuring
more comfort , Tilt tension adjustment , 4-position locking with anti-shock feature.
The pneumatic height adjustment has an adjustment stroke of 10.0 ± 0.3 cm.
The pedestal should be injection moulded in black 30% glass-filled Nylon and fitted with 5
nos. twin wheel castors.
The twin wheel castors should be injection moulded in black Nylon.

9.23.4 VISITORS CHAIRS Supplying & Fixing and placing Medium back Chair for cabin visitor with
SIZE/OVERALL DIMENSIONS: 640 mm(W) X 625 mm(D) X 910 mm(Ht), Height from floor to
back: 960mm Height from floor to seat: 500mm and having SEAT/ BACK ASSEMBLY:
• The seat shall be made of 12mm thick (7 layers) hot pressed plywood and molded seat
foam upholstered with fabric • The bottom cover shall be made by injection molded in back
PP to cover the
plywood • Seat size - 490mm X 500 mm • Effective seat depth: 455mm • Minimum height - Nos. 124 4,180.00 5,18,320.00
450 mm & Maximum height - 540mm • Seat ply – centre load tested @ 230 kgs • Seat ply –
1.700 kgs • PP seat cover - 0.660 kgs
•Backrest shall be made of injection molded in black polypropylene • The back shall have
auto contoured Lumbar support for achieving
comfortable seating posture

• Lumbar support shall be made of injection molded in black PP made of fabric ,and
upholstered with 1-inch U-foam • Backrest size – 600mm (Ht)X 490mm(W)
• Backrest shall be tested for 120000 cycles with the load of 45 kgs • 2. POLYURATHANE
FOAM: • Seat and Back
Foam shall be made of molded Polyurethane foam with following properties: o DENSITY: 52-
55 Kg/m3 o HARDNESS: 15-20 kgf o COMPRESSION RATIO: 50% 10 max o COMFORT /
INDENTATION HARDNESS: 15.4 3.Understructure - MS pipe duly powder coated Type - CH05

9.23.5 3 SEATER BENCH L:2000 Supplying and installing 3 seater bench whose Top, Seat and back
made of 18mm thick prelaminated particle board with 2mm pvc lipping, Shelf-18mm thick
prelam board. Frame struture made of 25*25*1.2mm thick C.R.C.A Steel pipe . All metal
components are Pretrated with nano technology powder coating process. 25mm square pipe
Nos. 7 11,940.00 83,580.00
side frame assemblies are connected with 25mm square pipe cross members. Seat and Top
panels are supported with 2 cross member each. M6 Haxagonal head leveler 6 Nos are used
for leveling on uneven surface. Type - CH06

PART D2_BOQ_COPT,IIT BOMBAY 106 of 92


Sr. No. Description of Items of work Unit Qty Unit Rate Amount (Rs.)
9.23.6 2 SEATER BENCH L:1050 Supplying and installing 3 seater bench whose Top, Seat and back
made of 18mm thick prelaminated particle board with 2mm pvc lipping, Shelf-18mm thick
prelam board. Frame struture made of 25*25*1.2mm thick C.R.C.A Steel pipe . All metal
components are Pretrated with nano technology powder coating process. 25mm square pipe
Nos. 14 8,340.00 1,16,760.00
side frame assemblies are connected with 25mm square pipe cross members. Seat and Top
panels are supported with 2 cross member each. M6 Haxagonal head leveler 6 Nos are used
for leveling on uneven surface. Type - CH07

9.23.7 WOODEN CHAIRS; Providing and Supplying wooden chair, made out of BTC wood with
40mmtappered vertical wooden Legs, wooden handrest and back rest in currved shaped as
per design. Cusioned seat finished with approved fabric (Rs. 500/-metre), PU Polish finish,
complete as per drawings etc all complete as per the Architectural drawings, as specified and
Nos. 70 1,485.00 1,03,950.00
as directed by the Engineer- in-Charge. Aprox. Size:- 500mm 500 mm Height of seat from FFL
450 mm Topof back rest from FFL -800 mm Type - CH08

9.23.8 SEMINAR CHAIRS - Supplying and installing training chair with writing pad with size:
450*450*900mmH.
BACKREST IS MADE OF PP UPHOLESTED WITH MESH. BACKREST IS CONNECTED TO FRAME
WITH HELP OF CONNECTOR’S
Nos. 158 3,250.00 5,13,500.00
MADE OF NYLON.
METAL FRAME IS FOLDABLE & AVAILABLE IN POWDER COATING. ARM PAD IS ADJUSTABLE
( FRONT & BACK )SEAT CUSHION Type - CH09

TOTAL OF FURNITURE WORKS 2,66,96,201.00