Ad-90.0-E-02053-Pdf Small Power Details

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

KEY PLAN

DRAWING

TRUE

SWITCHED SOCKET
SURFACE MOUNTED CANOPY
G.I PLATE
GI CONDUIT ISOLATOR (WEATHER
PROOF)
450

SPACEBAR SADDLE CLAMP

F.F.L

PVC CONDUIT 100x50mm G.I.


CONDUIT MAY BE SWITCHED SOCKET CHANNEL ARMOURED CABLE
SERVED FROM THE FLUSH MOUNTED SUPPORT
NOTES: FOLLOWING: BELOW
WEATHERPROOF
SLAB, IN SCREED OR
SEPARATE EARTH PULL BOX DATA SOCKET NOTES

800mm
FROM ABOVE.
CONDUCTOR ( GREEN & FLUSH MOUNTED
YELLOW ) SOCKET
BOX 120 1. FOR GENERAL NOTES; REFER TO DRAWING:

350
GALVANIZED PVC CONDUIT
SWITCHED SOCKET WALL STEEL CONDUIT WORK TOP LEVEL CONCEALED IN WALL
FLUSH MOUNTED CABLE TRAY WITH 2. THIS DRAWING IS THE PROPERTY OF AECOM AND MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE LEAD
CONDUIT FORMS THE 200x200x8mm THICK VENTILATED COVERS CONSULTANT'S AUTHORITY.
DATA SOCKET FLUSH MOUNTED WEATHERPROOF TWIN OR SINGLE
PROTECTIVE CONDUCTOR G.I. PLATE
SOCKET OUTLET SOCKET OUTLET 3. ALL DIMENSIONS ARE SHOWN IN MM, UNLESS NOTED OTHERWISE.
CONDUIT MAY BE SERVED FROM
DATA SOCKET FLUSH SEPARATE EARTH CONDUCTOR NOTES: 4. DO NOT SCALE OFF THIS DRAWING, CHECK ALL DIMENSIONS ON SITE AND NOTIFY THE COMPANY OF ANY DISCREPANCIES
MOUNTED CONNECTING EARTH TERMINAL OF G.I CABLE
SOCKET OUTLET TO AN EARTHING
BEFORE PROCEEDING WITH THE WORK.
SUPPORT
120 120 NOTES: TERMINAL IN ASSOCIATED BOX BRACKET 5. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MECHANICAL
300

SOCKET OUTLET TYPE TO BE AND ELECTRICAL DRAWINGS AND ALL RELEVANT SECTIONS OF THE SPECIFICATION.
200mm BLOCK
PVC CONDUIT DETERMINED ON LAYOUT DRAWINGS WORK
6. FOR COLUMN SIZES / RC WALL THICKNESS, SLAB THICKNESS & BEAM SIZES, REFER TO STRUCTURAL.
F.F.L CONCEALED IN WALL AND/OR SPECIFICATION. 7. THE LOCATION & SIZE OF THE MECHANICAL EQUIPMENTS & EQUIPMENT PLINTH ARE SHOWN FOR INDICATIVE PURPOSES
ONLY.
ROOF 8. FOR ADDITIONAL INFORMATION ON MEP FIXTURES & EQUIPMENTS, SEE RELATED MEP DRAWINGS.
9. HVAC EQUIPMENT LOCATED WITHIN THE BUILDING ARE FED FROM 20A DOUBLE POLE SWITCHED FUSED SOCKET & FLEX
CONDUIT MAY BE SERVED AS INDICATED. THE FEEDER HVAC EQUIPMENT IS DENOTED AT THE POWER SUPPLY OF EACH POINT.
NOTES: FROM THE FOLLOWING: 10. ACCESS HATCH OPENINGS FOR MEP SHAFTS: CONTRACTOR TOALLOW FOR ACCESS HATCH OPENINGS FOR SHAFTS AS
BELOW SLAB, IN SCREED OR PER MEPDESIGN REQUIREMENTS. THE SIZE AND LOCATIONS NEED TO BE COORDINATED IN SHOP DRAWINGS.
FROM ABOVE.
11.THE ELECTRICAL CONTRACTOR IS REQUIRED TO APPOINT A SPECIALIST EARTHING SUB-CONTRACTOR TO IMPLEMENT
THESE SPECIALIST PORTIONS OF THE WORK AND TO PERFORM A RESISTIVITY TEST OF THE SOIL BEFORE INSTALLING THE
TYPICAL EARTHING DETAIL TYPICAL INSTALLATION OF EARTHING SYSTEM. THE EARTHING DRAWING IS ONLY A TYPICAL LAYOUT OF THE EARTHING SYSTEM AND SHOULD NOT BE
TYPICAL INSTALLATION OF SURFACE OR TYPICAL INSTALLATION OF EXTERNAL 3 FOR SOCKET OUTLETS 4 SOCKETS ABOVE COUNTER
TYPICAL ISOLATOR TAKEN AS THE FINAL LAYOUT.
1 FLUSH MOUNTED SOCKET OUTLETS 2 MOUNTED SOCKET OUTLETS 5 MOUNTING DETAIL ON ROOF 12. PRESENCE DETECTORS SHALL BE MOUNTED AT THE SAME HEIGHT AS LUMINAIRES WITHIN EACH AREA, AND SHALL
SCALE: NTS
COVER A DETECTION RADIUS OF 10M
SCALE: NTS SCALE: NTS SCALE: NTS
SCALE: NTS 13. ALL LEVELS ARE RELATED TO DATUM LEVEL OF 0.000 WHICH IS THE EXTERNAL ROAD LEVEL AT POINT OF ENTRY INTO
THE BUILDING. FOR GRADING LEVELS REFER TO DRAWING NUMBERS BELOW:
14. FINAL COORDINATION OF CONTAINMENT WILL BE DONE ON SITE.
15.HVAC EQUIPMENT LOCATED AT THE ROOF LEVEL ARE FED FROM ISOLATORS AS INDICATED. THE FEEDER HVAC
STAINLESS STEEL EQUIPMENT IS DENOTED AT THE POWER SUPPLY OF EACH POINT.
FIXING AND
SUPPORTING AD-90.0-C-01030 DAS ISLAND -AREA 90.0 GRADING LAYOUT ROAD WORKS
ACCESSORIES AD-90.0-C-01031 DAS ISLAND -AREA 90.0 GRADING LAYOUT ROAD WORKS
200mm RELATES TO SWITCHES
(12mm OR 10mm) AD-90.0-C-01032 DAS ISLAND -AREA 90.0 GRADING LAYOUT ROAD WORKS
NOTES: MOUNTED ADJACENT TO SINGLE
AD-90.0-C-01033 DAS ISLAND -AREA 90.0 GRADING LAYOUT ROAD WORKS
LEAF DOORS. WHERE SWITCHES AD-90.0-C-01034 DAS ISLAND -AREA 90.0 GRADING LAYOUT ROAD WORKS
ARE MOUNTED ON THE RETURN
WALL ADJACENT TO A DOUBLE ISOLATOR METALLIC ANCHOR BOLT
LEAF DOOR THE SWITCHES (WEATHER PROOF) (TYPICAL) GI TRUNKING INSIDE
SHALL BE MOUNTED AT THE
LENGTH OF THE DOOR LEAF + PVC CONDUIT
1800 A.F.F.L
ELETRICAL ROOMS LEGEND
200mm.
100x50mm.G.I
CONCEALED IN WALL
AND ABOVE FALSE
ISOLATOR
PVC CONDUIT IN
CHANNEL SUPPORT CEILING
CONCEALED IN
DOOR FRAME WALL WALL
( TYPICAL )

CONDUIT

WALL
200
1200

SWITCHES

1450
ARMOURED CABLE DISTRIBUTION BOARD
FLUSH MOUNTED RUNNING ON [SURFACE MOUNTED]
100x100mm GRP CABLE TRAY OR LADDER
200x200x8mm.THICK GI U-CHANNEL WITH
G.I PLATE.
SPRING NUT
1300

NOTES: HEIGHT IS INDICATIVE. ACTUAL F.F.L


HEIGHT IS TO BE IN ACCORDANCE F.F.L 41x21mm UNISTRUT CONDUIT ADAPTOR
WITH LOCAL REGULATIONS. CHANEL [COMPLETE WITH

F.F.L
SPRING NUTS/BOLTS]
GI CABLE
CONCRETE BASE
TRUNKING
REFERENCE DRAWINGS
DRAWING No. DRAWING TITLE

TYPICAL INSTALLATION OF TYPICAL EXTERNAL ISOLATOR TYPICAL INSTALLATION TYPICAL SURFACE MOUNTED DISTRIBUTION BOARD TYPICAL TRUNKING
6 LIGHT SWITCHING DEVICES 7 MOUNTING DETAIL 8 OF INTERNAL ISOLATORS 9 INSTALLATION DETAIL 10 INSTALLATION DETAIL
SCALE: NTS SCALE: NTS SCALE: NTS SCALE: NTS
SCALE: NTS

ARMOURED CABLE FIXED ON


GLASS REINFORCED POLYESTER
CABLE TRAY OR LADDER
SUSPENDED FROM THE CEILING
SLAB NOTES:
CONDUITS ARE ONLY TO BE GRP CABLE TRUNKING - SIZE AS
CEILING SLAB CABLE GLAND CEILING SLAB INSTALLED IN SLAB, OR SCREED, AS INDICATED ON DRAWING
REQUIRED PER REGULATIONS.
FALSE CEILING FALSE CEILING
GLASS REINFORCED
POLYESTER CABLE LADDER CABLES RUNNING CABLES RUNNING
OR TRAY SLAB
EXPANSION BOLT OR
UNISTRUT CHANNEL OR TERMINATION BOX MULTI CORE ARMOURED
ON GRP CABLE TRAY ON GRP CABLE TRAY SLAB UNISTRUT CHANNEL OR 0 100 200 300 500 700mm
PREFERRED INSTALLATION CABLE FROM SMDB ON GRP TRUNKING PREFERRED SUPPORT
PREFERRED SUPPORT GRP CABLE TRAY MULTI CORE ARMOURED CABLE 20/25/32mmØ CONDUITS 20/25/32mmØ CONDUITS SYSTEM
SYSTEM GRP CABLE TRAY (SIZE AS PER LAYOUT) (SIZE AS PER LAYOUT)
FROM SMDB FROM SMDB ON GRP CABLE TRAY CONCEALED IN SCREED CONCEALED IN SCREED
CABLE TRAY SUPPORTS
CABLE TRAY SUPPORTS (QUANTITY AS PER LAYOUT) (QUANTITY AS PER LAYOUT) Scale 1:10
POWER AND EMERGENCY STOP CONTROL SLOTTED CHANNEL CABLE GLANDING
GRP TRUNKING
CABLE ON CABLE LADDER. CABLE GLANDING (TYP.) GRP TRUNKING
GRP TRUNKING (SIZE AS PER LAYOUT)
(SIZE AS PER LAYOUT)
(SIZE AS PER LAYOUT) CONCEALED CONDUIT APPROVAL STATUS A B C D
DISTRIBUTION BOARD
FALSE CEILING
PVC CONDUITS
EMBEDDED IN
THE WALL
DISTRIBUTION BOARD
DISTRIBUTION BOARD
DISTRIBUTION BOARD DRAWING STATUS FOR TENDER
GRP TRUNKING
1800

CABLE GLANDING (TYP.)


1800

LOCAL ISOLATOR CABLE GLANDING


EMERGENCY LOCK AND EMERGENCY CABLE TRAY SUPPORTS
DEPENDING ON HEIGHT OF CEILING

STOP FLUSH MOUNTED CABLE TRAY SUPPORTS


1800

1800
STOP PUSH BUTTON.
DISTRIBUTION MULTI CORE ARMOURED CABLE (TYP.)
BOARD FROM SMDB IN CABLE TRAY
GRP TRUNKING
1800mm (APPROX)

(SIZE AS PER LAYOUT) GRP CABLE TRAY


GLAND CABLES RUNNING
(SIZE AS PER LAYOUT) ON A GRP CABLE TRAY
C0 18-11-2020 ISSUED FOR TENDER J.B A.J J.W M.T
FFL
CABLES RUN ON
FFL
GRP CABLE TRAY CONCEALED CONDUIT
REV DATE DESCRIPTION BY CHK SD APPD
CABLE TRAY. SLAB

150

150
FFL FFL CONSULTANT/CONTRACTOR/SUB CONTRACTOR
20/25/32mmØ CONDUITS
VARIES

CONCEALED IN SCREED 20/25/32mmØ CONDUITS


(QUANTITY AS PER LAYOUT) SLAB SLAB
CONCEALED IN SCREED
MOTOR (QUANTITY AS PER LAYOUT)
FINISHED FLOOR
GI ANGLE LEVEL

ELEVATION SECTION ELEVATION SECTION

450mm
2 TIER POWER SKIRTING - COLOR
FFL TO MATCH ARCH. DESIGN
F.F.L DRAWING No. AD-90.0-E-02053

SHT. SIZE : A1 AECOM Filename (Internal use only): AD-90.0-E-02053-P-C0


PLINTH
PROJECT/PMR TITLE
EXPANSION AND REHABILITATION OF
TYPICAL DETAIL FOR MOTORS OR SIMILAR TYPICAL CONNECTION DETAIL OF ARMOURED TYPICAL DISTRIBUTION BOARD TYPICAL DISTRIBUTION BOARD TYPICAL 2-TIER POWER SKIRTING
11 EQUIPMENT INSTALLATION 12 CABLE ON FLUSH DISTRIBUTION BOARD
DAS ISLAND HARBOR
13 MOUNTING DETAIL. (TOP ENTRY) 14 MOUNTING DETAIL. (BOTTOM ENTRY) 15 INSTALLATION DETAIL.
CLIENT
SCALE: NTS SCALE: NTS SCALE: NTS SCALE: NTS SCALE: NTS

DRAWING TITLE DAS ISLAND - AREA 90.0


ADNOC LOGISTICS AND SERVICES ADMINISTRATION BUILDING
ELECTRICAL SMALL POWER DETAILS
ELECTRICAL
BUDGET REF. DRAWING No. SHT.No. REV.

1 ELECTRICAL INSTALLATION DETAILS - PART 1 -


AD-90.0 E 02053 01 C0
02053 SCALE 1 : 150 PROJ/PMR No. SCALE
4700001247 1 : 150
THE INFORMATION/DESIGN CONTAINED ON THIS DRAWING IS CONFIDENTIAL. IT MUST NOT BE COPIED, GIVEN AWAY, LENT OR MADE AVAILABLE TO A THIRD PARTY WITHOUT THE WRITTEN CONSENT OF ADNOC. Filename : AD-90.0-E-02053.dwg
ALL THE WORK TO BE CARRIED OUT IN ACCORDANCE WITH THE CONTRACT SPECIFICATION. EXPLANATIONS OF ABBREVIATIONS, SYMBOLS ETC. ARE GIVEN IN ADNOC CODES OF PRACTICE.