DRAWING
TRUE
SWITCHED SOCKET
SURFACE MOUNTED CANOPY
G.I PLATE
GI CONDUIT ISOLATOR (WEATHER
PROOF)
450
F.F.L
800mm
FROM ABOVE.
CONDUCTOR ( GREEN & FLUSH MOUNTED
YELLOW ) SOCKET
BOX 120 1. FOR GENERAL NOTES; REFER TO DRAWING:
350
GALVANIZED PVC CONDUIT
SWITCHED SOCKET WALL STEEL CONDUIT WORK TOP LEVEL CONCEALED IN WALL
FLUSH MOUNTED CABLE TRAY WITH 2. THIS DRAWING IS THE PROPERTY OF AECOM AND MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE LEAD
CONDUIT FORMS THE 200x200x8mm THICK VENTILATED COVERS CONSULTANT'S AUTHORITY.
DATA SOCKET FLUSH MOUNTED WEATHERPROOF TWIN OR SINGLE
PROTECTIVE CONDUCTOR G.I. PLATE
SOCKET OUTLET SOCKET OUTLET 3. ALL DIMENSIONS ARE SHOWN IN MM, UNLESS NOTED OTHERWISE.
CONDUIT MAY BE SERVED FROM
DATA SOCKET FLUSH SEPARATE EARTH CONDUCTOR NOTES: 4. DO NOT SCALE OFF THIS DRAWING, CHECK ALL DIMENSIONS ON SITE AND NOTIFY THE COMPANY OF ANY DISCREPANCIES
MOUNTED CONNECTING EARTH TERMINAL OF G.I CABLE
SOCKET OUTLET TO AN EARTHING
BEFORE PROCEEDING WITH THE WORK.
SUPPORT
120 120 NOTES: TERMINAL IN ASSOCIATED BOX BRACKET 5. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MECHANICAL
300
SOCKET OUTLET TYPE TO BE AND ELECTRICAL DRAWINGS AND ALL RELEVANT SECTIONS OF THE SPECIFICATION.
200mm BLOCK
PVC CONDUIT DETERMINED ON LAYOUT DRAWINGS WORK
6. FOR COLUMN SIZES / RC WALL THICKNESS, SLAB THICKNESS & BEAM SIZES, REFER TO STRUCTURAL.
F.F.L CONCEALED IN WALL AND/OR SPECIFICATION. 7. THE LOCATION & SIZE OF THE MECHANICAL EQUIPMENTS & EQUIPMENT PLINTH ARE SHOWN FOR INDICATIVE PURPOSES
ONLY.
ROOF 8. FOR ADDITIONAL INFORMATION ON MEP FIXTURES & EQUIPMENTS, SEE RELATED MEP DRAWINGS.
9. HVAC EQUIPMENT LOCATED WITHIN THE BUILDING ARE FED FROM 20A DOUBLE POLE SWITCHED FUSED SOCKET & FLEX
CONDUIT MAY BE SERVED AS INDICATED. THE FEEDER HVAC EQUIPMENT IS DENOTED AT THE POWER SUPPLY OF EACH POINT.
NOTES: FROM THE FOLLOWING: 10. ACCESS HATCH OPENINGS FOR MEP SHAFTS: CONTRACTOR TOALLOW FOR ACCESS HATCH OPENINGS FOR SHAFTS AS
BELOW SLAB, IN SCREED OR PER MEPDESIGN REQUIREMENTS. THE SIZE AND LOCATIONS NEED TO BE COORDINATED IN SHOP DRAWINGS.
FROM ABOVE.
11.THE ELECTRICAL CONTRACTOR IS REQUIRED TO APPOINT A SPECIALIST EARTHING SUB-CONTRACTOR TO IMPLEMENT
THESE SPECIALIST PORTIONS OF THE WORK AND TO PERFORM A RESISTIVITY TEST OF THE SOIL BEFORE INSTALLING THE
TYPICAL EARTHING DETAIL TYPICAL INSTALLATION OF EARTHING SYSTEM. THE EARTHING DRAWING IS ONLY A TYPICAL LAYOUT OF THE EARTHING SYSTEM AND SHOULD NOT BE
TYPICAL INSTALLATION OF SURFACE OR TYPICAL INSTALLATION OF EXTERNAL 3 FOR SOCKET OUTLETS 4 SOCKETS ABOVE COUNTER
TYPICAL ISOLATOR TAKEN AS THE FINAL LAYOUT.
1 FLUSH MOUNTED SOCKET OUTLETS 2 MOUNTED SOCKET OUTLETS 5 MOUNTING DETAIL ON ROOF 12. PRESENCE DETECTORS SHALL BE MOUNTED AT THE SAME HEIGHT AS LUMINAIRES WITHIN EACH AREA, AND SHALL
SCALE: NTS
COVER A DETECTION RADIUS OF 10M
SCALE: NTS SCALE: NTS SCALE: NTS
SCALE: NTS 13. ALL LEVELS ARE RELATED TO DATUM LEVEL OF 0.000 WHICH IS THE EXTERNAL ROAD LEVEL AT POINT OF ENTRY INTO
THE BUILDING. FOR GRADING LEVELS REFER TO DRAWING NUMBERS BELOW:
14. FINAL COORDINATION OF CONTAINMENT WILL BE DONE ON SITE.
15.HVAC EQUIPMENT LOCATED AT THE ROOF LEVEL ARE FED FROM ISOLATORS AS INDICATED. THE FEEDER HVAC
STAINLESS STEEL EQUIPMENT IS DENOTED AT THE POWER SUPPLY OF EACH POINT.
FIXING AND
SUPPORTING AD-90.0-C-01030 DAS ISLAND -AREA 90.0 GRADING LAYOUT ROAD WORKS
ACCESSORIES AD-90.0-C-01031 DAS ISLAND -AREA 90.0 GRADING LAYOUT ROAD WORKS
200mm RELATES TO SWITCHES
(12mm OR 10mm) AD-90.0-C-01032 DAS ISLAND -AREA 90.0 GRADING LAYOUT ROAD WORKS
NOTES: MOUNTED ADJACENT TO SINGLE
AD-90.0-C-01033 DAS ISLAND -AREA 90.0 GRADING LAYOUT ROAD WORKS
LEAF DOORS. WHERE SWITCHES AD-90.0-C-01034 DAS ISLAND -AREA 90.0 GRADING LAYOUT ROAD WORKS
ARE MOUNTED ON THE RETURN
WALL ADJACENT TO A DOUBLE ISOLATOR METALLIC ANCHOR BOLT
LEAF DOOR THE SWITCHES (WEATHER PROOF) (TYPICAL) GI TRUNKING INSIDE
SHALL BE MOUNTED AT THE
LENGTH OF THE DOOR LEAF + PVC CONDUIT
1800 A.F.F.L
ELETRICAL ROOMS LEGEND
200mm.
100x50mm.G.I
CONCEALED IN WALL
AND ABOVE FALSE
ISOLATOR
PVC CONDUIT IN
CHANNEL SUPPORT CEILING
CONCEALED IN
DOOR FRAME WALL WALL
( TYPICAL )
CONDUIT
WALL
200
1200
SWITCHES
1450
ARMOURED CABLE DISTRIBUTION BOARD
FLUSH MOUNTED RUNNING ON [SURFACE MOUNTED]
100x100mm GRP CABLE TRAY OR LADDER
200x200x8mm.THICK GI U-CHANNEL WITH
G.I PLATE.
SPRING NUT
1300
F.F.L
SPRING NUTS/BOLTS]
GI CABLE
CONCRETE BASE
TRUNKING
REFERENCE DRAWINGS
DRAWING No. DRAWING TITLE
TYPICAL INSTALLATION OF TYPICAL EXTERNAL ISOLATOR TYPICAL INSTALLATION TYPICAL SURFACE MOUNTED DISTRIBUTION BOARD TYPICAL TRUNKING
6 LIGHT SWITCHING DEVICES 7 MOUNTING DETAIL 8 OF INTERNAL ISOLATORS 9 INSTALLATION DETAIL 10 INSTALLATION DETAIL
SCALE: NTS SCALE: NTS SCALE: NTS SCALE: NTS
SCALE: NTS
1800
STOP PUSH BUTTON.
DISTRIBUTION MULTI CORE ARMOURED CABLE (TYP.)
BOARD FROM SMDB IN CABLE TRAY
GRP TRUNKING
1800mm (APPROX)
150
150
FFL FFL CONSULTANT/CONTRACTOR/SUB CONTRACTOR
20/25/32mmØ CONDUITS
VARIES
450mm
2 TIER POWER SKIRTING - COLOR
FFL TO MATCH ARCH. DESIGN
F.F.L DRAWING No. AD-90.0-E-02053