Base Plate INDIA CODE

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 18

Design of base plate

Project/Client :-
S.No Calculations References
1 Design forces
Factored Axial load Pu = 17 KN From analysis
Nature of axial load = Compression
Factored Shear force Fy = 2 KN
Dia of anchor bolts (HT bolts) = M 20 mm
No of bolts = 4 Nos
Grade of bolts = 8.8
Ultimate Tensile strength of bolt fu = 100 Mpa
Ultimate Tesile strength of plate fcu = 250 Mpa
Yield stress of plate fy = 250 Mpa
Yield stress of bolt fyb = 250 Mpa
Cube compressive strength of concrete fck = 20 Mpa
2 Geometric properties
Column section = ISMB
Depth of section = 400 mm
Width of flange = 140 mm
Clearence of holes = 2 mm
Dia of holes = Nominal dia of bolt + clearence = 22 mm
Minimum Edge distance = 33 mm Clause 10.2.4
Maximum edge distance = 12tε IS:800:2007
= 192 mm
ε = (250/fy)1/2
= 1
Edge distance provided = 150 mm
O.K

25 25

16
450
150 150 150
50

30
100

140

200
100

140

200
400

50
450

Minimum spacing of bolts (2.5 d) = 50 mm Clause 10.2.2 &


Maximum spacing of bolts (lesser of 32t or 300) = 300 mm 10.2.3
Spacing of bolt provided = 150 mm IS:800:2007
O.K
3 Check for base pressure
Bearing pressure of plate w = Pu/Ap
= 0.19 Mpa
Allowable bearing pressure = 0.6fck
= 12 Mpa
Safe
4 Check for Minimum Thickness of base plate Clause 7.4.3.1
Thickness of plate required IS:800:2007

t s ≥√ 2. 5 w (a2 −0 . 3 b2 )γ mo / fy>tf
ts = 1.22 mm
Thickness of plate required = 16 mm
Safe
4 Check for shear capacity of bolts Clause 10.3.3
Design shear strength of bolt, Vdsb = Vnsb/‫ע‬mb IS:800:2007
Nominal shear capacity, Vnsb
Vnsb = 32.63 KN
Vdsb = 26.104 KN

Calculated shear force per bolt Vd = 0.5 KN


Safe
5 Check for bearing capacity of bolts Clause 10.3.4
Design bearing strength of bolts Vdpb = Vnpb/‫ע‬mb IS:800:2007
Vnpb = 2.5kb d t fu
kb = 0.4
Vnpb = 32 KN
Vdpb = 25.6 KN
Calculated bearing strength of bolt Vb = 4.25 KN
Safe
6 Check for tension capacity of bolts
Design tension capacity of bolt Tdp = Tnp/‫ע‬mb
Nominal Tensile capacity of bolt
Tnp = 0.9fubAn<fybAsb(‫ע‬mb/‫ע‬mo)
0.9fubAn = N.G Mpa
fybAsb(‫ע‬mb/‫ע‬mo) = N.G Mpa
Nominal Tensile capacity of bolt Tnp = N.G Mpa
Design tension capacity of bolt Tdp = N.G Mpa
Calculated tension per bolt T = N.G Mpa
N.G
7 Check for combined shear and tension

N.G N.G
+ = N.G > 1.0
N.G N.G
N.G
Design of base plate
Project/Client :-

S.No Calculations References

1 Design forces
Axial load Pu = 156 KN From analysis
Nature of axial load = Compression
Bending moment about xx Mx = 0 KN.m
Bending moment about yy My = 0 KN.m
Lataral force along xx Fx = 0 KN
Lataral force along yy Fy = 0 KN
Dia of anchor bolts (HT bolts) = M 20 mm
No of bolts = 4 Nos

2 Geometric properties

Dia. Of pile = 300 mm


Width of column/pedestal = 450 mm
Depth of column/pedestal = 700 mm
Minimum spacing of piles = 750 mm As per IS:2911-
Centre to Centre distance of two adjacent pile = 750 mm Part-1, clause:5.6
Edge projection from face of piles
(Min 100-150mm) = 150 mm
Width of pile cap = 600 mm As per IS:2911-
Part-1,
Length of pile cap = 1350 mm clause:5.12.5
Depth of pile cap ( assumed) = 600 mm
Clear cover to the reinforcement = 75 mm
Grade of concrete fck = 20 Mpa
Grade of Steel fy = 415 Mpa
3 Load calculations
Weight of pile cap = 12.15 KN
Additional load due to moment = 0 KN
Total load on each pile = 84.08 KN
= O.K
4 Calculation of reinforcement
a)Bending theory
Bending moment about xx = 21.4404 KN.m
Design bending moment = 32.1606 KN.m
Dia of Main reinforcement = 12 mm
Dia of secondary reinforcement = 12 mm
Effective depth of pile cap = 519 mm
Mu/bd2 = 0.2
pt = 0.056 %
pt,min = 0.12 %
Area of steel required = 373.68 mm2

b)Truss theory
Tension at bottom = Pu/12ld(3l2-a2)
= 97.69 KN
Area of steel required = 270.572 mm2
Area of steel required
(max of bending & truss theory) = 373.68 mm2
No of bars required = 4 Nos
No of bars provided = 4 Nos
Area of steel provided = 452.16 mm2
5 Check for shear
a)One way shear
Percentage of steel provided = 0.145 %
ß = 0.87fy/6.89pt
= 17.42
Permissible shear stress, ζc = 0.273 Mpa Clause 40.5
Nominal shear stress ,ζv = 0.41 Mpa IS:456-2000
Shear span, av(C/C of pile/2-d/2+20% pile dia) = 0.18 m
Enhancement factor (2d/av) = 5.77
Modified shear strength, ζv = 1.57 Mpa
1.57>0.41
OK
b)Two way shear
Punching shear, V = 234 KN
Perrimeter of column, = 2300 mm
Punching shear stress, = 0.2 Mpa Clause 31.6.3
Permissible shear stress, = 1.11803 Mpa IS:456-2000
1.1180339887499>0.2
OK
Design of base plate
Project/Client :-
S.No Calculations References
1 Design forces
Factored Axial load Pu = 1100 KN From analysis
Nature of axial load = Tension
Factored Shear force Fy = 300 KN
Dia of anchor bolts (HT bolts) = M 36 mm
No of bolts = 4 Nos
Grade of bolts = 8.8
Ultimate Tensile strength of bolt fu = 100 Mpa
Ultimate Tesile strength of plate fcu = 250 Mpa
Yield stress of plate fy = 250 Mpa
Yield stress of bolt fyb = 250 Mpa
Cube compressive strength of concrete fck = 25 Mpa
2 Geometric properties
Column section = BUILT-UP I SECTION
Depth of section = 400 mm
Width of flange = 300 mm
Clearence of holes = 2 mm
Dia of holes = Nominal dia of bolt + clearence = 38 mm
Minimum Edge distance = 57 mm Clause 10.2.4
Maximum edge distance = 12tε IS:800:2007
= 144 mm
ε = (250/fy)1/2
= 1
Edge distance provided = 160 mm
Not OK

50 50

12
500
160 180 160
100

50
200

300

400
200

300

400
400

100
500

Minimum spacing of bolts (2.5 d) = 90 mm Clause 10.2.2 &


Maximum spacing of bolts (lesser of 32t or 300) = 300 mm 10.2.3
Spacing of bolt provided = 180 mm IS:800:2007
O.K
3 Check for base pressure
Bearing pressure of plate w = Pu/Ap
= 5.5 Mpa
Allowable bearing pressure = 0.6fck
= 15 Mpa
Safe
4 Check for Minimum Thickness of base plate Clause 7.4.3.1
Thickness of plate required IS:800:2007

t s ≥√ 2. 5 w (a2 −0 . 3 b2 )γ mo / fy>tf
ts = 10.29 mm
Thickness of plate required = 12 mm
Safe
4 Check for shear capacity of bolts Clause 10.3.3
Design shear strength of bolt, Vdsb = Vnsb/‫ע‬mb IS:800:2007
Nominal shear capacity, Vnsb
Vnsb = 105.73 KN
Vdsb = 84.584 KN

Calculated shear force per bolt Vd = 75 KN


Safe
5 Check for bearing capacity of bolts Clause 10.3.4
Design bearing strength of bolts Vdpb = Vnpb/‫ע‬mb IS:800:2007
Vnpb = 2.5kb d t fu
kb = 0.4
Vnpb = 43.2 KN
Vdpb = 34.56 KN
Calculated bearing strength of bolt Vb = 275 KN
Unsafe
6 Check for tension capacity of bolts
Design tension capacity of bolt Tdp = Tnp/‫ע‬mb
Nominal Tensile capacity of bolt
Tnp = 0.9fubAn<fybAsb(‫ע‬mb/‫ע‬mo)
0.9fubAn = 73.25 Mpa
fybAsb(‫ע‬mb/‫ע‬mo) = 289.02 Mpa
Nominal Tensile capacity of bolt Tnp = 73.25 Mpa
Design tension capacity of bolt Tdp = 58.6 Mpa
Calculated tension per bolt T = 275 Mpa
Unsafe
7 Check for combined shear and tension

75 275
+ = 6.86297 > 1.0
34.56 58.6
Unsafe

You might also like