Professional Documents
Culture Documents
Triplex Manual
Triplex Manual
OIL MIST
MONITORING
SYSTEM
QMI TRIPLEX™
Atmospheric Oil Mist Detection System Manual
The QMI TRIPLEX™ atmospheric oil mist detection systems can locate a hazardous
build up of oil mist in confined areas such as: pump rooms, bow thrusters, purifier
rooms, hydraulic pack areas, and test cells.
We can provide QMI MULTIPLEX™ atmospheric and engine oil mist detection systems.
The MULTIPLEX™ systems have up to 12 channels and can be used to monitor engine
condition continuously to see when and where repairs are needed thus avoiding
unnecessary engine wear and the resulting danger. The MULTIPLEX™ can also be
used for larger atmospheric systems. For more information please see our website:
www.oilmist.com
Errors and omissions excepted. As we strive to improve our service and products specifications may
change or vary.
Part 1 Introduction
Technical Specifications Part1-2
QMI TRIPLEX™ Central Monitor Unit (CMU) (Q01T):
Photograph and Features Part1-3
Dimensions of TRIPLEX Monitor Part1-4
Description of Q01T: TRIPLEX™ Central Monitor Unit (CMU) Part1-5
Description of (Q10) Detectors Part1-7
Photograph of Detector Part1-8
Drawing of Detector Head Part1-9
Dimensions of Triplex Monitor Part1-10
Part 2 Installation
Positioning and Location of Detectors Part2-2
Positioning of QMI Q10 Atmospheric Oil Mist Detector Part2-3
Schematic of Positioning of Detectors and Best Practice Part2-5
Cable Specifications Part2-7
Wiring Description Part2-8
Wiring of Socket Part2-9
Wiring for System Layout Part2-10
Photograph of Power Supply Relay Board (Q01T05) Part2-11
Drawing of PSB Part2-12
Enlarged Schematic of Connectors for Detectors, Alarms and
Power Connections on Monitor PSB Q01T05 Part2-13
Schematic of layout for Wiring Option 1: Part2-14
for 1 to 3 Detectors Part2-14
Drawing – Connection from detector to monitor Part2-15
Drawing – Wiring from detector to monitor Part2-16
Schematic of layout for Wiring Option 2: For 2 or 3 Detectors
using a Junction Box Part2-17
Photograph of unboxed 3 - way PCB (Q01T06) Part2-18
Drawing – Unboxed 3 - way PCB for a junction box Part2-19
Drawing – Wiring from monitor to PCB (Q01T06) Part2-20
Drawing – Connections from PCB to detectors Part2-21
Drawing – Wiring from junction box PCB to detectors Part2-22
Alarm Output Wiring Part2-23
Graph to show relationship between Oil Mist concentration and
Digital Alarm readout Part2-24
Part 3 Starting Up/ Running Procedure
Operation and Best Practice Part3-2
Operation of Alarm Relays Part3-3
Setting and Changing Alarm Levels Part3-4
Test Sequence Part3-5
Checking Alarm Levels and Reading Channels Part3-6
Changing Number of Detector Heads (DH) Part3-7
To Isolate or Restore a Channel Part3-8
Restore Alarms Part3-9
Location of Binary Switch Mounted on Processor Board Part3-11
Part 5 Maintenance
Maintenance Procedures Part5-2
Lens Cleaning Procedure Part5-3
Replacing Fan (Q1004) in Detector Part5-5
Maintenance Kit (Q01T07) Part5-6
QMI Oil Mist Spray in a Can Part5-7
Material Safety Data Sheet Part5-8
PART 6 SPARES
Codes and Description for Replacement Parts and Spares Part6-2
Procedure for Returning Equipment for Repair Part6-3
QMI Request for Repair or Service Part6-5
QMI Continual Support Information Request Part6-7
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
Introduction Part1-1
Atmospheric Oil Mist Detection System
Introduction
Part 1
TRIPLEX
Technical Specifications
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
Glands (as shown above) are not supplied as we do not know the diameter of cable to
be used. The monitor is supplied with blind grommets.
Channel switches
Power indicator
Fuse FS3
Operating instructions
Serial number
TRIPLEX
110mm 260mm
MAGNETIC PEN
FUSE
180mm
HINGE
KEY
230mm
280mm
325mm
110mm
35mm
91mm
230mm
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
Access to the CMU is by way of the hinged Display Panel sub-assembly. The 4 x M6
socket head screws retain the display panel. Upon removal of the screws the panel can
be swung away from the main enclosure.
TRIPLEX PCB (Q01T04) (see Part 1-3 and Part 2-11, 2-12, 2-13)
The display panel sub - assembly carries the main TRIPLEX PCB Type MP3 Processing
Board, with the Binary Switch and EPROM, which is attached to the display (monitor
faceplate) by 6 x cheese head screws. The EPROM faces the display and cannot be
seen when the CMU is open.
2. POWER SUPPLY RELAY BOARD (Q01T05) with PSU (see Part 2-11)
The Power Supply Relay Board consists of a switch mode power supply unit mounted
on a PCB. The PCB holds the fuses, the transistor TR1 (Q0111), and the terminal plugs
and carries the alarm relays.
The terminal plugs used for wiring are provided as part of the QMI TRIPLEX system. It
is very important that the installers pay attention to the shape of the connectors so as
not to damage the plugs or sockets and to ensure a good connection.
Please note the shape of the plug, which is rounded on the lower end to ensure that
plugs are connected in the correct way. Force will allow incorrect attachment and may
damage the connectors.
TRIPLEX
There are 3 fuses on the TRIPLEX Power Supply Relay Board, see fault directory in
Part 4.
FS1 (Q0114) is a 1.25 A anti-surge fuse. This is connected to TR1 and is the supply to
the detector heads. The LED 1, which is underneath, will flash when all is well.
FS2 (Q0112) is a 400mA anti-surge fuse for 12 volt power to the fans. The LED will
light when all is well.
FS3 (Q0115) is a 3.15 A anti-surge fuse and is fitted to the side of the monitor.
The lead engineer holds the only set of keys (Q0103) to change settings. It is possible
to check the settings without using the security key switch, see Part 3-4.
NOTE: The monitor does not have an on/off switch this is to prevent the oil mist
detectors from being switched off. To turn off the power disconnect the power
supply.
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
The detector operates using the principle of light scatter (nephelometry). The power
and signal are transmitted to and from the monitor through a single cable sending a
timed analogue signal. All detectors sample simultaneously and continuously every
half- second (500 milliseconds).
The universal joint is fitted to bulkhead or deck allowing the detector to be positioned
facing the flow of air in the chamber being monitored.
The sub-assembly is fitted to the universal joint by 4 screws, which can be removed if
and when the detector lens requires cleaning.
b) CHAMBER
Inside the unit are the PCB, integral fan, and sensing lenses. Power is supplied to the
12-volt fan by a single cable, which is connected to the
monitor (or to a junction box). The fan draws the sample of air past the sensors
through the outlet ports.
In the front of the detector head unit are the air intake louvers, and an LED, which
shows green when the fan is working. The electronics are mounted on the back of
the chamber casing and are protected by the cover sealed to IP 65.
At the back of the unit is the multi-purpose power and signal socket. Next to the
socket is the mounting spigot.
Introduction Part1-8
TRIPLEX
Photograph of Detector
Atmospheric Oil Mist Detection System
Introduction Part1-9
Atmospheric Oil Mist Detection System
Green LED
73 mm
200 mm 113 mm
Inspection cover 41 mm
Drawing of Detector Head
100 mm
Detector
6.5 mm
ARTICULATED
JOINT
SOCKET
12 mm
3 slots 6.5mm wide 65 mm
equispaced on 45ø
TRIPLEX
110mm 260mm
MAGNETIC
PEN
FUSE
180mm
HINGE
KEY
230mm
280mm
OVERALL WIDTH WITH HINGE AND
MAGNETIC KEY
325mm
110mm
35mm
91mm
230mm
Installation Part2-1
Atmospheric Oil Mist Detection System
Installation
Part 2
TRIPLEX
It must be taken into consideration that the number of detectors will depend on the
pressure being released into the atmosphere which is relative to the volume of the
space. It will also depend on the amount of air movement.
In a large engine room you may need 4 or 5 detectors (for which you would use a QMI
MULTIPLEX™ Atmospheric Oil Mist Detection System), for a hydraulic pack room 1 to
3 detectors are sufficient. In purifier and compressor rooms one is usually enough. For
all other spaces such as steering gear or bowthruster housing use 1 or 2 detectors.
NOTE: Detectors cannot be used in cargo pump rooms as they have not been certified
for hazardous zones.
LOCATION OF DETECTORS
Please follow the guidelines outlined below to get the best results.
We recommend using our Oil Mist Spray in a Can (see Part 5-7) or a smoke generator
to judge the way the air flows over the machinery. Normally air will move toward
ventilation extractors or the turbo charger, therefore, the detector must be placed in
the air stream facing the airflow as close as possible to the machinery.
The detector comes with a fixing flange which is welded on the universal joint.We
suggest the length of cable that runs to the detector is longer than required to enable
the detectors to be moved at a later date if necessary.
To confirm that the detectors are correctly positioned you should carry out the following
test; wait until the engines, ventilation and other machinery are fully operational, then
once again use your Oil Mist Spray in a Can or smoke generator to prove the detectors
are correctly positioned. The detector should be rotated until positioned mid airflow as
indicated by the movement of smoke.
NOTE: Always place the detector in a position so that it can be easily maintained as
the detectors should be cleaned regularly. See Part 5-3.
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
There are so many variables in the detection of oil mist in the atmosphere that it is by no
means an exact science. Common sense has a part to play when positioning detectors.
What are the factors that determine the positioning and number of
detectors needed?
Four factors determine good positioning and number of detectors. These factors
should be considered together and a smoke generator is a good way to observe air
movement and test positioning of the detectors.
b. Air circulation
In addition, the movement of air affects how many detectors should be installed. If a
room has only one vent then the detector placed near this vent will be able to sample
the air extracted from the room. However, if there is more than one vent or point
of extraction a detector is best placed in each path of air being drawn from towards
each of these vents. This is why a smoke generator or Oil Mist Spray in a Can is
used to ensure that the detector points towards the potential source of oil mist. The
detector should be installed with the intake louvers facing the path of the smoke
as shown by the smoke generator. The smoke generator will also show any eddies
or paths that the air may follow in the chamber which is important to ensure that
detectors are correctly positioned.
In hydraulic pack areas there should be a detector between each extractor and the
TRIPLEX
packs which normally means 2 to 3 detectors especially if the pack is in the engine
room. This should be bourne in mind with any areas are being monitored.
In an engine room several detectors are needed but the exact location will vary
according to airflow.
Extractor/ Vent
EDDY 1
source of
oil mist
Extractor/ Vent
EDDY 2
Location of Detector
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
The articulated universal joint allows the detector to be positioned mid airflow.
See Part 1-8 for the drawing of the detector and articulated universal joint.
BEST PRACTICE
Until the ship is in operation, to avoid contamination of the lenses after installation,
cover detectors with a plastic bag. This will prevent paint or other materials dirtying
or damaging the lenses, blocking the detector louvers and fan. These outcomes may
permanently damage the detectors and/or require detectors to be returned to QMI for
repair.
NOTE: Any damage of this nature will not be covered by our guarantee.
TRIPLEX
For setting alarm levels See Part 3-4 of this manual for this procedure. Begin by setting
all the detectors at 0.05mg/L. There will always be areas where there is oil mist; for
instance in the purifier room. The alarm level must be set to a higher level than needed
so that the system does not go into alarm when there is no problem.
TEST PROCEDURE
As these detectors are sensitive to smoke, steam or oil mist, artificial smoke can be
used to test the detectors. This is the most effective way of proving the detectors are
working.
The simplest test is to use a QMI Oil Mist Spray in a Can which is part of the maintenance
kit. See Part 5-7.
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
Cable Specifications
For the following connection we RECOMMEND THE MINIMUM TYPE AND SIZE as
follows:
Halogen free instrumentation, control and communication cable for fixed installation in
ships or equivalent appropriate specifications for application.
Example supplier: Helkama of Finland (LKM - HF for 3 x 1.5 power cable) and (RFE
- HF for 4 x 2 x 0.5 mm2 twisted connection cables.)
WIRING OF ALARM
If wiring just one side of each relay is either open or closed, use 6 cores.
If both sides of relay are being wired 9 cores will be required.
The screen is normally connected to PIN NO. 5. No earth should be made at the
Detector Head end as this could result in ground loops. Earths made to any other point
from the screen wire between Monitor and Detector Head will be ineffective and could
cause additional interference.
TRIPLEX
Wiring Description
The wires are terminated into screw type plugs. These plug into the connectors on the
TRIPLEX™ power supply relay board (PSB). They have to be plugged in the correct way
round. See photograph of power supply board Part 2–11.
The Mains connector is a 3 - pin with Live, Neutral, and Earth. On the Power Supply
Relay Board this is marked L, N +
Cable is 3 core of 1.5mm2 and can be sourced from Helkama part number is LKM - HF
3 x 1.5.
The detectors are wired using 3 twisted - pair cable. Each connector is wired left to
right and numbered 1 to 6. The cable specification is 3 twisted pair of 0.5mm2 or
3 twisted pair of 0.75 mm2 where distance is over 100 meters.
This cable can be sourced from Helkama: part number is RFE - HF 4 x 2 x 0.5 mm2 or
4 x 2 x 0.75 mm2.
The cable to use for wiring of alarms can be the same as used for wiring of air sensors.
If you intend to use all four alarms you will need a 4 twisted pair cable.
Glands are not supplied as we do not know what diameter cable will be used. The
monitor is supplied with Blind Grommets.
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
Wiring of Socket
125mm
j Retaining ring
k Connecting block with terminals
l Bared and tinned wires
m Main housing of socket
n Cable locking screen
o Main securing thread to hold socket to plug
p 24mm adhesive heat shrink sleeving (not supplied by QMI)
Assemble instructions
a) Strip back about 125mm of outer sheathing of cable and separate wires. Then tin
ends of wires and screen being used.
c) Wire bared wires and screen to correct numbered terminals of Part 2. Numbers are
shown by the terminals. Use drawing QMI-06-1119 on Part 2-16.
d) Reassemble and look with part number j
e) Pull heat shrink p over first part of m and wires to main cable and then shrink in
the appropriate way.
TRIPLEX
For 1, 2, or 3 detectors where each detector has individual cables connected to the
monitor. All wiring connectors for the detectors, alarms and power are on the Power
Supply Relay Board.
Drawings:
QMI-06–119: Connections from detectors to monitor Part 2-15
QMI-06–120: Wiring from detectors to monitor Part 2-15
For 2 or 3 detectors with wiring from the monitor to the plant room with 1 cable the
cable is wired into a PCB mounted in a junction box (supplied by the installer). Then
individual cables are run to the detector.
Drawings:
Installation Part2-11
Atmospheric Oil Mist Detection System
(Q01T05)
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
Installation Part2-12
TRIPLEX
Atmospheric Oil Mist Detection System
1 2 3 4 5 6
SHUT
DETECTOR 2 FAN FAILURE EARLY FAULT DOWN MAIN
Input 0 + No C NC No C NC No C NC No C NC
1 2 3 4 5 6
DETECTOR 3
Fan Failure must
have a link
1 2 3 4 5 6 between the first
two points as
shown.
Atmospheric Oil Mist Detection System
Installation Part2-13
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
Atmospheric Oil Mist Detection System
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
CONTROL ROOM
WIRING DIAGRAM TRIPLEX MONITOR Q01T
QMI-05-1118
Cable 4 x 2 x 0.5mm²
PLANT ROOM
UNIVERSAL JOINT
CONNECTOR
DRAWING Q10 DETECTOR
QMI-05-1119
Installation Part2-15
Atmospheric Oil Mist Detection System
Installation Part2-16
TRIPLEX
Atmospheric Oil Mist Detection System
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
CONTROL ROOM
TRIPLEX MONITOR Q01T
POWER 110/240VAC
TO ALARM PANEL
Cable 4 x 2 x 0.5mm²
or 7 x 2 x 0.5mm²
Cable 7 x 2 x 0.5mm²
twisted pair
For distance over 100m
use 0.75 size wire.
Could be 5 twisted pair
cable if available
CONNECTOR
DRAWING Q10 DETECTOR
QMI-05-1119
Installation Part2-18
TRIPLEX
Installation Part2-19
Atmospheric Oil Mist Detection System
Depth 3.5cm
Height 10cm
Width 13cm
Dimensions of PCB
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
Installation Part2-20
TRIPLEX
Atmospheric Oil Mist Detection System
Installation Part2-21
Atmospheric Oil Mist Detection System
Installation Part2-22
TRIPLEX
Atmospheric Oil Mist Detection System
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
4. The cable used should be a minimum 6 - cores and can range from a minimum
thickness of 0.25mm2 up to a maximum 2.50mm2
There are three warning alarms: Early warning, Shutdown, and Main. There is also a
fault alarm.
If you require a contact to close an alarm wire one core to NO and one core to C.
If you require a contact to open on alarm you wire one core to NC and one to C.
Relay 6
Relay 4 Relay 5 Relay 7
SHUT
FAN FAILURE EARLY FAULT DOWN MAIN
Input 0 + No C NC No C NC No C NC No C NC
TRIPLEX
FLASHING FLASHING
GREEN
YELLOW RED
1.50
MAXIMUM ALLOWABLE DENSITY BEFORE ALARM (1.3 mg/L)
1.25
1.00 2.00
L
VE
LE ED
0.75 I TY ER
V W
TI LO
N SI B E
SE Y
0.50 E T O NL 1.00
ES N
PR CA
CH
0.25 HI 0.50
W
0
10 20 30 40 50 60 70 80 90 100
FULL ALARM LEVEL
DIGITAL READING
% OF ALARM WITH 1.3 mg/L EPROM
Calibration Graph for 1.3 mg/L EPROM and the LEL for Oil Mist
TRIPLEX
Oil mist is continuously drawn through each detector and the level of oil mist density
is monitored. This process is continuous at each detector. The signals are fed to the
micro-processor TRIPLEX PCB that is located in the CMU.
The signals are scanned at 500 millisecond intervals and the data is presented as a
digital display reading from 0% to 100% of alarm level.
Although oil mist samples are measured in milligrams/litre the reading per channel is
presented as a percentage of 1.3mg/L.
EPROM ES 1 STANDARD (marked: OMD ES1 1.30 mg/L) Maximum Alarm Setting
1.3mg/L.
Best Practice
The power supply to the monitor is cut off, reset the monitor so that each detector
has the maximum setting of the installed EPROM. If necessary, reset alarm to original
settings.
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
The relays work in conjunction with the lights on the CMU display panel:
ALARM SEQUENCE
The minimum alarms used are the Main alarm and Fault alarm. The functional
shutdown (or slowdown) can be used to shutdown the plant.
If used, the functional first relay activates at 80% and is an early warning alarm.
The second main alarm and third (slow or shutdown) alarm are activated at 100%.
A fault alarm relay is completely divorced from the other relay systems and is only
activated after a fault has developed in the oil mist detection system. No relays will
activate for 2.5 seconds, as the monitor will check first that the fault is in the system
and not a problem with the environment.
Even when this fault alarm relay is activated the instrument goes on monitoring unless
there is a major malfunction of the monitor or detector. Information is also being
continuously given as a digital display of the highest concentration of oil mist and its
location.
The digital display will always indicate the channel (i.e. area) with the highest level
of oil mist. IN THE EVENT OF A FAULT ALARM IT WILL BE THE FIRST CHANNEL TO
GO INTO THE FLASHING GREEN, AMBER, RED CONDITION THAT IS INDICATED ON
THE DISPLAY (F1, F2, AND F3).
NOTE: THERE IS A ONE - MINUTE DELAY when the fault alarm sounds. After a self -
test or a channel check the display will always revert to the channel with the highest
oil mist level reading.
TRIPLEX
During the setting up procedure normal operation of the CMU is disabled, therefore to
set and change alarm levels:
1. With the security key supplied (Q0103), release the security switch, which is
fitted to prevent unauthorised adjustment of the system.
2. Turn the key clockwise 1/4 turn (and no more). The light above ‘Check Alarm
Settings’ will illuminate.
3. Place the magnetic pen (Q0109) flat against the circle marked ‘Check Alarm
Settings’.
4. Place the magnetic pen flat against the ‘Raise’ Alarm Level circle marked with
‘+’ or ‘Lower” Alarm Level circle marked with ‘ - ‘. Raise and remove the pen
away from the circle once for each increment until the required level is reached.
The level will be indicated on the digital ‘Reading’.
5. Place the magnetic pen flat against the circle marked ‘Channel Number’ to set
that channel to the level indicated at the digital reading.
6. To set another channel repeat steps 4 and 5.
7. When setting is complete turn the key anti - clockwise back 1/4 turn, this locks
the system, then remove the key.
8. After the key has been turned to secured state, it is possible to check that
the settings by placing the pen on ‘Check Alarm Settings’ then on ‘Channel
Number’. The new set level will then be displayed.
9. To reset any channel ALL above items MUST be repeated
Channel
identification
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
Test Sequence
BEFORE BEGINNING THE TEST PROCEDURE WARN THE CHIEF ENGINEER AND
CAPTAIN.
To activate the test procedure make sure the security key is turned to running mode
then place the magnetic pen over the circle marked ‘TEST’. The sequential testing
system will commence as follows:
2. The running (green), anticipatory (amber) and alarm (red) indicators will
illuminate in sequence.
4. All digital readouts will then indicate ‘111’ showing that all segments of the
numerical display are working with no fade.
5. Each detector lens will be indicated (NOTE: ‘Cd’ indicates clean lens).
When ‘dd’ (dirty detector) appears on the display, detector lenses are under
80% clean. Refer to lens cleaning instruction. See Part 5-3. When dirty ‘F2’
will automatically show on the display. If ignored it will go to ‘F3’.
6. All external relays with the exception of the functional relay will operate for
10 seconds. If the system has an audio alarm system IT IS RECOMMENDED
THAT THE PERSONNEL SHOULD BE WARNED OF THE IMPENDING TEST.
The test includes a test of the fault monitoring circuit, i.e. watchdog, when
‘F9’ will appear momentarily In the event of a CMU failure ‘F9’ will be
displayed continuously.
In this case the PCB of the Power Supply Relay Board must be replaced.
7. After the relays have been tested the CMU will automatically return to display
the channel with the highest concentration of oil mist.
9. When using the self - test facility, the display will show the condition of
the head i.e. ‘dd’ (the detector is dirty) or ‘Cd’ (the detector is clean).
HOWEVER, ONE FULL MINUTE SHOULD ELAPSE BEFORE USING THE
SELF-TEST FACILITY AGAIN. This is to allow the software to latch back into
the correct running mode; otherwise erroneous signals may be displayed.
During this sequence isolated heads may be displayed ‘Cd’.
Should any function throughout the sequence fail to operate as specified, please refer
to Fault Finding Section, see Part 4.
TRIPLEX
To check the pre-set alarm level setting for each individual channel, first place the
magnetic pen over the circle marked ‘ALARM LEVEL’. The alarm level indicator will
illuminate. Place the pen over the ‘CHANNEL’ number. The channel identification
digital display will be shown digitally as a milligrams per litre value in mg/L of oil mist
density. Should the alarm level need to be adjusted then follow the ‘Initial Setting - up
Procedure’ (Changing alarm levels) and ‘RESET’ the system as previously described.
See Part 3-4.
Place the magnetic pen over the required channel circle. The channel number selected
will be shown digitally on the ‘Channel Identification’ display alongside the digital read-
out of the percentage density of the pre-set alarm level at the channel. After one
minute the display will revert to the channel with the highest oil mist reading.
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
Detector
Heads SW3 SW4 SW5 SW6
Required
1 Off On On On
2 On Off On On
3 Off Off On On
If the display is showing 3 channels and (for example) only 2 detectors have been
fitted, the display will then show the unused channel flashing amber, green and red
lights. Also, the display reading will show the ‘F1’ fault on the unused channel.
To correct or change the QMI TRIPLEX™ to show only 2 channels and cancel the other
position showing, the following procedure is carried out:
2. Using the ‘T’ Allen key provided, unscrew the front 4 x M6 screws to open the
CMU cover. One screw is located at each corner of the QMI TRIPLEX™ monitor.
3. The front of the monitor is hinged and the front panel can now be swung open.
The displayed TRIPLEX PCB can be seen screwed in the lid. There is no need to remove
or unscrew the TRIPLEX PCB from the lid.
4. For safety, disconnect the 3 - pin power connector from the QMI TRIPLEX™
5. The binary switch blocks are located on the TRIPLEX PCB (Q01T04). There are
a total of 6 binary switches - two of these do not operate.
TRIPLEX
As a temporary measure it is possible to isolate the Detector Head from the monitor
panel (’isolate’ in this instance is to remove the Detector head signal from the monitor
via the software).
To carry out the isolate function, turn security switch key to set mode, place the
magnetic pen on ‘ISOLATE’ circle, then place it over the ‘CHANNEL’ number. Turn the
key back to RUN mode. The channel /Detector Head is now isolated and the display
will now be blank. If the pen is placed over the isolated ‘CHANNEL’ number ‘IC’ will
appear on the display.
After the Detector Head has been replaced and/or the lens cleaned, reinstate the
channel by turning the key to set mode, place the magnetic pen on ‘ISOLATE’ circle
then on to ‘RESET’. Finally place the magnetic pen on to the ‘CHANNEL’ number and
turn the security key to operating mode. This will put the channel and associated
detector back on line.
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
Restore Alarms
There are two stages of oil mist alarm indication:
The channel number will be indicated and the digital reading will indicate the percentage
density of the pre-set mist alarm level. The early warning alarm relay will operate.
NOTE: This alarm is automatically operated when the oil mist density level reaches
80% of the pre-set alarm level.
2. FULL ALARM.
At 100% of alarm level the red indicator will flash indicating that the oil mist level is
above the pre-set alarm level. The offending channel will be displayed alongside the
digital read-out level. The functional shutdown relay alarm RL9 will operate if wired
into the system. At this level RL10, the main alarm, will be activated. Further action
should be taken in accordance with the standard procedures.
Over-riding the QMI TRIPLEX™ system during procedures that may introduce particles
into the atmosphere (e.g. painting) is at the operator’s discretion. If such a function is
required it should be incorporated in the ship’s overall system.
IMPORTANT: When any alarm sounds all personnel should leave the area.
TRIPLEX
3. FAULT ALARMS
The fault alarms indicate if there is any fault in the monitoring system. The monitor
faceplate has a list of the fault alarms and their significance. This uses relay RL8. See
table below for the fault conditions as presented on the monitor faceplate. For more
information see the fault directory in Part 4.
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
Fault Finding
Part 4
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
Fault Directory
TRIPLEX
Maintenance Part5-1
Atmospheric Oil Mist Detection System
Maintenance
Part 5
TRIPLEX
Maintenance Procedures
The QMI TRIPLEX™ incorporates an operational fault finding system, which will identify
operational and component breakdowns. During operational breakdowns, a fault code
is displayed against the relevant detector number. The possible fault codes are listed
on the monitor front plate.
In the event of a component breakdown or fault, the CPU light will come on (see Fault
Directory, Part 4)
With all fault indications the fault warning relay is non - energised. The relay may be
returned to normal through the ‘RESET’ function. The warning indication on the digital
display will persist until the fault is corrected or the channel isolated.
A large percentage of returns under Warranty are in fact due to dirty lenses. Very
often, due to difficult working conditions and lack of experience, the lenses in the
Detector Head are not properly cleaned. This problem is made more difficult because
the operator has to return to the Monitor in order to check the cleanliness of the lenses.
A simple way to help the cleaning process is to use the suggestion on Part 5-5.
The Monitor will indicate when the lenses need cleaning (Fault Directory Part 4)
The monitor will indicate when there is a Fan Fault (Fault Directory Part 4)
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
To clean, the lens in the event of oil or condensation build up, use the following
guidelines:
3. Holding the Detector, undo the 4 screws fixing the Detector body to the
universal joint. Use the Allen Key tool from the Maintenance Kit.
5. In a clean area, remove cover plate by undoing the 4 Button Head Screws.
The tool is in the Maintenance Kit.
6. 3 lenses will be visible inside the chamber. Using a clean cloth and the cleaning
solution ‘Clean All’ to wipe the lenses clean. For badly contaminated lenses,
repeat until clean. Polish the lenses with a clean and dry cloth.
DO NOT SATURATE THE LENSES WITH FLUID.
TRIPLEX
IMPORTANT NOTES
1.The detector head electronics are factory calibrated and cannot be serviced
on site.
In the event of a fault the detector must be sent back to QMI unless it is a
faulty fan then just change the fan as shown in PART 5-5.
2. DO NOT USE diesel oil, acetone or kerosene to clean detectors and detector lenses.
3. ONLY use the ‘clean all’ cleaning liquid provided in the maintenance kit to the
clean lenses.
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
+ _
fan
circuit board
fan
failure LED
screw
ADJUSTING FAN FAILURE ON Q10 - FH FAN
WARNING: Any attempt to adjust other components on the circuit board will
invalidate the guarantee and may stop the sensor working.
TRIPLEX
Q01T02 Manual
Q1007 M 2.5 Hexagonal Allen Key For detector lid, inspection cover
and fan.
Q0112 Anti Surge Fuse 400 mA For FS2 on Power Supply Relay
Board ( Pack of 5 )
Q0114 1.25 Amp fuse for FS1 on For FS1 on Power Supply Relay
power relay board Board ( Pack of 5 )
Q0115 3.15 Amp fuse for FS3 on For FS3 on side of Monitor
side of Monitor ( Pack of 5 )
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
OPERATING INSTRUCTIONS
One can will last for about 5 minutes if used continuously but as only a very short
burst of spray is required, many detectors can be tested.
Hold the can about 1M away from the detector being tested or any equipment to be
monitored and use only as directed.
It is important that the spray is not used within 2M of an open flame or directed into
anyone’s face. If it gets into eyes rinse with cool water.
To remove any mist keep the ventilation going as the mist can hang around for up to
2 hours in still air. The spray can easily be wiped off any surface with a soapy cloth if
too much spray has been used.
CHARACTERISTICS
• Odorless
• Long Lasting
• No CFCs
• No Heat
• Non-Toxic
• Completely Safe
• Non-Irritating
• Immediate Use
• Meets Safety Standards
• Ozone Safe
TRIPLEX
Quality Monitoring Instruments Limited provide this MSDS in order to promote consumer
understanding of the hazards associated with these products.
The information contained herein should be made available to all QMI employees,
agents, contractors, and customers. In turn, these same should make this MSDS
available to their employees, agents, contractors and customers. As such this MSDS
shall be included with every can and in our manuals identified below.
I. IDENTIFICATION
PRODUCT NAMES “MG-550 Haze in a Can”. Where data differs discretely by product
(not over a range) it will be presented in the above product order.
III. INGREDIENTS
These products are mostly “Oil-based” Mineral oil solutions. As such, toxicity is
minimal. These products have been shipped internationally for more than 5 years under
the manufacturer’s name, and are considered “non-hazardous” by most national health
and safety regulatory bodies.
Due to the fact that de-ionized water forms the base for all these solutions, no
detectable fire or explosion hazard exists. Flammability is undetermined due to the
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
No exposure limits have been determined for these products, nor for any of the
ingredients from which they are formulated.
Swallowing has no adverse effects in low doses. Higher doses may induce nausea and
vomiting, but with no long-term toxicity. Inhalation produces no adverse effects when
used according to standard practices. Continuous exposure to highly concentrated
fog may lead to throat/ respiratory tract irritation. Under such conditions, irritation
should subside immediately upon moving to an area of low fog concentration. The fog
produced by these products will be adequately filtered by any 10-20 micron filtration
system. Contact with the liquid may cause minimal temporary irritation to exposed skin
areas. Eye contact with the liquid may also cause minimal, temporary irritation. In all
cases of contact with the liquid, flushing of the exposed area with water is sufficient.
No contra-indications may be determined, as the ingredients have no independently
dietary/ medicinal regimens. Treatment of erroneous overexposure may be determined
by health personnel, with principal attention given to the control of symptoms and
overall clinical status.
Spills will result in a slippery film on most surfaces. Flushing with water is a sufficient
response. Liquids may be safely disposed according to standard waste disposal
methods.
The liquids described herein are stable formulas. No avoidable reactive risks can be
determined through an extrapolation of all possible uses. Exposure to air, heat, water
and oxidants poses no risk for reaction. Non-standard combustion of these formulas
may produce aldehydes, ketones, carbon dioxide and/ or carbon monoxide.
Other Requirement: The IATA dangerous goods regulations are fully in compliance
with ICAO annex 18 and its associated technical instructions.
IX. CONCLUSION
TM1/ JANUARY 2008 Maintenance Part5-9
Atmospheric Oil Mist Detection System
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
The products covered by this MSDS are not regulated by any international regulating
bodies, including the WHMIS. As such, they may be classified as non-hazardous. In
view of the above MSDS, the most critical special information concerns protecting
employees from irritation which may accompany long-term exposure to the products.
They should be enabled to avoid repeated contact with skin, eyes and/ or clothing.
Rubber or otherwise coated gloves and eye protection should be worn when handling
large volumes or quantities of these products.
X. TRANSPORT INFORMATION
Marine transport
IMDG/UM Non-hazardous goods
Air transport
ICAO/IATA-DGR Non-hazardous goods
Dispatch by post Permitted
Spares Part6-1
Atmospheric Oil Mist Detection System
SPARES
PART 6
TRIPLEX
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
1. Make sure the equipment being returned has a full report with it indicating what
the problem being experienced is, especially informing us of the fault number that is
displayed on the Monitor (e.g. F1.)
Also indicate the Monitor Serial Number (e.g. T108). This will be found on the front
plate of the display on the right above the fault directory.
The Detector Serial Number (e.g. A2099) is shown on a label behind the slots at the
front of the detector.
Please remove free oil from detector so as to not to damage detector further in
transit.
2. Supply QMI with an order and order number to cover the work to be carried out,
as the goods will not be returned without an order being received.
NOTE. Detectors returned for service or repair will be guaranteed for 18 months. This
does not include the fan in the detector. See Part 2-5.
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
CHECKLIST
Summary of Problem:
EMAIL qmi@oilmist.com WEBSITE www.oilmist.com 5 Hampstead West, 224 Iverson Road, London, England, NW6 2HL TEL +44 (0)20 7328 3121
TRIPLEX
It would be helpful if you would take the time to provide us with the information
outlined below. Having the details you have supplied will allow us to provide up
- dated information on your system and will allow us to respond more quickly to any
questions or problems you might have in the future.
Should you need to return equipment for service or repair, please see Part 6-3 of this
manual for details on how the equipment should be returned.
Return address (please send a copy of paperwork to QMI London for customs
clearance)
(Repair for Quality Monitoring Instruments)
Cambertronics, Unit 15
Manfield Park Industrial Estate
Guildford Road, Cranleigh,Surrey,
GU6 8PT, UK
email: qmi@oilmist.com