Professional Documents
Culture Documents
Busbar Protection
Busbar Protection
• During saturated CT, by adding high impedance in relay coil can effectively
control the saturation problem.
• Those relays design with high impedance work well in this situation
• Several lines terminated on protected bus will result of different burden of CTs at
external faults
• Large core saturation for modern network is problem
• In order to avoid saturation effect time delay practice was adopted
• But this solution for modern power system is inadequate
• Another early solution was a form of biased percentage differential protection,
• which also suffered from the need for current transformers with very large cores.
• Because of these difficulties, the current differential form of bus protection is
seldom used.
Mason gives a formula for estimating the maximum flux density in the
current transformer in terms of the symmetrical components of the CT
primary current is:
1. Locate the junction point of the CT's at a central point with respect to the
CT locations and use heavy wire in order to hold down the resistance of the
leads.
2. Choose CT ratios so that the maximum magnitude of external fault
current is less than about 20 times the CT rating.
3. Set the relay pickup at least twice the load current of the most heavily
loaded circuit.
4. Use inverse-time overcurrent relays to provide some time delay and
account for the dc component of current
Most of the differential bus protection schemes suffer from two types of
problems:
(1) current transformer saturation, and
(2) careful current transformer selection, matching, and design restrictions
on the burden presented to each transformer. Current transformer
saturation is particularly difficult for buses that are near synchronous
generators, because of the high dc component of fault currents
supplied by the generators.
One type of bus differential protection that solves these problems is the
"half-cycle” protection scheme that uses auxiliary current transformers for
proper impedance matching and detects the fault condition before the
current transformers reach saturation.
The designs based on the fact that a conventional CT will deliver current
for about 2.0 ms, even under fault conditions, before saturation occurs. The
half-cycle relay is designed to detect the fault and initiate tripping before
saturation occurs.
Assignment