SWP For Installation of Underground Pipes For Fire Hydrant System
SWP For Installation of Underground Pipes For Fire Hydrant System
SWP For Installation of Underground Pipes For Fire Hydrant System
Date :
Prepared by :
PURPOSE
To establish safe working method as guide to site personnel in installing underground
pipes for fire hydrant system
RESPONSIBILITY
Site Supervisor – Ensure to brief workers on this procedures before commencing works
Safety Personnel – To ensure that the procedures stated herein is being adhered at all
times
Worker – To adhere to any instructions by the Site Supervisor and ensure to understand
these procedures
PROCEDURES
1
Rev No : 0
Date :
Prepared by :
Ensure that excavated materials are not place near the edge of the excavation (at least
1m away)
Avoid parking/driving the excavator on soft, uneven surface or near the edge of
excavated trench
Do not use the excavator to lift materials if it has no valid LM Cert. Otherwise, observe
SWL.
Apply water during excavation (whenever necessary)
Ensure workers to wear appropriate PPE (dust mask, goggles)
a. Using excavator
2
Rev No : 0
Date :
Prepared by :
Check all sharp objects prior to start work. Put protection when necessary
Workers to wear appropriate PPE (long sleeve shirts, hand gloves, safety shoes etc.
7. Pressure Test
Site Supervisor to ensure the pressure gauge is properly calibrated prior to use.
Certificate of calibration must be valid
Connection of equipment into pipe must be check by the Site Supervisor prior to start
pressure testing
Tie the hose to the pipe with rope to prevent it from a sudden impact in case of
dislodging.