Power transformers TOH type


Compliant with IEC-76 standards, COMMISSION REGULATION (EU) No 548/2014, and its
amendment EU 2019/1783 on implementing Directive 2009/125/EC of the European Parliament and
of the Council with regard to small, medium and large power transformers (Ecodesign Tier 2).

Distribution oil step-down three phase two winding


transformers with a power of 25 to 1250 kV·A with a voltage
to 24 kV are targeted at national economy use, indoor and
outdoor type.

Technical specifications
TOH-25 – 1250 Power transformers are hermetically
sealed with voltage of primary winding to 24 kV and voltage of
secondary winding 0,4 or 0,42 kV.
Connections and vector group – Dyn11, Dyn5; Yzn11
or another.
The transformers provide off load tapping on primary
side. For this purpose transformers are equipped with high-
voltage switcher, connected to high voltage winding allowing
for voltage control in steps with unplugged transformer on HV
sides with a range of ±2 х 2,5 %
Symbolic representation structure

TOH - Х/Х U1 ECO2


Т – three phase transformer,
O – oil-immersed cooling with natural circulation of air and oil (ONAN)
H – hermetic,
Х – nominal power, кVА,
Х – winding voltage HV, kV,
U1 – temperate climate and outdoor use,
ECO2 - Ecodesign Tier 2.

Service conditions
Altitude above the sea level – up to 1000 m.
Distribution oil hermetic transformers

Ambient air temperature:


- for moderate climate - from –45ОС to +40ОС;
Relative humidity of atmosphere – not exceeding 98% at +25 ОС.
Transformers are not suitable for work:
- in explosive and corrosive environment (containing gas, vaporizations, elevated concentration of dust
etc.);
- in vibratory operation and jolting.

Transformers construction
TOH-25-1250 rectangular shape transformer tanks are produced with corrugated walls without oil
conservator. For the purpose of lifting tank and transformer in the assembled condition hooks, located
underneath the upper tank frame are used. On a tank lid oil filler crane (plug) is located, on the bottom of the
tank oil drain cock is located, testing crane (plug), grounding bolt.
Active part comprises windings, high-voltage switch and magnet core, produced from high-quality
electrotechnical steel. Steel cutting is performed on «GEORG» line, magnet core is made according to the
«Step-Lap» scheme. Transformer windings are made of aluminum.

2023
ТOH 2
_____________________________________________________________________________________

HV and LV bushings are located on the lid. HV and LV dismountable externally mounted bushings,
porcelain tube insulators.
For oil level control tank lid is equipped with float oil level indicator. For measuring temperature of top
layers of oil in the tank, transformer is equipped with thermometer.
Oil volume expansion, depending on transformer temperature, is compensated due to the changes of
pressure inside the tank, configuration and volume change of corrugated walls.
In hermetic transformers (type TOH) oil does not contact with air and does not age. They do not
require additional expenditures when put into operation.
In transformers with a power to 1250 kVA for length and side travel of transformers rollers are
installed.

Acoustic performance of power oil transformers


with a power to 1250 kVA

Sound level*
Power, kV∙А
(not exceeding), dBA
100 41
160 44
250 47
315 48
400 50
630 52
800 52
1000 55
1250 56

*Sound level for transformers to 100 kVA whould not exceed 40 dBA
Distribution oil hermetic transformers

2023
ТOH 3
_____________________________________________________________________________________

Hermetic power transformers TOH type with a power to 1250 kVA


and voltage to 24 kV
Distribution oil hermetic transformers

Technical specification of TOH series transformers with a power


to 1250 kVA and voltage to 24 kV

2023
ТOH 4
_____________________________________________________________________________________

Power,
50 100 160 250 315 400 630 630 800 1000 1250
kVA

Vector group Dyn11, Yyn0

No-load losses*, W 81 130 189 270 324 387 540 540 585 693 855

Load losses*, W 750 1250 1750 2350 2800 3250 4600 4600 6000 7600 9500

Short-circuit
4 4 4 4 4 4 4 6 6 6 6
voltage, %

L 980 1100 1120 1180 1260 1260 1450 1490 1520 1580 1620

B 710 710 710 760 830 840 900 900 960 1100 1100

H 1350 1390 1480 1560 1600 1720 1855 1840 1855 1855 2030
Measurements**, mm.

С 1260 1280 1350 1410 1490 1610 1755 1740 1745 1745 1685

D 265 265 265 265 265 265 265 265 265 265 265

A 265 265 265 265 265 265 265 265 265 265 265

E 105 105 105 120 150 150 150 150 150 150 150

F 105 105 105 120 150 150 150 150 150 150 150

K 520 520 520 520 670 670 670 670 820 820 820

Oil weight**, kg 165 195 260 300 330 385 550 550 590 720 760

Total weight**, kg 760 1010 1150 1490 1785 1940 2800 2800 3150 3400 4040

* Maximal loss levels.


**Dimensions and weights
Dimensions and weights are for guidance only.
The definitive drawings following from the order will commit us contractually.
Distribution oil hermetic transformers

For other voltages, impedance voltages and vector groups, weights and dimensions can are different (consult
us).

2023